POWER MA X,
THE NEW WINNING SOLUTION
FOR THE PL ANT ROOM

POWER MAX IS THE NEW Thanks to the countless possible


BERETTA SOLUTION AS MODULAR configurations as stand-alone or
CONDENSING WALL-HUNG BOILER cascade application up to 1120
SYSTEM Kw, POWER MAX is Beretta winning
solution both for new buildings and
Fully designed, developed and renovations, from energy retrofitting
industrialized by Beretta, complete to the replacement of old boiler
with all flue options, hydraulic and systems.
safety accessories, POWER MAX is The ease of mounting and the
the ideal choice for central heating maximum flexibility of installation,
systems of large domestic properties combined with high efficiency and low
and commercial buildings, like hotels, emissions, make this product stand out
sports centres, schools, office buildings, in the category of commercial and light
factories, etc. commercial appliances.

STAND-ALONE LINEAR CASCADE BACK-TO-BACK


CONFIGURATIONS CONFIGURATIONS CASCADE CONFIGURATIONS

3
LO W N OX C O M P L I A N T
CL ASS 6

NEW

C A S C A D E SYS T E M S
U P TO 112 0 K W

D I G I TA L
ELECTRONIC
CONTROL

PAT E N T E D
S TA I N L E S S S T E E L
H E AT E XC H A N G E R S

B U I LT- I N P U M P
U P TO 70 K W

WIDE RANGE OF
AC C E S S O R I E S

4
P O W E R M A X , A R E A L I N N O V AT I O N

POWER MAX IS AN INNOVATIVE thermal shock and increase the lifespan;


PRODUCT WITHIN BERETTA polluting emissions have been reduced
CONDENSING MODULAR SYSTEMS below the most stringent limits (Class 6
NOx according to UNI EN 15502); the system
All the components of the previous range control is 10 times faster than the previous
have been re-examined and redesigned: one. A new, wider range of accessories is also
the heat exchanger works with surface available as standard.
temperatures decreased by 18% to reduce

N E W PAT E N T E D C O N D E N S I N G H E AT E XC H A N G E R S
M A D E O F S TA I N L ES S S T EEL .

8 V E R S I O N S FR O M 3 4. 9 TO 131 K W, T H AT CA N B E
I N S TA L L E D I N S TA N D - A LO N E O R CA S CA D E
C O N FI G U R AT I O N .

P O S S I B L E CA S CA D E C O N F I G U R AT I O N S U P TO 112 0 K W
W I T H EM B E D D E D ‘ M A N AG I N G / D E PE N D I N G’ C O N T R O L
LO G I C S .

P O S S I B L E CA S CA D E C O N FI G U R AT I O N S W I T H F R A M E :
L I N E A R O R B AC K-TO - B AC K .

MODULATING AND MODULAR POWER REGULATION


W I T H AU TO M AT I C B U R N E R I G N I T I O N S EQ U E N C E R E V E R S A L .

S I M U LTA N E O U S M A N AG E M E N T O F T WO D I F F E R E N T
C I R C U I T S: D H W TA N K A N D H I G H T EM PER AT U R E . U P TO 16
A D D I T I O N A L M I X E D ZO N E S AVA I L A B L E A S AC C ES S O RY.

AU TO M AT I C S U M M E R / W I N T E R R E V E R S A L .

‘A N T I - L E G I O N E L L A’ F U N C T I O N A S S TA N DA R D.

S U I TA B L E FO R R E M OT E C O N T R O L M A N AG E M E N T
( 0 -10 V I N PU T O R M O D B U S) V I A O P T I O N A L K I T.

AVA I L A B I L I T Y O F A W I D E R A N G E O F SYS T E M AC C ES S O R I ES .

L P G C O N V E R S I O N K I T S U PPL I ED A S S TA N DA R D.

