SERVICE MANUAL
MODELS: LK-0320CC/AC LK-10B0CH/AH
LK-0420CC/AC LK-13B0CH
LK-0520CC/AC LK-15B0CH/AH
LK-05B0CC/AC LK-18B0CH
LK-06B0CH/AH LK-20B0CH/AH
LK-08B0CH/AH LK-25B0CH/AH
LK-09B0CH
Contents
Model Number Nomenclature...............................................................................................3

General Data ..........................................................................................................................4

Performance Data..................................................................................................................7

Electrical Requirements .....................................................................................................19

Dimensions ..........................................................................................................................21

Refrigerant Circuit Diagram................................................................................................29

Cooling Cycle Operating Pressures/Superheat Charging Chart ....................................30

Wiring Diagram ....................................................................................................................45

Troubleshooting Guide .......................................................................................................51

Electronic Parts Troubleshooting Guide ...........................................................................57

Features of Controller .........................................................................................................63

Exploded View and Replacement Parts List .....................................................................69

Specification of Components.............................................................................................81

—2—
Model Number Nomenclature

LK-08B0CH C: Convertible
H: Horizontal Flow
D: Down Flow

C: Cooling Only
H: Heat Pump
A: Gold fin outdoor

Development Sequence

1 : 115/60/1 2 : 220/60/1 3 : 208-230/60/1


5 : 200-220/50/1 6 : 220-240/50/1 7 : 100/50(60)/1
8 : 380-415/50/3 9 : 380-415/60/3 A : 220/50/3
B : 220/60/3 C : 440-460/50/3 D : 440-460/60/3

Nominal cooling capacity


03 : 3 ton 08 : 7.5 ton 15 : 15 ton
04 : 4 ton 09 : 8.5 ton 18 : 17.5 ton
05 : 5 ton 10 : 10 ton 20 : 20 ton
06 : 6.25 ton 13 : 12.5 ton 25 : 25 ton

LG
Single Package Air Conditioner

—3—
General Data
Table-1
Nominal ton (Ton) 3 4 5 5 6.25
Models LK-0320CC LK-0420CC LK-0520CC LK-05B0CC LK-06B0CH/AH
Capacity Gross Cooling Capacity (BTU/hr) 3,8700 49,900 66,000 66,000 75,000
(Kcal/h) 9,753 12,324 16,129 16,632 18,901
ARI Net Cooling Capacity (BTU/hr) 37,500 48,000 61,500 61,500 72,000
(Kcal/h) 9,451 12,097 15,499 15,498 18,145
Electrical Data Voltage (V,PH) 220V,1PH 220V,1PH 220V,1PH 220V, 3PH 220V,3PH
M.C.A(with standard motor) Cooling (Amps) 28.8 34.4 42.3 29.3 35
Power Input Cooling (Watt) 4,290 5,580 6,600 6,600 7,650
Performance Air Circulation Nominal CFM CFM 1,200 1,600 2,000 1,850 2,500
EER Cooling (BTU/hr.W) 8.7 8.6 9.3 9.3 9.4
Sound Rating Cooling dB(A) 8 8.4 8.8 8.2 8.8
Features Wired Remote Controller - - - - ¥
Time Delay Safety Function ¥ ¥ ¥ ¥ ¥
Cooling Operation Mode ¥ ¥ ¥ ¥ ¥
Heating Operation Mode(with E/Heater) ¥ ¥ ¥ ¥ ¥
Soft Dry Operation - - - - ¥
Timer Setting (24-Hour on/off) - - - - ¥
Auto rastart mode - - - - -
Humidifier function - - - - ¥
Test function - - - - ¥
Self-Diagnosis Function - - - - ¥
Filter type washable & Anti-fungus washable & Anti-fungus washable & Anti-fungus - washable & Anti-fungus
Compressor Type Reciprocating Reciprocating Reciprocating Reciprocating Reciprocating
Quantity 1 1 1 1 1
Outdoor Coil Type High efficiency High efficiency High efficiency High efficiency High efficiency
Tube size(O.D) (inch) 0.375 0.375 0.375 0.375 0.375
(mm) 9.52 9.52 9.52 9.52 9.52
Row/FPI 2R/16FPI 2R/16FPI 2R/16FPI 2R/18FPI 2R/16FPI
Lengh (inch) 39 39 53.9 54.3 53.1
(mm) 990 990 1,370 1,380 1,350
Face area (sq.ft) 7.58 7.58 10.49 10.56 11.81
(m2) 0.7 0.7 0.97 0.98 1.1
Indoor Coil Type High efficiency High efficiency High efficiency High efficiency High efficiency
Tube size(O.D) (inch) 0.375 0.375 0.375 0.375 0.375
(mm) 9.52 9.52 9.52 9.52 9.52
Row/FPI 2R/16FPI 3R/16FPI 3R/16FPI 3R/18FPI 3R/16FPI
Lengh (inch) 24.4 24.4 24.4 21.65 37.9
(mm) 620 620 620 550 963
Face area (sq.ft) 5.09 5.09 5.09 4.21 7.11
(m2) 0.47 0.47 0.47 0.39 0.66
Outdoor Fan Type Propeller Propeller Propeller Propeller Propeller
No. Used/Diameter(in.) 1EA/24" 1EA/24" 1EA/24" 2EA/18" 1EA/24"
Drive Type Direct Direct Direct Direct Direct
CFM 3600 3,600 3,600 3,300 4,600
No. Motor/Motor output(Hp) 1/0.5 1/0.5 1/0.5 2/0.15 1/0.5
Motor RPM 1,080 1,080 1,080 1,000 1,130
Indoor Fan Type Centrifugal Blower Fan
No. Used 1EA 1EA 1EA 1EA 1EA
Diameter/Width(in.) 11"/11" 11"/11" 11"/11" 11"/11" 13"/13"
Drive Type/Motor Step Direct/3 Direct/3 Direct/3 Direct/3 Belt/1
No.motors 1EA 1EA 1EA 1EA 1EA
Motor output(standard/oversized) 0.75Hp/N.A 0.5Hp/N.A 0.75Hp/N.A 0.75Hp/N.A 1.5Hp/3.0Hp
Motor rpm(Standard/oversized) 1,080/N.A 995/N.A 1,080/N.A 1,080/N.A 1,700/1730
Drain Connection Size(in.) 3/4" 3/4" 3/4" 3/4" 3/4"
Refrigerant Refrigerant Charge (Lbs) 6.2 6.2 7.3 6.38 10.1
Dimensions Indoor unit (WxHxD) (inch) 64.17*34.45*45.08 64.17*34.45*45.08 64.17*34.45*45.08 50.39*31.89*43.7 85.43*35.04*46.93
(mm) 1630*875*1145 1630*875*1145 1630*875*1145 1280*810*1110 2170*890*1159
Weight Net (kg) 190 200 220 190 260
(lbs) 419 441 485 419 573

1) Test Condition of ARI Rated Cooling Capacity :


Ambient:95°F , Air entering temprature : 80°F DB and 67°F WB
2) ARI standard
210/240 or 360 for EER
270 for Sound
3) Filters are standard supply.

—4—
General Data
Table-2
Nominal ton (Ton) 7.5 8.5 10 12.5
Models LK-08B0CH/AH LK-09B0CH LK-10B0CH/AH LK-13B0CH
Capacity Gross Cooling Capacity (BTU/hr) 92,000 107,000 126,000 151,000
(Kcal/h) 23,185 26,966 31,502 38,054
ARI Net Cooling Capacity (BTU/hr) 88,000 102,000 118,000 142,000
(Kcal/h) 22,177 25,706 29,738 35,786
Electrical Data Voltage (V,PH) 220V,3PH 220V,3PH 220V,3PH 220V,3PH
M.C.A(with standard motor) Cooling (Amps) 43 52.6 57.6 73
Power Input Cooling (Watt) 9,750 11,090 12,800 16,500
Performance Air Circulation Nominal CFM CFM 3,000 3,400 4,000 5,000
EER Cooling (BTU/hr.W) 9.0 9.2 9.2 8.6
Sound Rating Cooling dB(A) 8.8 9.2 9.2 9.2
Features Wired Remote Controller ¥ ¥ ¥ ¥
Time Delay Safety Function ¥ ¥ ¥ ¥
Cooling Operation Mode ¥ ¥ ¥ ¥
Heating Operation Mode(with E/Heater) ¥ ¥ ¥ ¥
Soft Dry Operation ¥ ¥ ¥ ¥
Timer Setting (24-Hour on/off) ¥ ¥ ¥ ¥
Auto rastart mode - - - -
Humidifier function ¥ ¥ ¥ ¥
Test function ¥ ¥ ¥ ¥
Self-Diagnosis Function ¥ ¥ ¥ ¥
Filter type washable & Anti-fungus washable & Anti-fungus washable & Anti-fungus washable & Anti-fungus
Compressor Type Reciprocating Reciprocating Reciprocating Reciprocating
Quantity 1 2 2 2
Outdoor Coil Type High efficiency High efficiency High efficiency High efficiency
Tube size(O.D) (inch) 0.375 0.375 0.375 0.375
(mm) 9.52 9.52 9.52 9.52
Row/FPI 2R/16FPI 2R/16FPI 2R/16FPI 2R/16FPI
Lengh (inch) 55.9 66.9 66.9 87
(mm) 1,420 1,700 1,700 2,200
Face area (sq.ft) 12.42 17.66 17.66 22.86
(m2) 1.15 1.64 1.64 2.12
Indoor Coil Type High efficiency High efficiency High efficiency High efficiency
Tube size(O.D) (inch) 0.375 0.375 0.375 0.375
(mm) 9.52 9.52 9.52 9.52
Row/FPI 3R/16FPI 2R/16FPI 3R/16FPI 3R/16FPI
Lengh (inch) 42.1 37.9 37.9 45.3
(mm) 1,070 963 963 1,150
Face area (sq.ft) 7.9 9.48 9.48 11.32
(m2) 0.73 0.88 0.88 1.05
Outdoor Fan Type Propeller Propeller Propeller Propeller
No. Used/Diameter(in.) 1EA/24" 1EA/26" 1EA/26" 1EA/26"
Drive Type Direct Direct Direct Direct
CFM 4,600 7,000 7,000 7,800
No. Motor/Motor output(Hp) 1/0.5 1/1.3 1/1.3 1/1.3
Motor RPM 1,130 1,130 1,130 1,130
Indoor Fan Type Centrifugal Blower Fan
No. Used 1EA 1EA 1EA 1EA
Diameter/Width(in.) 13"/13" 15"/11" 15"/11" 15"/15"
Drive Type/Motor Step Belt/1 Belt/1 Belt/1 Belt/1
No.motors 1EA 1EA 1EA 1EA
Motor output(standard/oversized) 1.5Hp/3.0Hp 3.0Hp/5.0Hp 3.0Hp/5.0Hp 3.0Hp/5.0Hp
Motor rpm(Standard/oversized) 1700/1730 1730/1750 1730/1750 1730/1750
Drain Connection Size(in.) 3/4" 3/4" 3/4" 3/4"
Refrigerant Refrigerant Charge (Lbs) 10.4 7.7/circuit 7.3/circuit 8.6/circuit
Dimensions Indoor unit (WxHxD) (inch) 85.43*35.04*46.93 85.43*41.34*48.89 85.43*41.34*48.89 85.43*41.34*61.02
(mm) 2170*890*1159 2170*1050*1242 2170*1050*1242 2170*1050*1550
Weight Net (kg) 280 330 350 400
(lbs) 617 728 772 882

1) Test Condition of ARI Rated Cooling Capacity :


Ambient:95°F , Air entering temprature : 80°F DB and 67°F WB
2) ARI standard
210/240 or 360 for EER
270 for Sound
3) Filters are standard supply.
—5—
General Data

Table-3
Nominal ton (Ton) 15 17.5 20 25
Models LK-15B0CH/AH LK-18B0CH LK-20B0CH/AH LK-25B0CH/AH
Capacity Gross Cooling Capacity (BTU/hr) 183,000 208,000 270,000 333,000
(Kcal/h) 46,119 52,419 68,044 83,921
ARI Net Cooling Capacity (BTU/hr) 172,000 192,000 260,000 320,000
(Kcal/h) 43,347 48,387 65,524 80,645
Electrical Data Voltage (V,PH) 220V,3PH 220V,3PH 220V,3PH 220V,3PH
M.C.A(with standard motor) Cooling (Amps) 86 102 124 133
Power Input Cooling (Watt) 20,600 22,590 26,600 33,000
Performance Air Circulation Nominal CFM CFM 6,000 7,000 8,000 10,000
EER Cooling (BTU/hr.W) 8.6 8.5 9.8 9.7
Sound Rating Cooling dB(A) - - - -
Features Wired Remote Controller ¥ ¥ ¥ ¥
Time Delay Safety Function ¥ ¥ ¥ ¥
Cooling Operation Mode ¥ ¥ ¥ ¥
Heating Operation Mode(with E/Heater) ¥ ¥ ¥ ¥
Soft Dry Operation ¥ ¥ ¥ ¥
Timer Setting (24-Hour on/off) ¥ ¥ ¥ ¥
Auto rastart mode - - - -
Humidifier function ¥ ¥ ¥ ¥
Test function ¥ ¥ ¥ ¥
Self-Diagnosis Function ¥ ¥ ¥ ¥
Filter type washable & Anti-fungus washable & Anti-fungus washable & Anti-fungus washable & Anti-fungus
Compressor Type Reciprocating Reciprocating Reciprocating Reciprocating
Quantity 2 2 2 2
Outdoor Coil Type High efficiency High efficiency High efficiency High efficiency
Tube size(O.D) (inch) 0.375 0.375 0.375 0.375
(mm) 9.52 9.52 9.52 9.52
Row/FPI 2R/16FPI 2R/16FPI 2R/16FPI 2R/16FPI
Lengh (inch) 73 85 79 87
(mm) 1,850 2,160 2,000 2,200
Face area (sq.ft) 22.26 25.98 32.81 36.09
(m2) 2.07 2.41 3.05 3.35
Indoor Coil Type High efficiency High efficiency High efficiency High efficiency
Tube size(O.D) (inch) 0.375 0.375 0.375 0.375
(mm) 9.52 9.52 9.52 9.52
Row/FPI 3R/16FPI 3R/16FPI 2R/16FPI 3R/16FPI
Lengh (inch) 44.9 55.1 55.9 55.9
(mm) 1,140 1,400 1,420 1,420
Face area (sq.ft) 13.09 16.08 23.29 23.29
(m2) 1.22 1.49 2.16 2.16
Outdoor Fan Type Propeller Propeller Propeller Propeller
No. Used/Diameter(in.) 2EA/26" 2EA/26" 2EA/26" 2EA/28"
Drive Type Direct Direct Direct Direct
CFM 10,800 14,100 14,800 16,700
No. Motor/Motor output(Hp) 2/1.3 2/1.3 2/1.3 2/2.0
Motor RPM 1,130 1,130 1,130 1,130
Indoor Fan Type Centrifugal Blower Fan
No. Used 1EA 1EA 1EA 1EA
Diameter/Width(in.) 15"/15" 15"/15" 18"/18" 18"/18"
Drive Type/Motor Step Belt/1 Belt/1 Belt/1 Belt/1
No.motors 1EA 1EA 1EA 1EA
Motor output(standard/oversized) 4.0Hp/5.0Hp 5.0Hp/7.5Hp 5.0Hp/7.5Hp 7.5Hp/N.A
Motor rpm(Standard/oversized) 1730/1750 1750/3500 3500/3510 3510/N.A
Drain Connection Size(in.) 1" 1" 1" 1"
Refrigerant Refrigerant Charge (Lbs) 10.6/circuit 11.5/circuit 13.9/circuit 15.7/circuit
Dimensions Indoor unit (WxHxD) (inch) 95.98*47.44*69.53 95.98*47.44*69.53 109.21*65.35*74.02 109.21*65.35*74.02
(mm) 2438*1230*1766 2438*1230*1766 2774*1660*1880 2774*1660*1880
Weight Net (kg) 550 600 820 870
(lbs) 1213 1323 1808 1918

1) Test Condition of ARI Rated Cooling Capacity :


Ambient:95°F , Air entering temprature : 80°F DB and 67°F WB
2) ARI standard
210/240 or 360 for EER
270 for Sound
3) Filters are standard supply.
—6—
Performance Data
Table-4 Supply Fan Performance LK-0320CC

High Speed Mid Speed Low Speed


CFM
ESP BHP ESP BHP ESP BHP

1,000 1.41 0.62 0.75 0.31 0.62 0.3


1,100 1.32 0.64 0.65 0.32 0.54 0.32
1,200 1.12 0.66 0.58 0.34 0.3 0.35
1,300 0.96 0.69 0.52 0.37 0.21 0.41
1,400 0.73 0.74 0.38 0.39 - -
1,500 0.50 0.78 0.28 0.43 - -

Table-5 Supply Fan Performance LK-0420CC

High Speed Mid Speed Low Speed


CFM
ESP BHP ESP BHP ESP BHP
1,300 1.30 0.39 0.88 0.39 0.42 0.39
1,400 1.16 0.42 0.71 0.42 0.21 0.43
1,500 1.03 0.46 0.54 0.45 - -
1,600 0.89 0.49 0.37 0.48 - -
1,700 0.75 0.52 0.19 0.52 - -
1,800 0.61 0.56 0.02 0.55 - -
1,900 0.47 0.59 - - - -
2,000 0.34 0.62 - - - -

Table-6 Supply Fan Performance LK-0520CC

High Speed Mid Speed Low Speed


CFM
ESP BHP ESP BHP ESP BHP
1,700 0.85 0.54 0.79 0.44 0.30 0.51
1,800 0.77 0.55 0.68 0.49 0.03 0.56
1,900 0.67 0.59 0.59 0.54 - -
2,000 0.57 0.65 0.37 0.58 - -
2,100 0.51 0.67 0.23 0.63 - -
2,200 0.41 0.72 0.06 0.67 - -
2,300 0.26 0.80 - - - -
2,400 0.11 0.89 - - - -

• Fan motor heat(MBH)= 5.09 x Fan Bhp


• Test Condition: ➊ Voltage : 220V
❷ Operating Mode: Fan operation mode with clean filter, dry coil, without electric heater.
• Do not operate the unit at a cooling airflow that is less then 350cfm/1.2MBH.

