Beruflich Dokumente
Kultur Dokumente
A fuse rating is the current need to blow (break) the fuse. When a fuse has blown it removes electrical power from
an electrical circuit. The fuse rating is usually on the side of the fuse. Thefuse rating is usually defined in 'amps' –
amps are the unit of measurement of electrical current.
This dielectric strength specified in Voltage/distance specifies the voltage a certain material may withstand
without being crossed by any current.
When for some reason the fuse breaks we intende that the circuit is “breaked” totally. And the voltage spec
of the fuse ensures that if the voltage between the two ends of the fuse, after break, stays below the voltage
specs the fuse wont be crossed by any current that will flow through the material gap, being “material” the
means where the wire was in. Could be air or any other insulation material.
For instance the air has a dielectric strenght of 350V/cm. ( Note: there some factors that will affect the value
of dielectric strength of materials besides the material itself)
UL Fuse Classification Chart
INTERRUPTING AC AVAILABLE LITTELFUSE BUSSMAN EDISON
UL FUSE OVERLOAD
RATING, VOLTAGE AMPERE SERIES SERIES SERIES
CLASS CHARACTERISTICS
AMPERES RATING RATINGS NUMBER NUMBER NUMBER
KLDR
1
/10 - 30 CCMR FNQR HCTR
CC TIME-DELAY 200,000 600 1
/5 - 30 (formerly LPCC EDCC
KLMR)
1
CC FAST-ACTING 200,000 600 /10-30 KLKR KTKR HCLR
The following are standards which are accepted and used as requirements by which manufacturers must
design their fuses. These standards are continuously being updated, it's important to refer to the latest
version when designing or constructing your next project.
The following information is provided to analyze several of these fuse classes, along with pertinent
performance characteristics and ratings.
Class CC fuses.
These non-renewable fuses are current-limiting and intended for the protection of components sensitive to
short-time overloads, non-inductive loads, and short-circuit protection of motor circuits.
Current ratings range from 0A to 30A, and the voltage rating is 600VAC. Class CC fuses are available with
DC ratings. The interrupting rating is 200kA rms symmetrical.
Class CC fuses must be labeled "Current Limiting," and may be labeled "Time Delay." The optional time-
delay test requirements for this class of fuses (a minimum 12-sec opening time at 200% fuse current rating)
is different than that of other larger body fuses.
Class G fuses.
These fuses were specifically created for use in lighting and appliance panel boards that are equipped with a
special fusible-switch unit. These are non-renewable cartridge fuses that are for use only in AC circuits
where interrupting ratings to 100kA rms symmetrical are required. These can also be available with DC
ratings.
G Class fuses conform to standard 248-5, and are rated for 600VAC (0A to 20A) and 480VAC (25A to
60A). They are available in four ferrule sizes: 0A to 15A, 16A to 20A, 1A to 30A, and 31A to 60A. The
innovative design of this class of fuse was selected so as to prevent the interchangeability with any other
fuse class.
Class G fuses are current-limiting and are able to be so labeled per UL 248-5, which prescribes the
maximum peak let-through and I2t let-through values permitted for this class of fuse.
The time delay test feature is optional. It is important to realize that the test calls for a minimum opening
time of 12 sec at 200% of the fuse ampere rating which differs Class H, K, and R fuses.
Class H fuses.
This is a cartridge fuse and is intended for general purpose branch circuit, lighting circuit,
and the protection of non-inductive equipment like electric ovens and resistance heaters.
You can select from renewable and non-renewable Class H fuses. The renewable fuses
allow the user to replace the internal fusible link after the fuse operates.
All Class H units are tested for short-circuit requirements and are available with DC
ratings. The short-circuit power factors are relatively high: 0.45 to 0.50 for fuses rated
110A to 600A, and 0.85 to 0.90 for fuses rated 100A and less. The actual short-circuit
power factors encountered in typical installations are on the order of the above test values,
when the available short-circuit current is 10kA rms symmetrical or less.
With respect to the time delay feature of fuses, the renewable types cannot perform the time delay but the
non-renewable can.
Class H fuses, both non-renewable and renewable, are often misapplied in the electrical industry for a couple
reasons. First, their minimal 10kA interrupting rating is easy to exceed in an industrial plant or commercial
building. Second, workers unfamiliar with the differences between devices might be tempted to install more
than one link in a renewable fuse.
Class J fuses.
These non-renewable fuses are current-limiting and conform to 248-8. Current ratings of UL Class J fuses
range from 0A to 600A, and the voltage rating is 600VAC. Class J fuses are available with DC ratings. The
interrupting rating is 200kA rms symmetrical. Fuses with 300kA interrupting ratings are available. Time-
delay labeling is available if the fuse meets the UL optional time-delay test requirements of a minimum 10-
sec opening time at 500% of fuse current rating.
