Content
1. Warnings·
······
····
·······
····
······
·····
·····
·····
···
·······
····
·· ··2
····
4. Wiring diagram·
·····
······
····
···
···
·····
···
·······
····
······
···
···
····
··5
9. Functional parameters····
·····
··········
···
·······
····
······
···
···
·····
·12
-1-
AUTOMATIZACIÓN DE SISTEMAS Y PROCESOS INDUSTRIALES ASM S.A. DE C.V
RFC.: ASP100409TR2
asmx
DE LAS DUNAS #44 COL. RESIDENCIAL ACUEDUCTO C.P. 07279 MÉXICO D.F.
Tel: (55)5367-5105; (55)6363-8971
EMAIL: info@asmx.com.mx
MR
www.asmx.com.mx
1 Warnings
1.1 The adjustment, maintenance and inspection of this product must be carried
out by suitably trained personnel. Before operating this product, read the
information contained in this document carefully.
1.2 Before connecting the product to the power supply check that the product’s
requirement corresponds with the power supply available. Before starting any
work on electric/electronic components disconnect power from system.
1.3 Confusion between input terminal (L, N) and output terminal (U, V, W) would
damage this product.
1.4 A reliable ground connection is required to avoid electric shock. Failure to do
so could lead to injure.
1.5 Do not touch the control terminal with hand during power on. It may cause
electric shock.
1.6 Charging indicator light should be completely turned off and positive or
negative main line voltage should be under 36V when operating this product.
Failure to do so may cause electric shock.
1.7 Prevent screw, metal swarf, gasket and other foreign substance enter this
product. It may cause fire and damage property or fire.
1.8 Wrap and protect the end bare part of cable used in major circuit with
insulation tape. Failure to do so may cause damage property.
1.9 4SW control mode or encoder mode to connect cable can be selected. When
4SW control mode is selected, P43 parameter should be set. That is the
logical value of input four switches signal.
-2-
AUTOMATIZACIÓN DE SISTEMAS Y PROCESOS INDUSTRIALES ASM S.A. DE C.V
RFC.: ASP100409TR2
asmx
DE LAS DUNAS #44 COL. RESIDENCIAL ACUEDUCTO C.P. 07279 MÉXICO D.F.
Tel: (55)5367-5105; (55)6363-8971
EMAIL: info@asmx.com.mx
MR
www.asmx.com.mx
Remark: Connect No. 1 to 7 control terminal with non-voltage signal or open collector
signal. The voltage of signal end is +12 VDC, input common line 8 is 0V.
-3-
AUTOMATIZACIÓN DE SISTEMAS Y PROCESOS INDUSTRIALES ASM S.A. DE C.V
RFC.: ASP100409TR2
asmx
DE LAS DUNAS #44 COL. RESIDENCIAL ACUEDUCTO C.P. 07279 MÉXICO D.F.
Tel: (55)5367-5105; (55)6363-8971
EMAIL: info@asmx.com.mx
MR
www.asmx.com.mx
Power on 094
P06
Press “SET” button to confirm
-4-
AUTOMATIZACIÓN DE SISTEMAS Y PROCESOS INDUSTRIALES ASM S.A. DE C.V
RFC.: ASP100409TR2
asmx
DE LAS DUNAS #44 COL. RESIDENCIAL ACUEDUCTO C.P. 07279 MÉXICO D.F.
Tel: (55)5367-5105; (55)6363-8971
EMAIL: info@asmx.com.mx
MR
www.asmx.com.mx
4.Wiring diagram
External Signals
Input Common(COM)
8
Safety Sensor
L 5
INPUT SIGNAL
N
4
Close Signal(CLOSE)
ZKC01 VVVF 2
Open Signal(OPEN)
INVERTER 1
NO
A3
B3
NC
OUTPUT SIGNAL
MOTOR A2
Close Arrival Signal Output (DCL)
W
B2
V Arrival Signal Output Common(COM)
C2
U
A1
Open Arrival signal output (DOL)
B1
C1
Warning: When connecting the cable of open/close arrival signal output, to be sure that
logic status of door operator output and elevator controller input should be matched.
