AHMEDABAD, GUJARAT
Sr.
Comments Response SPPL Comments
No.
According to your mail all We Will update once we have
actuator have end switch for clearance on Point No. 2 & 3
1
open and close position which below.
needs to show in P&ID.
In this Project all instrument As discussed with Mr. Towhid, As per contract you have
items must be ATEX/IECEx one SOV with POC can be to provide us all SOV and
certified and suitable for Zone 2 introduced at upstream of diesel Flow regulator Control
(Class 1 Div 2). Without POC, pump for safety purpose. And no Valve with POC. As you are
not acceptable. We have need to change in existing not providing the POC type
procured same valve from arrangement of burner system as SOV, downstream of pump
China. for, Pressure Jet Burners, Fuel Oil in diesel line for high
Pressure is very high & SOV with pressure, then you must
POC in not available in that high provide us one SOV with
pressure segment. open/close limit switch
(mechanical POC) with
Only 1 Vendor (Honeywell – field indicator upstream of
Maxon) had agreed to provide the pump.
Oil side SOV valve as per your
2 given specification (SOV with As Techmotech is unable
POC, open close limit switch and to provide according to
local indication). Additional Price contract than the change
for such valve = Rs. 10,85,000. should comply the safety
Spare valve will be our burner requirement / norm of
vendor standard SOV. If spare is SPL. If there any price
required as per client’s impact for that SPL is not
specification, same additional liable. So there is no logical
price is applicable. ground that Thermotech
can claim the cost.
We prefer Client to procure this
valve from its Chinese vendor. If
client can give us its vendor
name, we can check price from
our side & revert back.
Page 1 of 3
The Attached manual of SOV Our Burner Vendor normally The SOV you offer is POC
for GAS don't have POC and provide SOV with POC in gas line by electronics Proximity
valve status Indication. as per specification we switch. So, this SOV is ok if
submitted earlier. you provide us the gas
For Special requirement of client regulator Control valve
on SOV with POC + open/close with POC. But if the gas
limit switch & local indication, regulator Control valve
our Burner Vendor is not don’t have POC then you
advising to install the same as it must provide us with
is old models & further spares (mechanical POC)
availability is also concern. Open/close limit switch
The earlier proposed valves by and field indicator.
us is new series of supplier & its
parts availability is guaranteed As per contract all SOV of
with our vendor. Pilot line should be POC
type.
As discussed with Mr. Tohliq, we
have to provide SOVs (SOV-5-6,
5-7 & 5-11) as per their special
requirement & specification (SOV
with POC, open close limit switch
and local indication) in off gas
3
main line.
This special valves are available
with only 1 vendor : Honeywell
– Maxon & its total price
including 1 spare SOV as per
spare item list = Rs. 53,88,000.
For Pilot gas line SOV (SOV-5-
16,5-17 & 5-18) with normal POC
(As proposed earlier) is
acceptable.
Page 2 of 3
We must need below input For SOV please give your Replied at point No 3
from SOV and CV for safety confirmation on point no. 2 and
operation of Burner: 3.
Vent valve close limit Switch
Vent valve open limit Switch
Prepared by,
Daxesh Patel
Page 3 of 3