Class K fuses.
These non-renewable fuses are available in 250VAC and 600VAC ratings, with current ratings from 0A to
600A. Class K fuses are available with DC ratings.
The interrupting ratings may be 50kA, 100kA, or 200kA rms symmetrical. Class K-1 fuses provide the best
degree of current limitation. On the other hand, Class K-5 fuses provide a lesser degree of current limitation.
The standards requirements for Class K fuses prescribe maximum peak let-through current and maximum
I2t let-through energy for each class and all are current-limiting fuses. Interestingly, these fuses cannot be
labeled as current limiting because they are interchangeable with Class H fuses, which are noncurrent
limiting.
Class L fuses
These non-renewable fuses are current-limiting and conform to 248-10. They're designed for the
protection of feeders and service entrance equipment.
Current ratings for UL Class L fuses range from 601A to 6000A, and the voltage rating is 600VAC. Class L
fuses are available with DC ratings. Available case sizes are 800A, 1,200A, 1,600A, 2,000A, 2,500A,
3,000A, 4,000A, 5,000A, and 6,000A. The interrupting rating is 200kA rms symmetrical. (300kA fuses are
available.)
As with the other classes of fuses conforming to 248 (G, J, R, and T), Class L fuses must be labeled "Current
Limiting." They may be labeled "Time Delay," although the standard doesn't have a requirement for their
time-delay characteristics.
Class R fuses
These non-renewable fuses are made in 250VAC and 600VAC ratings, with current ratings from 0A to
600A. Class R fuses are available with DC ratings. They have an interrupting rating of 200kA rms
symmetrical and are separated into two separate classes, RK1 and RK5. RK1 fuses are available with
interrupting ratings of 300kA.
Both RK1 and RK5 fuses are current-limiting and meet standard-prescribed maximum peak instantaneous
let-through current and maximum I2t let-through energy requirements.
Class R fuses must be labeled "Current Limiting" and may be labeled "Time Delay," which means that they
meet the optional time-delay test by not opening in less than 10 seconds at 500% of fuse ampere rating.
One of the most important aspects of electrical wiring of photovoltaic systems is fusing. Fuses provide
integral protection against overcurrents that could otherwise damage your valuable PV equipment.
Furthermore, using an incorrect fuse can be extremely hazardous!
When sizing the fuse, the most common calculation method is to multiply the continous load/feed current of
a branch by 1.25, and using the closest rated fuse that is greater than your result. However, there are
exceptions to this calculation method.
We have observed that a very common mistake is to use a fuse that is rated for 600 VAC on a DC
disconnect that is rated for 600 VDC. At first sight, the cable size, the current rating may seem correct,
however, the voltage rating (a small description on the fuse) is even more important than the current rating
in some circumstances. AC rated fuses SHOULD NOT be used in DC voltage circuits unless DC application
ratings are provided by the fuse manufacturer.
The characteristics and certification of the fuses are usually defined on the fuse label. UL and CSA are the
most common fuse certifications used in North America. The fuse label may provide information on the
applicable AC or DC voltage, the maximum current rating and other information such as “interrupting
rating”, “current limiting”, “time-delay” and “fast-acting”. The definitions of these specifications are
explained below.
Please refer to NEC code Article 240 Overcurrent Protection when sizing the fuses for your application.
Interrupting rating: Interrupting rating is the current that a fuse, circuit breaker, or other electrical apparatus
is able to interrupt without being destroyed or causing an electric arc with unacceptable duration.
Current limiting: A current-limiting device is one that reduces the peak let-thru current to a value
substantially less than the potential peak current that would occur if the current-limiting device were not
used.
Time-delay: A fuse in which the burnout action depends on the time it takes for the overcurrent heat to build
up in the fuse and melt the fuse element.
Fast-acting: A fuse that opens on overload and short-circuits very quickly. Fast-acting fuse is not designed to
withstand temporary overload currents associated with some electrical loads.
Max.
