DESCRIPTION
The ARM III Disconnect is a keyed switch that
enables the operator to put the suppression release
circuit that the switch is connected to in a
“DISARMED” condition by electrically isolating the
connected agent release modules (ARM) from the
releasing circuit. This allows the operator to work in
the area protected by the suppression system
without accidentally releasing the system. The
switch can be ordered with or without status LEDs
(Green – ARMED and Red – DISARMED). The
LEDs provide positive indication of the status of the
releasing circuit. LEDs require 24 VDC auxiliary ®
® th
Fike , 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013-0610 U.S.A. ● Tel: (816) 229-3405 ● Fax: (816) 229-4615
While every precaution has been taken during the preparation of this document to ensure the accuracy of its content, Fike assumes no responsibility for errors or omissions.
Fike reserves the right to make changes to the product or this document without notice.
www.fike.com P/N 06-472 Rev. 0 page 1 of 4
SAFETY NOTICES SWITCH ASSEMBLY
Read all of the following safety notices before The disconnect switch is shipped unassembled and
attempting to install or use this device. Personal must be assembled in the field using the following
injury or accidental release of the suppression instructions:
system may result if the following instructions are not
1. Remove the switch components (faceplate and
followed.
switch) from the shipping package.
a WARNING 2. Remove the operator from the contact block by
1. The SHP, SHP-Pro, Rhino, and Intella-Scan pulling up the locking lever and turning it to the
left as shown in Exhibit 2.
control panels are equipped with an
ARM/DISABLE switch for the releasing circuit(s). o
If using the ARM III Disconnect switch with these
panels, the ARM/DISABLE switch on the panel n
must be in the ARM position for the switch to
operate properly. DO NOT use the
ARM/DISABLE switch simultaneously with the p
ARM III Disconnect switch.
2. A manual actuator can also be used to fire the
GCA’s. If is extremely important to make sure n Pull up the locking lever. p Pull out the contact block.
the GCA is not connected to a manual actuator
before considering the circuit “DISARMED”. o Turn the lever to the left.
Exhibit 2: Removing and Installing
the Contact Block
ICaution
1. Only ARMs that are connected to the ARM III 3. Remove the locking ring from the operator and
Disconnect switch will be disconnected by the insert the operator into the switch faceplate from
user operated key switch. the front as shown in Exhibit 3. Reinstall the
2. The ARM III Disconnect switch DOES NOT locking ring onto the operator from the back and
remove the firing charge stored in the ARM’s tighten with pliers or locking ring wrench (02-
capacitor. It removes the charging current to the 12318), making sure that the TOP marking on
releasing circuit and allows time for the ARMs to the operator is aligned with the top center of the
de-energize until there is insufficient energy to faceplate.
activate the GCA.
Face Plate
® th
Fike , 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013-0610 U.S.A. ● Tel: (816) 229-3405 ● Fax: (816) 229-4615
P/N 06-472 Rev. 0 page 2 of 4 www.fike.com
SWITCH INSTALLATION AND TESTING
INSTRUCTIONS
The ARM III Disconnect switch is installed into the 7. Functionally test the operation of the
releasing circuit between the associated control Suppression Disconnect switch in both the
panel or releasing module and the ARM(s) itself. ARMED and DISARMED modes. Correct any
problems before proceeding to next step.
The following steps must be followed in order to
properly install and test the operation of the 8. Attach the Suppression Disconnect faceplate to
suppression disconnect switch. Failure to follow the back-box with supplied mounting screws and
these steps could result in improper operation or turn key switch to DISARMED position.
accidental release of the suppression system.
9. Remove the jumper wire from the ARM red/blue
terminals and reconnect the GCA wires.
Installation and Testing Steps:
10. Turn the key switch to the ARMED position. The
1. Disconnect all power to the ARM circuit(s) and
system is now operational.
allow 7-10 minutes for ARM capacitor charge to
dissipate.