5
THE RANGE
The POWER MAX range is available in 8 models, starting from 34.9 kW up to 131 kW.
The installation can be stand-alone or it is possible to connect in cascade several POWER
MAX units of the same model until reaching a maximum output of 1.12 MW.

9 34,9
POWER MA X 50 P DEP
9 45
POWER MA X 50 P
14 57
POWER MA X 65 P
14 68
POWER MA X 80 P

19,4 90
POW E R M A X 10 0
19,4 97
P O W E R M A X 11 0
22,4 112
P O W E R M A X 13 0
26,2 131
P O W E R M A X 15 0

DEP MODEL INDICATES A REDUCED OUTPUT BOILER APPROVED BY THE MANUFACTURER.

P MODELS INDICATE THAT THE BOILERS ARE SUPPLIED AS STANDARD WITH A BUILT-IN CIRCULATION PUMP.

THE OTHER MODELS ALLOW TO INSTALL A CIRCULATION PUMP (AS OPTIONAL KIT) OR A 2-WAY VALVE,
OUTSIDE THE BOILER.

CH Flow CH Return Gas


Flue gas Air O I
Model outlet intake
F R G
O I

POWER MAX 50 P DEP 1” 1/2 1” 1/2 1” DN80 DN80

POWER MAX 50 P 1” 1/2 1” 1/2 1” DN80 DN80

POWER MAX 65 P 1” 1/2 1” 1/2 1” DN80 DN80

POWER MAX 80 P 1” 1/2 1” 1/2 1” DN80 DN80

R G F

POWER MAX 100 1” 1/2 1” 1/2 1” DN110 DN110

POWER MAX 110 1” 1/2 1” 1/2 1” DN110 DN110

POWER MAX 130 1” 1/2 1” 1/2 1” DN110 DN110

POWER MAX 150 1” 1/2 1” 1/2 1” DN110 DN110

6
H I G H O U T P U T F R O M C O M PAC T D I M E N S I O N S
POWER MAX stands out for its compact dimensions, a feature increasingly appreciated also in
the plant room, which further enriches the profile of high installation flexibility of the product.

1000/1165 mm

600 mm 435 mm

WIDTH HEIGHT DEPTH

600 mm 1000 mm 435 mm


for all models for the models: for all models
50 P DEP, 50 P, 65 P, 80
P, 100, 110

1165 mm
for the models: 130, 150
T E C H N O L O GY: C O M B U S T I O N
THE NEW HEAT EXCHANGER

POWER MAX heat exchanger, designed pressure drops and ensure the best heat
in absolute symbiosis with the pre-mixed transfer.
gas burner, represents one of the top This results in a more homogeneous “wall
technological advantages of the system. temperature”, which means longer lifespan
In fact, from a good synergy between and better performance. The pre-mixed
combustion and heat exchange derives the burner has also been designed to keep polluting
best transformation of the chemical energy emissions below the most restrictive European
of the fuel into useful heat energy to be limits, allowing POWER MAX to be in Class 6
transmitted to water. POWER MAX heat NOx according to UNI EN 15502, the best one.
exchanger is made of high quality stainless
steel so as to ensure its unchangeability and POWER MAX models feature two different
reliability over time. Design, water path and types of heat exchangers as in the following
flow sections have been optimised to limit tables.

VERSIONS UP TO 45 kW
POWER MAX 50 P DEP - 50 P

HELICAL HEAT EXCHANGER

MATERIAL: STAINLESS STEEL

SINGLE-TUBE WITH SMOOTH SURFACE

P-SHAPED PROFILE
FOR HIGH HEAT EXCHANGE

ADVANTAGES
Compact design.
No direct exposure of the plating to the flame,
which allows lower surface temperatures, with
subsequent reduction in heat loss.
Optimised profile:
- to fully exploit the whole available surface,
translating into increased exchange
surface;
- to facilitate condensate drainage,
preventing stagnation.
High reliability thanks to the use of steel with
great tube thickness (1.2 mm).