ACVoltage UL
Fuse Type Current Classification General Use
Rating Notes
Rating
-Non-
480/600
renewable
21A / VAC, UL
Class G -Current
60A DC 248-5
limiting
Optional
-Time-delay
-Non-
renewable
Class H UL
-Current
(Renewable) 248-7
limiting Circuits having relatively low levels of available short
250/600 -Fast acting circuit current, Industrial and commercial applications
600A VAC,
DC having frequent outages where a renewable type fuse is
-Non-
Optional desired
renewable
Class H (Non- UL
-Current
Renewable) 248-6
limiting
-Time-delay
-Non-
250/600
renewable
VAC, UL
Class K 600A -Current
DC 249-9
limiting
Optional
-Fast acting
Electric Fuse Types
In 1847 French physicist and watch maker Louis François Clément Breguet recommended a reduced strip conductor to
protect telegraph station from lightning strikes. He thought by melting smaller wires would protect the apparatus and wiring
inside the building. By 1864 a variety of wires and foil fusible apparatus were used for the purpose of protection
of telegraph cables and lighting systems. In 1890 Thomas Alva Edison patented a fuse as a part of his electrical distribution
system. Electrical fuses are sacrificial elements in an electrical circuit which protect the system from over current. Fuses are
designated to open circuit during an occurrence of excessive current due to the presence of an overload or fault and prevent
the further damage of the system.
Various components of a fuse are: melt fuse element, set of contacts and supporting body. Fuse element are generally made
of materials with low melting point, high conductivity and less deterioration due to oxidation. They are inserted in series
with the circuit to be protected. Under normal operating conditions the fuse element in kept at a temperature below its
melting point so that it carries normal current without overheating. During the occurrence of short circuit or overload, the
current in the fuse element increases beyond the rated value. This raises the temperature leading to melting of fuse element
thus disconnecting the circuit protected by it. The magnitude of the over current decides the time required for the blow out
of the fuse. Greater the current, smaller the time required for the fuse to blow out or it can be said that fuse has an inverse
time-current characteristics.
The function of the fuse is to carry normal current without interruption and during an over current situation it rapidly heats
up to melting point and isolates the circuit protected by it. For the satisfactory performance of the fuse, the following
desired characters of the fuse element is necessary.
No material has all the desired characters in common so compromise must be made in the selection of fuse elements.
The commonly used materials for fuse elements are Tin, Lead, Copper, Zinc and Silver etc. For currents up to 10A Tin or
and alloy of Tin and Lead (63% Tin and 37% Lead) is used. For higher voltages copper or silver is used. Copper is usually
tinned to prevent it from oxidation. Zinc strips are used when a considerable time-lag is required as it does not melt quickly
for small overloads.
Nowadays despite of its high cost silver is used for the following reasons.
High conductivity. So for a given rating of the fuse element, the mass of silver metal required is much less than
other elements.
Free from oxidation
Silver does not deteriorate when used in dry air.
The coefficient of expansion of copper is very low so it can carry the rated current continuously for a long time
without interruption.
Silver vaporises at a temperature much lower than the one at which its vapour will rapidly ionise. So when an arc
is formed through the vaporised portion of the element, the arc path has high resistance so that the short circuit
current is quickly interrupted.
The resistance of silver increases abruptly as the melting temperature is reached, making the transition from
melting to vaporisation occurs instantaneously.
Important Terms
It is the current which the fuse element can carry without overheating or melting. It depends on the temperature rise in the
contacts of the fuse holder, fuse material and the surrounding of the fuse.
Fuse Current
It is the minimum current at which the fuse element melts. Its value will be higher than the current rating of the fuse
element.
For a round wire the approximate relationship between the fuse current I and the diameter d of the wire is given by
I = kd3/2
k is a constant called the fuse contact. The value of k depends on the material used for making fuse element.
The value of k for various elements as found by Sir William Henry Preece is given below
Value of k
Sl. No. Material
d in cm d in mm
1 Copper 2530 80
2 Aluminium 1873 59
Fusing factor
It is the ration of fusing current to the current rating of the fuse element.
Prospective Current
From Figure 2 the fault current would normally have a large first loop but it generate sufficient energy to melt the fuse
element before the peak value of the first loop is reached. The rms value of the first loop of fault current is known as
prospective current. Prospective current is defined as the rms value of first loop of fault current is the fuse is replaced by an
ordinary conductor of negligible resistance.
Cut-Off Current
It is the maximum value of fault current reached when the fuse melts. The current corresponding to the point ‘a’ is called
cut-off current. The cut-off value depends on
Pre-arcing Time
It is the time between commencement of the fault current and the instant when cut-off occurs. When a fault occurs, the fault
current rises rapidly and as the fault current reaches a cut-off value the fuse melts and an arc is initiated. The time between
the occurrence of the fault and the instant the arc is initiated is called the pre-arcing time. The value of pre-arcing time is
generally small and a typical value is 0.001 second.
Arcing Time
The time between the pre-arcing time and the instant at which the arc is extinguished.