Factory setting of door operator is normal close output. Users select the corresponding
logic status according to actual situation of elevator controller. (Terminal A1)—open
arrival signal normal open output, (Terminal A2)—close arrival signal normal open output,
(Terminal C1-C2)—output common line.
-5-
AUTOMATIZACIÓN DE SISTEMAS Y PROCESOS INDUSTRIALES ASM S.A. DE C.V
RFC.: ASP100409TR2
asmx
DE LAS DUNAS #44 COL. RESIDENCIAL ACUEDUCTO C.P. 07279 MÉXICO D.F.
Tel: (55)5367-5105; (55)6363-8971
EMAIL: info@asmx.com.mx
MR
www.asmx.com.mx
Frequency Hold
d17 d32 OPEN hold
d19
wait
current d40
time
d45 Hold operation
d33
d20
d30
d29 d16
p02 d43
d15 d21
d28
DOOR area 2 3 4 6 7 8 9
OPEN signal
CLOSE signal
OPEN arrival
signal
OPEN speed
change signal
CLOSE speed Note) The speed change does not occur
change signal with the CLOSE speed change signal.
CLOSE arrival
signal
Start timer d47
Open curve
Caution:
(1) Open arrival hold frequency is d21, hold current is d40. Hold time is d42, range from 0.1 to 999
(sec). Hold state will be keep if set time to 0.
(2) Frequency in high speed general set as one step. I.e. set parameter d17=d19. The parameter
acceleration/deceleration d32 which between d17 and d19 will doesn’t work.
(3) Increase P05 value properly can improve door motor torque during the low speed. Caution: It
will cause over current 、over load fault or over heating protection if the parameter P05 value set
too high.
-6-
AUTOMATIZACIÓN DE SISTEMAS Y PROCESOS INDUSTRIALES ASM S.A. DE C.V
RFC.: ASP100409TR2
asmx
DE LAS DUNAS #44 COL. RESIDENCIAL ACUEDUCTO C.P. 07279 MÉXICO D.F.
Tel: (55)5367-5105; (55)6363-8971
EMAIL: info@asmx.com.mx
MR
www.asmx.com.mx
d27
d36
d35 p02 d44
d22 d14
d34
DOOR area 10 11 12 14 15 0 1
OPEN signal
CLOSE signal
OPEN arrival
signal
OPEN speed Note) The speed change does not occur
change signal with the OPEN speed change signal.
CLOSE speed
change signal
CLOSE arrival
signal
Start timer d49
Close curve
Caution:
(1) Close arrival hold frequency is d14, hold current is d41. Hold time is d42, range from 0.1 to 999
(sec). Hold state will be keep if set time to 0.
(2) Frequency in high speed general set as one step. I.e. set parameter d24=d26. At this time
acceleration/deceleration d32 which between d24 and d26 doesn’t work.
(3) Increase P05 value properly can improve close door motor torque during the low speed. Caution:
It will cause over current 、over load fault or over heating protection if the parameter P05 value
set too high.
-7-
AUTOMATIZACIÓN DE SISTEMAS Y PROCESOS INDUSTRIALES ASM S.A. DE C.V
RFC.: ASP100409TR2
asmx
DE LAS DUNAS #44 COL. RESIDENCIAL ACUEDUCTO C.P. 07279 MÉXICO D.F.
Tel: (55)5367-5105; (55)6363-8971
EMAIL: info@asmx.com.mx
MR
www.asmx.com.mx
Open operation
d18 Hold
d19 wait OPEN hold
d17 current d40
d33
time
d31 d32
d45 Hold operation
d30 d20
d29
d16 d43
d15 d21
d28
2 3 4 5 6 7 8 9
d02 d03 d04 d05 d06 d07 d08
ON
ON
ON
ON
100%
0%
Open curve
Caution:
(1) Open arrival hold frequency is d21, hold current is d40. Hold time is d42, from 0.1 to 999 (sec).
Hold state will be keep if set time to 0.
(2) Frequency in high speed general set as one length. I.e. set parameter d17=d18=d19. At this
time acceleration/deceleration d31 and d32 which between d17and d19 doesn’t work.
(3) Increase P05 value properly can improve open door motor torque during the low speed. Caution:
It will cause over current 、over load fault or over heating protection if the parameter P05 value
set too high.