8
VERSIONS FROM 57 TO 131 KW
POWER MAX 65 P - 150

HELICAL HEAT EXCHANGER

MATERIAL: STAINLESS STEEL

DOUBLE TUBE, WITH SMOOTH


CONCENTRIC TUBES

FIVE-SIDED SHAPE PROFILE FOR


INTERNAL TUBE AND ROUND
SHAPE PROFILE FOR EXTERNAL
TUBE

HYDRAULIC CIRCULATION IN
PARALLEL

ADVANTAGES
Patented geometry heat exchanger,
consisting of two concentric smooth
stainless steel tubes, with pentagonal
internal section and circular external
section respectively, specifically designed
to maximise the exchange surface, offer
maximum resistance to corrosion and
allow the possibility of working with high
Δt (up to 40°C), thus reducing setup times.

9
19

01

18

02
03

17
04

16

15

05

14

06

07

08
13

09
12

10

11

R E P R E S E N TAT I V E I N T E R N A L V I E W O F
POWER MA X
( m o d e l s 6 5 P - 15 0 )

10
T E C H N O L O GY: T H E S T R U C T U R E
The heat module of POWER MAX is switch on the return tube to check the
designed for open flue operation, which minimum pressure and detect the return
can be converted to room-sealed flue, temperature (∆T control) for modulating
using the appropriate accessory. pump control (PWM).
All models are provided with flowmeter for The flue gas temperature probe checks
control of the minimum flow rate on the the correct operation and the request for
delivery tube, and a minimum pressure cleaning of the heat exchanger, if any.

KE Y

01 FLUE GAS ANALYSIS OUTLET

02 FLUE GAS CONNECTION

03 GAS VALVE

04 FAN

05 COMBUSTION CHAMBER 20

06 ELECTRICAL PANEL

07 FLUE GAS CLAPET VALVE

08 DRAIN TAP

09 MINIMUM PRESSURE SWITCH


CALIBRATED AT 0.7 BAR
21
10 CIRCULATION PUMP
(FITTED AS STANDARD ON P MODELS,
AVAILABLE AS AN ACCESSORY FOR
THE OTHER MODELS)
20 EXPANSION VESSEL
11 FLOWMETER
21 3-WAY VALVE
12 FLUE GAS PROBE

13 RETURN PROBE

14 CONTROL PANEL
The models 50 P DEP and 50 P
15 IGNITION/ DETECTION ELECTRODE feature a different heat exchanger,
as described in the previous
16 SAFETY THERMOSTAT WITH MANUAL pages, and allow installing a
RESET FROM BOARD 3-way valve inside the boiler for
the production of domestic hot
17 DELIVERY PROBE
water.
18 AUTOMATIC DRAIN VALVE It is also possible to install an
optional expansion vessel inside
19 CASING PANELS the boiler itself.

11
T E C H N I C A L D ATA

POWER MAX
Description u.o.m. 50 P
50 P 65 P 80 P 100 110 130 150
DEP
Type of appliance Condensing heat appliance B23, B53; B53P
Fuel G20-G25-G30-G31
Appliance category II2H3P
Combustion chamber vertical
38,7 50 63 76 100 108 124 146
Maximum nominal heat input at furnace referred to the HCV (LCV) kW
(34,9) (45) (57) (68) (90) (97) (112) (131)
10 10 15 15 21,6 21,6 24,9 29,2
Minimum nominal heat input at the furnace referred to the HCV (LCV) kW
(9) (9) (14) (14) (19,4) (19,4) (22,4) (26,2)
Useful (nominal) heat output kW 34,4 44,2 56 68 88 95 110 129

| ** Values referred to the atmospheric pressure above sea level.