2. Disconnect GCA wiring from ARM and properly SPARE PARTS
shunt. Install jumper wire in ARM red/blue 02-12294 Double contact block (2 NC)
terminals. 02-12295 Double contact block (2 NO)
02-12296 Replacement keys
a WARNING 02-12297 4 block switch
Failure to disconnect power to the releasing 02-12298 5 block switch
circuit(s) and disarm the GCA(s) prior to 02-12300 Single contact block (NO)
installation of the switch may cause accidental 02-12314 2 block switch
discharge of the suppression agent. 02-12315 3 block switch
02-12316 Single contact block (NC)
3. Select appropriate location for mounting switch 02-12317 Double contact block (1 NC / 1 NO)
and secure back-box to wall with suitable 02-12318 Locking ring wrench
anchors. 02-3013 Green LED
02-3009 Red LED
Back Box Options 02-1553 2.2K, .5W, 5% resistor
Switch without LEDs 10-2714 Cover plate w/o LED holes
For surface mounting, use a two-gang masonry 10-2713 Cover plate with LED holes
box (Raco 691 or equal) with a depth of 2.5”
(6.35cm). For flush mounting, use a two-gang
mud ring (raised ½” minimum) on a 4 in square x
2-1/8” deep box.
Switch with LEDs
For surface mounting, use a two-gang masonry
box (Raco 696 or equal) with a depth of 3.5”
(8.89cm). For flush mounting, use a two-gang
mud ring on a 4 in square x 3-1/2” deep box
(Raco 256 or equal).
4. Route conduit and field wiring (i.e., releasing
circuit, auxiliary power and supervisory circuit)
into back-box. Verify that wiring is free from
ground fault or short-circuit conditions before
proceeding.
5. Connect field wiring to appropriate terminals on
the switch contact block as shown in Exhibit 4 or
5, making sure to observe circuit polarity.
6. Reconnect all power to ARM releasing circuits.
Do NOT reconnect GCA wire leads to the ARM
at this time.
® th
Fike , 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013-0610 U.S.A. ● Tel: (816) 229-3405 ● Fax: (816) 229-4615
www.fike.com P/N 06-472 Rev. 0 page 3 of 4
NO NC
SWITCH TERMINAL BLOCKS
(BACKSIDE OF FACEPLATE)
NC
SUPERVISORY CIRCUIT
TO NEXT
FROM CONTROL PANEL
BLUE
DISCONNECT
GRN
RED
YEL
OR ADDRESSABLE
SWITCH OR TO NEXT AGENT RELEASE
MONITOR MODULE
END-OF-LINE MODULE (ARM) OR
AGENT RELEASE CIRCUIT RESISTOR END-OF-LINE RESISTOR
FROM CONTROL PANEL -
OR RELEASING MODULE +
TS1
- + + -
SQUIB/GCA
NOTES:
1. WIRING DIAGRAM SHOWS SWITCH IN ARMED POSITION. R
2. ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED.
CAPACITOR
DISARMED
R
24 VDC - G
(SEE NOTE 3) + ARMED
NC NO NC
NO NC
SWITCH TERMINAL BLOCKS
(BACKSIDE OF FACEPLATE)
SUPERVISORY CIRCUIT
TO NEXT
FROM CONTROL PANEL
BLUE
DISCONNECT
GRN
RED
YEL
OR ADDRESSABLE
SWITCH OR TO NEXT AGENT RELEAS
MONITOR MODULE
END-OF-LINE MODULE (ARM) OR
AGENT RELEASE CIRCUIT RESISTOR END-OF-LINE RESISTOR
FROM CONTROL PANEL -
OR RELEASING MODULE +
TS1
- + + -
NOTES: SQUIB/GCA
® th
Fike , 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013-0610 U.S.A. ● Tel: (816) 229-3405 ● Fax: (816) 229-4615
P/N 06-472 Rev. 0 page 4 of 4 www.fike.com