-8-
AUTOMATIZACIÓN DE SISTEMAS Y PROCESOS INDUSTRIALES ASM S.A. DE C.V
RFC.: ASP100409TR2
asmx
DE LAS DUNAS #44 COL. RESIDENCIAL ACUEDUCTO C.P. 07279 MÉXICO D.F.
Tel: (55)5367-5105; (55)6363-8971
EMAIL: info@asmx.com.mx
MR
www.asmx.com.mx
d25 Hold
d26 CLOSE hold
d24 wait current d41
d37 d38 d39 time
d46 Hold operation
ON
ON
ON
ON
100%
0%
Close curve
Caution:
(1) Close end holding frequency is d14, holding current is d41. Holding time is d42, from 0.1 to 999
(sec). Holding will be keep if set time to 0.
(2) Frequency in high speed general set as one length. I.e. set parameter d24=d25. At this time
acceleration/deceleration d37 which between d24 and d25 doesn’t work.
(3) Increase P05 value properly can improve open door moment during low speed. Caution: It will
cause over current 、over load fault or over heating protection if the parameter P05 value set too
high.
-9-
AUTOMATIZACIÓN DE SISTEMAS Y PROCESOS INDUSTRIALES ASM S.A. DE C.V
RFC.: ASP100409TR2
asmx
DE LAS DUNAS #44 COL. RESIDENCIAL ACUEDUCTO C.P. 07279 MÉXICO D.F.
Tel: (55)5367-5105; (55)6363-8971
EMAIL: info@asmx.com.mx
MR
www.asmx.com.mx
7 Basic adjustment 1
Functional parameters have been pre-set before door inverter leave factory. User can
adjust open/close door curve parameters according to actual need.
Steps:
(1) Set control mode as panel button mode: P08=1,P09=1or 4.
(2) Adjust open/close door curve parameter refer to open/close curve and relative
parameter.
(3) Press ▲ or ▼ to check open/close door curve.
(4) Set control mode as terminal control mode: P08=2(Factory setting)
8 Basic adjustment 2
Please confirm following steps when change motor connect cables, change speed
or open/close end switches logic value (NO/NC)
8.1 confirm parameter n16, n17 (input /output signal monitor)
Parameter n16 is input signal monitor, include ① ~⑨ 。
Parameter n17 is output signal monitor; include open arrival output, close arrival
output and fault output.
Caution: Monitor signal ⑤ 、⑧ 、⑨ has not been defined before leave factory, can not
monitor here
① ―――Open door command signal/ RY3 output signal [parameter P48 setting]
② ―――Close door command signal/ RY2 output signal [parameter P49 setting]
③ ―――Open arrive signal/ RY1 output signal [parameter P50 setting]
④ ―――Close arrive signal
⑤ ―――Light cell/ safety edge signal
⑥ ―――Open door speed change signal
⑦ ―――Close door speed change signal
- 10 -
AUTOMATIZACIÓN DE SISTEMAS Y PROCESOS INDUSTRIALES ASM S.A. DE C.V
RFC.: ASP100409TR2
asmx
DE LAS DUNAS #44 COL. RESIDENCIAL ACUEDUCTO C.P. 07279 MÉXICO D.F.
Tel: (55)5367-5105; (55)6363-8971
EMAIL: info@asmx.com.mx
MR
www.asmx.com.mx
Switch to n parameter mode by pressing “MODE” key. Then press ▲ or ▼ key to get
corresponding monitor parameter. Input/output signal status can be seen if you
press “SET”.
8.2 Confirmation of input terminal logic (NO/NC) setting. Push door to open arrival position
to measure switches status before setting input switches logic value.
Switches input signal logic setting parameter―――P43
8.2.1 Setting value: 1―――This signal will effective when input signal terminal and input
common line connection is normal close (NC).
0―――This signal will effective when input signal terminal and input
common line connection is normal open (NO).