Maximum nominal heat output (80-60°C) P4 G20 kW 34,4 44,2 55,7 67,0 88,3 95,3 109,8 129,0
Maximum nominal heat output (50-30°C) - G20 kW 38,0 48,8 61,9 73,9 97,4 105,1 121,1 142,1
Maximum nominal heat output (60-40°C) - G20 kW 36,6 47,0 59,6 71,4 93,8 101,1 116,2 137,3
Heat output 30% with return 30°C P1 G20 kW 11,5 14,7 18,7 22,3 29,4 31,7 36,6 43,0
Minimum nominal heat output (80-60°C) - G20 kW 8,9 8,9 13,5 13,5 19,2 19,2 22,1 26
Seasonal space heating energy efficiency class A A A A - - - -
Seasonal space heating energy efficiency ηs % 93,1 93,1 93,1 93,1 - - - -
Efficiency at nominal heat input and high Useful heat 88,5 88,4 88,4 88,2 88,3 88,2 88,6 88,2
η4 %
temperature regime HCV (LCV) input (60-80°C) (98,4) (98,3) (98,3) (97,9) (98,0) (97,9) (98,3) (97,9)
Efficiency at 30% of nominal heat input and low Useful heat 98,4 98,2 98,2 98 98,1 98 98 98,1
η1 %
temperature regime HCV (LCV) input 30% (109,5) (109,2) (109,2) (108,8) (108,9) (108,8) (108,8) (108,9)
Losses through chimney with burner operating at max nominal output
% 2,3 2,3 2,3 2,3 2,5 2,6 2,5 2,6
(80-60°C)
Losses at chimney with burner operating at 30% of nominal output
% 0,5 0,5 0,5 0,5 0,6 0,6 0,5 0,6
(50-30°C)
W 45 57 72 87 115 124 143 168
Thermal losses in Standby mode Pstby
% 0,1 0,1 0,1 0,1 0,1 0,1 0,1 0,1
Yearly energy consumption QHE GJ 71 91 117 141 - - - -
Noise (sound power level) LWA at max P dB(A) 51 52 53 54 55 56 57 57

*Weight values calculated according to standard EN 15502.


(referred to
Emissions (*) NOx mg/kWh 42,0 43,9 34,2 36,4 38,1 38,7 39,3 46,1
HCV)
CO2 % 9-9 9-9 9-9 9-9 9-9 9-9 9-9 9-9
Emissions at max/min heat input (G20)
CO ppm 63/2,3 73/2,3 79/6,5 90/6,5 81/7,5 91,5/7,5 89/4,6 91,5/5,6
Maximum nominal heat input (LCV) G25 kW 35 50 53 65 85 93 107 127
Minimum nominal heat input (LCV) G25 kW 9 9 13 13 18,1 18,5 21,4 24,5
CO2 % 9-9 9-9 9-9 9-9 9-9 9-9 9-9 9-9
Emissions at max/min heat input (G25)
CO ppm 72/3,2 80/3,2 92/7 93,5/7 84/8 94/8 92/6 95/7
CO2 % 10,4-9,9 10,4-9,9 10,4-10,4 10,4-10,4 10,4-10,4 10,4-10,4 10,4-10,4 10,4-10,4
Emissions at max/min heat input (G30)
CO ppm 132/6 137/6 138/10 142/10 148/11 159/11 172/13 180/15
CO2 % 10,4-9,9 10,4-9,9 10,4-10,4 10,4-10,4 10,4-10,4 10,4-10,4 10,4-10,4 10,4-10,4
Emissions at max/min heat input (G31)
CO ppm 136/8 141/8 142/11 147/11 153/12 163/12 177/14 185/16
Flue gas temperature at max P and min P 80-60°C °C 66,5/61 67,5/61 71/61 72/61 76/62 78/62 75/61 77/61
Flue gas temperature at max P and min P 50-30°C °C 44/32 45/32 45/33 46/33 47/35 49/35 45/33 48/35
Flue gas mass airflow (**) Kg/s 0,015 0,02 0,025 0,03 0,04 0,046 0,05 0,06
Water side resistance (∆T 20°C) mbar - - - - 160 210 350 510
Useful head available (∆ 20°C) mbar 250 420 490 390 - - - -
Maximum operating pressure bar 6
Minimum working pressure bar 0,7
Maximum allowed temperature °C 100
Blocking thermostat activation temperature °C 95
Temperature adjustment range (min / max) °C 30 / 80
Heat module water content l 5 5 15 15 17 17 23 25
Max. condensate production at 100% nominal power (50-30°C) l/h 5,4 7 8,9 10,1 13,6 15 17,5 19,8
Electrical power supply V-Hz 230-50
Electrical protection level IP IPX4D
Electrical power absorbed at full load Elmax W 75 105 63 77 150 203 205 302
Electrical power absorbed at partial load Elmin W 31 34 30 30 36 31 44 45
Electrical power absorbed in stand-by mode P sb W 9 9 13 13 6 6 6 8
Net weight kg 64 64 64 64 69 69 84 90

