Beruflich Dokumente
Kultur Dokumente
enquiries@hyquip.co.uk
www.hyquip.co.uk/web/index
H7125
Notices:
Assembly of the product requires basic electrical knowledge:
▶ The product may only be re-wired and assembled by
qualified personnel.
▶ De-energize the amplifier before any work!
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
Factory setting VT 3000 1)
2/12
VT-VSPA2-1-2X/V0/... VT 3026 1) (RE 29935) VT 3013 VT 3014
VT-VSPA2-1-1X/T1 VT-VSPA2-50-1X/T1
(RE 30093) VT 3006 1) (RE 29937) (RE 29937)
VT-VSPA2-1-1X/T5 VT-VSPA2-50-1X/T5
Observe (RE 29926) VT 3017 VT 3018
(RE 30112) (RE 30113)
footnote 1)! Observe (RE 29939) (RE 29939)
footnote 1)!
.WRZ
3DREP6
(to component
(from component
series 6X) 4WRA6 4WRA10
series 2X),
Configuration for: A4VG…EP2 DBEP6, 3DREP6 4WRA6 4WRA10 (from compo- (from compo-
.WRZ
(in each case nent series 2X) nent series 2X)
(from component
component
series 7X)
series 1X)
Inversion Non-inverting
Jumper open Jumper open Jumper open Jumper open Jumper open Jumper open Jumper open
J1 Jumper open
J3 Jumper open
Step function Step function on
Jumper open Jumper open Jumper open Jumper open Jumper open Jumper open Jumper open
VT-VSPA2-1-2X/V0/T1, .../T5 | Valve amplifier
J4 Jumper open
Clock frequency Setting by means Jumper 6 open
170 Hz 100 Hz ±10% 2) 170 Hz ±10% 190 Hz ±10% 2) 300 Hz ±10% 2) 180 Hz ±10% 2) 220 Hz ±10% 2)
J5, J6 closed of potentiometer f 100 Hz ±10% 2)
Maximum current
Setting by means 2) 2) 2) 2)
setting 1500 mA 600 mA 800 mA 1500 mA 1500 mA 2500 mA 2500 mA 1500 mA
of Gw+ and Gw–
J7 closed
Step level Setting by means 2) 2) 2) 2)
500 mA 200 mA 200 mA 500 mA 500 mA 350 mA 350 mA 500 mA
J8, J9 closed of S+ and S–
1) When using the amplifiers VT-VSPA2-1-2X/V0/... as replacement for the amplifier types VT 3000, VT 3006 and VT 3026, the supply voltage must lie between 28 and 30 VDC!
enquiries@hyquip.co.uk
+44 (0)1204 699 959
In all measurements, you must measure from the measuring socket "I" against "M0"!
www.hyquip.co.uk/web/index
For more information (characteristic curves, etc. …) refer to the data sheets specified above.
Please note:
The order of the following steps must imperatively be observed!
Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
+44 (0)1204 699 959
enquiries@hyquip.co.uk
www.hyquip.co.uk/web/index
REXROTH
-1 4Q T Gw+ S+ Gw- S-
J4 J10
Zw J9 J8
w1
w2
J3 J1
w3
w4 f
t1 J5
t2 J2
J6
t3 J7
t4
t5
012
EF
3456
BCD
Measuring
7 89 A
I w point selec-
tor switch
v
VSPA2
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
+44 (0)1204 699 959
enquiries@hyquip.co.uk
www.hyquip.co.uk/web/index
Modification work
▶ VT-VSPA2-1-2X/V0/T1 serves as replacement for: The following modification work must be made before the
– VT 3000, VT 3013, VT 3014, VT 3026, exact adjustment of the VT-VSPA2-1-2X/V0/T1 or T5:
VT-VSPA2-1-1X/T1, VT-VSPA2-50-1X/T1 ▶ Card holder replacement:
When replacing one of the amplifiers listed on the left
▶ VT-VSPA2-1-2X/V0/T5 serves as replacement for: by the amplifiers VT-VSPA2-1-2X/V0/T1 and T5, the
– VT 3006, VT 3017, VT 3018, VT-VSPA2-1-1X/T5, existing card holder with the DIN female multipoint
VT-VSPA2-50-1X/T5 connector VT 3002-1-2X/32D must be additionally
replaced by a card holder with the female multipoint
connector VT 3002-1-2X/48F.