8.2.2 Setting method: 0――15bit decimal input
Setting value*weight=Amount (use it as setting value)
For example: If set open speed change input signal, close speed change input signal,
open arrive input signal and close arrive input signal to NC, others are NO, setting value
will be 1×16+1×8+0×4+1×2+1×1=27
- 11 -
AUTOMATIZACIÓN DE SISTEMAS Y PROCESOS INDUSTRIALES ASM S.A. DE C.V
RFC.: ASP100409TR2
asmx
DE LAS DUNAS #44 COL. RESIDENCIAL ACUEDUCTO C.P. 07279 MÉXICO D.F.
Tel: (55)5367-5105; (55)6363-8971
EMAIL: info@asmx.com.mx
MR
www.asmx.com.mx
9. Functional parameters
Function list include “P area parameter P01~P79 and d area parameter d00~d53.
P area parameter: P01~79
No. Functional descriptions Setting range Factory
data
P01 No function
P02 Enter holding decelerate time(S) 0-999 0.3
P03 No function
P04 V/F curve 0(constant torque mode) 0
1(square torque mode)
- 12 -
AUTOMATIZACIÓN DE SISTEMAS Y PROCESOS INDUSTRIALES ASM S.A. DE C.V
RFC.: ASP100409TR2
asmx
DE LAS DUNAS #44 COL. RESIDENCIAL ACUEDUCTO C.P. 07279 MÉXICO D.F.
Tel: (55)5367-5105; (55)6363-8971
EMAIL: info@asmx.com.mx
MR
www.asmx.com.mx
- 13 -
AUTOMATIZACIÓN DE SISTEMAS Y PROCESOS INDUSTRIALES ASM S.A. DE C.V
RFC.: ASP100409TR2
asmx
DE LAS DUNAS #44 COL. RESIDENCIAL ACUEDUCTO C.P. 07279 MÉXICO D.F.
Tel: (55)5367-5105; (55)6363-8971
EMAIL: info@asmx.com.mx
MR
www.asmx.com.mx
- 14 -
AUTOMATIZACIÓN DE SISTEMAS Y PROCESOS INDUSTRIALES ASM S.A. DE C.V
RFC.: ASP100409TR2
asmx
DE LAS DUNAS #44 COL. RESIDENCIAL ACUEDUCTO C.P. 07279 MÉXICO D.F.
Tel: (55)5367-5105; (55)6363-8971
EMAIL: info@asmx.com.mx
MR
www.asmx.com.mx
D area parameter:d00~d53
No. Function description Setting range Factory data
d00 No function
d01 setting value of door width 0-65535 14.2
d02 Close arrival position (%) 0-100 4
d03 Open speed change position 1 0-100 6
(%)
d04 Open speed change position 2 0-100 15
(%)
d05 Open speed change position 3 0-100 22
(%)
d06 Open speed change position 4 0-100 60
(%)
d07 Open speed change position 5 0-100 75
(%)
d08 Open arrival position (%) 0-100 94
d09 Close speed change position 1 0-100 90
(%)
d10 Close speed change position 2 0-100 86
(%)
d11 Close speed change position 3 0-100 75
(%)
d12 Close speed change position 4 0-100 35
(%)
d13 Close speed change position 5 0-100 20
(%)
d14 Close arrival hold frequency 0-250 2
(Hz)
d15 Open frequency 1 (Hz) 0-250 4
d16 Open frequency 2 (Hz) 0-250 6
d17 Open frequency 3 (Hz) 0-250 30
d18 Open frequency 4 (Hz) 0-250 30
d19 Open frequency 5 (Hz) 0-250 30
d20 Open frequency 6 (Hz) 0-250 4
d21 Open arrival hold frequency 0-250 2
(Hz)
d22 Close frequency 1 (Hz) 0-250 8
d23 Close frequency 2 (Hz) 0-250 26
d24 Close frequency 3 (Hz) 0-250 26
d25 Close frequency 4 (Hz) 0-250 26
- 15 -
AUTOMATIZACIÓN DE SISTEMAS Y PROCESOS INDUSTRIALES ASM S.A. DE C.V
RFC.: ASP100409TR2
asmx
DE LAS DUNAS #44 COL. RESIDENCIAL ACUEDUCTO C.P. 07279 MÉXICO D.F.