—7—
Performance Data

Table-7 Supply Fan Performance LK-05B0CC

High Speed Middle Speed Low Speed


CFM
ESP BHP ESP BHP ESP BHP
1,500 0.71 0.59 0.68 0.48 0.59 0.46
1,600 0.64 0.62 0.60 0.50 0.55 0.47
1,700 0.56 0.64 0.51 0.52 0.41 0.51
1,800 0.49 0.66 0.43 0.55 0.20 0.56
1,900 0.42 0.68 0.35 0.57 – –
2,000 0.35 0.70 0.26 0.59 – –
2,100 0.28 0.72 0.18 0.61 – –
2,200 0.21 0.74 0.09 0.64 – –
2,300 0.13 0.76 0.01 0.66 – –
2,400 0.06 0.78 – – – –
• Fan motor heat(MBH)= 5.09 x Fan Bhp
• Test Condition: ➊ Voltage : 220V
❷ Operating Mode: Fan operation mode with clean filter, dry coil, without electric heater.
• Do not operate the unit at a cooling airflow that is less then 300cfm/12MBH.

Table-8 Supply Fan Performance LK-06B0CH/AH

External Static Pressure(inches of water)


CFM 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.25 1.5
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5HP STANDARD MOTOR & DRIVE 1.5HP STANDARD MOTOR & HIGH STATIC DRIVE KIT
2,000 637 0.23 661 0.32 685 0.40 709 0.48 734 0.56 758 0.64 782 0.72 806 0.80 831 0.89 855 0.97 915 1.17 961 1.37
2,250 666 0.38 690 0.46 714 0.54 738 0.62 763 0.71 787 0.79 811 0.87 835 0.95 859 1.03 884 1.11 944 1.32 990 1.52
2,500 698 0.55 722 0.63 746 0.71 771 0.80 795 0.88 819 0.96 843 1.04 867 1.12 892 1.20 916 1.28 976 1.49 1022 1.69
2,750 734 0.75 758 0.83 782 0.91 806 1.00 831 1.08 855 1.16 879 1.24 903 1.32 927 1.40 952 1.48 1012 1.69 1058 1.89
3,000 773 0.98 797 1.06 821 1.14 845 1.22 870 1.31 894 1.39 918 1.47 942 1.55 966 1.63 991 1.71 1051 1.92 1097 2.12
3HP OVER SIZE MOTOR & DRIVE

• Fan motor heat(MBH) = 3.26 x Fan Bhp


• Test Condition: ➊ Voltage : 220V
❷ Operating Mode: Fan operation mode with clean filter, dry coil, without electric heater.
• Do not operate the unit at a cooling airflow that is less then 350cfm/1.2MBH.

Table-9 Fan speed Data LK-06B0CH/AH

6 Turn Open 5 Turn Open 4 Turn Open 3 Turn Open 2 Turn Open 1 Turn Open Closed
Standard Motor & Drive
Fan Speed 633 683 732 782 832 881 931
Standard Motor & High Static
Drive Accessory Fan Speed 722 779 835 892 948 1005 1062
Over size Motor & Drive
Fan Speed 805 855 904 954 1004 1053 1103

• Factory set at 3 turns open.


—8—
Performance Data

Table-10 Supply Fan Performance LK-08B0CH/AH

External Static Pressure(inches of water)


CFM 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.25 1.5
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5HP STANDARD MOTOR & DRIVE
2,400 - - - - 730 0.58 753 0.64 777 0.71 800 0.77 823 0.83 846 660 869 0.95 893 1.01 951 1.16 1009 1.32
2,700 725 0.69 748 0.75 772 0.81 795 0.87 818 0.93 841 1.00 865 1.06 888 702 911 1.18 934 1.24 992 1.39 1050 1.55
3,000 772 0.96 795 1.02 818 1.08 841 1.14 865 1.21 888 1.27 911 1.33 934 749 957 1.45 981 1.51 1039 1.67 1097 1.82
3,300 823 1.28 846 1.34 870 1.40 893 1.46 916 1.52 939 1.58 962 1.64 986 800 1009 1.77 1032 1.83 1090 1.98 1148 2.13
3,600 879 1.64 903 1.70 926 1.76 949 1.82 972 1.88 995 1.94 1019 2.01 1042 856 1065 2.13 1088 2.19 1146 2.34 1204 2.50
3HP OVER SIZE MOTOR & DRIVE

• Fan motor heat(MBH) = 3.26 x Fan Bhp


• Test Condition: ➊ Voltage : 220V
❷ Operating Mode: Fan operation mode with clean filter, dry coil, without electric heater.
• Do not operate the unit at a cooling airflow that is less then 350cfm/1.2MBH.

Table-11 Fan speed Data LK-08B0CH/AH

6 Turn Open 5 Turn Open 4 Turn Open 3 Turn Open 2 Turn Open 1 Turn Open Closed
Standard Motor & Drive
Fan Speed 709 765 821 876 932 987 1043
Over size Motor & Drive
Fan Speed 918 975 1031 1088 1144 1201 1257

• Factory set at 3 turns open.

—9—
Performance Data

Table-12 Supply Fan Performance LK-09B0CH

External Static Pressure(inches of water)


CFM 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP STANDARD MOTOR & DRIVE
2,720 609 0.53 615 0.58 623 0.62 632 0.67 642 0.72 653 0.76 665 0.81 678 0.85 693 0.90 707 0.94 722.9 0.99 739 1.03
3,060 640 0.75 645 0.80 653 0.84 662 0.89 672 0.93 684 0.98 696 1.02 709 1.07 723 1.11 738 1.42 753.4 1.21 806 1.25
3,400 676 1.01 682 1.06 689 1.10 698 1.15 708 1.19 720 1.24 732 1.28 745 1.33 759 1.37 774 1.42 789.4 1.46 806 1.51
3,740 718 1.31 723 1.35 731 1.40 740 1.44 750 1.49 761 1.54 774 1.58 787 1.63 801 1.67 816 1.72 831.3 1.76 848 1.81
4,080 765 1.65 771 1.70 779 1.74 788 1.79 798 1.83 809 1.88 822 1.92 835 1.97 849 2.01 864 2.06 879.3 2.10 896 2.15

External Static Pressure(inches of water)


CFM 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2
3 HP STANDARD MOTOR & HIGH STATIC DRIVE KIT
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP STANDARD MOTOR & DRIVE
2,720 756 1.08 774 1.12 792 1.17 811 1.21 831 1.26 851 1.30 872 1.35 893 1.39
3,060 787 1.30 804 1.34 823 1.39 842 1.43 861 1.48 881 1.52 902 1.57 923 1.61
3,400 823 1.55 840 1.60 859 1.64 878 1.69 897 1.73 917 1.78 938 1.82 959 1.87
3,740 865 1.85 882 1.90 901 1.94 920 1.99 939 2.03 959 2.08 980 2.12 1001 2.17
4,080 913 2.20 930 2.24 949 2.29 968 2.33 987 2.38 1007 2.42 1028 2.47 1049 2.51

• Fan motor heat(MBH) = 3.10 x Fan Bhp


• Test Condition: ➊ Voltage : 220V
❷ Operating Mode: Fan operation mode with clean filter, dry coil, without electric heater.
• Do not operate the unit at a cooling airflow that is less then 350cfm/1.2MBH.

Table-13 Fan speed Data LK-09B0CH

6 Turn Open 5 Turn Open 4 Turn Open 3 Turn Open 2 Turn Open 1 Turn Open Closed
Standard Motor & Drive
Fan Speed 566 604 643 682 720 759 798
Standard Motor & High Static
Drive Accessory Fan Speed 779 832 886 939 992 1046 N.A

• Factory set at 3 turns open.

— 10 —
Performance Data

Table-14 Supply Fan Performance LK-10B0CH/AH

External Static Pressure(inches of water)


CFM 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP STANDARD MOTOR & DRIVE
3,200 654 0.85 660 0.90 667 0.94 676 0.99 686 1.03 698 1.08 710 1.13 723 1.17 737 1.22 752 1.26 768 1.31 784 1.35
3,600 700 1.18 705 1.23 713 1.27 722 1.32 732 1.36 743 1.41 756 1.45 769 1.50 783 1.54 798 1.59 813 1.63 830 1.68
4,000 754 1.57 759 1.61 767 1.66 776 1.70 786 1.75 798 1.79 810 1.84 823 1.88 837 1.93 852 1.97 867 2.02 884 2.07
4,400 816 2.02 822 2.06 830 2.11 839 2.15 849 2.20 860 2.24 873 2.29 886 2.33 900 2.38 915 2.42 930 2.47 947 2.51
4,800 889 2.53 894 2.58 902 2.62 911 2.67 921 2.71 932 2.76 945 2.80 958 2.85 972 2.89 987 2.94 1002 2.98 1019 3.03

3 HP STANDARD MOTOR & HIGH STATIC DRIVE KIT 5 HP OVER SIZE MOTOR & DRIVE

External Static Pressure(inches of water)


CFM 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP STANDARD MOTOR & DRIVE
3,200 801 1.40 819 1.44 837 1.49 856 1.53 875 1.58 895 1.62 916 1.67 937 1.71
3,600 847 1.72 864 1.77 883 1.81 3 HP STANDARD MOTOR & HIGH STATIC DRIVE KIT
902 1.86 921 1.91 941 1.95 962 2.00 983 2.04
4,000 901 2.11 918 2.16 937 2.20 956 2.25 975 2.29 995 2.34 1016 2.38 1037 2.43
4,400 964 2.56 981 2.61 1000 2.65 1019 2.70 1038 2.74 1058 2.79 1079 2.83 1100 2.88
4,800 1036 3.08 1053 3.12 1072 3.17 1091 3.21 1110 3.26 1130 3.30 1151 3.35 1172 3.39
5 HP OVER SIZE MOTOR & DRIVE

• Fan motor heat(MBH) = 3.10 x Fan Bhp


• Test Condition: ➊ Voltage : 220V
❷ Operating Mode: Fan operation mode with clean filter, dry coil, without electric heater.
• Do not operate the unit at a cooling airflow that is less then 350cfm/1.2MBH.

Table-15 Fan speed Data LK-10B0CH/AH

6 Turn Open 5 Turn Open 4 Turn Open 3 Turn Open 2 Turn Open 1 Turn Open Closed
Standard Motor & Drive
Fan Speed 655 700 745 790 835 880 924
Standard Motor & High Static
Drive Accessory Fan Speed 779 832 886 939 992 1046 N.A
Over size Motor & Drive
Fan Speed 891 952 1013 1074 1135 1196 N.A

• Factory set at 3 turns open.

— 11 —
Performance Data
Table-16 Supply Fan Performance LK-13B0CH

External Static Pressure(inches of water)


CFM 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP STANDARD MOTOR & DRIVE
4,000 - - - - 669 1.30 685 1.36 701 1.43 717 1.49 733 1.56 749 1.62 765 1.69 781 1.75 797 1.82 813 1.88
4,500 692 1.65 708 1.72 724 1.78 740 1.85 756 1.91 772 1.98 788 2.04 804 2.11 820 2.17 836 2.24 852 2.30 868 2.37
5,000 756 2.23 772 2.29 788 2.36 804 2.42 820 2.49 836 2.55 852 2.62 868 2.69 884 2.75 900 2.82 916 2.88 932 2.95
5,500 831 2.90 847 2.96 863 3.03 879 3.09 895 3.16 911 3.22 927 3.29 943 3.35 959 3.42 975 3.49 991 3.55 1007 3.62
6,000 917 3.67 933 3.73 949 3.80 965 3.86 981 3.93 997 3.99 1013 4.06 1029 4.12 1045 4.19 1061 4.25 1077 4.32 1093 4.38

External Static Pressure(inches of water) 5 HP OVER SIZE MOTOR & DRIVE


CFM 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP STANDARD MOTOR & DRIVE
4,000 829 1.95 845 2.01 861 2.08 877 2.14 893 2.21 909 2.27 925 2.34 941 2.40
3 HP STANDARD MOTOR & HIGH STATIC DRIVE KIT
4,500 884 2.43 900 2.50 916 2.56 932 2.63 948 2.69 964 2.76 980 2.83 996 2.89
5,000 948 3.01 964 3.08 980 3.14 996 3.21 1012 3.27 1028 3.34 1044 3.40 1060 3.47
5,500 1023 3.68 1039 3.75 1055 3.81 1071 3.88 1087 3.94 1103 4.01 1119 4.07 1135 4.14 5 HP OVER SIZE MOTOR & DRIVE
6,000 1109 4.45 1125 4.51 1141 4.58 1157 4.64 1173 4.71 1189 4.77 - - - -

• Fan motor heat(MBH) = 3.10 x Fan Bhp


• Test Condition: ➊ Voltage : 220V
❷ Operating Mode: Fan operation mode with clean filter, dry coil, without electric heater.
• Do not operate the unit at a cooling airflow that is less then 350cfm/1.2MBH.

Table-17 Fan speed Data LK-13B0CH

6 Turn Open 5 Turn Open 4 Turn Open 3 Turn Open 2 Turn Open 1 Turn Open Closed
Standard Motor & Drive
Fan Speed 655 700 745 790 835 880 924
Standard Motor & High Static
Drive Accessory Fan Speed 779 832 886 939 992 1046 N.A
Over size Motor & Drive
Fan Speed 831 888 945 1002 1059 1116 1173

• Factory set at 3 turns open.

— 12 —
Performance Data
Table-18 Supply Fan Performance LK-15B0CH/AH

External Static Pressure(inches of water)


CFM 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
4 HP STANDARD MOTOR & LOW STATIC DRIVE KIT
4,800 646 1.58 663 1.66 679 1.73 696 1.81 713 1.88 730 1.96 747 2.03 764 2.11 780 2.18 797 2.26 814 2.33 831 2.41
5,400 695 2.16 712 2.24 729 2.31 746 2.39 763 2.46 780 2.54 796 2.61 813 2.69 830 2.76 847 2.84 864 2.91 881 2.99
6,000 754 2.85 771 2.92 788 3 805 3.07 821 3.15 838 3.22 855 3.3 872 3.37 889 3.45 906 3.52 923 3.6 939 3.67
6,600 822 3.65 839 3.72 856 3.8 873 3.87 890 3.95 906 4.02 923 4.1 940 4.17 957 4.25 974 4.32 991 4.39 1008 4.47
7,200 900 4.56 917 4.63 934 4.71 951 4.78 968 4.86 985 4.93 - - - - - - - - - - - -

External Static Pressure(inches of water) 5 HP OVER SIZE MOTOR & DRIVE


CFM 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

4,800 848 2.48 865 2.56 882 2.63 898 2.71 915 2.78 932 2.86 949 2.93 966 3.01
4 HP STANDARD MOTOR & DRIVE
5,400 898 3.06 914 3.14 931 3.21 948 3.29 965 3.36 982 3.44 999 3.51 1015 3.59
6,000 956 3.75 973 3.82 990 3.9 1007 3.97 1024 4.05 1040 4.12 1057 4.2 1074 4.27
6,600 1024 4.54 1041 4.62 1058 4.69 1075 4.77 1092 4.84 1109 4.92 1125 4.99 - -
5 HP OVER SIZE MOTOR & DRIVE
7,200 - - - - - - - - - - - - - - - -

• Fan motor heat(MBH) = 3.10 x Fan Bhp


• Test Condition: ➊ Voltage : 220V
❷ Operating Mode: Fan operation mode with clean filter, dry coil, without electric heater.
• Do not operate the unit at a cooling airflow that is less then 350cfm/1.2MBH.

Table-19 Fan speed Data LK-15B0CH/AH

6 Turn Open 5 Turn Open 4 Turn Open 3 Turn Open 2 Turn Open 1 Turn Open Closed
Standard Motor & Low Static
Drive Accessory Fan Speed 544 583 623 662 792 741 781
Standard Motor & Drive
Fan Speed 692 742 792 842 893 943 993
Over size Motor & Drive
Fan Speed 891 952 1013 1074 1135 1196 N.A

• Factory set at 3 turns open.

— 13 —
Performance Data

Table-20 Supply Fan Performance LK-18B0CH

External Static Pressure(inches of water)


CFM 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP STANDARD MOTOR & LOW STATIC DRIVE ACCESSORY 5 HP STANDARD MOTOR & DRIVE
5,600 – – – – 718 2.26 742 2.38 765 2.50 789 2.63 813 2.78 836 2.92 857 3.06 879 3.21 903 3.37 927 3.53
6,300 745 2.84 768 2.98 791 3.11 812 3.24 833 3.37 854 3.51 875 3.65 897 3.82 918 3.98 937 4.14 957 4.30 976 4.46
7,000 822 3.86 843 4.01 864 4.16 884 4.31 904 4.46 923 4.60 941 4.75 960 4.90 979 5.08 999 5.26 1018 5.44 1036 5.61
7,700 900 5.11 920 5.27 939 5.44 957 5.60 976 5.77 993 5.93 1010 6.09 1027 6.24 1044 6.41 1061 6.59 1079 6.78 1097 6.98
8,400 979 6.59 997 6.78 1014 6.96 1031 7.14 1048 7.32 1065 7.49 1081 7.67 1097 7.84 1113 8.02 1128 8.19 1143 8.37 1159 8.57

External Static Pressure(inches of water)


CFM 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP STANDARD MOTOR & DRIVE 7.5 HP OVER SIZE MOTOR & DRIVE

5,600 949 3.70 971 3.88 993 4.06 1014 4.24 1036 4.42 1058 4.60 1079 4.79 1101 4.97
6,300 997 4.63 1018 4.81 1039 4.99 1059 5.19 1079 5.38 1098 5.58 1117 5.78 1136 5.98
7,000 1053 5.79 1070 5.97 1088 6.15 1106 6.34 1125 6.54 1144 6.74 1163 6.95 1181 7.17
7,700 1114 7.18 1131 7.37 1147 7.56 1163 7.76 1179 7.95 1194 8.15 1211 8.36 1228 8.58
8,400 – – – – – – – – – – – – – – – –

• Fan motor heat(MBH) = 3.03 x Fan Bhp


• Test Condition: ➊ Voltage : 220V
❷ Operating Mode: Fan operation mode with clean filter, dry coil, without electric heater.
• Do not operate the unit at a cooling airflow that is less then 350cfm/1.2MBH.
• Motor S.F: 1.15

Table-21 Fan speed Data LK-18B0CH

6 Turn Open 5 Turn Open 4 Turn Open 3 Turn Open 2 Turn Open 1 Turn Open Closed
Standard Motor & Low Static
Drive Accessory Fan Speed 692 739 787 834 881 929 976
Standard Motor & Drive
Fan Speed 891 952 1013 1074 1135 1196 1257
Over size Motor & Drive
Fan Speed 1017 1086 1156 1225 1295 N.A N.A

• Factory set at 3 turns open.