Total Operating Time
The sum of pre-arcing and arcing times. It may be noted that the operating time of a fuse (0.002seonds) is much lower than
that of a circuit breaker (0.2 seconds). A fuse in series with a circuit breaker of low breaking capacity is useful and
economical way of providing adequate short circuit protection. In that case the fuse will blow fast even before the circuit
breaker begins to operate.
Breaking Capacity
It is the rms value of the AC component of maximum prospective current that a fuse can deal with at a rated service voltage.
Types of Fuses
Since its invention, a lot of improvements have been made and now a variety of fuses are available. Some fuses even have
arrangements to extinguish the arc that appears when the fuel element melts. Fuses are generally classified into two:
Rewirable fuses also known as kit-kat type fuses are used to interrupt fault currents of lower magnitude. It consists of two
parts: a base and a fuse carrier. The base is made of porcelain and carrier the fixed contacts to which the incoming and
outgoing phase wires are connected. The fuse carrier is also made of porcelain and fuse elements between the terminals. The
fuse carrier can be inserted or removed at any time.
When a fault occurs the fuse element is blown out and the circuit is interrupted. The fuse carrier can be taken out and the
blown out fuse element can be replaced by a new one. It is then inserted to the base to restore the supply.
Advantages:
Detachable fuse carrier permits the replacement of fuse element without coming in contact with live parts.
Cost of replacement is negligible.
Disadvantages:
Possibility of renewal with fuse wire of wrong size and improper material.
Low breaking capacity, so cannot be used in circuits with higher fault current levels.
The fuse element is subjected to deterioration by oxidation through the continuous heating up of the element.
This reduces the current rating of the fuse. Thus the fuse operates at a current lower than the rated value.
Uncertainty in the protective capacity of the fuse since it is affected by ambient conditions.
Accurate calibration of the fuse is not possible as the fusing current depends on the length of the fusing element.
Semi enclosed rewirable fuses have capacity up to 500A but their breaking capacity is much lower so their use is limited to
domestic and lighting applications only.
The shortcomings of uncertain and low breaking capacity of semi enclosed rewirable fuse are overcome in HRC cartridge
fuse. It consist of a heat resisting ceramic body with metal end caps to which is welded silver current carrying element. The
space surrounding the element is completely packed with a filling powder. The filling powder can be of chalk, plaster of
paris, quartz or marble dust and act as an arc quenching and cooling medium.
Figure 5: HRC Fuses
The HRC cartridge fuse carried the normal current without overheating. During the occurrence of a fault, the current
increases and the fuse element melts before the fault current reaches its first peak. The heat produced in the process
vaporises the melted silver element. The chemical reaction between the silver vapours and the filling powder results in a
high resistance substance that helps in quenching the arc.
Advantages
Disadvantages
In some case, the HRC fuse is provided with a tripping device. During the occurrence of a fault the fuse is blown out and
the tripping device causes the circuit breaker to operate. The body of the fuse is made of a ceramic material with a metal cap
attached rigidly to both ends. The caps are connected by a number of silver fuse elements. At one end of the fuse there is a
plunger. Under fault condition it hits the tripping mechanism of the circuit breaker and causes it to operate. The plunger is
electrically connected by means of a fusible link, chemical charge and a tungsten wire to the other end of the cap.
When fault occurs, the silver fuse elements are the first to be blown out and the current is then transferred to the tungsten
wire. The weak link in series with the tungsten wire gets fused and causes the chemical charge to be detonated. This forces
the plunger to move outward to operate the circuit breaker. The travel of the plunger is so set that it is not ejected from the
fuse body under the fault conditions.
Advantages over the fuse without triggering device
In case of a single phase fault on a three phase system, the plunger operates the tripping mechanism of circuit
breaker to open all the three phase and thus prevents ‘single phasing’
The effect of full short circuiting need not be considered in the choice of circuit breaker. This prevents from the
use of expensive circuit breakers
The fuse tripped circuit breaker is generally capable of dealing with fairly small fault current itself. This avoids the
necessity for replacing the fuse except after highest currents fir which it is intended
Due to the fact that the low voltage fuses has low current rating and breaking capacity they cannot be used for modern high
voltage systems. With the advancement in technology researches found a way to protect the high voltage circuits; the high
voltage fuses.
The construction of high voltage cartridge fuse is similar to that of a low voltage cartridge fuse except that special features
are incorporated in the former. On some design the fuse element is wound in the form of a helix so as to avoid the effects
due to corona at high voltages. In another design, there are two fuse elements in parallel, one low resistance (silver wire)
and one high resistance (tungsten wire). Under normal operating conditions the low resistance element carries the normal
current. During the occurrence of a fault the low resistance element is blown out and the high resistance element reduces the
short circuit current and finally breaks the circuit. High voltage cartridge fuses are used up to 33kv with breaking capacity
of about 8700A. Ratings in the order of 200A at 6.6kv and 11kV and 50A at 33kV are also available.
