System Description
Parallel Connected Diode Supply Units
(ACS800-307 or ACS800-507)
ACS800 multidrive manuals
GENERAL DRIVE MANUALS 1) Code (EN)
OPTION MANUALS 5)
Manuals for Fieldbus Adapters, I/O Extension Modules etc.
System Description
3AFE68824729 REV A
EN
EFFECTIVE: 2.11.2006
Table of contents
Table of contents
Hardware description
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Restrictions in use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Non-redundant system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Single line block diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6-pulse non-redundant system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
12-pulse non-redundant system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Redundant system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Single line block diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6-pulse redundant system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
12-pulse redundant system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Table of contents
6
Redundant system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table of contents
7
Safety instructions
Follow all safety instructions delivered with the drive.
• Read the complete safety instructions before you install, commission, or use
the drive. The complete safety instructions are given in ACS800 Multidrive Safety
Instructions [3AFE64760432 (English)].
• Read task specific safety instructions before starting the task. See the section
describing the task.
Reader
The reader is expected to know the standard electrical wiring practices, electronic
components, and electrical schematic symbols.
Other documents
User documentation of a multidrive delivery contains technical drawings and a set of
manuals. Technical drawings are tailor-made for each delivery. The composition of
the manual set depends on the composition of the drive.
The multidrive manuals are listed below. The codes refer to the original English
manuals.
Manual Included in …
• ACS800 Multidrive and ACS800 Multidrive Modules, Safety Instructions every delivery
(3AFE64760432)
• ACS800 Parallel Connected Diode Supply Units (ACS800-307 or ACS800- deliveries with two
507) System Description (3AFE68824729) parallel diode
supply units
• ACS800-307 and -507 Cabinet-installed Diode Supply Unit User’s Manual deliveries which
(3AFE64494023) include a diode
supply unit
Manual Included in …
• ACS800 Common Converter Control Application (CCCA) 7.x Firmware deliveries with two
Manual (3AFE68699061) parallel IGBT
supply units
• NDBU-85/95 DDCS Branching Units User's Manual (3BFE64285513)
• ACS800 Parallel Connected Diode and IGBT Supply Units System deliveries with
Description parallel diode &
IGBT supply units
… etc.
Inverter unit An entity containing all inverter modules controlling a motor, together with
their control electronics, and I/O and auxiliary components.
Hardware description
Overview
The maximum size of a diode supply unit is 4540 kVA (5×D4 modules in parallel).
However, two diode supply units can be connected in parallel, when there is a need
for a higher power or redundancy. It is possible to connect two 3×D4 up to two 5×D4
units (max. 2×4540 kVA) to the same DC system.
Restrictions in use
Parallel connected DSUs must be located at the rear ends of the drive DC bus.
Other configurations are not allowed due to short circuit current withstand limitation
of the drive DC busbars.
The DSUs must be of the same size, for example two 3×D4. This ensures the equal
distribution of the load.
A common supply transformer is possible for a system with up to two 3×D4 units, if
the impedance and short-circuit tolerance of the supply transformer permit. Own
transformers are needed for systems with more than two 3×D4 units.
When using two supply transformers, they must be identical.
A common 3-winding transformer can be used for 6-pulse DSUs provided each DSU
is supplied by an own secondary (secondaries of same size, having same tolerances
the one in triangle the other in star meaning 12-pulse to the network) to get the
galvanic isolation between DSUs.
Hardware description
12
Non-redundant system
Controls
In a non-redundant system both supply units can be controlled with one set of door
switches, i.e. with one on/off/start switch, reset button and emergency stop button.
For details, see the circuit diagrams delivered with the drive.
Q1 Q1
Q9 Q9
Earthing switch Earthing switch
(optional) (optional)
DSU 1 DSU 2
D4 D4 D4 D4 D4 D4
DC supply
for inverters
A common two- or three-winding transformer is also possible.
Hardware description
13
U<
U<
U<
Q1 Q1 Q1 Q1
Air circuit Air circuit
breaker breaker
DSU 1 DSU 2
D4 D4 D4 D4 D4 D4
DC supply
for inverters
Hardware description
14
Redundant system
Redundancy
Redundancy is possible if the system is dimensioned for a double DSU, each
running at 50% load. If one DSU fails, the drive continues operating without the
failed DSU with the other loaded at 100% power. The faulty DSU can be
disconnected from a live DC bus (and AC power source), repaired and reconnected
back to a live DC bus.
Note: Charging circuits are needed between the DC bus and the DSU, if the DSU is
reconnected to a live DC bus.
Controls
In a redundant system, both DSUs have their own on/off/start-switches allowing the
starting and stopping of the other DSU while the other is running. However, the
emergency stop circuits are always interlocked, i.e. one emergency stop button
switches off all DSUs. For details, see the circuit diagrams delivered with the drive.
Hardware description
15
Q1 Q1
Q9 Q9
Earthing switch Earthing switch
(optional) (optional)
DSU 1 DSU 2
D4 D4 D4 D4 D4 D4
Q31 Q31
DC switch DC switch
Q30 Q30
In a redundant system, there is a DC switch (Q30) for disconnecting the DSU from
the DC bus. There is also a charging circuit which allows the safe connection of the
DSU to a live DC bus. See chapter Start-up and operation for instructions.
Hardware description
16
U<
U<
U<
Q1 Q1 Q1 Q1
Air circuit Air circuit
breaker breaker
Q9 Q9 Q9 Q9
DSU 1 DSU 2
D4 D4 D4 D4 D4 D4
Q31 Q31
DC switch DC switch
Q30 Q30
In a redundant system, there is a DC switch (Q30) for disconnecting the DSU from
the DC bus. There is also a charging circuit which allows the safe connection of the
DSU to a live DC bus. See chapter Start-up and operation for instructions.
Hardware description
17
Close the air circuit breaker Q1 and start the system: Turn the three-
position operating switch on the cabinet door from 0 to START position for
2 s.
Close the air circuit breaker Q1 and start the first DSU: Turn the
three-position operating switch on the cabinet door from 0 to START
position for 2 s.
Repeat the steps for the second DSU.
This chapter gives an example of the control connections for both non-redundant
and redundant systems. Included are only circuit diagrams describing the controls.
Note: See your delivery specific circuit diagrams for complete information.
In the example circuit diagrams 01 refers to DSU unit 1 and 02 refers to DSU unit 2.
Non-redundant system
Redundant system