— 14 —
Performance Data

Table-22 Supply Fan Performance LK-20B0CH/AH

External Static Pressure(inches of water)


CFM 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP STANDARD MOTOR & DRIVE
6,400 - - - - - - - - 477 1.18 502 1.34 526 1.51 549 1.68 573 1.87 598 2.08 620 2.30 644 2.50
7,200 - - - - - - 497 1.68 522 1.88 545 2.06 567 2.23 589 2.42 610 2.61 638 2.80 649 3.02 671 3.25
8,000 - - 488 2.00 517 2.23 544 2.47 568 2.70 590 2.93 611 3.13 631 3.32 651 3.52 670 3.72 687 3.94 706 4.16
8,800 507 2.72 538 2.90 565 3.15 590 3.40 614 3.66 636 3.93 656 4.17 675 4.40 694 4.62 712 4.83 728 5.05 745 5.28
9,600 559 3.74 587 3.90 613 4.24 637 4.51 660 4.79 682 5.08 702 5.36 721 5.64 739 5.89 756 6.13 772 6.37 787 6.61

7.5 HP OVER SIZED MOTOR & DRIVE


External Static Pressure(inches of water)
CFM 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2 5 HP STANDARD MOTOR & HIGH STATIC DRIVE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP STANDARD MOTOR & DRIVE 5 HP STANDARD MOTOR & HIGH STATIC DRIVE
8,000 666 2.70 687 2.89 709 3.11 731 3.34 753 3.57 773 3.80 793 4.03 812 4.27
9,000 693 3.48 713 3.72 736 3.94 756 4.17 774 4.39 793 4.62 813 4.86 833 5.12
10,000 724 4.38 741 4.62 763 4.88 783 5.14 803 5.40 822 5.66 840 5.91 858 6.16
10,500 763 5.51 778 5.75 797 5.99 814 6.24 831 6.50 849 6.79 869 7.07 887 7.28 7.5 HP OVER SIZED MOTOR & DRIVE
11,000 804 6.94 818 7.09 836 7.34 852 7.59 862 7.85 880 8.14 900 8.42 918 8.63

• Fan motor heat(MBH) = 3.03 x Fan Bhp


• Test Condition: ➊ Voltage : 220V
❷ Operating Mode: Fan operation mode with clean filter, dry coil, without electric heater.
• Do not operate the unit at a cooling airflow that is less then 350cfm/1.2MBH.
• Motor S.F: 1.15

Table-23 Fan speed Data LK-20B0CH/AH

6 Turn Open 5 Turn Open 4 Turn Open 3 Turn Open 2 Turn Open 1 Turn Open Closed
Standard Motor & Drive
Fan Speed 477 509 540 572 604 636 667
Standard Motor & High Static
Drive Accessory Fan Speed 661 706 750 794 838 882 926
Over size Motor & Drive
Fan Speed 757 808 858 909 959 1009 N.A

• Factory set at 3 turns open.

— 15 —
Performance Data
Table-24 Supply Fan Performance LK-25B0CH/AH

External Static Pressure(inches of water)


CFM 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
7.5 HP STANDARD MOTOR & LOW STATIC DRIVE 7.5 HP STANDARD MOTOR & DRIVE
8,000 481 2.01 513 2.19 541 2.37 567 2.55 591 2.73 615 2.91 638 3.09 661 3.27 685 3.45 709 3.65 731 3.87 753 4.10
9,000 514 2.64 545 2.82 572 3.00 597 3.18 621 3.36 643 3.54 670 3.72 693 3.90 711 4.08 734 4.28 753 4.50 773 4.73
10,000 547 3.34 577 3.52 603 3.70 627 3.88 650 4.06 672 4.24 702 4.42 725 4.60 738 4.78 760 4.98 779 5.20 797 5.43
10,500 580 4.12 609 4.30 634 4.48 656 4.66 680 4.84 702 5.02 734 5.20 757 5.38 766 5.56 787 5.76 805 5.98 821 6.21
11,000 613 4.97 641 5.15 665 5.33 687 5.51 711 5.69 732 5.87 767 6.05 790 6.23 795 6.41 814 6.61 832 6.83 847 7.06

External Static Pressure(inches of water)


CFM 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
7.5 HP STANDARD MOTOR & DRIVE
8,000 773 4.32 793 4.54 812 4.76 831 4.98 849 5.20 867 5.42 885 5.64 906 5.86
9,000 792 4.77 812 5.11 830 5.34 849 5.56 867 5.78 885 6.00 903 6.22 924 6.44 7.5 HP STANDARD MOTOR & HIGH STAIC DRIVE
10,000 813 5.37 832 5.72 849 5.98 868 6.20 886 6.42 904 6.64 922 6.86 943 7.08
10,500 837 6.08 854 6.41 870 6.66 889 6.88 907 7.10 925 7.32 943 7.54 964 7.76
11,000 863 6.87 880 7.21 894 7.45 913 7.67 931 7.89 949 8.11 967 8.33 988 8.55

• Fan motor heat(MBH) = 2.96 x Fan Bhp


• Test Condition: ➊ Voltage : 220V
❷ Operating Mode: Fan operation mode with clean filter, dry coil, without electric heater.
• Do not operate the unit at a cooling airflow that is less then 350cfm/1.2MBH.
• Motor S.F:1.15

Table-25 Fan speed Data LK-25B0CH/AH

6 Turn Open 5 Turn Open 4 Turn Open 3 Turn Open 2 Turn Open 1 Turn Open Closed
Standard Motor & Low Static
Drive Accessory Fan Speed 447 509 540 572 604 636 667
Standard Motor & Drive
Fan Speed 586 625 664 703 742 781 820
Standard Motor & High Static
Drive Accessory Fan Speed 757 808 858 909 959 1009 N.A

• Factory set at 3 turns open.

— 16 —
Performance data
Table-26 Accessory Static Pressure Drops (in. aq)

Standard Electric Heater


Unit Model No. cfm
Filter 5KW 9KW 10KW 15KW 18KW 36KW
960 0.02 0.01 - 0.01 - - -
LK-0320CC/AC 1200 0.03 0.01 - 0.01 - - -
1440 0.03 0.02 - 0.02 - - -
1280 0.03 0.01 - 0.01 0.03 - -
LK-0420CC/AC 1600 0.03 0.02 - 0.02 0.04 - -
1920 0.05 0.03 - 0.04 0.07 - -
1600 0.03 0.02 - 0.02 0.03 - -
LK-0520CC/AC 2000 0.05 0.03 - 0.04 0.06 - -
2400 0.07 0.04 - 0.05 0.09 - -
1480 0.03 0.02 0.02 - - - -
LK-05B0CC/AC 1850 0.05 0.03 0.04 - - - -
2220 0.07 0.04 0.05 - - - -
2000 0.03 - 0.01 - - 0.01 -
LK-06B0CH/AH 2500 0.06 - 0.01 - - 0.02 -
3000 0.09 - 0.02 - - 0.03 -
2400 0.04 - 0.01 - - 0.02 -
LK-08B0CH/AH 3000 0.08 - 0.01 - - 0.03 -
3600 0.12 - 0.02 - - 0.04 -
2720 0.04 - 0.01 - - 0.06 -
LK-09B0CH 3400 0.07 - 0.01 - - 0.08 -
4080 0.09 - 0.02 - - 0.11 -
3200 0.06 - 0.01 - - 0.07 -
LK-10B0CH/AH 4000 0.10 - 0.01 - - 0.10 -
4800 0.14 - 0.02 - - 0.15 -
4000 0.08 - - - - 0.03 -
LK-13B0CH 5000 0.13 - - - - 0.06 -
6000 0.18 - - - - 0.09 -
4800 0.06 - - - - 0.04 0.04
LK-15B0CH/AH 6000 0.09 - - - - 0.06 0.07
7200 0.13 - - - - 0.10 0.11
5600 0.06 - - - - 0.05 0.05
LK-18B0CH 7000 0.11 - - - - 0.07 0.07
8400 0.15 - - - - 0.11 0.12
6400 0.07 - - - - - 0.05
LK-20B0CH/AH 8000 0.10 - - - - - 0.09
9600 0.14 - - - - - 0.14
8000 0.08 - - - - - 0.07
LK-25B0CH/AH 10000 0.13 - - - - - 0.13
12000 0.18 - - - - - 0.17

— 17 —
Performance Data
Table-27 Electric Heating Capacity

Total Stage 1 Stage 2


MODEL No. of Stages
Input(KW) Output(MBH) Input(kw) Output(MBH) Input(kw) Output(MBH)
LK-0320CC 5 17.07 1 5 17.07 - -
10 34.14 1 10 34.14 - -
LK-0420CC 5 17.07 1 5 17.07 - -
10 34.14 1 10 34.14 - -
15 68.28 1 15 68.28 - -
LK-0520CC 5 17.07 1 5 17.07 - -
10 34.14 1 10 34.14 - -
15 68.28 1 15 68.28 - -
LK-05B0CC 5 17.07 1 5 17.07 - -
9 30.72 1 9 30.72 - -
LK-06B0CH/AH 9 30.72 1 9 30.72 - -
18 61.43 1 18 61.43 - -
LK-08B0CH/AH 9 30.72 1 9 30.72 - -
18 61.43 1 18 61.43 - -
LK-09B0CH 9 30.72 1 9 30.72 - -
18 61.43 1 18 61.43 - -
LK-10B0CH/AH 9 30.72 1 9 30.72 - -
18 61.43 1 18 61.43 - -
LK-13B0CH 18 61.43 1 18 61.43 - -
LK-15B0CH/AH 18 61.43 1 18 61.43 - -
36 122.86 2 18 61.43 18 61.43
LK-18B0CH 18 61.43 1 18 61.43 - -
36 122.86 2 18 61.43 18 61.43
LK-20B0CH/AH 36 122.86 2 18 61.43 18 61.43
LK-25B0CH/AH 36 122.86 2 18 61.43 18 61.43
Note: 1. The output ratings shown above is at 240V.
For other voltage, Output = Capacity Multiplier x Rated Output
Voltage Capacity Multiplier
2. E/heater Voltage range is 208~240V. 208 0.75
220 0.84
230 0.92
240 1.00

Table-28 Air Temperature Rise Across Electric Heater(°F)

Capacity Stage LK-0320CC/AC LK-0420CC/AC LK-0520CC/AC LK-05B0CC/AC LK-06B0CH/AH LK-08B0CH/AH LK-09B0CH LK-10B0CH/AH LK-13B0CH/AH LK-15B0CH/AH LK-18B0CH/AH LK-20B0CH/AH LK-25B0CH/AH
(1200CFM) (1600CFM) (2000CFM) (1850CFM) (2500CFM) (3000CFM) (3400CFM) (4000CFM) (5000CFM) (6000CFM) (7000CFM) (8000CFM) (10000CFM)
5KW 1 13.2 9.9 7.9 8.5 - - - - - - - - -
9KW 1 - - - 17.1 11.4 9.5 8.4 7.1 - - - - -
10KW 1 26.3 19.8 15.8 - - - - - - - - - -
18KW 1 - - - - 22.8 18.2 16.7 14.2 11.4 9.5 8.1 - -
36KW 2 - - - - - - - - - 19.0 16.2 14.2 11.4
(KW x 3413)
• Temp. Rise across Electric Heater =
(1.08 x CFM)
• If you want to take temp rise at different airflow use above equation.

— 18 —
Electrical Requirements
Electrical Requirements

Table-29 Cooling

Unit Operating Standard indoor fan motor Oversize indoor fan motor
Tons MODEL
Voltage Range *M.C.A. *M.F.S. *M.C.B *M.C.A. *M.F.S. *M.C.B
3 LK-0320CC/AC 198~242 28.8 40 40 - - -
4 LK-0420CC/AC 198~242 34.4 50 50 - - -
5 LK-0520CC/AC 198~242 42.3 60 60 - - -
5 LK-05B0CC/AC 187~253 29.3 40 40 - - -
6.25 LK-06B0CH/AH 198~242 35 50 50 37.7 60 60
7.5 LK-08B0CH/AH 198~242 43 60 60 45.7 60 60
8.5 LK-09B0CH 198~242 52.6 70 70 - - -
10 LK-10B0CH/AH 198~242 57.6 70 70 64.8 80 80
12.5 LK-13B0CH 198~242 73 90 90 79 100 100
15 LK-15B0CH/AH 198~242 86 100 100 91 110 110
17.5 LK-18B0CH 198~242 102 110 110 110 125 125
20 LK-20B0CH/AH 198~242 124 150 150 132 150 150
25 LK-25B0CH/AH 198~242 133 150 150 - - -
Note: *M.C.A.: Minimum Circuit Ampacity
*M.F.S.: Maximum Fuse Size
*M.C.B.: Maximum Circuit Breaker

Table-30 Electric Heating

HEATER HEATER Standard indoor fan motor Oversize indoor fan motor
MODEL POWER SUPPLY
MODEL NO. CAPACITY(kW) *M.C.A. *M.F.S. *M.C.B *M.C.A. *M.F.S. *M.C.B
LKAEH052 5 32.2 50 50 - - -
LK-0320CC/AC 1Ø, 220V, 60HZ
LKAEH102 10 55 60 60 - - -
LKAEH052 5 34.2 50 50 - - -
LK-0420CC/AC LKAEH102 10 1Ø, 220V, 60HZ 57 70 70 - - -
LKAEH152 15 79.7 90 90 - - -
LKAEH052 5 34.2 50 50 - - -
LK-0520CC/AC LKAEH102 10 1Ø, 220V, 60HZ 57 70 70 - - -
LKAEH152 15 79.7 90 90 - - -
LKAEH05B 5 24.5 30 30 - - -
LK-05B0CC/AC 3Ø, 220V, 60HZ
LKAEH09B1 9 36.3 40 40 - - -
LKAEH09B 9 35.1 50 50 38.1 50 50
LK-06B0CH/AH 3Ø, 220V, 60HZ
LKAEH18B 18 58.7 70 70 61.5 70 70
LKAEH09B 9 35.1 50 50 38.1 50 50
LK-08B0CH/AH 3Ø, 220V, 60HZ
LKAEH18B 18 58.7 70 70 61.5 70 70
LKAEH09B 9 41.2 60 60 - - -
LK-09B0CH 3Ø, 220V, 60HZ
LKAEH18B 18 64.8 80 80 - - -
LKAEH09B 9 41.2 60 60 48.4 60 60
LK-10B0CH/AH 3Ø, 220V, 60HZ
LKAEH18B 18 64.8 80 80 72 90 90
LKAEH09B 9 41.2 60 60 48.4 60 60
LK-13B0CH 3Ø, 220V, 60HZ
LKAEH18B 18 64.8 80 80 72 90 90
LKAEH18B 18 82 100 100 88 100 100
LK-15B0CH/AH 3Ø, 220V, 60HZ
LKAEH36B 36 122 125 125 130 150 150
LK-18B0CH LKAEH36B 36 3Ø, 220V, 60HZ 130 150 150 139 150 150
LK-20B0CH/AH LKAEH36BL 36 3Ø, 220V, 60HZ 130 150 150 139 150 150
LK-25B0CH/AH LKAEH36BL 36 3Ø, 220V, 60HZ 139 150 150 - - -
Note: ➊ The heater Capacity shown above is at 240V.
❷ Voltage range is 208~240V.
*M.C.A.: Minimum Circuit Ampacity
*M.F.S.: Maximum Fuse Size
*M.C.B.: Maximum Circuit Breaker
— 19 —
Electrical Requirements

Table-31 Evaporator Fan Motor --- 60 Hz

Standard indoor fan motor Oversize indoor fan motor


MODEL
No Volts Phase HP FLA LRA No Volts Phase HP FLA LRA
LK-0320CC/AC 1 220 1 0.75 5.9 12.3 - - - - - -
LK-0420CC/AC 1 220 1 0.5 4.3 9.3 - - - - - -
LK-0520CC/AC 1 220 1 0.75 5.9 12.3 - - - - - -
LK-05B0CC/AC 1 220 1 0.75 5.9 12.3 - - - - - -
LK-06B0CH/AH 1 220 3 1.5 6.7 40.2 1 220 3 3 9.4 81
LK-08B0CH/AH 1 220 3 1.5 6.7 40.2 1 220 3 3 9.4 81
LK-09B0CH 1 220 3 3.0 9.4 81 - - - - - -
LK-10B0CH/AH 1 220 3 3.0 9.4 81 1 220 3 5 16.6 108.5
LK-13B0CH 1 220 3 3.0 9.4 81 1 220 3 5 16.6 108.5
LK-15B0CH/AH 1 220 3 4.0 12.5 90 1 220 3 5 16.6 108.5
LK-18B0CH 1 220 3 5.0 16.6 108.5 1 220 3 7.5 24.2 164.4
LK-20B0CH/AH 1 220 3 5.0 16.6 115 1 220 3 7.5 24.2 164.4
LK-25B0CH/AH 1 220 3 7.5 24.2 164.4 - - - - - -

Compressor and Outdoor Fan Motor --- 60 Hz


Table-32

COMPRESSOR OUTDOOR FAN MOTOR


MODEL
No Volts Phase HP FLA LRA No Volts Phase HP FLA LRA
LK-0320CC/AC 1 208-230 1 3.0 19.0 105 1 220 1 0.5 3.4 10.8
LK-0420CC/AC 1 208-230 1 4.0 19.2 110 1 220 1 0.5 3.4 10.8
LK-0520CC/AC 1 208-230 1 5.0 24.6 147 1 220 1 0.5 3.4 10.8
LK-05B0CC/AC 3 208-230 1 5.0 16.0 150 2 220 1 0.15 0.9 1.4
LK-06B0CH/AH 1 208-230 3 6.0 18.3 158 1 220 1 0.5 3.4 10.8
LK-08B0CH/AH 1 208-230 3 7.5 25.2 190 1 220 1 0.5 3.4 10.8
LK-09B0CH 2 208-230 3 4.0 14.0 137 1 220 1 1.3 6.2 19.5
LK-10B0CH/AH 2 208-230 3 5.0 16.0 150 1 220 1 1.3 6.2 19.5
LK-13B0CH 2 208-230 3 6.0 18.3 158 1 220 1 1.3 6.2 19.5
LK-15B0CH/AH 2 208-230 3 7.5 25.2 190 2 220 1 1.3 6.2 19.5
LK-18B0CH 2 208-230 3 8.5 29.0 228 2 220 1 1.3 6.2 19.5
LK-20B0CH/AH 2 208-230 3 10.0 33.5 264 2 220 1 1.3 6.2 19.5
LK-25B0CH/AH 2 208-230 3 12.0 43.1 252 2 220 3 2.0 6.7 40.2