▶ Carry out the re-wiring according to the following table.
Re-wiring table
VT-VSPA2-1-2X/V0/T1 VT-VSPA2-1-2X/V0/T5
Terminal VT30... VT-VSPA2...1X Terminal Terminal
2a Output switch-over ±9 V Not available 1) Not available 1)
Table 2: Re-wiring
1) If the relevant function has previously been used, please refer to your sales contact partner.
The individual functions that are assigned to the relevant terminals are shown in the block diagrams on the follow-
ing pages.
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
Positive command
value controls
solenoid "B".
X1 Current command value at "w" X1
Negative command
0 to +6 V for solenoid "A"
value controls 14c
Ramp external 0 to –6 V for solenoid "B"
solenoid "A". 14a 8
Actual current value IA at "IA"
12c Actual current value IB at "IB"
Command value 5 ±6 V
12a F Pilot current
Command value 4 ±9 V w solenoid "A"
8a 7
Command value 3 ±9 V F 30a
10a F IA 7
Command value 2 ±9 V t u
10c i 24a
Command value 1 ±9 V F F F F 1 S
R1 R2 R3 R4 5 Solenoid "A"
K5
3 4 6
F
1 S IB
K4.1 S
K3.1 J5, J6
K1.1 K2.1
2 22a
16a F
Command value 6 u 9 i
Differential input 16c H12 u 28a
Reference potential u S Solenoid "B"
7
7
K6 Pilot current
2a
Auxiliary voltage ±9 V solenoid "B" 18a Command value
+
10 after ramp
20c 32a
Measurement zero (M0) is + 9 V =
increased by 9 V as compared to M0
20a F 2,5 A T 32c + UB
26c H11
the 0 V operating voltage 9 V 2200 µF Operating voltage
1 F
8c K1 H1 26a
Call-up command value 1 0V
4a K2 H2 F
Call-up command value 2
6a
enquiries@hyquip.co.uk
K3 H3 F
+44 (0)1204 699 959
28c
Relay call-up voltage (+24 V)
1 Command values
2 Differential input
3; 6 Summing device
H1 to H4 Display of the command value call-ups K1 to K6 Call-up relay
4 Ramp generator
H11 "power on" R1 to R4 Command values
5 Step function generator
H12 "Ready for operation" t Ramp time F = on front plate
Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
Valve amplifier | VT-VSPA2-1-2X/V0/T1, .../T5
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
9 Monitoring
10 Mains adapter
6/12
solenoid "B". 0 to –6 V for solenoid "B"
X1 X1
Negative command K1.2 K2.2 Actual current value IA at "IA"
value controls K3.2 Actual current value IB at "IB"
K4.2
solenoid "A". 14c F F F F F
Ramp external t5 t1 t2 t3 t4 8
14a
3 4 6
F
M0 H11 2,5 A T
26c Operating voltage
to the 0 V operating voltage 9 V
1 F
8c K1 H1 26a
Call-up command value 1 0V
4a K2 H2 F
Call-up command value 2 F
6a K3 H3
Call-up command value 3 F
6c K4 H4
Call-up command value 4
18c K5
enquiries@hyquip.co.uk
+44 (0)1204 699 959
Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
Positive command value Current command value at "w"
(0 V to 10 V 0 to +6 V for solenoid "A"
or 0 to –6 V for solenoid "B"
12 mA to 20 mA) X1 Actual current value IA at "IA" X1
8
controls solenoid "B". 14c Actual current value IB at "IB"
Ramp external 14a F
w Ba
12c 8
Command value 5 ±6 V F 7 30a
12a Gwa u
Negative command value Command value 4 ±9 V IA
(–10 V to 0 V 8a t F PI i 24a
Command value 3 ±9 V Solenoid "A"
or 10a 1 5
Command value 2 ±9 V K5
4 mA to 12 mA) 10c
Command value 1 ±9 V F F F F
controls solenoid "A". R1 R2 R3 R4
3 4 6 IB F
K4 å å
K3
K1 K2 J5, J6
18a Zw Gwb 7
Command value after ramp Solenoid "B"
22a
16c PI i
Command value 6 u/i 28a
Differential input 16a u
Reference potential u 2 11
+ UB J1
J4 10 8
=1 Bb
J7: Enable internal J7
30c
Enable external (+UB)
F 2c
H11 "Ready for operation"
Block diagram/pin assignment VT-VSPA2-1-1X/T1