12
U S E R I N T E R FAC E

POWER MAX IS EQUIPPED WITH A


MODERN AND USER-FRIENDLY
CONTROL PANEL, PROVIDED WITH
A COVER.

THE INTERFACE FEATURES


A BACKLIT DISPLAY WHICH
COMMUNICATES WITH THE
USER/INSTALLER THROUGH
ICONS, IN A SIMPLE AND
INTUITIVE WAY.

CONTROL INTERFACE
PRIMARY INFORMATION

01
01 Backlit display
02
02 MENU/RESET key: it allows accessing the RESET
main menu and restoring the operation after a
stop due to an anomaly 03 PROG 03
MENU
03 Navigation keys
04 Main switch (located on the equipment lower
side)
04

09 08
9 8

8.8:8.8
8.8:8.8
°C
0
77
DISPLAY VIEW °F
OUTSIDE
SECONDARY INFORMATION
BAR
110
0 PSI

1 2 3 4 5 6
01 02 03 04 05 06

01 Icon displayed when the heating mode is enabled. 05 Icon displayed when a Permanent or Temporary error
Flashing when there is a heat request occurs.

02 Icon displayed when the DHW production mode is 06 Icon displayed when the climatic mode
enabled. Flashing when there is a request for domestic operation is active (Par. 2001= 1 or 2)
hot water 08 Large numeric display: displaying of the current value
03 Icon displayed when entering the "Installer" or 09 Small numeric display: displaying of system
"Manufacturer” menu pressure or parameter number

04 Icon displayed when the burner of the equipment is on 10 Icon displayed when the external probe is connected

13
T mandata
(°C)
t max (°C) Par. 2024 T set max (°C)

2109 Par. 0003 Setpoint @TA=ON

2109
HYDR AULICS Par. 2028
Setpoint attenuazione
@TA=OFF

t min (°C) T mandata


Par. 2023 T set min (°C)
(°C)
°C) (°C)
CIRCULATION
Par. 2024
PUMPS T set max (°C) (°C)
terna T esterna

ThePar.
models
0003
POWER MAX 55 P DEP, POWER MAX 55 P, POWER MAX 65 P and POWER MAX 80 P are
Setpoint @TA=ON
equipped with circulation
Par. 2028 pump.
Setpoint attenuazione
@TA=OFF

°C) Par. 2023 900 T set min (°C)

°C) 800 T esterna (°C)


POWER MA X 65 P

700
POWER MA X 80 P
Residual head [mbar]

600

500
900
400
800
300
700
POWER MA X 55 P DEP 200
Residual head [mbar]

POWER MA X 55 P 600
100
500
3.5 4.0 4.5 5.0 5.5 6.0
0
] 400 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0
Flow [m 3/h]
300

200

100
4.0 4.5 5.0 5.5 6.0
0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0
Flow [m 3/h]