— 20 —
Dimensions
LK-0320CC/LK-0420CC/LK-0520CC
Unit: inch(mm)
UNITS LK-0320CC/0420CC/0520CC
A 34.45(875)
B 45.08(1145) CLEARANCE 34" CLEARANCE 16"(HORIZONTAL)
CLEARANCE 34"(DOWNFLOW)
C 64.17(1630)
D 47.2(1199)
E 8.50(216)
F
CLEARANCE 34"
F 2.76(70)
E
A
G 3.15(80)
Center Line of Hole
D
G
B
1" Dia. Hole Control Wires
1.5" Dia. Hole Power Wires C

1.5" Dia. Hole Other Purpose


CLEARANCE 48"

3/4" Condensate Location


Unit: inch(mm)
UNITS LK-0320CC/0420CC/0520CC
H 14.02(356)
J 7.91(201)
S R
U E
20(508)

K 14.02(356) P T

14.02(356)
L 6.85(173)
P U
L R
M 4.57(116) Y N
N 20.0(508)
2.76(70)

14.02(356) 4.92(125) 20(508)

3/4" Condensate Location

S R
U E
20(508)

P T
14.02(356)

P U
L R
Y N
2.76(70)

14.02(356) 4.92(125) 20(508)

3.86(98)

— 21 —
Dimensions
LK-05B0CC

Unit: inch(mm) CLEARANCE 36" CLEARANCE 18"


(HORIZONTAL)
UNITS LK-05B0CC CLEARANCE 36"
(DOWNFLOW)
A 31.89(810)
B 43.31(1100)
C 50.39(1280)
F CLEARANCE 36"
D 29.49(749) A
E
E 9.65(245) Center Line of Hole
G
F 2.36(60)
D
G 2.76(70) 1" Dia. Hole Control Wires B
1.5" Dia. Hole Power Wires C
1.5" Dia. Hole Other Purpose

CLEARANCE 48"

Unit: inch(mm)
UNITS LK-05B0CC
A 13.86(352)
B 9.21(234)
C 10.47(266)
D 3.86(98)
RETURN
SUPPLY

E 4.33(110)
G F
F 19.53(496)
G 14.41(366)
E

A B C D

3/4" Condensate Location


A 3.82(97)
Unit: inch(mm)
UNITS LK-05B0CC
6.26(159) 13.86(352) 9.25(235) 10.47(266)

A 19.53(496) RETURN
B 14.41(366)

SUPPLY

B 3.82(97)

— 22 —
Dimensions
LK-06B0CH/AH, LK-08B0CH/AH

Unit: inch(mm)
UNITS LK-06B0CH/AH, LK-08B0CH/AH
A 35.04(890) CLEARANCE 34"
CLEARANCE 16"
B 46.93(1159)
C 85.43(2170)
D 10.43(265)
E 2.76(70)
F 2.36(60) CLEARANCE 34"
G 3.54(90) A

C
B
CLEARANCE 46" F 1.5" Dia. Hole Other Purpose
E 1.5" Dia. Hole Power Wires
D G
1" Dia. Hole Control Wires

Center Line of Hole

Unit: inch(mm)
UNITS LK-06B0CH/AH, LK-08B0CH/AH
H 15.47(393)
J 16.18(411) S R
K 18.82(478)
U E
P T
L 2.40(61) P U
M 5.35(136) L R N
N 26.89(683)
Y N
M

H J K L

— 23 —
Dimensions
LK-09B0CH, LK-10B0CH/AH, LK-13B0CH

Unit: inch(mm) CLEARANCE 34"


UNITS LK-09B0CH, LK-10B0CH/AH LK-13B0CH CLEARANCE 16"(HORIZONTAL)
A 41.34(1050) 41.34(1050)
B 48.89(1242) 61.02(1550)
C 85.43(2170) 85.43(2170) G
F
E
D 55.0(1397) 55.08(1399)
CLEARANCE 34"
Center Line of Hole
E 6.10(155) 6.10(155) A
D
F 8.46(215) 8.46(215)
C
G 10.43(265) 10.43(265) 1" Dia. Hole Control Wires
B
1.5" Dia. Hole Power Wires
1.5" Dia. Hole Other Purpose

CLEARANCE 46"

Unit: inch(mm)
UNITS LK-09B0CH, LK-10B0CH/AH LK-13B0CH
H 16.06(408) 18.43(468)
S R
J 14.02(356) 11.65(296) U E
K 20.16(512) 20.16(512) P T
L 2.44(62) 2.44(62)
P U N
L R
M 2.01(51) 4.92(125) Y N
M

N 34.33(872) 34.41(874)

H J K L

— 24 —
Dimensions

LK-15B0CH/AH, LK-18B0CH

Horizontal Application Unit


Rear View Showing Duct Openings For Horizontal Air Flow

Unit: inch(mm)
UNITS LK-15B0CH/AH, LK-18B0CH
CLEARANCE 34" CLEARANCE 16"(HORIZONTAL)
A 47.44(1205)
B 69.53(1766)
C 95.98(2438)
G
D 63.11(1603) F
E
E 6.29(160) CLEARANCE 34"
Center Line of Hole A
F 8.66(220) D
G 11.02(280)
C
1" Dia. Hole Control Wires
B
1.5" Dia. Hole Power Wires
1.5" Dia. Hole Other Purpose

CLEARANCE 46"

Horizontal Unit
Rear View Showing Duct Openings For Horizontal Air Flow

Unit: inch(mm)
UNITS LK-15B0CH/AH, LK-18B0CH
H 24.53(623)
S R
I 9.17(233)
U E
J 24.53(623) P T
K 2.36(60) P U M
L 5.08(129) L R
M 40.24(1022)
Y N
L

H I J K

— 25 —
Dimensions
LK-20B0CH/AH, LK-25B0CH/AH

Horizontal Application Unit


Rear View Showing Duct Openings For Horizontal Air Flow

Unit: inch(mm)
UNITS LK-20B0CH/AH, LK-25B0CH/AH
CLEARANCE 34" CLEARANCE 16"(HORIZONTAL)
A 65.35(1660)
B 74.02(1880)
C 109.21(2774)
D 69.69(1770) F
E
E 7.68(195) CLEARANCE 34"
Center Line of Hole A
F 11.89(302) D

B
2" Dia. Hole Power Wires
1.5" Dia. Hole Other Purpose(3EA)

CLEARANCE 46"

Horizontal Unit
Rear View Showing Duct Openings For Horizontal Air Flow

Unit: inch(mm)
UNITS LK-20B0CH/AH, LK-25B0CH/AH
H 25.57(649.5)
S R
I 15.28(388) U E
J 27.34(694.5) P T

M
K 2.40(61) P U
L 6.10(155)
L R
Y N
M 57.09(1450)
L

H I J K

— 26 —
Dimensions
7.5~10 Ton Accessories

FRESH AIR HOOD


(MANUAL)

Weights
Maximum Unit and Corner Weights (Lbs) and Center of Gravity Dimensions (In.)
Unit Maximum Weights (lbs) Corner Weights (lbs) Center of Gravity (In.)
Tons Model No. Shipping2 Net E F
A B C D
3 LK-0320CC/AC 474 419 138 109 82 91 29 20
4 LK-0420CC/AC 496 441 147 114 85 95 28 20
5 LK-0520CC/AC 540 485 165 124 91 106 28 19
6.5 LK-06B0CH/AH 728 573 190 151 111 122 39 18
7.5 LK-08B0CH/AH 772 617 209 161 116 132 38 17
8.5 LK-09B0CH 926 728 248 187 135 157 37 19
10 LK-10B0CH/AH 970 772 261 197 145 168 37 20
12.5 LK-13B0CH 1036 882 299 225 166 193 36 25
15 LK-15B0CH/AH 1455 1213 411 310 228 264 40 28
17.5 LK-18B0CH 1565 1323 450 343 248 282 42 29
20 LK-20B0CH/AH 2171 1808 639 438 320 411 43 31
25 LK-25B0CH/AH 2281 1918 697 460 328 433 42 30
Note: 1.Corner weights are given for information only.
2. Weights are approximate.

A B

D C
CENTER OF GRAVITY

— 27 —
Dimensions
Weights
Maximum Unit and Corner Weights (Lbs) and Center of Gravity Dimensions (In.)

Unit Maximum Weights (lbs) Corner Weights (lbs) Center of Gravity (In.)
Tons Model No. Shipping 2
Net A B C D E F
5 LK-0520CC 441 49 146 115 85 95 22 20

A B

D C
CENTER OF GRAVITY

— 28 —
Refrigerant Circuit Diagram
• Model: LK-0320CC/AC, LK-0420CC/AC SERVICE LOW-PRESSURE
VALVE SWITCH
LK-0520CC/AC, LK-06B0CH/AH
LK-08B0CH/AH, LK-05B0CC/AC
CAPILLARY
SUCTION TUBE
LINE

HI-PRESSURE
SWITCH SERVICE
OUTDOOR (OPTION) VALVE S INDOOR
COIL COIL
D
DISCHARGE
LINE

• Model: LK-09B0CH, LK-10B0CH/AH, LK-13B0CH : REFRIGERANT FLOW

LK-15B0CH/AH, LK-18B0CH, LK-20B0CH/AH


LK-25B0CH/AH SUCTION LINE
CIRCUIT #2
LOW-PRESSURE SUCTION LINE
SWITCH
CIRCUIT #1
SERVICE CAPILLARY
VALVE LOW-PRESSURE
SWITCH TUBE(18PLACE)
HI-PRESSURE HI-PRESSURE
SWITCH SWITCH
(OPTION) (OPTION) SERVICE
VALVE
SERVICE SERVICE
VALVE VALVE
CIRAUIT #2

CIRCUIT #1

S
COMP 2
D
DISCHARGE
LINE

S
COMP 1
D
DISCHARGE
LINE
OUTDOOR COIL CIRCUIT #1 INDOOR COIL
CIRCUIT #2
: REFRIGERANT FLOW

— 29 —
Cooling Cycle Operating Pressures/Superheat Charging Chart
1. Superheat Charging Chart(LK-0320CC)
CHART BASED ON 400 CFM/TON INDOOR AIR FLOW AND 50% RELATIVE HUMIDITY.

INDOOR DRY BULB TEMPERATURE


50
95 Notes:
45 90 1. MEASURE INDOOR DRY BULB TEMPERATURE.
2. MEASURE OUTDOOR DRY BULB TEMPERATURE.
85
40 3. MEASURE SUCTION PRESSURE AT PRESSURE
80 TAP ON OUTDOOR UNIT.
35 4. MEASURE SUCTION TEMPERATURE NEAR
75 PRESSURE TAP ON OUTDOOR UNIT.
SUPERHEAT ˚F

30 5. DETERMINE DEGREES SUPERHEAT FROM


70 TEMPERATURE PRESSURE CHART OR LOW SIDE
MANIFOLD GAUGE.
25
6. FIND THE INTERSECTION WHERE THE OUTDOOR
TEMPERATURE AND INDOOR TEMPERATURE
20
MEET AND READ DEGREES SUPERHEAT. IF UNIT
SUPERHEAT IS MORE THAN 5° ABOVE CHART
15 VALUE, ADD R-22 UNTIL WITHIN 5°. IF UNIT
SUPERHEAT IS MORE THAN 5° BELOW CHART
10 VALUE, REMOVE R-22 UNTIL WITHIN 5°.
7. IF SUPERHEAT IS BELOW THE 5° LIMIT LINE, DO
5 NOT ADD R-22.
DO NOT ADD CHARGE IF LIMIT LINE
POINT FALLS BELOW THIS LINE
55 60 65 70 75 80 85 90 95 100 105 110 115
OUTDOOR TEMPERATURE ˚F

2. Superheat Charging Chart(LK-0420CC)


CHART BASED ON 400 CFM/TON INDOOR AIR FLOW AND 50% RELATIVE HUMIDITY.

INDOOR DRY BULB TEMPERATURE


50
95
Notes:
45 90 1. MEASURE INDOOR DRY BULB TEMPERATURE.
2. MEASURE OUTDOOR DRY BULB TEMPERATURE.
85
40 3. MEASURE SUCTION PRESSURE AT PRESSURE
80 TAP ON OUTDOOR UNIT.
35 4. MEASURE SUCTION TEMPERATURE NEAR
75 PRESSURE TAP ON OUTDOOR UNIT.
SUPERHEAT ˚F

30 5. DETERMINE DEGREES SUPERHEAT FROM


70
TEMPERATURE PRESSURE CHART OR LOW SIDE
25 MANIFOLD GAUGE.
6. FIND THE INTERSECTION WHERE THE OUTDOOR
20 TEMPERATURE AND INDOOR TEMPERATURE
MEET AND READ DEGREES SUPERHEAT. IF UNIT
SUPERHEAT IS MORE THAN 5° ABOVE CHART
15
VALUE, ADD R-22 UNTIL WITHIN 5°. IF UNIT
SUPERHEAT IS MORE THAN 5° BELOW CHART
10 VALUE, REMOVE R-22 UNTIL WITHIN 5°.
7. IF SUPERHEAT IS BELOW THE 5° LIMIT LINE, DO
5 NOT ADD R-22.
DO NOT ADD CHARGE IF LIMIT LINE
POINT FALLS BELOW THIS LINE
55 60 65 70 75 80 85 90 95 100 105 110 115
OUTDOOR TEMPERATURE ˚F

— 30 —
Cooling Cycle Operating Pressures/Superheat Charging Chart
3. Superheat Charging Chart(LK-0520CC)
CHART BASED ON 400 CFM/TON INDOOR AIR FLOW AND 50% RELATIVE HUMIDITY.

INDOOR DRY BULB TEMPERATURE


50
95
Notes:
45 90
1. MEASURE INDOOR DRY BULB TEMPERATURE.
85 2. MEASURE OUTDOOR DRY BULB TEMPERATURE.
40
3. MEASURE SUCTION PRESSURE AT PRESSURE
80 TAP ON OUTDOOR UNIT.
35
75 4. MEASURE SUCTION TEMPERATURE NEAR
SUPERHEAT ˚F

PRESSURE TAP ON OUTDOOR UNIT.


30
70 5. DETERMINE DEGREES SUPERHEAT FROM
TEMPERATURE PRESSURE CHART OR LOW SIDE
25 MANIFOLD GAUGE.
6. FIND THE INTERSECTION WHERE THE OUTDOOR
20 TEMPERATURE AND INDOOR TEMPERATURE
MEET AND READ DEGREES SUPERHEAT. IF UNIT
15 SUPERHEAT IS MORE THAN 5° ABOVE CHART
VALUE, ADD R-22 UNTIL WITHIN 5°. IF UNIT
SUPERHEAT IS MORE THAN 5° BELOW CHART
10
VALUE, REMOVE R-22 UNTIL WITHIN 5°.
7. IF SUPERHEAT IS BELOW THE 5° LIMIT LINE, DO
5 NOT ADD R-22.
DO NOT ADD CHARGE IF LIMIT LINE
POINT FALLS BELOW THIS LINE
55 60 65 70 75 80 85 90 95 100 105 110 115
OUTDOOR TEMPERATURE ˚F

4. Superheat Charging Chart(LK-05B0CC)


CHART BASED ON 350 CFM/TON INDOOR AIR FLOW AND 50% RELATIVE HUMIDITY.

INDOOR DRY BULB TEMPERATURE


50
95 Notes:
45 90 1. MEASURE INDOOR DRY BULB TEMPERATURE.
2. MEASURE OUTDOOR DRY BULB TEMPERATURE.
85
40 3. MEASURE SUCTION PRESSURE AT PRESSURE
TAP ON OUTDOOR UNIT.
80
35 4. MEASURE SUCTION TEMPERATURE NEAR
75 PRESSURE TAP ON OUTDOOR UNIT.
SUPERHEAT ˚F

30 5. DETERMINE DEGREES SUPERHEAT FROM


70 TEMPERATURE PRESSURE CHART OR LOW SIDE
MANIFOLD GAUGE.
25
6. FIND THE INTERSECTION WHERE THE OUTDOOR
TEMPERATURE AND INDOOR TEMPERATURE
20 MEET AND READ DEGREES SUPERHEAT. IF UNIT
SUPERHEAT IS MORE THAN 5° ABOVE CHART
15 VALUE, ADD R-22 UNTIL WITHIN 5°. IF UNIT
SUPERHEAT IS MORE THAN 5° BELOW CHART
VALUE, REMOVE R-22 UNTIL WITHIN 5°.
10
7. IF SUPERHEAT IS BELOW THE 5° LIMIT LINE, DO
NOT ADD R-22.
5
DO NOT ADD CHARGE IF LIMIT LINE
POINT FALLS BELOW THIS LINE
55 60 65 70 75 80 85 90 95 100 105 110 115
OUTDOOR TEMPERATURE ˚F

— 31 —
Cooling Cycle Operating Pressures/Superheat Charging Chart
4. Cooling Cycle Operating Pressure (LK-06B0CH/AH)
COOLING CYCLE OPERATING PRESSURES

COMPRESSOR DISCHARGE PRESSURE, PSIG

B˚F
B˚F
450

/W
B˚F
B˚F

/W

DB
/W

DB
/W

DB

ID
DB

ID
400

/72
ID

/67
ID

86
/62

80
/57
115˚F OD AMBIENT

74
68
350
105˚F OD AMBIENT

300 95˚F OD AMBIENT

85˚F OD AMBIENT
250
75˚F OD AMBIENT
200 65˚F OD AMBIENT

55˚F OD AMBIENT
150
55 60 65 70 75 80 85 90 95 100

COMPRESSOR SUCTION PRESSURE, PSIG


TO CHECK OPERATING PRESSURES
1. Start the unit and allow the pressures to stabilize.
5. Plot the outdoor dry bulb and the indoor DB/WB temperature
2. Measure Indoor air DB/WB temperature entering the indoor coil.
onto the chart.
3. Measure Outdoor air dry bulb temperature.
6. At the point of intersection, read down for the suction pressure
4. Take discharge and suction pressure readings.
and to the left for the discharge pressure.
Chartss based on 400 CFM/;ton Indoor air flow

5. Superheat Charging Chart(LK-06B0CH/AH)


SUPERHEAT CHARGING CHART

40
To Determine Design Superheat-A) Start along bottom axis at outdoor temp.
B) Go up to the curve representing the indoor
COMPRESSOR SUPERHEAT, (˚F)

temp.(or interpolate)
C) Go horizontally and read superheat on left axis
30
86/7
2 ID
DB/
WB
˚F
20 80/
74 867
68 /62 ID
DB
/5 ID /W
7 DB B˚F
ID /W
DB B˚
/W F
10 B˚
F

0
50 60 70 80 90 100 110 120

OUTDOOR AMBIENT TEMPERATURE, DB (˚F)


1) Refrigerant chage – ADD if superheat is more than 5F above curve value
– REDUCE if superheat is more than 5F below curve value
– OK if superheat is within 5F of chart value
2) Do not add refrigerant if the superheat is less than 5F
3) Curves are based on 400 CFM/Ton Indoor Airflow and 50% R.H.
4) System must be running at stabilized conditions before measuring superheat.

