SINGLE LINE DIAGRAM

BUS A

BUS B

M M 89 M 89 M 89 M 89 M 89 M 89 M 89

VT VT L IL

Bus coupler breaker,


L L 2000A
Bus VT change
over switch over voltage LCB, 2000A GCB ,2000A
prot.(59)
Spare
Distance Current Differential CT6
protection (21) CT8 Cable Prot.(Main) 1000/750/350/1A
Auto reclose 11 CL11
1000 / 1A 15 CT15
CT5 F50/51
350 / 1A CT9
Distance /over Over current
voltage prot. CT7 1000 / 1A
12 CL12 14 CT14 / Earth Fauit
Synchro 1000 / 1A CT4 Spare
Trip
check 350 / 1A
CT6
relay (25) Bus bar Protection
CT6 Current Differential 1000/750/350/1A
Meter -1 13 CL13
1000 / 1A Low Impedance/breaker 13 CT13
CT3 Cable Prot.(Back Up)
failure relay (Main) 350 / 1A CT2
Meter -2 2000 / 1A
14 12 CT12CT2
Details of functions used CT2 Bus bar Protection 2000 / 1A CT2
in distance protection 2000 / 1A High Impedance 2000 / 1A
relay Check Zone
15 11 CT11
CT1 2000
1. Phase distance . CT1 / 1A
protection 2000 / 1A
2. Earth fault distance . O O
protection
F F
3. Directional earth fault
4. SOTF C C
5. Weak in feed PUP IL
6. Power swing block IL
7. Out of step locking M
Isolator
8. Fault locator

HES
SA
BUS COUPLER

420KV
PLCC
Wave trap X C
L A
M
P B
E L
E
LA
CVT
336V, 20KA
CT7(1)
350 / 1A
07

06 CT06
CT6(2) Current Differential
350 / 1A Cable Prot.(Back Up)
Special
Energy 05 CT05
CT5(3)
Meter 350 / 1A

CT4 04

Please register
LINE FEEDER
PDFcamp on http://www.verypdf.com/, thank you. 350 / 1A

CT3 (5)
Current Differential
Cable Prot.(Main)
350/ 1A 03

NCT1 NCT2 64-R


350 / 1A 350/ 1A
70 MVA
01 02 GT CS04
50-51 50/51 Measuring
2500/5A 04

CS01 CS02 CS03 CS05 CS06 CS07


150/5A 10000/1
CS02 10000/1
CS03 2500/5A 2500/5A
CS06 2500/5A
01 02 03 05 06 07
MTR - A
UAT Transformer

01 02 03
CE01
10000/1 CE02 Ext. 415/ /3 :
CE03
10000/1 Transformer 110/ /3
200/5A

MTR - B
Details of functions used Transformer A VG04 50VA VG03 50VA VG02
& B protection relay 50VA 50-51E
V
1. Generator -Trans. Over all differential . 13.8/ /3:110/ / 3
protection (87GT)
2. G/T Restricted earth fault protection (64R)
3. Time delay neutral O/C relay (51N)
Metering SCR-2
11 CG11
CG11
10000 / 5A 2000A

CG10
10 CG10
10000 / 5A SCR-1
2000A AC 415V - 50Hz
AVR/ CG9CG9
MCR 9
10000 / 5A

64F
GEN, Excitation System
189MVA,13.8K 41
V,50HZ,0.9 pf,
Details of functions used GEN A & B 214.3rpm DR
220V
protection relay CG7 DR DC
0.9 Ohm
5000 / 5A batter
1.Generator phase differential protection . y
7 87 S Inter turn
(87G) GEN - B
Protection 8 Dtff. Prot.
2. Generator phase fault impedance (21G) . CG8
backup 5000 / 5A
3. Reverse power (32)
4. Loss of field (40) Metring 6
CG6
5. Negative phase sequence O/C relay (46) GEN - A 10000 / 5A
6. Instantenious O/C relay (50) backup Protection
7. Inverse Time delay O/c relay (51) Spare CG5CG5
5
8. Out of step protection (78) 10000 / 5A
9. VT fuse failure monitoring relay (60-1), (60-2)
10. 95% stator ground fault (59N) (64-G2) ROTOR
11. 100% stator ground fault (27TN) (64-G1) 4 CG4CG4
12. Over/Under frequency protection (81) 10000 / 5A
13. Over voltage (59/59D)
14. Under voltage (27) 49 STATOR
CG3
CG3
15.Over fluxing relay (24) 3 51SH
16. Inadvertment energizing relay 50/27 10000 / 5A
Shaft CT ratio
2 CG2CG2 500/1
10000 / 1A S
H
A
CG1CG1
1 F
10000 / 1A
T
Isolator

N 13.8KV/240V, Single
phase Transrormer
G
R