PRESSURE DROPS ON WATER SIDE OF GENERATORS


1000

The models POWER MAX 100, 900


POWER MAX 110, POWER MAX 130 and POWER MAX 150 are not
provided with circulation pump, which must be installed inside or outside the equipment.
For its dimensioning, consider800
pressure drops on water side of the heat modules, shown in the diagram
below.
700
Pressure drop [mbar]

3.5 4.0 4.5 5.0 5.5 6.0 6.5 600


m 3/h] 1000
500
900
400
P O W E R M A X 15 0
800
300
700
200
Pressure drop [mbar]

4.0 4.5 5.0 5.5 6.0 6.5 600


100 P O W E R M A X 13 0
500
0
400 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0
Flow [m 3/h]
300
P O W E R M A X 11 0
P O W E R M A X 10 0
200

100

0
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0
Flow [m 3/h]
7.0 8.0 9.0 10.0 11.0 12.0

]
14
2024
data T set max (°C) T Par. 2024
mandata T set max (°C) T Par. 2024
mandata
(°C) Par. 2019
(°C) (°C)
2024 T set max (°C) Par.
Par. 2024
2021 Par. 2028 T set2109
Par. max (°C) Par.
Par. 2024
0003
2019
Par. 2019
2021 Par. 2028
Par. 2109
Par. 2021 Par. 2028 Par. 2109
Par. 2109 Par. 0003
2019
2021 Par. 2028
Par. 2109
2023 T set min (°C) Par. 2023 Par.
T set2109
min (°C) Par. 2023

Par. 2020
INJECTION PUMP KIT
Par. 2022 Par. 2025 T esterna (°C) Par. 2020 Par. 2022 Par. 2025 T esterna (°C)
2023 T set min (°C) Par. 2023 T set min (°C) Par. 2023

Par. 2020 For2022


Par. thePar.
models POWER
MAX 100, POWER MAX
2025 T esterna (°C) Par. 110,
2020 POWER
Par. 2022MAX 130T esterna
Par. 2025 and POWER
(°C) MAX 150, which are
not provided with circulation pump, pump kits are available, that can be installed inside or outside the
equipment. Please find below the characteristic curves of the three circulation pumps

900

Managing 800
900
PID 12
Managing 700
800
Managing
PID 10
12

head [mbar]
600
700
PID PID
Managing 108

[mbar]
500

head [mbar]
Managing CIRCULATION PUMP 600
PID PID
Head [m.c.d.a.]

THAT CAN BE INSTALLED 6


8

Residual
100% PID PID 400
500

head
Managing ON THE MODELS POWER
[m.c.d.a.]
Head [m.c.d.a.]

64
100% PID MAX
PID 100, 110 AND 130.
300

Residual
Managing

Residual
400

100% 100% PID PID 42 200


300
Managing
Head

Managing
100% 100% PID PID 100
20 200
100% 100% 100% PID PID 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0
Managing 0
0 100
Flow [m 3
/h] 0
100% 100% 100% PID PID 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0
0
33 0
Flow [m /h] 0.

14

12
14

10
12

CIRCULATION 108
Head [m.c.d.a.]

PUMP THAT CAN BE


86 1000
INSTALLED ON THE
[m.c.d.a.]
Head [m.c.d.a.]

MODELS POWER MAX 900


64 1000
130 (HIGH HEAD) AND
150 (LOW HEAD ONLY). 800
Head

42 900

700
800
20

drop [mbar]
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 600
700
0 Flow [m /h] 3

[mbar]
drop [mbar]
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 500
600

Pressure
Flow [m 33/h]
400
drop
500
Pressure
Pressure
300
400
14
200
300
12
14 100
200
10
12
0
100
0
108 0
Head [m.c.d.a.]

0
0.
CIRCULATION 86
[m.c.d.a.]
Head [m.c.d.a.]