— 32 —
Cooling Cycle Operating Pressures/Superheat Charging Chart
6. Cooling Cycle Operating Pressure(LK-08B0CH/AH)
COOLING CYCLE OPERATING PRESSURES
500

COMPRESSOR DISCHARGE PRESSURE, PSIG

B˚F
B˚F

/W
B˚F

/W
450

B˚F

DB
/W

DB
/W

ID
DB

ID
DB

/72
ID

/67
400

86
ID

/62

80
115˚F OD AMBIENT

/57

74
68
350 105˚F OD AMBIENT

95˚F OD AMBIENT
300
85˚F OD AMBIENT
250
75˚F OD AMBIENT

200 65˚F OD AMBIENT


55˚F OD AMBIENT
150
50 55 60 65 70 75 80 85 90 95 100 105

COMPRESSOR SUCTION PRESSURE, PSIG


TO CHECK OPERATING PRESSURES
1. Start the unit and allow the pressures to stabilize.
5. Plot the outdoor dry bulb and the indoor DB/WB temperature
2. Measure Indoor air DB/WB temperature entering the indoor coil.
onto the chart.
3. Measure Outdoor air dry bulb temperature.
6. At the point of intersection, read down for the suction pressure
4. Take discharge and suction pressure readings.
and to the left for the discharge pressure.
Chartss based on 400 CFM/;ton Indoor air flow

7. Superheat Charging Chart(LK-08B0CH/AH)


SUPERHEAT CHARGING CHART

40
To Determine Design Superheat-A) Start along bottom axis at outdoor temp.
B) Go up to the curve representing the indoor
COMPRESSOR SUPERHEAT, (˚F)

temp.(or interpolate)
C) Go horizontally and read superheat on left axis
30
86/7
2 ID
DB/
WB
˚F
20 80/
74 867
68 /62 ID
DB
/5 ID /W
7 DB B˚F
ID /W
DB B˚
/W F
10 B˚
F

0
50 60 70 80 90 100 110 120

OUTDOOR AMBIENT TEMPERATURE, DB (˚F)


1) Refrigerant chage – ADD if superheat is more than 5F above curve value
– REDUCE if superheat is more than 5F below curve value
– OK if superheat is within 5F of chart value
2) Do not add refrigerant if the superheat is less than 5F
3) Curves are based on 400 CFM/Ton Indoor Airflow and 50% R.H.
4) System must be running at stabilized conditions before measuring superheat.

— 33 —
Cooling Cycle Operating Pressures/Superheat Charging Chart
8. Operating Pressure Curve(LK-09B0CH/LK-10B0CH/AH)
Circuit #1
(Based on Indoor Airflow of 400 CFM/Ton)
FULL LOAD

86/72 ID DB/WB˚F
500

80/67 ID DB/WB˚F
74/62 ID DB/WB˚F
68/57 ID DB/WB˚F
450
DISCHARGE PRESSURE, PSIG

400 115˚F OD AMBIENT

105˚F OD AMBIENT
350

95˚F OD AMBIENT
300
85˚F OD AMBIENT
250 75˚F OD AMBIENT

65˚F OD AMBIENT
200
55˚F OD AMBIENT

150
55 60 65 70 75 80 85 90 95 100 105
SUCTION PRESSURE, PSIG
TO CHECK OPERATING PRESSURES
1. Start the unit and allow the pressures to stabilize.
5. Plot the outdoor dry bulb and the indoor DB/WB temperature
2. Measure Indoor air DB/WB temperature entering the indoor coil.
onto the chart.
3. Measure Outdoor air dry bulb temperature.
6. At the point of intersection, read down for the suction pressure
4. Take discharge and suction pressure readings.
and to the left for the discharge pressure.

Circuit #2
(Based on Indoor Airflow of 400 CFM/Ton)
FULL LOAD
500
86/72 ID DB/WB˚F
80/67 ID DB/WB˚F
74/62 ID DB/WB˚F

450
68/57 ID DB/WB˚F
DISCHARGE PRESSURE, PSIG

400

115˚F OD AMBIENT
350
105˚F OD AMBIENT

300
95˚F OD AMBIENT

250 85˚F OD AMBIENT

75˚F OD AMBIENT
200
65˚F OD AMBIENT
55˚F OD AMBIENT
150
55 60 65 70 75 80 85 90 95 100 105
SUCTION PRESSURE, PSIG
TO CHECK OPERATING PRESSURES
1. Start the unit and allow the pressures to stabilize.
5. Plot the outdoor dry bulb and the indoor DB/WB temperature
2. Measure Indoor air DB/WB temperature entering the indoor coil.
onto the chart.
3. Measure Outdoor air dry bulb temperature.
6. At the point of intersection, read down for the suction pressure
4. Take discharge and suction pressure readings.
and to the left for the discharge pressure.

— 34 —
Cooling Cycle Operating Pressures/Superheat Charging Chart
9. Superheat Charging Chart(LK-09B0CH/LK-10B0CH/AH)
SUPERHEAT CHARGING CHART
(Based on Indoor Airflow of 400 CFM/Ton)

50
COMPRESSOR SUPERHEAT, DEG F

To Determine Required Superheat-


A) Plot the Outdoor Temperature onto the bottom axis of the curve.
B) Move vertically to the appropriate indoor DB/WB temp.(or interpolated temp)
40 C) At the point of intersection, (OD & ID) read horizontally to the left the required superheat.

86/72 ID DB/WB˚F
30
80/87 ID DB/WB˚F
80/67
74/62 ID DB/WB˚F

20 68/57 ID DB/WB˚F

10

0
35 45 55 65 75 85 95 105 115

OUTDOOR AMBIENT, DB F

1) Refrigerant chage – ADD if superheat is more than 5F above curve value


– REDUCE if superheat is more than 5F below curve value
– OK if superheat is within 5F of chart value
2) Do not add refrigerant if the superheat is less than 5F
3) Curves are based on 400 CFM/Ton Indoor Airflow and 50% R.H.
4) System must be running at stabilized conditions before measuring superheat.

— 35 —
Cooling Cycle Operating Pressures/Superheat Charging Chart
10. Operating Pressure Curve(LK-13B0CH)
COOLING CYCLE PRESSURE CURVE
(Based on 5000 CFM Indoor Airflow)
FULL LOAD
500

86/72 ID DB/WB˚F
80/67 ID DB/WB˚F
74/62 ID DB/WB˚F
450

68/57 ID DB/WB˚F
DISCHARGE PRESSURE, PSIG

400
115˚F OD AMBIENT

350 105˚F OD AMBIENT

95˚F OD AMBIENT
300
85˚F OD AMBIENT
250
75˚F OD AMBIENT

65˚F OD AMBIENT
200
55˚F OD AMBIENT

150
45 50 55 60 65 70 75 80 85 90 95 100 105
SUCTION PRESSURE, PSIG
TO CHECK OPERATING PRESSURES
1. Start the unit and allow the pressures to stabilize.
5. Plot the outdoor dry bulb and the indoor DB/WB temperature
2. Measure Indoor air DB/WB temperature entering the indoor coil.
onto the chart.
3. Measure Outdoor air dry bulb temperature.
6. At the point of intersection, read down for the suction pressure
4. Take discharge and suction pressure readings.
and to the left for the discharge pressure.

11. Superheat Charging Chart(LK-13B0CH)


Charts Based on Indoor Airflow of 400 CFM/Ton
40
To Determine Required Superheat-
A) Plot the Outdoor Temperature onto the bottom axis
COMPRESSOR SUPERHEAT, (˚F)

of the curve.
B) Move vertically to the appropriate indoor DB/WB temp.
(or interpolated temp)
30 C) At the point of intersection, (OD & ID) read horizontally
to the left the required superheat.

20

86/72 ID DB/WB˚F
10

68/57 ID DB/WB˚F 74/62 ID DB/WB˚F 80/87 ID DB/WB˚F


80/67
0
50 60 70 80 90 100 110 120
OUTDOOR AMBIENT TEMPERATURE, DB (˚F)

1) Refrigerant chage – ADD if superheat is more than 5F above curve value


– REDUCE if superheat is more than 5F below curve value
– OK if superheat is within 5F of chart value
2) Do not add refrigerant if the superheat is less than 5F
3) Curves are based on 400 CFM/Ton Indoor Airflow and 50% R.H.
4) System must be running at stabilized conditions before measuring superheat.

— 36 —
Cooling Cycle Operating Pressures/Superheat Charging Chart
12. Operating Pressure Curve(LK-15B0CH/AH)
COOLING CYCLE PRESSURE CURVE
(Based on Indoor Airflow of 6000 CFM)
ONE CONDENSER FAN “ON”
450

86/72 ID DB/WB˚F
80/67 ID DB/WB˚F
400
DISCHARGE PRESSURE, PSIG

74/62 ID DB/WB˚F
68/57 ID DB/WB˚F
350
65˚F OD AMBIENT

55˚F OD AMBIENT
300
45˚F OD AMBIENT

250 35˚F OD AMBIENT

200

150
45 50 55 60 65 70 75 80 85 90 95 100 105
SUCTION PRESSURE, PSIG
TO CHECK OPERATING PRESSURES
1. Start the unit and allow the pressures to stabilize.
5. Plot the outdoor dry bulb and the indoor DB/WB temperature
2. Measure Indoor air DB/WB temperature entering the indoor coil.
onto the chart.
3. Measure Outdoor air dry bulb temperature.
6. At the point of intersection, read down for the suction pressure
4. Take discharge and suction pressure readings.
and to the left for the discharge pressure.

COOLING CYCLE PRESSURE CURVE


(Based on Indoor Airflow of 6000 CFM)
BOTH CONDENSER FANS “ON”
550
86/72 ID DB/WB˚F

500
80/67 ID DB/WB˚F
DISCHARGE PRESSURE, PSIG

74/62 ID DB/WB˚F
68/57 ID DB/WB˚F

450

400
115˚F OD AMBIENT

350 105˚F OD AMBIENT

95˚F OD AMBIENT
300
85˚F OD AMBIENT

250 75˚F OD AMBIENT

65˚F OD AMBIENT
200
55˚F OD AMBIENT

150
45 50 55 60 65 70 75 80 85 90 95 100 105
SUCTION PRESSURE, PSIG
TO CHECK OPERATING PRESSURES
1. Start the unit and allow the pressures to stabilize.
5. Plot the outdoor dry bulb and the indoor DB/WB temperature
2. Measure Indoor air DB/WB temperature entering the indoor coil.
onto the chart.
3. Measure Outdoor air dry bulb temperature.
6. At the point of intersection, read down for the suction pressure
4. Take discharge and suction pressure readings.
and to the left for the discharge pressure.

— 37 —
Cooling Cycle Operating Pressures/Superheat Charging Chart
13. Superheat Charging Chart(LK-15B0CH/AH)
SUPERHEAT CHARGING CHART
(Based on Indoor Airflow of 400 CFM / Ton)
ONE CONDENSER FAN “ON”
50
COMPRESSOR SUPERHEAT, DEG F

To Determine Required Superheat-


A) Plot the Outdoor Temperature onto the bottom axis of the curve.
B) Move vertically to the appropriate indoor DB/WB temp.(or interpolated temp)
40 C) At the point of intersection, (OD & ID) read horizontally to the left the required superheat.

30

20

10
86/72 ID DB/WB˚F
80/87 ID DB/WB˚F
80/67
74/62 ID DB/WB˚F
0
35 45 55 65 75 85 95
OUTDOOR AMBIENT, DB F
1) Refrigerant chage – ADD if superheat is more than 5F above curve value
– REDUCE if superheat is more than 5F below curve value
– OK if superheat is within 5F of chart value
2) Do not add refrigerant if the superheat is less than 5F
3) Curves are based on 400 CFM/Ton Indoor Airflow and 50% R.H.
4) System must be running at stabilized conditions before measuring superheat.

SUPERHEAT CHARGING CHART


(Based on Indoor Airflow of 400 CFM / Ton)
BOTH CONDENSER FANS “ON”
50
COMPRESSOR SUPERHEAT, DEG F

To Determine Required Superheat-


A) Plot the Outdoor Temperature onto the bottom axis of the curve.
B) Move vertically to the appropriate indoor DB/WB temp.(or interpolated temp)
40 C) At the point of intersection, (OD & ID) read horizontally to the left the required superheat.

86/72 ID DB/WB˚F
30
80/87 ID DB/WB˚F
80/67
74/62 ID DB/WB˚F

20 68/57 ID DB/WB˚F

10

0
35 45 55 65 75 85 95 105 115
OUTDOOR AMBIENT, DB F
1) Refrigerant chage – ADD if superheat is more than 5F above curve value
– REDUCE if superheat is more than 5F below curve value
– OK if superheat is within 5F of chart value
2) Do not add refrigerant if the superheat is less than 5F
3) Curves are based on 400 CFM/Ton Indoor Airflow and 50% R.H.
4) System must be running at stabilized conditions before measuring superheat.

— 38 —
Cooling Cycle Operating Pressures/Superheat Charging Chart
14. Operating Pressure Curve(LK-18B0CH)
COOLING CYCLE PRESSURE CURVE
(Based on Indoor Airflow of 400 CFM /Ton)
ONE CONDENSER FAN “ON”
425

86/72 ID DB/WB˚F
80/67 ID DB/WB˚F
375

74/62 ID DB/WB˚F
DISCHARGE PRESSURE, PSIG

68/57 ID DB/WB˚F
65˚F OD AMBIENT
325
55˚F OD AMBIENT

45˚F OD AMBIENT
275

35˚F OD AMBIENT

225

175
45 50 55 60 65 70 75 80 85 90 95 100 105
SUCTION PRESSURE, PSIG
TO CHECK OPERATING PRESSURES
1. Start the unit and allow the pressures to stabilize.
5. Plot the outdoor dry bulb and the indoor DB/WB temperature
2. Measure Indoor air DB/WB temperature entering the indoor coil.
onto the chart.
3. Measure Outdoor air dry bulb temperature.
6. At the point of intersection, read down for the suction pressure
4. Take discharge and suction pressure readings.
and to the left for the discharge pressure.

COOLING CYCLE PRESSURE CURVE


(Based on Indoor Airflow of 400 CFM /Ton)
BOTH CONDENSER FANS “ON”
550
86/72 ID DB/WB˚F

500
80/67 ID DB/WB˚F
DISCHARGE PRESSURE, PSIG

74/62 ID DB/WB˚F
68/57 ID DB/WB˚F

450

400
115˚F OD AMBIENT

350 105˚F OD AMBIENT

95˚F OD AMBIENT
300
85˚F OD AMBIENT

250
75˚F OD AMBIENT
65˚F OD AMBIENT
200
55˚F OD AMBIENT

150
45 50 55 60 65 70 75 80 85 90 95 100 105 110
SUCTION PRESSURE, PSIG
TO CHECK OPERATING PRESSURES
1. Start the unit and allow the pressures to stabilize.
5. Plot the outdoor dry bulb and the indoor DB/WB temperature
2. Measure Indoor air DB/WB temperature entering the indoor coil.
onto the chart.
3. Measure Outdoor air dry bulb temperature.
6. At the point of intersection, read down for the suction pressure
4. Take discharge and suction pressure readings.
and to the left for the discharge pressure.

— 39 —
Cooling Cycle Operating Pressures/Superheat Charging Chart

15. Superheat Charging Chart(LK-18B0CH)


SUPERHEAT CHARGING CHART
(Based on Indoor Airflow of 400 CFM / Ton)
ONE CONDENSER FAN “ON”

50
COMPRESSOR SUPERHEAT, DEG F

To Determine Required Superheat-


A) Plot the Outdoor Temperature onto the bottom axis of the curve.
40 B) Move vertically to the appropriate indoor DB/WB temp.(or interpolated temp)
C) At the point of intersection, (OD & ID) read horizontally to the left the required superheat.

30

20

10
86/72 ID DB/WB˚F
80/87 ID DB/WB˚F
80/67
74/62 ID DB/WB˚F
0
30 40 50 60 70 80 90
OUTDOOR AMBIENT, DB F

SUPERHEAT CHARGING CHART


(Based on Indoor Airflow of 400 CFM / Ton)
BOTH CONDENSER FANS “ON”

50
To Determine Required Superheat-
COMPRESSOR SUPERHEAT, DEG F

A) Plot the Outdoor Temperature onto the bottom axis of the curve.
B) Move vertically to the appropriate indoor DB/WB temp.(or interpolated temp)
40 C) At the point of intersection, (OD & ID) read horizontally to the left the required superheat.

86/72 ID DB/WB˚F
30 80/87 ID DB/WB˚F
80/67
74/62 ID DB/WB˚F

68/57 ID DB/WB˚F
20

10

0
35 45 55 65 75 85 95 105 115
OUTDOOR AMBIENT, DB F

1) Refrigerant chage – ADD if superheat is more than 5F above curve value


– REDUCE if superheat is more than 5F below curve value
– OK if superheat is within 5F of chart value
2) Do not add refrigerant if the superheat is less than 5F
3) Curves are based on 400 CFM/Ton Indoor Airflow and 50% R.H.
4) System must be running at stabilized conditions before measuring superheat.

— 40 —
Cooling Cycle Operating Pressures/Superheat Charging Chart
16. Operating Pressure Curve(LK-20B0CH/AH)
COOLING CYCLE PRESSURE CURVE
(Based on Indoor Airflow of 400 CFM /Ton)
ONE CONDENSER FAN “ON”
425

86/72 ID DB/WB˚F
80/67 ID DB/WB˚F
375
DISCHARGE PRESSURE, PSIG

74/62 ID DB/WB˚F
68/57 ID DB/WB˚F
325
65˚F OD AMBIENT

55˚F OD AMBIENT
275

45˚F OD AMBIENT

225
35˚F OD AMBIENT

175
45 50 55 60 65 70 75 80 85 90 95 100 105
SUCTION PRESSURE, PSIG

TO CHECK OPERATING PRESSURES


1. Start the unit and allow the pressures to stabilize.
5. Plot the outdoor dry bulb and the indoor DB/WB temperature
2. Measure Indoor air DB/WB temperature entering the indoor coil.
onto the chart.
3. Measure Outdoor air dry bulb temperature.
6. At the point of intersection, read down for the suction pressure
4. Take discharge and suction pressure readings.
and to the left for the discharge pressure.