2a K6 10 F
Auxiliary voltage ±9 V H12
+ =1 32c
9 3,15 AT
Measurement zero (M0) is increased + 9 V 20c 32a + UB
20a =
by 9 V as compared M0
to the 0 V operating voltage 9 V 26c Operating voltage
2200 µF
8c K1 1 H1 F 26a
0V
Call-up command value 1 F
4a K2 H2
Call-up command value 2
6a K3 H3 F
Call-up command value 3
enquiries@hyquip.co.uk
+44 (0)1204 699 959
6c K4 H4 F
Call-up command value 4 1 Command values
18c K5
Call-up "Ramp off" 2 Differential input
4c K6
Call-up "Switch-over auxiliary voltage" 28c 3; 6 Summing device
Relay call-up voltage (+24 V)
www.hyquip.co.uk/web/index
4 Ramp generator
5 Step function generator
7 PI current controller
H1 to H4 LED display of the command value call-ups Zw Zero point command value
8 Output stage with clock generator
K1 to K6 Call-up relay Ba Pilot current solenoid "A" F = on front plate
9 Power supply unit
R1 to R4 Command values Bb Pilot current solenoid "B"
10 Monitoring
Gwa Command value attenuator solenoid "A" t Ramp time
Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
Valve amplifier | VT-VSPA2-1-2X/V0/T1, .../T5
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
RE 30110-Z, edition: 2013-09, Bosch Rexroth AG
7/12
Positive command value Current command value at "w"
(0 V to 10 V 0 to +6 V for solenoid "A"
8/12
or X1 K1.2 K2.2 0 to –6 V for solenoid "B" X1
12 mA to 20 mA) K3.2 K4.2 Actual current value IA at "IA" 8
controls solenoid "B". 14c Actual current value IB at "IB"
F F F F F
Ramp external 14a t5 t1 t2 t3 t4
F
w Ba
12c 8
Negative command value Command value 5 ±6 V F 7 30a
12a Gwa u
(–10 V to 0 V Command value 4 ±9 V IA
8a PI i 24a
or Command value 3 ±9 V Solenoid "A"
10a 1 5
4 mA to 12 mA) con- Command value 2 ±9 V K5
10c
trols solenoid "A". Command value 1 ±9 V F F F F
R1 R2 R3 R4
3 4 6 IB F
K4 å å
K3 J5, J6
K1 K2
Command value after ramp 18a Zw 7
30c
Enable external (+UB)
F 2c
H11 "Ready for operation"
Block diagram/pin assignment VT-VSPA2-1-1X/T5
2a K6 10 F
Auxiliary voltage ±9 V H12
+ =1 32c
9 3,15 AT
20c 32a + UB
Measurement zero (M0) is increased + 9 V =
20a
by 9 V as compared M0
26c Operating voltage
to the 0 V operating voltage 9 V 2200 µF
8c K1 1 H1 F 26a
Call-up command value 1 0V
4a K2 H2 F
Call-up command value 2
6a K3 H3 F
Call-up command value 3
6c K4 H4 F
Call-up command value 4 1 Command values
18c K5
Call-up "Ramp off" 2 Differential input
enquiries@hyquip.co.uk
+44 (0)1204 699 959
4c K6
Call-up "Switch-over auxiliary voltage"
28c 3; 6 Summing device
Relay call-up voltage (+24 V)
4 Ramp generator
5 Step function generator
www.hyquip.co.uk/web/index
7 PI current controller
H1 to H4 LED display of the command value call-ups Zw Zero point command value
8 Output stage with clock generator
K1 to K6 Call-up relay Ba Pilot current solenoid "A"
9 Power supply unit
R1 to R4 Command values Bb Pilot current solenoid "B"
10 Monitoring
Gwa Command value attenuator solenoid "A" t1 to t5 Ramp times
11 Cable break monitoring F = on front plate
Gwb Command value attenuator solenoid "B"
(only with 4 to 20 mA)
Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
Positive command value Current command value at "w"
(0 V to 10 V 0 to +6 V for solenoid "A"
or 0 to –6 V for solenoid "B"
X1 X1
12 mA to 20 mA) Actual current value IA at "IA"
14c
8
controls solenoid "B". Actual current value IB at "IB"
Ramp external 14a
F
Negative command value w Ba (R7)
12c 8
(–10 V to 0 V Command value 5 ±6 V F 7 30a
12a u
or Command value 4 ±9 V IA