PUMP THAT CAN BE


INSTALLED ONLY ON 64

THE MODEL POWER


Head

2
4
MAX 150.
20
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0
0 Flow [m 3/h]
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0
33
Flow [m /h]

15
TEN GOOD REASONS
TO CHOOSE POWER MA X
CASCADE SYSTEMS

MA X I MUM P E RF O RM AN C E IN AN Y M A X IM U M EA S E O F M A IN T EN A N C E
CONDI TI ON
The POWER MAX range is designed for an easy
The modulation of a POWER MAX cascade system is maintenance with direct frontal access to all the
considerably higher than that of a single boiler. In fact, internal components. Maintenance of the single
through the control of the number of heat modules in module of the cascade system can be carried out
operation, the system optimises the power delivered even if the other modules are running.
according to the actual requirements.
In the middle seasons - spring and autumn - when the
demand is lower because of the favourable climatic M A X IM U M S PA C E O P T IM IS AT IO N
conditions, or in buildings with very variable needs The cascade POWER MAX system is designed
depending on the presences (Hotels and Restaurants), to take as little space as possible, so as to be
the cascade control will activate only the boilers suitable for both condominiums and commercial
required, ensuring the necessary power to meet the buildings. The compact size of the single module
actual heat needs. (1000x600x435 mm) and an innovative frame,
able to contain more than 1 MW in 2.6 m2, allow
installation even in small plant rooms.
CONTI NUI TY O F S E RV IC E
W I THOUT C O N C E RN
POWER MAX cascade systems are much more reliable M A X IM U M F LEX IBILIT Y
than monobloc boilers. In case of a unit downtime, The POWER MAX system is suitable for plant
the rest of the system is not involved and continues to rooms where space is limited: thanks to the wide
operate to meet the heat requirements. range of accessory kits, POWER MAX is available
for stand-alone wall-mounted application, or for
cascade application, with linear or back to back
B ES T CHOI C E F O R RE PL AC E M E N T configurations. It is also possible to choose output
The modularity of POWER MAX systems is the right and configuration according to the requirements
solution in case of replacement of central heating and the space available.
systems with difficult access to the plant room: each
unit of the cascade can be easily transported and has
reduced dimensions and weight. M A X IM U M EA S E O F IN S TA LLAT IO N
Cascade heat modules POWER MAX can be
easily installed thanks to the large number of
MA X I MUM C O S T- E F F E C T IV E N E S S F O R accessory kits available. Every single module can
R EP L A CEME N T be transported separately to the plant room, easily
The high efficiency of the system, together with the passing through any door. The installer will only
condensing technology, make POWER MAX system have to assemble modules and kits with simple,
the ideal solution for energy retrofits. easy and fast operations.
There is no need to wait for the existing boiler to break
down, as the cost of replacement pays for itself in a
M A X IM U M M O D U LAT IO N RA N GE
few years thanks to the saving on gas supply.
A N D ELEC T RO N IC M A N A GEM EN T S P EED

POWER MAX boilers feature an electronic board


MA X I MUM RESPECT FOR THE E N V IRON M EN T able to manage complex systems thanks to
Heat modules POWER MAX have reached the best the precision of calculation programs and to
NOx emission class (Class 6 according to UNI EN the processing speed. Thanks to the onboard
15502) thanks to the total premix burner with micro electronics, with the addition of the accessory kit
flame. Moreover, the cascade system manages the for flue and hydraulics, it is possible to manage up
ignition of the burners, activating only those necessary to 10 modules in cascade, thus reaching a very high
for the current heat requirements, thus reducing CO2 modulation ratio.
emissions.

16
M A X I M U M A P P L I C AT I O N
FLEXIBILIT Y
Each model of POWER MAX can be installed 148 applications.
in cascade with up to 10 modules, except for The number increases significantly if we add plate
POWER MAX 150 that can be configured with heat exchangers and hydraulic separators as
up to 8 modules. Considering the number of accessory kits to these configurations.
linear and back-to-back configurations, POWER This adaptability allows POWER MAX to stand out
MAX range allows implementing 140 types of in the reference scenario of high power boilers,
cascade configurations, which added to the single a plus that is increasingly appreciated also in the
applications of the various models reaches plant room.