COOLING CYCLE PRESSURE CURVE


(Based on Indoor Airflow of 400 CFM /Ton)
BOTH CONDENSER FANS “ON”
550
86/72 ID DB/WB˚F

500
80/67 ID DB/WB˚F
DISCHARGE PRESSURE, PSIG

74/62 ID DB/WB˚F
68/57 ID DB/WB˚F

450

400
115˚F OD AMBIENT
350
105˚F OD AMBIENT

300 95˚F OD AMBIENT

85˚F OD AMBIENT
250
75˚F OD AMBIENT
200 65˚F OD AMBIENT
55˚F OD AMBIENT
150
45 50 55 60 65 70 75 80 85 90 95 100 105 110
SUCTION PRESSURE, PSIG
TO CHECK OPERATING PRESSURES
1. Start the unit and allow the pressures to stabilize.
5. Plot the outdoor dry bulb and the indoor DB/WB temperature
2. Measure Indoor air DB/WB temperature entering the indoor coil.
onto the chart.
3. Measure Outdoor air dry bulb temperature.
6. At the point of intersection, read down for the suction pressure
4. Take discharge and suction pressure readings.
and to the left for the discharge pressure.

— 41 —
Cooling Cycle Operating Pressures/Superheat Charging Chart

17. Superheat Charging Chart(LK-20B0CH/AH)


SUPERHEAT CHARGING CHART
(Based on Indoor Airflow of 400 CFM / Ton)
ONE CONDENSER FAN “ON”
50
COMPRESSOR SUPERHEAT, DEG F

To Determine Required Superheat-


A) Plot the Outdoor Temperature onto the bottom axis of the curve.
40 B) Move vertically to the appropriate indoor DB/WB temp.(or interpolated temp)
C) At the point of intersection, (OD & ID) read horizontally to the left the required superheat.

30

20

10
86/72 ID DB/WB˚F
80/87 ID DB/WB˚F
80/67
74/62 ID DB/WB˚F
0
30 40 50 60 70 80 90
OUTDOOR AMBIENT, DB F

SUPERHEAT CHARGING CHART


(Based on Indoor Airflow of 400 CFM / Ton)
BOTH CONDENSER FANS “ON”
50
To Determine Required Superheat-
COMPRESSOR SUPERHEAT, DEG F

A) Plot the Outdoor Temperature onto the bottom axis of the curve.
B) Move vertically to the appropriate indoor DB/WB temp.(or interpolated temp)
40 C) At the point of intersection, (OD & ID) read horizontally to the left the required superheat.

86/72 ID DB/WB˚F
30 80/87 ID DB/WB˚F
80/67
74/62 ID DB/WB˚F

68/57 ID DB/WB˚F
20

10

0
35 45 55 65 75 85 95 105 115
OUTDOOR AMBIENT, DB F

1) Refrigerant chage – ADD if superheat is more than 5F above curve value


– REDUCE if superheat is more than 5F below curve value
– OK if superheat is within 5F of chart value
2) Do not add refrigerant if the superheat is less than 5F
3) Curves are based on 400 CFM/Ton Indoor Airflow and 50% R.H.
4) System must be running at stabilized conditions before measuring superheat.

— 42 —
Cooling Cycle Operating Pressures/Superheat Charging Chart
18. Operating Pressure Curve(LK-25B0CH/AH)
COOLING CYCLE PRESSURE CURVE
(Based on Indoor Airflow of 400 CFM /Ton)
ONE CONDENSER FAN “ON”
450

86/72 ID DB/WB˚F
400
DISCHARGE PRESSURE, PSIG

80/67 ID DB/WB˚F
74/62 ID DB/WB˚F
350

68/57 ID DB/WB˚F
65˚F OD AMBIENT
300
55˚F OD AMBIENT

250
45˚F OD AMBIENT

35˚F OD AMBIENT
200

150
45 50 55 60 65 70 75 80 85 90 95 100 105
SUCTION PRESSURE, PSIG
TO CHECK OPERATING PRESSURES
1. Start the unit and allow the pressures to stabilize.
5. Plot the outdoor dry bulb and the indoor DB/WB temperature
2. Measure Indoor air DB/WB temperature entering the indoor coil.
onto the chart.
3. Measure Outdoor air dry bulb temperature.
6. At the point of intersection, read down for the suction pressure
4. Take discharge and suction pressure readings.
and to the left for the discharge pressure.

COOLING CYCLE PRESSURE CURVE


(Based on Indoor Airflow of 400 CFM /Ton)
BOTH CONDENSER FANS “ON”
550
86/72 ID DB/WB˚F
80/67 ID DB/WB˚F

500
74/62 ID DB/WB˚F
68/57 ID DB/WB˚F
DISCHARGE PRESSURE, PSIG

450

400

115˚F OD AMBIENT
350
105˚F OD AMBIENT
300
95˚F OD AMBIENT

250 85˚F OD AMBIENT


75˚F OD AMBIENT
200 65˚F OD AMBIENT
55˚F OD AMBIENT
150

100
45 50 55 60 65 70 75 80 85 90 95 100 105

TO CHECK OPERATING PRESSURES SUCTION PRESSURE, PSIG


1. Start the unit and allow the pressures to stabilize.
5. Plot the outdoor dry bulb and the indoor DB/WB temperature
2. Measure Indoor air DB/WB temperature entering the indoor coil.
onto the chart.
3. Measure Outdoor air dry bulb temperature.
6. At the point of intersection, read down for the suction pressure
4. Take discharge and suction pressure readings.
and to the left for the discharge pressure.

— 43 —
Cooling Cycle Operating Pressures/Superheat Charging Chart

19. Superheat Charging Chart(LK-25B0CH/AH)


SUPERHEAT CHARGING CHART
(Based on Indoor Airflow of 400 CFM / Ton)
ONE CONDENSER FAN “ON”
50
COMPRESSOR SUPERHEAT, DEG F

To Determine Required Superheat-


A) Plot the Outdoor Temperature onto the bottom axis of the curve.
B) Move vertically to the appropriate indoor DB/WB temp.(or interpolated temp)
40 C) At the point of intersection, (OD & ID) read horizontally to the left the required superheat.

30

20

10
86/72 ID DB/WB˚F
80/87 ID DB/WB˚F
80/67
74/62 ID DB/WB˚F
0
35 45 55 65 75 85 95
OUTDOOR AMBIENT, DB F

SUPERHEAT CHARGING CHART


(Based on Indoor Airflow of 400 CFM / Ton)
BOTH CONDENSER FANS “ON”

50
COMPRESSOR SUPERHEAT, DEG F

To Determine Required Superheat-


A) Plot the Outdoor Temperature onto the bottom axis of the curve.
B) Move vertically to the appropriate indoor DB/WB temp.(or interpolated temp)
40 C) At the point of intersection, (OD & ID) read horizontally to the left the required superheat.

86/72 ID DB/WB˚F
30
80/87 ID DB/WB˚F
80/67
74/62 ID DB/WB˚F

20 68/57 ID DB/WB˚F

10

0
35 45 55 65 75 85 95 105 115
OUTDOOR AMBIENT, DB F
1) Refrigerant chage – ADD if superheat is more than 5F above curve value
– REDUCE if superheat is more than 5F below curve value
– OK if superheat is within 5F of chart value
2) Do not add refrigerant if the superheat is less than 5F
3) Curves are based on 400 CFM/Ton Indoor Airflow and 50% R.H.
4) System must be running at stabilized conditions before measuring superheat.

— 44 —
Wiring Diagram
LK-0320CC/LK-0420CC/LK-0520CC

1fl, 220V, 60Hz 1fl, 220V, 60Hz


POWER SUPPLY POWER SUPPLY DIAGRAM WIRING NOTE

FIELD WIRING BK : BLACK OR : ORANGE YL : YELLOW


USING BR: BROWN RD : RED
ELECTRIC CRANKCASE
HEATER FACTORY WIRING BL : BLUE WH: WHITE
HEATER

TERMINAL BLOCK TRANS


BK BL TIME DELAY P.C.B
BK
BL
BL
FUSE
(250V, 10A) RD YL BK

BL
A T1 T2
(For E/heater)
MAGNETIC

MAGNETIC
CONTACT

L1 L2 CONTACT L
A (For comp) AC 24V
B L1 L2 N
Fan
1
LOW PRESSURE S/W

B
T1 T2 Comp
2
POWER RELAY
( For l/motor)
4 A Heater
WH 3
6 ELECTRO-MECHANICAL
CAPACITOR

B
THERMOSTAT
BK
EH BK WH RD 1 AC 24V
OR R
Fan
P.T.C

ELECTRIC HEATER OR BL WH 2
G
WH BK 3 Comp
CAPACITOR Y
WH TERMINAL Heater
YL 4
R S RD BLOCK W
BR YL BK
C (SUPER-HI) 5
WH MECHANICAL
COMP OR (LOW) RD 6 THERMOSTAT
b
c WH

MOTOR a TERMINAL
BR YL BK OR (IN) BLOCK
NOTE
CAPACITOR
YL CRANKCASE
MOTOR BR
MODEL HEATER P.T.C a b c
(OUT) LK-0320CC X X BK(SUPER-HI) RD(LOW) BL(HI)
LK-0420CC O O BK(SUPER-HI) BL(HI) RD(LOW)
LK-0520CC X O BK(SUPER-HI) BL(HI) RD(LOW)

P/NO : 3854A30047A

— 45 —
Wiring Diagram
LK-05B0CC

3Ø 220V,60Hz 3Ø 220V,60Hz DIAGRAM WIRING NOTE


POWER SUPPLY POWER SUPPLY
FACTORY WIRING BK:BLACK OR: ORANGE YL: YELLOW
R S T R S T BR:BROWN RD:RED
USING OPTIONAL WRING
FIELD WIRING BL: BLUE WH:WHITE
ELECTRIC
HEATER

TERMINAL BLOCK TRANS


BK BL TIME DELAY P.C.B
BK CUT "a" POINT OF WIRE
BL AND CONNECT THERMISTER
BL FOR EVA (OPTION)
FUSE
(250V, 10A) RD YL BK
MAGNETIC CONTACT

BL
(For E/heater)

"a"

L
MAGNETIC
CONTACT
AC 24V
N
(For comp)
THERHISTER
FAN
1
FOR EVA

POWER RELAY
Comp

(FOR I/motor)
(OPTION)
LOW PRESSURE S/W

2
4 A
Heater
EH 3
6 B ELECTRO-MECHANICAL
ELECTRIC HEATER THERMOSTAT

BK RD 1 AC 24V
OR R
OR BL WH 2 FAN
G
CAPACITOR CAPACITOR
BK 3 Comp
Y
TERMINAL 4 Heater
BK WH RD BLOCK YL W
BR YL BR YL BK 5
T1 T2 T3
WH MECHANICAL
OR BL(HI) RD 6 THERMOSTAT
COMP
RD (LOW) WH

MOTOR BK(SUPER-HI)
(IN)
BR YL BK OR BR YL BK OR
TERMINAL
CAPACITOR BLOCK
YL
MOTOR MOTOR BK
(OUT) (OUT)

P/NO.: 3854A30047D

— 46 —
Wiring Diagram

LK-06B0CH/AH, LK-08B0CH/AH

USING ELECTRIC
HEATER
POWER SUPPLY 3fl 3WIRE
3fl 220V
60Hz EH 220V,60Hz
FIRE ALARM
POWER SUPPLY
HUMIDIFIER
REMOVE JUMP WIRE WHEN ELECTRIC TERMINAL BLCOK
CONNECTING FIRE ALARM BR
HEATER
SYSTEM

BK BK
FUSE BK
CANNOT BE USED WHEN
USING THERMOSTAT BK
YL
1 (5A 250V)
WH FUSE WH

FILLER
WH
2 (5A 250V)
TERMINAL 1 3fl 3WIRE
TERMINAL
BLOCK 220V,60Hz
BK
POWER SUPPLY

BR
TRANS WH
BK
ELECTRO-MECHANICAL
THERMOSTAT FUSE
HEATER
L
MAGNETIC
AC 24V 250V/3.15A HUMID CONTACT
N BK BK
POWER
FAN TRANS
1
COMP
Ry1

BR BK WH BK BK
2
Ry12

HEAT CAPACITOR
Ry4

3 0 2 6
POWER CRANKCASE
FAN HEATER
RELAY YL BR OR BK
COMP 4 8
Ry10

1
RD WH BK
MECHANICAL WH
THERMOSTAT T3 T2 T1 YL BR OR BK
BR BK WH RD
AC 24V RD
THERMOSTAT

R
WH AC 13V COMP MOTOR
G
FAN BK OUT
COMP OR AC 24V MAIN PCB ASM
Y
W
HEAT BR NOTE
MOTOR
2 FILLER IN
1 TERMINAL 2 THERMISTOR FIELD WIRING
CUT AND REMOVE FACTORY WIRING
ANTICIPATOR(RESISTOR)
BR
TABLE BK :BLACK RD :RED
BR
RD BR :BROWN WH:WHITE
RD
YL
MODEL CRANKCASE HEATER OR:ORANGE YL :YELLOW
YL LOW PRESSURE SWITCH
LK-06B0CH X
REMOTE FILLER REMOVE JUMP WIRE WHEN
LK-08B0CH O
CONTROLLER TERMINAL 3 CONNECTING THERMOSTAT 3854A20004A

— 47 —
Wiring Diagram
LK-09B0CH, LK-10B0CH/AH, LK-13B0CH

WIRING DIAGRAM
USING ELECTRIC
HEATER
POWER SUPPLY 3fl 3WIRE
3fl 220V
60Hz EH 220V,60Hz
FIRE ALARM
POWER SUPPLY
HUMIDIFIER
REMOVE JUMP WIRE WHEN ELECTRIC TERMINAL BLCOK
CONNECTING FIRE ALARM BR
HEATER
SYSTEM

FUSE BK RD
BK BK 3fl 3WIRE
CAN NOT BE USED WHEN
USING THERMOSTAT BK
YL
1 (5A 250V) RD WH 220V,60Hz
WH WH FUSE WH POWER
FILLER
2 (5A 250V)
WH
BK
SUPPLY
TERMINAL 1 TERMINAL BK
TERMINAL BLCOK
BLOCK1
BK

BR
TRANS
WH
BK

CONTACT(A)

CONTACT(B)
MAGNETIC

MAGNETIC
YL

HEATER FUSE HUMID


ELECTRO-MECHANICAL BK
THERMOSTAT
COMP(A)

250V/3.15A
POWER
Ry1

L
TRANS

WH
AC 24V
BK
POWER RELAY1

N
FAN 1 BK
2 6
Ry12

1 COMP(B)

POWER RELAY2
Ry4

Ry3

COMP FAN
2 4 0
OUT 0 4 8
HEAT COMP
Ry10
Ry11

3 IN
6
1
BR
WH

WH
RD

WH
BK

MECHANICAL BR
THERMOSTAT
AC 24V RD
THERMOSTAT

R BK WH RD BK WH RD
WH
WH
RD
BK

AC 13V
G
FAN BK
MAIN PCB ASM 3 T1 T2 T3 T1 T2 T3
CAPACITOR
BK
BK

COMP OR AC 24V

BK
BK
Y MOTOR

OR
BR

BK
YL
HEAT BR THERMISTOR(B)
W
2 FILLER
IN
T.P 4 COMP(A) COMP(B)
BK
BK

1 TERMINAL 2 TERMINAL

OR
BR

BK

BK
BK
YL
BLOCK2
CUT AND REMOVE
ANTICIPATOR(RESISTOR) MOTOR
THERMISTOR(A) OUT
BK BK WH WH T.P
BR
BR
RD LOW PRESSURE LOW PRESSURE
RD
YL
YL SWITCH(A) SWITCH(B)
NOTE
REMOTE FILLER REMOVE JUMP WIRE WHEN
CONTROLLER TERMINAL 3 CONNECTING THERMOSTAT BK :BLACK RD :RED
FIELD WIRING
BR :BROWN WH:WHITE
FACTORY WIRING OR:ORANGE YL :YELLOW 3854A20008A

— 48 —
Wiring Diagram
LK-15B0CH/AH, LK-18B0CH, LK-20B0CH/AH

NOTE
WIRING DIAGRAM
FIELD WIRING
FACTORY WIRING
POWER
SUPPLY 3fl 3WIRE BK : BLACK RD : RED
3fl 220V
EH 220V,60Hz EH BR : BROWN WH: WHITE
60Hz POWER OR: ORANGE YL : YELLOW
HUMIDIFIER SUPPLY
ELECTRIC ELECTRIC
HEATER(A) TERMINAL BLCOK HEATER(B)
BR BR
AC220V
RD
BK BK FUSE BK
CAN NOT BE USED WHEN
USING THERMOSTAT BK
USING ELECTRIC 1 (5A 250V)
RD WH
3fl 3WIRE
220V,60Hz
HEATER WH FUSE WH
POWER
FILLER
2 (5A 250V)
WH BK
SUPPLY
TERMINAL BK
TERMINAL 1 REMOVE JUMP WIRE
YL BLOCK1 WH TERMINAL BLOCK
WHEN CONNECTING
BK FIRE ALARM SYSTEM
TRANS
BR BR
FIRE WH BK
ALARM BK
BK
ELECTRO-MECHANICAL

CONTACT(A)

CONTACT(B)
COMP(B)

MAGNETIC

MAGNETIC
THERMOSTAT (A) (B) FUSE HUMID YL
L HEATER 250V/3.15A
AC 24V
N
Ry1

Ry2

POWER BK
COMP(A)

TRANS

WH
BK
FAN
1
POWER RELAY1

COMP 1 2 6
Ry12

2
Ry5
Ry4

Ry3

POWER RELAY3
HEAT FAN COMP BK BK BK BK
3 0 4 8
BK WH RD 4 0
OUT(A)
BR BK WH RD
Ry10
Ry11

IN OUT(B) BK BK BK BK
MECHANICAL T1 T2 T3 T1 T2 T3 6 1
BR
THERMOSTAT
WH CRANKCASE CRANKCASE
AC 24V RD COMP(A) COMP(B)
THERMOSTAT

HEATER HEATER
R
CN14
BK WH
WH AC 13V
FAN BK BR
THERMISTOR EVA(B)
G
Y
COMP
HEAT
OR
BR
AC 24V
CN13 3
W MAIN PCB ASM
4 CAPACITOR
CAPACITOR

OR
FILLER

BK
BK
BR

BK
YL
2
1
TERMINAL 2 CN12
THERMISTOR EVA(A)
TERMINAL

OR
BR

BK

BK
BK
WH

YL
RD

BK
BK

BLOCK2
CUT AND REMOVE

OR

BK
BK
BR

BK
YL
ANTICIPATOR(RESISTOR)

OR
BR
POWER RELAY2

BK

BK
BK
YL
WH
RD

MOTOR
BK

BR BK BK WH WH
BK
BK

BR 4 0 OUT(B)
RD
LOW PRESSURE LOW PRESSURE MOTOR MOTOR T.P
RD OUT(A)
YL SWITCH(A) SWITCH(B) IN 6
YL T.P 1 T.P
BK
BK

REMOTE FILLER REMOVE JUMP WIRE WHEN THERMISTOR OUT


TERMINAL 3 CONNECTING THERMOSTAT
CONTROLLER 3854A20011A

— 49 —
Wiring Diagram
LK-25B0CH/AH

— 50 —
Troubleshooting Guide
In general, possible trouble is classified in two causes.
The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air
Conditioning caused by a defect in the refrigeration circuit and improper application.
Unit runs but ineffective cooling

Ineffective Cooling or Heating

Check of cold (warm) air cir- Check of outdoor coil Check heat load increase in
culation for smooth flow. (heat exchanger) & the fan cooling operation.
operation.