Solenoid "A"
8a i 24a
4 mA to 12 mA) Command value 3 ±9 V t F PI
10a 1 5
controls solenoid "A". Command value 2 ±9 V K5
10c
Command value 1 ±9 V F F F F
R1 R2 R3 R4
3 4 6 IB F
K4 å å
K3
K1 K2 J5, J6
18a Zw 7
Command value after ramp (R6) 22a
16c PI i
Command value 6 u/i Solenoid "B"
Differential input 16a u 28a
Reference potential/GND u 2 11
+ UB J1
J4 10 8
Bb (R8)
J7: Enable internal =1
J7
30c
Enable external (+UB)
F 2c "Ready for operation"
H11
2a K6 10 F
Block diagram/pin assignment VT-VSPA2-50-1X/T1
6c K4 H4 F 1 Command values
Call-up command value 4
18c K5
Call-up "Ramp off" 2 Differential input
4c K6
Call-up "Switch-over auxiliary voltage" 3; 6 Summing device
28c
Relay call-up voltage (+24 V)
www.hyquip.co.uk/web/index
4 Ramp generator
5 Step function
7 PI current controller
H1 to H4 LED display of the command value call-ups Zw (R6) Zero point command value
8 Output stage with clock generator
K1 to K6 Call-up relay Ba (R7) Pilot current solenoid "A"
9 Power supply unit
R1 to R4 Command values Bb (R8) Pilot current solenoid "B"
10 Monitoring
t Ramp time
Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
Valve amplifier | VT-VSPA2-1-2X/V0/T1, .../T5
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
RE 30110-Z, edition: 2013-09, Bosch Rexroth AG
9/12
Positive command value Current command value at "w"
(0 V to 10 V 0 to +6 V for solenoid "A"
10/12
or K1.2 K2.2 0 to –6 V for solenoid "B"
X1 X1
12 mA to 20 mA) K3.2 K4.2 Actual current value IA at "IA"
14c 8
controls solenoid "B". F F F F F Actual current value IB at "IB"
Ramp external t5 t1 t2 t3 t4
14a
F
w Ba (R7)
Negative command value 12c 8
Command value 5 ±6 V F 7 30a
(–10 V to 0 V 12a u
Command value 4 ±9 V IA
Solenoid "A"
or 8a i 24a
Command value 3 ±9 V PI
4 mA to 12 mA) 10a 1 5
Command value 2 ±9 V K5
controls solenoid "A". 10c
Command value 1 ±9 V F F F F
R1 R2 R3 R4
3 4 6 IB F
K4 å å
K3
K1 K2 J5, J6
18a Zw
J7
30c
Enable external (+UB)
F 2c "Ready for operation"
H11
2a K6 10 F
Block diagram/pin assignment VT-VSPA2-50-1X/T5
7 PI current controller
H1 to H4 LED display of the command value call-ups Zw (R6) Zero point command value
8 Output stage with clock generator
K1 to K6 Call-up relay Ba (R7) Pilot current solenoid "A"
9 Power supply unit
R1 to R4 Command values Bb (R8) Pilot current solenoid "B"
10 Monitoring
t1 to t5 Ramp times
11 Cable break monitoring F = on front plate
(only with 4 to 20 mA)
Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
+44 (0)1204 699 959
enquiries@hyquip.co.uk
www.hyquip.co.uk/web/index
Commissioning
Step 4.1: Apply +10 V at pin b14 and connect pin b16
with 0 V.
Using the Gw+ potentiometer, set the
maximum current according to table 1.
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
+44 (0)1204 699 959
enquiries@hyquip.co.uk
www.hyquip.co.uk/web/index
Notes
© This document, as well as the data, specifications and other information set
forth in it, are the exclusive property of Bosch Rexroth AG. It may not be
reproduced or given to third parties without its consent.
The data specified above only serve to describe the product. No statements
concerning a certain condition or suitability for a certain application can be
derived from our information. The information given does not release the user
from the obligation of own judgment and verification. It must be remembered
that our products are subject to a natural process of wear and aging.
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389