These fuses are filled with carbon tetrachloride and they have wide range of application in high voltage systems. They may
be used in circuits with 100A rated current in 132kV system. The breaking capacity is of the order of 6100A. It consists of a
glass tube filled with carbon tetrachloride solution with both ends sealed with brass caps. The fuse wire is sealed at one end
of the tube and the other end is held strongly by a phosphor bronze spiral spring fixed at one end of the glass tube.
Fig 8 shows the essential parts of a liquid fuse. When the current exceeds the predetermined limit the fuse wire is blown out.
As the fuse wire melts the spring retracts the part of the wire through liquid director and draws it completely into the liquid.
The small quantity of gas generated at the point of fusion forces part of the liquid into the passage through liquid director
and it effectively extinguish the arc.
Metal clad oil immersed fuses were developed as a substitute for oil circuit breakers. They operate satisfactorily under fault
conditions in high voltage circuits.
Self-resetting fuses are Polymeric Positive Temperature Coefficient(PPTC) thermistor which uses thermoplastic conductive
element. It breaks the circuit as it increases device resistance during an over current condition. When the fault current is
cleared the device then cools and return to lower resistance or in other words PPTC thermistor is self resetting. They are
ofthen used in nuclear or aerospace applications where the replacement of the fuse is difficult. They are also used in
computer mother boards so that any short circuit in keyboard or mouse does not damage the mother board.
Figure 10: Resettable Fuses
Thermal Fuses
They are single operation devices that work mainly as temperature sensitive protective device. Their reduced size and cost
effectiveness make them useful as a protective device in systems where thermal variations are experienced during ordinary
working conditions. The thermal fuse consists of a contact spring which is enclosed into a wax pellet. The pellet is
constructed to melt at a set temperature. When the wax get heated it melts and the spring get stretched till it open the circuit.
Another type of thermal fuse uses a specially composed solder that melts at a predetermined temperature. Thermal fuses are
also called thermal links or thermal cutouts. A thermal fuse can be found in consumer equipment such as water heaters, hair
dryers or small transformer poweredelectronics equipments.
They are mainly used in DC power applications where quick clear is required during an over current condition. Reduce
in fuse aging, improve reliability and resilience and enhance high temperature performance are the main highlights.
They are used when high current is required and space is critical. Due to their high reliability and strong arc suppression
property they are used for over current protection in power supplies servers, communication equipment etc.
Figure 12: High Current Rated Fuses
They are used to protect from damages caused by over current on systems that experience large and frequent surges as part
of their normal operation.
Telecom Fuses
Telecom fuse offers low temperature rise performance under sneak current fault to prevent damages to circuit trace or
multilayer board. The low profile and small footprint make them suitable for high density and space constraint applications.
Figure 13: Telecom Fuses
They provide over current protection to systems using DC power up to 63V. The monolithic, multilayer design provides the
highest hold current in the smallest foot print, reduces diffusion related aging, improve product reliability and resilience and
high temperature performance in a wide range of circuit design.
Very fact acting at 200% and 300% overloads. Provides Over current protection to systems using DC power up to 63V
Automotive Fuses
They are used to protect the wiring and equipment in vehicles. Automotive fuses can be mounted in fuse block, inline fuse
holders or fuse chips. Some automotive fuses are also used in non-automotive applications. Standards for automotive fuses
are published by Society of Automotive Engineers (SAE) International. Automotive fuses are classified into Blade fuses,
Class tube or Bosch type, Fusible links and Fuse limiters. Most automotive fuses rated 32V are used on circuits rated 24V
DC and below. Certain vehicles use dual 12/24V DC electrical system will require fuse rated at 58V DC.
Several fuses are connected in series at various levels of a power distribution system so that only the fuse electrically closest
to the fault is blown out. This process is called coordination or discrimination and may require the time current
characteristics of two fuses plotted on a common current basis. Fuses are selected so that the minor branch fuse disconnects
its circuit before the supplying major branch fuse starts to melt. So only the fault circuit is interrupted with minimum
disturbance to other circuit fed by a common supplying fuse.
Fuse Law
The current carrying capacity of a fuse depends on the material used, the cross sectional area, length of the
element, the state of the surface and the surrounding of the fuse.
Heat produced per second = Heat lost due to conduction, convection and radiation
Where d is the diameter, l is the length and a is the area of cross section of the fuse element
Advantages
Disadvantages