Unexpected residue
Dirty indoor coil Check gas leakage.
(heat exchanger.)

Added electrical utencil


Malfunction of fan. Repair gas leak.

Check of inside gas


Clogging of air filter. Replacement of unit if the pressure.
unit is beyond repair.

Obstruction at air outlet.


Adjust refrigerant
charge.

Countermeasure against
above trouble.

Malfunction of compressor.

Check clogging in refrigera-


tion circuit.
Satisfactory operation with
Replacement of
temperature difference of
compressor
inlet & outlet air ;
Repair clogging in refrigera- COOLING : 7~10°C
tion circuit. HEATING : 15~17°C

— 51 —
Troubleshooting Guide

Fails to Start

Check power source. Check of circuit breaker


and fuse.

Check control switch


setting. Check control switch.

Compressor only fails to Fan only fails to start.


start.
Electric heater is not energized

Improper wiring.
Drop of power voltage. Loose terminal connection.

Defect of fan motor


Defect of compressor Improper wiring
capacitor.
capacitor.(Only single Phase
power supply Model)

Irregular motor resistance


Capacitor check.(Only single (Ω)
Phase power supply Model) Irregular motor insulation
(Ω)
Replacement of capacitor.
(Only single Phase power
supply Model) Replacement of fan motor.

Improper electric heater


Irregular motor resistance ( Ω ) Regular but fails to start.

Replacement of electric
Irregular motor insulation ( Ω ) heater.
Replacement of compressor.

Replacement of compressor

— 52 —
Troubleshooting Guide

PACKAGE AIR CONDITIONER VOLTAGE LIMITS

NAME PLATE RATING MINIMUM MAXIMUM


200 - 220 V 180 V 242 V
220 V 198 V 242 V
220 - 240 V 198 V 264 V

1. No cooling and heating operation performed


1) Both the blower and the compressor do not work

WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Other parts except the • Electric supply interrupted Measure power sypply
unit • Defective power wiring with a tester in case that • Repair a switch box and
• Cut off power fuse the same power source is relative instrument.
supplied to other equip- • Replacement of fuse
ment except the unit, • Request a power
what and where troubled supplier to repair.
can be discovered by
checking the operation of
other equipment.

Too low voltage Measure it with a tester. Check the power source.
Use a thick cable if nec-
essary.
Magnetic switch for com- Control point is on condi- Make short-circuit, then Replace it if necessary.
pressor & fan motor tion of "OFF" due to trou- measure it with tester.
ble.

Operating switch Troubled or defective Check it with the eyes or Repair or replace it.
contactor tester.

2) Only Indoor blowers do not work

WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Motor • Over heated Check it with tester Repair or replace it.


• Wiring short

Capacitor Defected Check it with a tester. Replace it.

• Cut- OFF of wiring


Electric wiring • Short circuited on Rewiring or Repair.
Check it with a tester.
operation

— 53 —
Troubleshooting Guide

3) Only outdoor fan does not work

WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Motor • Over-heated Check how it is insulated. Repair or replace it.


• Wire short

Electric Wiring Cut off of wiring Check it with a tester. Rewiring or repair.
Short circuited on
operation

4) Only compressor does not work

WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Magnetic switch for Defective contact, Check it with the eyes on Repair or replace it.
compressor motor magnetic coil troubled. with a tester.

Compressor motor Troubled over-heated Check how it is insulated. Replace or repair the
(layer short) compressor.

High pressure switch Troubled or defective Check it with a tester. Replace it if neces-
(Option part) contact or operating sary.

Electric circuit Defective connection or Check it with a tester. Rewiring or push reset
disconnection of the circuit button.
for compressor.

— 54 —
Troubleshooting Guide

2. The Units discontinue after the operation started


WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Outdoor coil Coil is dirty *1 Checking Wash it by means of


something like chemical
washing.

In-condensable gas Air intruded into the In the event that Extract air by vacuum
blended. refrigerant pipe line *1 difference between the pump, then replenish
saturating temperature (charge) the refrigerant.
corresponding to high
pressure and the
temperature of air
discharged from the
outdoor coil is more than
15°C, incondensable gas
may be blended.

High pressure switch Improper adjustment Check it with a pressure Read just it to normal
(Option part) gauge. operating pressure.
(Note)
Don't alternate the
specified adjusting
pressure. If the adjusted
pressure exceed the
specified range, it will
cause a great accident.

Refrigerant A shortage of refrigerant Check pressure Replenish the


amount. * 2 refrigerant. Repair the
spot where it is leaked.

Outdoor Fan Reverse rotation of fan Confirm the wind blowing If reversed, connect
Obstacle out upward. interchanged wires to
Air short circuit *1 each terminal.
Check it with eyes.
Power wirings.

Note: Use an appropriate measuring instrument for readjustment.


*1: High-pressure switch moves.
*2: Low- pressure switch moves.

— 55 —
Troubleshooting Guide
3. The unit is working, but not cooling and heating sufficiently
(Both blower and compressor are working)
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Load Much Cooling or Heating Heat load increased. Do necessary disposal


load Window or door has many respectively.
cracks or gaps.

Air flow Obstacle disturbs Intake Checking Correct it.


of uniform airflow.

Short air volume Reverse rotation of Checking Correct it.


blower.

Refrigerant Shortage in the charged Coil inlet pipe is frosted Recharge it.
refrigerant. (Repair the leakage spot).

Air passage Improper or foreign bodies Checking Correct or clear the


foreign bodies.

Air filter Clogged with dust Checking Cleaning

4. All the functions are performed as specified, but very noisy and vibrant
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Compressor Liquid refrigerant flooding • Check for refrigerant over-charge.


back from the evaporator. • Check to see if the intake air temperature is
extremely cold.
• Check for insufficient air flow quantity.

Faulty Discharge valve • Checking • Replace the


and suction valve. compressor

Blower Fan broken. Checking Repair or replace it.


Clear the foreign bodies.
Foreign matters intruded.

Screws Looseness or fail-off of Checking Correct


screws

Electric troubles Defective contact. Checking Repair and clean or


(Magnetic contactor) Defective contact point. replace it.
Rusting and foreign mat-
ters in the iron core con-
tact face. Defective con-
tact of the
operating switch.

Others Improper installation Checking Correct it.

— 56 —
Electronic parts Troubleshooting Guide
Possible trouble 1 : The unit does not operate.

Is the input voltage of NO 1. Check the Fuse.


transformer AC220V? 2. Check the wiring of AC220V.

YES

Is the output voltage of NO 1. Exchange the transformer.


transformer AC24V & AC13V? 2. Check the connector of
transformer.
YES

Is the output voltage NO


of IC02D(7805) on the 1. Exchange IC02D(7805) on
main PCB DC5V? the main PCB.
2. Check the D01D~D05D, R05C
YES on the main PCB.

Is the output voltage NO


of IC01D(7812 ) on the 1. Exchange IC01D(7812) on
main PCB DC12V? the main PCB.
2. Check the D01D~D05D,
YES R05C on the main PCB.

Is the output voltage NO


of IC01A(7036) on the 1. Exchange IC01A(7036) on
main PCB DC5V? the main PCB.

YES

NO 1. Exchange OSC.
OSC vibration?
2. Check the pattern around
OSC on the main PCB.
YES

1. Exchange main PCB ASS'Y

Possible trouble 2 : The remote-controller does not operate.

NO
Is the power ON? 1. Exchange or exchange FUSE.
2. Check the input voltage of
Main PCB ASS'Y.
YES

Is the input voltage NO 1. Check or exchange the IC01D


of remote-controller on the Main PCB.
DC12V? 2. Check or exchange the
YES Connector (RED, BROWN)
of the remote controller.
1. Exchange remote-controller
2. Check or exchange the Main
PCB ASS'Y.

— 57 —
Electronic parts Troubleshooting Guide

Possible trouble 3 : Key input of remote-controller does not respond.

Is the connection between YES 1. Check or repair Connector wiring.


MAIN PCB and remote-controller 2. Exchange the Connector.
correct?
NO

YES 1. Replace the pressed key.


Is any key on the remote-controller
keeping pressed? 2. Exchange the Knob or Key.

NO

Is there Check(F**) on YES


the remote controller LCD? 1. Remove cause of Check.
2. Reenergize the power supply.

NO

Is the input power voltage of YES


remote-controller DC12V? 1. Check or exchange IC01D
(7812) on the MAIN PCB.

NO

Is there OSC vibration on YES


the remote-controller PCB? 1. Exchange OSC
2. Check the pattern around OSC
on the remote-controller PCB.
NO

YES 1. Check Keys.


Do Keys have troubles?
2. Repair or exchange Key.

NO

Exchange remote-controller.

Possible trouble 4 : LCD display on the remote-controller shows some trouble.

Are there trouble in YES


LCD parts? 1. Check crack, damage of LCD.
2. Check LCD pattern.

NO

Is there trouble in the YES 1. Check or repair all IC with


remote-controller PCB dust or moisture on the PCB.
ASS'Y? 2. Exchange remote-controller
NO PCB.

Exchange remote-controller.

— 58 —
Electronic parts Troubleshooting Guide
Possible trouble 5 : No cooling operation performed.

NO
Is the unit operating? 1. Press power ON/OFF button.

YES

NO 1. Press cooling operation key.


Is the cooling mode?
2. After reenergizing power supply,
press power "ON/OFF" button.

YES

NO 1. Set flowing.
Set Temp. < Room Temp.?
'Set Temp. < Room Temp.'

YES

Is the output NO
voltage of IC02D on the MAIN 1. Check or exchange IC01D,
PCB DC5V? IC02D on the MAIN PCB.

YES

Is the output NO
voltage of IC02M's 14PIN on the 1. Check or exchange IC02M.
MAIN PCB DC0V?
2. Check 3-minutes time delay.

YES

Is the voltage NO
between 1PIN of CN2 and 1. Check or exchange RY10.
NEUTRAL 220V?

YES

Is the magnetic contactor NO 1. Check the wiring of Magnetic


for compressor OK? contactor.
2. Exchange Magnetic contactor.

YES

1. Check Compressor and


Capacitor for Compressor.

NOTE: 3ø model has not capacitor for compressor.

— 59 —
Electronic parts Troubleshooting Guide
Possible trouble 6 : No heater operation performed.

NO
Is the heater operation? 1. Select heater operation mode.

YES

NO 1. Reconnetting power supply.


Is the heater LCD "ON"? press Heater Key.

YES

NO 1. Set following.
Set temp. > Room temp.?
'Set temp. > Room temp.'

YES

Is the output NO
voltage of IC02D on the 1. Check or exchange IC01D,
MAIN PCB DC5V? IC02D on the MAIN PCB.

YES

Is the output NO
voltage of IC01M's 16PIN on the 1. Check or exchange IC01M.
MAIN PCB 0V?

YES

Is the voltage NO
between 1PIN of CN5 and 1. Check or exchange RY1.
NEUTRAL 220V?

YES

NO 1. Check the wiring of Magnetic


Is the magnetic contactor for
heater OK? contactor.
2. Exchange Magnetic contactor.

YES

Check or exchange E/Heater.

— 60 —
Electronic parts Troubleshooting Guide
Possible trouble 7 : No humidifier operation performed.

NO 1. Press cooling or fan operation


Is the indoor fan operation? or heater operation key.

YES

NO
Is the HUMID LCD "ON"? 1. Press humidifier Key.

YES

Is the output NO
voltage of IC02D on the 1. Check or exchange IC01D.
MAIN PCB DC5V? IC02D on the MAIN PCB.

YES

Is the output NO
voltage of IC02M's 12PIN on 1. Check or exchange IC02M.
the MAIN PCB 0V?

YES

Is the voltage NO
between 1PIN of CN4 and 1. Check or exchange RY12.
NEUTRAL 220V?

YES

Is the magnetic NO 1. Check the wiring or Magnetic


contactor for humidifier OK? contactor.
2. Exchange Magnetic contactor.

YES

Check the humidifier.

— 61 —
Electronic parts Troubleshooting Guide
Possible trouble 8 : Indoor motor does not operate.

NO
Is the unit operating? 1. Press power ON/OFF button.
2. Reconnect the power supply.

YES

Is the output
voltage of IC01M's 13PIN on NO
1. Check or exchange IC01M.
the MAIN PCB 0V?

YES

Is the voltage NO
between 1PIN of CN7 and 1. Check or exchange RY4.
NEUTRAL 220V?

YES

Is the "Power relay" for NO 1. Check the wiring of


indoor motor OK? "Power relay".
2. Exchange "Power relay".
YES

Check the indoor motor.

Possible trouble 9 : Outdoor motor does not operate.

NO
Is it cooling operation? 1. Press power "ON/OFF" button.
2. Select cooling operation.

YES

NO 1. Set following.
Is the compressor operating?
Set temp. < Room temp.
2. Wait, if the unit has operating
with 3-minute time delay.
YES

1. Check wiring for outdoor


motor and magnetic contactor.
2. Check outdoor motor & capacitor.

— 62 —
Features of Controller
1. Main Controller Circuit Diagram

— 63 —
Features of Controller
2. Feature of Main Controller

— 64 —
Features of Controller

3. Feature of Remote-Controller PCB ASS'Y

4. Feature of Remote-Controller LCD

— 65 —
Features of Controller
5. Timer PCB Circuit Diagram

12V

8 R06M DO1M
R03M R01M 12V
1K Q01M 1N4148 AC220V
220K 47K KRC107K 60Hz
3 + 1
2 - RY01M
JQ1a-12V

C01M
+
R02M
3.3uF 47K IC01M
4 KA393
L1
D02D~D05D ZNR
12V 1SR139-600 INR14D471
IC01D D04D D02D L2
Magnetic
0 1 Relay
7812
+ D05D
D03D
C04D C01D
104 470uF L3
C02D
25V 104 RY01M
TRANS JQ1a-12V

6. Timer PCB ASSY

D1 CN1
C3 IC1 C1 D2
D7 C2

D3 CN2
R7

R3
R2
R4

D4
C5
D5
R1
Q1

IC2
C4
C7
IC3

R9

CN3
R10
R5

R8

D6
Q2
R6

RY1
C8
C6

PCB: 2Q01062A

— 66 —
Features of Controller

7. Error Mode & Corrective Method


Error mode Cause of error Sensing condition of error Method of SVC Remark
OPEN/SHORT of Voltage of sensing: Over 4.8V 1. Check the voltage of "CO1H" Room
F01 room temp. Voltage of sensing: Less than on the remote controller. temp.(25°C)
sensor 0.5V 2. Check the temp. sensor of = DC 2.5V
remtote controller.
OPEN/SHORT of Voltage of sensing: Over 4.8V 1. Check C03H, R03H, R08H of Pipe temp.(25°C)
F02 indoor pipe temp. Voltage of sensing: Less than Main PCB. = DC 2.2V
0.5V 2. Check the temp. sensor of
sensor indoor pipe.
Communication Communication interruption 1. Check the connecting wire Input voltage of
Error between remote controller and between main PCB remote remote-controller
Main PCB for 2 minutes. controller. = DC 12V
F03 2. Check the input voltage of
remote-controller.
3. Check the wiring of
remote-controller.

8. Principal part list of controller

No. PART No. PART NAME REMARKS


1 6871A20039A MAIN PCB ASS'Y
2 0ITO874000E MICOM(MAIN) MICOM
3 6920AQ9033F RELAY RY1, RY4, RY10, RY12
4 6212AQ9002J OSCILLATOR OSC01B
5 6900AQ9028D FUSE FUSE(*250V, T3. 15A)
6 6102A90001A VARISTOR ZNR01J
7 6171AQ2138D POWER-TRANS TRANS(220V/60Hz 240V/50Hz)
8 6323AQ2333T INDOOR PIPE SENSOR A-CYCLE(IN)
9 6711A20007B WIRED REMOCON 6711A20007B
10 0ITO641010B MICOM(WIRED REMOCON) MICOM
11 6304A30001C LCD
12 6871A20043A PCB ASS'Y(WIRED REMOCON)

— 67 —
Features of Controller
9. Explanation of principal function
■ Flow Chart

START(Power supply)

YES

1. Initialize "micom".
2. A/D convert.
3. Main PCB: Waiting cooling operation.
4. Remote controller: Waiting input. NO
Dehumidification Mode? Heater operation mode?
YES
A

YES YES
NO
Power ON?
Dehumidification operating NO
Set Temp. > Indoor Temp.
YES

NO YES
Cooling Mode? Stop condition?
Heater operating
YES YES YES

NO Go to A
NO
Set Temp. < Indoor Temp. Stop condition?

YES YES

YES Go to A
Time delay mode

NO

Cooling operating Fan only operating

NO NO
Stop condition? Stop condition?