STAND-ALONE
CONFIGURATIONS

LINEAR CASCADE
CONFIGURATIONS

70

BACK-TO-BACK CASCADE
CONFIGURATIONS

70

OUTPUT RANGE FOR CASCADE APPLICATIONS

9 349
Summary table POWER MA X 50 P DEP
of output range (2-10 P C S)
for each model in 9 450
POWER MA X 50 P
cascade application (2-10 P C S)
14 570
POWER MA X 65 P
(2-10 P C S)
14 680
POWER MA X 80 P
(2-10 P C S)
19,4 900
POW E R M A X 10 0
(2-10 P C S)
19,4 970
P O W E R M A X 11 0
(2-10 P C S)
22,4 1120
P O W E R M A X 13 0
(2-10 P C S)
26,2 1048
P O W E R M A X 15 0
(2- 8 P C S)

17
POWER MA X, CASCADE DIMENSIONS

LINEAR CASCADE APPLICATIONS

D
D

A A B B E
E
C C

Description 50 P DEP 50 P 65 P 80 P 100 110 130 150

A mm 1494 1494 1494 1494 1494 1494 1494 1494

B mm 2242 2242 2242 2242 2242 2242 2242 2242

5978
C (10 units) mm 7472 7472 7472 7472 7472 7472 7472
(max 8 units)

D mm 2051 2051 2051 2051 2051 2051 2221 2221

E mm 525 525 525 525 525 525 525 525

BACK-TO-BACK CASCADE APPLICATIONS


D
D

A A B B E
E
C C

Description + 50 P DEP 50 P 65 P 80 P 100 110 130 150

A mm 1494 1494 1494 1494 1494 1494 1494 1494

B mm 2242 2242 2242 2242 2242 2242 2242 2242

2988
C (5+5 units) mm 3740 3740 3740 3740 3740 3740 3740
(max 4+4 units)

D mm 2051 2051 2051 2051 2051 2051 2221 2221

E mm 970 970 970 970 970 970 970 970

18
REMOTE CONTROL KIT AND MANAGEMENT OF ADDITIONAL ZONES
The remote control kit is an accessory that allows the hourly management of the generator and of any additional zones to
which the additional ‘Electronic zone management kit’ must be matched. The remote control is absolutely essential in case
of systems that communicate through MODBUS protocol.

CONTROL INTERFACE

01 02 03 04 05 06 07 08 09

KEY 1 2 3 4 5 6 7 8 9

01 Backlit display, 255x80 pixels (106.4x39.0mm)


02 RESET key: it allows resetting the operation after a stop due to an anomaly
03 MENU key: it allows accessing the main menu
04 ESC key: in the menu navigation it allows exiting a menu item and go back to the previous one
05/09 Navigation keys ◄, ▼, ●, ►, ▲

ELECTRONIC ADDITIONAL ZONE MANAGEMENT KIT

This accessory for additional zone management must be positioned


outside the generator, on the DIN bar placed inside the electrical
panel. It is provided with all the inputs and outputs to control a mixed
system. For its correct operation it is mandatory to provide for the
temperature probe for mixed system.

KEY
TS Safety thermostat
TR Setting thermostat (zone)
S2 Flow probe (zone)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 BUS Board bus
V2 Mixing valve (zone)
P2 Zone circulation pump
bl
L1 N L2 L PE N L PE N

TS TR S2 BUS V2 P2 AE

19
27015475_0 EN 03/2019

SCAN AND DISCOVER


POWER MAX

Trading Address:
Via Risorgimento, 23/A
23900 LECCO (LC) Italy
Tel. +39 0341 277111
Fax +39 0341 277263
www.berettaheating.com

In order to improve its products, Beretta reserves the right to modify the characteristics
and information contained in this catalogue at any time and without prior notice.This
catalogue, therefore, cannot be considered as contractually binding on third parties.