Tel: (55)5367-5105; (55)6363-8971
EMAIL: info@asmx.com.mx
MR
www.asmx.com.mx
- 16 -
AUTOMATIZACIÓN DE SISTEMAS Y PROCESOS INDUSTRIALES ASM S.A. DE C.V
RFC.: ASP100409TR2
asmx
DE LAS DUNAS #44 COL. RESIDENCIAL ACUEDUCTO C.P. 07279 MÉXICO D.F.
Tel: (55)5367-5105; (55)6363-8971
EMAIL: info@asmx.com.mx
MR
www.asmx.com.mx
(s)
d50 CLOSE deceleration timer(SW 0-3 0.1
mode) (s)
d51 No function
d52 Door width measurement 0.5-250 10
frequency (Hz)
d53 Door position percent value 0-100 0
output setting
- 17 -
AUTOMATIZACIÓN DE SISTEMAS Y PROCESOS INDUSTRIALES ASM S.A. DE C.V
RFC.: ASP100409TR2
asmx
DE LAS DUNAS #44 COL. RESIDENCIAL ACUEDUCTO C.P. 07279 MÉXICO D.F.
Tel: (55)5367-5105; (55)6363-8971
EMAIL: info@asmx.com.mx
MR
www.asmx.com.mx
10.2 Troubleshooting
Display Details and cause of fault Remedies
Over current during acceleration ·Check for an open output phase and
Over current during constant Eliminate sudden changes inload
speed ·Increase the acceleration/deceleration
Over current during deceleration times
OC
·Adjust the torque boost level
·Check the restart in inertia
·Do not switch the electromagnetic
contactor at the load side.
·Excessive internal DC voltage ·Increase the acceleration time
during acceleration
·Excessive internal DC voltage ·Eliminate excessive changes in load
OU
during acceleration
·Excessive internal DC voltage ·Increase the deceleration time
during constant speed
·Power supply voltage drops to ·Measure the power supply voltage and
LU less than 85% of rating Check output open-phase
- 18 -
AUTOMATIZACIÓN DE SISTEMAS Y PROCESOS INDUSTRIALES ASM S.A. DE C.V
RFC.: ASP100409TR2
asmx
DE LAS DUNAS #44 COL. RESIDENCIAL ACUEDUCTO C.P. 07279 MÉXICO D.F.
Tel: (55)5367-5105; (55)6363-8971
EMAIL: info@asmx.com.mx
MR
www.asmx.com.mx
If forget too many changed parameters, user can renew the parameters to factory setting.
Detail step as following:
1. Initialize parameter: settingP42=1。
2. Adjustment open/close door curve (follow basic adjustment 1step).
- 19 -
AUTOMATIZACIÓN DE SISTEMAS Y PROCESOS INDUSTRIALES ASM S.A. DE C.V
RFC.: ASP100409TR2
asmx
DE LAS DUNAS #44 COL. RESIDENCIAL ACUEDUCTO C.P. 07279 MÉXICO D.F.
Tel: (55)5367-5105; (55)6363-8971
EMAIL: info@asmx.com.mx
MR
www.asmx.com.mx
Note1.) When the door width is being mesured,start the operation after ensuring that there
is no obstacle on the way.If there is obstacle on the way, the position where the
obstacle is located is determined to be the arrival position. So the measurement
cannot be made correctly.
Note2.) Set the encoder constant of P52 correctly.
Setting data
Non
Energize
energize Function Conditions for relay to turn ON
in
in
on-state
on-state
0 r0 Run signal ON when run signal is ON or during inverter output
1 r1 Reverse run signal ON when the inverter is running in reverse.
2 r2 Arrival signal ON when the output frequency is within the setting frequency
2 Hz
3 r3 Overload alarm ON when the output current is 140% of the reference
current(3.6A) or higher or when the electronic thermal level
is reached.
4 r4 OPEN arrival signal The detection position of the encoder is in ON hold area or
OPEN arrival signal is turned ON.
5 r5 CLOSE arrival signal The detection position of the encoder is in OFF hold area or
CLOSE arrival signal is turned ON.
6 r6 Obstacle detection ON when fault ON operation of obstacle detection
signal
7 r7 Fault alarm ON when the inverter is in the fault trip state.
16 r16 Door position output Setting door position percent output function. ( position
[Encoder mode] percent value set by parameter d53)
- 20 -