YES YES

Go to A Go to A

— 68 —
Exploded View and Replacement Parts List
1. LK-0320CC/0420CC/0520CC
• Exploded View

435311
554031

346810

349610

359012

249950
559010
567480
W6920
W0CZZ

269140
566000 546810
566001
261704
W0CZZ
549610

354212 554160
152302

552102

330870

websi
te
http://
e-mai
www.
l http://
LGEs
www. ervice
LGEs .com
ervice
.com/t
echsu
p.htm
l
website
e-mail http://ww
http://ww w.LGEse
w.LGEse rvice.com
rvice.com

/techsup.
html

738281 738290

— 69 —
Exploded View and Replacement Parts List
• Replacement Parts List(LK-0320CC/LK-0420CC/LK-0520CC) (Units:mm)

No. PARTS NAME PART No. LK-0320CC LK-0420CC LK-0520CC REMARK


2A01196A 1 - - CR38K6-PFV-502
554160 COMPRESSOR ASSEMBLY 5417A20009A - 1 - AVD5548EXN
5417A20008A - - 1 H25A62QCBCA
566000 SWITCH,PRESSURE 6600A20004D 1 1 1 OFF:2.0kgf,ON:3.5kgf
5403A20016D - - 2 2Rx14CxL1370
554031 CONDENSER ASSY,FIRST
5403A20016E 2 2 - 2Rx14CxL990
5421A20029A - 1 1 3Rx30CxL620
354212 EVAPORATOR ASSY,FIRST
5421A20042A 1 - - 2Rx30CxL620
3E92334G 6 - - ID1.4xL1200
552102 TUBE CAPILLARY,BEND 5424AP3074D 10 ID1.4xL1000
5424AP3074G 10 ID1.4xL1600
330870 DRAIN PAN ASSY 3087A30003A 1 1 1
152302 FILTER(MECH),A/C 5230A20003B 1 1 1
359012 FAN ASSY,BLOWER 2A00578P 1 1 1 D280xW280
346810 MOTOR ASSEMBLY,INDOOR 4681A20022 1A 1B 1A A:0.75Hp,B:0.5Hp
349610 MOUNT ASSEMBLY,MOTOR(INDOOR) 3G00788D 1 1 1
W6920 RELAY(FOR INDOOR MOTOR) 6920AP3194B 1 1 1 220VAC,25A
567480 P.T.C 3A01911B - 1 1
CAPACITOR,DRAWING(15µF,450VAC) 0CZZA20001B - 1 1 15µF/450VAC
CAPACITOR,DRAWING(6µF,400VAC) 2A00986D 1 - - 6µF,400VAC
CAPACITOR,DRAWING(60µF,450VAC) 0CZZA20001D - - 1 FOR COMP
W0CZZ
CAPACITOR,DRAWING(40µF,400VAC) 2A00986B 1 - - FOR COMP
CAPACITOR,DRAWING(45µF,400VAC) 2A00986A - 1 - FOR COMP
CAPACITOR,DRAWING(12µF,400VAC) 0CZZA20001C 1 1 1 FOR OUTDOOR MOTOR
269140 TIMER 3Q01017B 1 1 1
261704 TRANSFORMER,POWER 6171AQ2165C 1 1 1
566001 SWITCH,MAGNET 2A00771F 1 1 1 200V,40A,24V CONTROL
249950 CONTROL BOX ASSEMBLY,SINGLE 4995A20055 1B 1C 1A
549610 MOUNT ASSY MOTOR(OUTDOOR) 3A00434A 1 1 1
546810 MOTOR ASSEMBLY OUTDOOR 4681A20019A 1 1 1 1,080RPM/0.5Hp
559010 FAN,PROPELLER 1A00284A 1 1 1 OD 600
435311 GRILLE ASSY,DISCHARGE(OUTDOOR) 2A00144V 1 1 1
738290 MANUAL,OWNERS 3828A30037E 1 1 1
738281 MANUAL,SERVICE 3828A30014P 1 1 1

— 70 —
Exploded View and Replacement Parts List
2. LK-06B0CH/AH, LK-08B0CH/AH
• Exploded View 435311

346810

249950

261704
359012 268714

342800
W6920 559010
W0CZZ

546810
566001

152302 549610

354212 554160 554031


566000
552102

263230

330870

websi
te
http://
e-mai
www.
l http://
LGEs
www. ervice
LGEs .com
ervice
.com/t
echsu
p.htm
l
website
e-mail http://ww
http://ww w.LGEse
w.LGEse rvice.com
rvice.com

/techsup.
html

267110
738281 738290

— 71 —
Exploded View and Replacement Parts List

• Replacement Parts List(LK-06B0CH, LK-08B0CH/AH) (Units:mm)

No. PARTS NAME PART No. LK-06B0CH LK-06B0AH LK-08B0CH LK-08B0AH REMARK
5417A20007A - - 1 1 H25G094DBDE
554160 COMPRESSOR ASSY,FINAL
5417A20008C 1 1 - - H26A72QDBLA
5403A20016B - - 2 - 2Rx16CxL1420
5403A20016G 2 - - - 2Rx16CxL1350
554031 CONDENSER ASSY,BENT
5403A20016M - 2 - - 2Rx16CxL1350
5403A20016T - - - 2
359012 FAN ASSEMBLY,BLOWER 5835A20001A 1 1 1 1 D320 x W320
342800 BEARING 4A00131A 2 2 2 2
346810 MOTOR ASSY,INDOOR 4681A20018A 1 1 1 1 1.5Hp
330870 DRAIN PAN ASSY 3087A20002B 1 1 1 1
5421A20025A - - 1 1 3Rx27CxL1070
354212 EVAPORATOR ASSY,FIRST
5421A20025B 1 1 - - 3Rx27CxL963
3E92334G 10 10 - - ID1.4xL1200
552102 TUBE CAPILLARY,BEND
3H03750K - - 10 10 ID1.4xL700
263230 THERMISTOR ASSY 6323AQ2333T 1 1 1 1
5230A20003A 1 1 1 1
152302 FILTER(MECH),A/C
5230A20003C 1 1 1 1
566000 SWITCH,PRESSURE 6600A20004C 1 1 1 1 OFF:2.0kgf,ON:3.5kgf
268714 PWB(PCB) ASSY,MAIN 6871A20085G 1 1 1 1
566001 SWITCH,MAGNET 2A01031C 1 1 1 1 220V,40A,220V CONTROL
W6920 RELAY(FOR IDM) 6920AP3400A 1 1 1 1 220V,25A,220V CONTROL
261704 TRANSFORMER,POWER 6171AQ2138D 1 1 1 1
W0CZZ CAPACITOR,DRAWING(12µF,450VAC) 0CZZA20001C 1 1 1 1 FOR OUTDOOR MOTOR
549610 MOUNT ASSY 3A00434A 1 1 1 1
546810 MOTOR ASSY,OUTDOOR 4681A20019B 1 1 1 1 1,130RPM/0.5Hp
559010 FAN PROPELLER 1A00284A 1 1 1 1 OD 600
435311 GRILLE ASSY,DISCHARGE(OUTDOOR) 2A00144J 1 1 1 1
249950 CONTROL BOX ASSEMBLY,SINGLE 4995A20054 1A 1A 1B 1B
267110 REMOTE CONTROLLER ASSY 6711A20043A 1 1 1 1
738290 MANUAL,OWNERS 3828A20151A 1 1 1 1
738281 MANUAL,SERVICE 3828A30014P 1 1 1 1

— 72 —
Exploded View and Replacement Parts List
3. LK-09B0CH, LK-10B0CH/AH, LK-13B0CH
• Exploded View

346810 359012
435311

249950
342800

268714

559010

261704
354212
W6920
152302 W0CZZ
546810
W6920

549610 566001
566001

566000

552102
263230

554160 554031

554031
330870

websi
te
http://
e-mail
www.
http:// LGEs
www. ervice
LGEs .com
ervice
.com/t
echsup
.html

website
e-mail http://ww
http://ww w.LGEse
w.LGEse rvice.com
rvice.com

/techsup.
html

554031
267110
738281 738290 554031

— 73 —
Exploded View and Replacement Parts List
• Replacement Parts List(LK-09B0CH, LK-10B0CH/AH, LK-130BCH) (Units:mm)

No. PARTS NAME PART No. LK-09B0CH LK-10B0CH LK-10B0AH LK-13B0CH REMARK
5417A20008B - 2 - H25A62QDBLA
554160 COMPRESSOR ASSY 5417A20008C - - - 2 H26A72QDBLA
5417A20008D 2 - - - H25A54QDBLA
5403A20018B 1 1 - - 2Rx18CxL850
5403A20018F - - - 1 2Rx18CxL1100
5403A20018P - - 1 -
5403A20018D 1 1 - - 2Rx20CxL850
5403A20018H - - - 1 2Rx20CxL1100
554031 CONDENSOR ASSY 5403A20018R - - 1 -
5403A20017B 1 1 - - 2Rx18CxL850
5403A20017F - - - 1 2Rx18CxL1100
5403A20017P - - 1 -
5403A20017D 1 1 - - 2Rx20CxL850
5403A20017H - - - 1 2Rx20CxL1100
5403A20017R - - 1 -
566000 SWITCH,PRESSURE 6600A20004C 2 2 2 2 OFF:2.0kgf,ON:3.5kgf
359012 FAN ASSEMBLY,BLOWER 5835A20003 1A 1A 1A 1B A:D380xL280/B:D380xL380
346810 MOTRO ASSY,INDOOR 4681A20025A 1 1 1 1 3ø,3Hp
342800 BEARING 4A00131A 2 2 2 2
330870 DRAIN PAN ASSY 3087A20004 1H 1B 1B 1D
5421A20030A - 2 2 - 3Rx18CxL963
354212 EVAPORATOR ASSY,FIRST 5421A20030B - - - 2 3Rx18CxL1150
5421A20030C 2 - - - 2Rx18CxL963
5424AP3074D 18 - - - ID1.2xL1000
552102 TUBE,CAPILLARY BEND 3E92334G - 18 18 - ID1.4xL1200
3H03750H - - - 18 ID1.4xL1100
6323AQ2333T 1 1 1 1 BLACK
263230 THERMISTOR ASSY
6323AQ2333U 1 1 1 1 BLUE
152302 FILTER(MECH),A/C 5230A20003 2D 2D 2D 2E
249950 CONTROL BOX ASSEMBLY,SINGLE 4995A20016A 1 1 1 1
268714 PWB(PCB) ASSY,MAIN 6871A20085H 1 1 1 1
261704 TRANSFORMER,POWER 6171AQ2138D 1 1 1 1
W6920 RELAY(FOR INDOOR MOTOR) 6920AP3400A 1 1 1 1 220V,25A,220V CONTROL
566001 SWITCH,MAGNET 2A01031A 2 2 2 2 220V,30A,220V CONTROL
W0CZZ CAPACITOR,DRAWING(20µF,450VAC) 0CZZA20001E 1 1 1 1 FOR OUTDOOR MOTOR
W6920 RELAY(FOR OUTDOOR MOTOR) 6920AP3194A 1 1 1 1
549610 MOUNT ASSY MOTOR(OUTDOOR) 4961A30003A 1 1 1 1
546810 MOTOR ASSY,OUTDOOR 4681A20026A 1 1 1 1 1,130RPM/1.3Hp
559010 FAN ASSY,PRPPELLER 5901A20004A 1 1 1 1 OD660
435311 GRILLE ASSY,DISCHARGE(OUTDOOR) 2A00144G 1 1 1 1
267110 REMOTE CONTROLLER ASSY 6711A20043A 1 1 1 1
738290 MANUAL,OWNERS 3828A20151A 1 1 1 1
738281 MANUAL,SERVICE 3828A30014P 1 1 1 1

— 74 —
Exploded View and Replacement Parts List

4. LK-15B0CH/AH, LK-18B0CH
• Exploded View 435311
For LK-18B0CH For LK-15B0CH/AH
346810 346810

359012

342800

359012
249950
342800
559010

152302
261704
546810 W6920

268714
W0CZZ

549610 W6920
566000
566001

354212
552102
263230

554160

554031
330870

263230
websit
e http://
e-mail
www.
http:// LGEse
www.
rvice.c
LGEse
om
rvice.c
om/tec
hsup.h
tml
website
e-mail http://ww
http://ww w.LGEse

w.LGEse rvice.com
rvice.com

/techsup.
html

554031
267110
738281 738290

— 75 —
Exploded View and Replacement Parts List
• Replacement Parts List(LK-15B0CH/LK-18B0CH) (Units:mm)

No. PARTS NAME PART No. LK-15B0CH LK-15B0AH LK-18B0CH REMARK


554160 COMPRESSOR ASSY,FINAL 5417A20007A 2 2 - H25G094DBDE
5417A20007B - - 2 H25G104DBDE
5403A20023A 2 - - 2Rx22CxL925
CONDENSER ASSY,FIRST 5403A20078F - 2 - 2Rx22CxL925
5403A20023D - - 2 2Rx22CxL1080
554031
5403A20023C 2 - - 2Rx22CxL925
CONDENSER ASSY,BENT 5403A20079C - 2 - 2Rx22CxL925
5403A20023F - - 2 2Rx22CxL1080
566000 SWITCH,PRESSURE 6600A20004C 1 1 1 OFF:2.0kgf,ON:3.5kgf
359012 FAN ASSEMBLY,BLOWER 5835A20003B 1 1 1 D380xL380
4681A20025B 1 1 - 4Hp
346810 MOTOR ASSY,INDOOR
4681A20031C - - 1 5Hp
342800 BEARING 4A00131A 2 2 2
330870 DRAIN PAN ASSY 3087A20004F 1 1 1
5421A30035A 2 2 - 3Rx21CxL1140
354212 EVAPORATOR ASSY
5421A30035B - - 2 3Rx21CxL1400
3H01535X - - 20 ID 1.6 x L1400
552102 TUBE CAPILLARY,BEND
5425AR3147X 20 20 - ID 1.6 x L1200
6323AQ2333T 1 1 1 BLACK
263230 THERMISTOR ASSY 6323AQ2333U 1 1 1 BLUE
6323AQ3214H 1 1 1
152302 FILTER(MECH),A/C 5230A20003F 2 2 2
249950 CONTROL BOX ASSEMBLY,SINGLE 4995A10007 1C 1C 1B
268714 PWB(PCB) ASSY,MAIN 6871A20085J 1 1 1
261704 TRANSFORMER,POWER 6171AQ2138D 1 1 1
RELAY(FOR INDOOR MOTOR) 6920AP3400A 1 1 1 220V,25A,220V CONTROL
W6920
RELAY(FOR OUTDOOR MOTOR) 6920AP3194A 2 2 2
566001 SWITCH,MAGNET(FOR COMP) 2A01031C 2 2 2 220V,40A,220V CONTROL
W0CZZ CAPACITOR,DRAWING(20µF,450VAC) 0CZZA20001 2C 2C 2E FOR OUTDOOR MOTOR
3A00434A 2 2 -
549610 MOUNT ASSY MOTOR
4961A30003A - - 2
4681A20026A 1 1 1 1,130RPM/1.3Hp
546810 MOTOR ASSY,OUTDOOR
4681A20026B 1 1 1 1,130RPM/1.3Hp
1A00284A 2 2 - OD 600
559010 FAN ASST PROPELLER
5901A20004A - - 2 OD 660
435311 GRILLE ASSY,DISCHARGE(OUTDOOR) 2A00144 2J 2J 2G
267110 REMOTE CONTROLLER ASSY 6711A20043A 1 1 1
738290 MANUAL,OWNERS 3828A20151A 1 1 1
738281 MANUAL,SERVICE 3828A30014P 1 1 1

— 76 —
Exploded View and Replacement Parts List
5. LK-20BCH/AH, LK-25B0CH/AH
• Exploded View 435311

346810

359012

342800

249950

559010

261704
546810 W6920

268714
W0CZZ

W6920
566000 549610

566001

552102 354212
263230

554160

554031
330870

263230
websi
te
http://
e-mai
www.
l http://
LGEs
www. ervice
LGEs .com
ervice
.com/t
echsu
p.htm
l
website
e-mail http://ww
http://ww w.LGEse
w.LGEse rvice.com
rvice.com

/techsup.
html

554031
267110
738281 738290

— 77 —
Exploded View and Replacement Parts List

• Replacement Parts List(LK-20B0CH/LK-25B0CH) (Units:mm)

No. PARTS NAME PART No. LK-20B0CH LK-20B0AH LK-25B0CH LK-25B0AH REMARK
330870 DRAIN PAN ASSY 3087A20006 1D 1D 1B 1B
5417A20007C 2 2 - - H25G124DBDE
554160 COMPRESSOR ASSY,FINAL
5417A20007D - - 2 2 H25G144DBDE
5403A20023G 3 - - - 2Rx20CxL1000
5403A20078G - 3 - - 2Rx20CxL1000
CONDENSER ASSY,FINAL
5403A20023K - - 3 - 2Rx20CxL1100
5403A20078H - - - 3 2Rx20CxL1100
554031
5403A20023J 3 - - - 2Rx20CxL1100
5403A20079D - 3 - - 2Rx20CxL1100
CONDENSER ASSY,BENT
5403A20023M - - 3 - 2Rx20CxL1100
5403A20079E - - - 3 2Rx20CxL1100
5421A20035C 2 2 - - 2Rx30CxL1420
354212 EVAPORATOR ASSY
5421A20035D - - 2 2 3Rx30CxL1420
6323AQ2333T 1 1 1 1 BLACK
263230 THERMISTOR ASSY 6323AQ2333U 1 1 1 1 BLUE
6323AQ3214H 1 1 1 1
3H01535R 20 20 - - ID1.6xL1000
552102 TUBE CAPILLARY,BEND
5210A30040J - - 30 30 ID1.6xL1600
152302 FILTER(MECH),A/C 5230A20003H 4 4 4 4
566000 SWITCH,PRESSURE 6600A20004C 1 1 1 1 OFF:2.0kgf,ON:3.5kgf
342800 BEARING 4A00131B 2 2 2 2
359012 FAN ASSEMBLY,BLOWER 5835A20003D 1 1 1 1 D450xL450
4681A20031B 1 1 - - 5Hp
346810 MOTOR ASSY,INDOOR
4681A20031A - - 1 1 7.5Hp
4961A30003A 2 2 - -
549610 MOUNT ASSY MOTOR(OUTDOOR)
4961A20007A - - 2 2
4681A20032A - - 1 1 3ø,2Hp
4681A20032B - - 1 1 3ø,2Hp
546810 MOTOR ASSY,OUTDOOR
4681A20026C 1 1 1ø,1.3Hp
4681A20026B 1 1 1ø,1.3Hp
5901A20004A 2 2 - - OD 660
559010 FAN ASST PROPELLER
5901A20004D - - 2 2 OD 700
435311 GRILLE ASSY,DISCHARGE(OUTDOOR) 2A00144 2G 2G 2L 2L
249950 CONTROL BOX ASSEMBLY,SINGLE 4995A10008 1B 1B 1A 1A
W6920 RELAY 6920AP3400A 3 3 3 3 220V,25A,220V CONTROL
268714 PWB(PCB) ASSY,MAIN 6871A20085J 1 1 1 1
261704 TRANSFORMER,POWER 6171AQ2138E 1 1 1 1
566001 SWITCH,MAGNET 2A01031E 2 2 2 2 220V,60A,220V CONTROL
W0CZZ CAPACITOR,DRAWING(20µF,450VAC) 0CZZA20001E 2 2 - - FOR OUTDOOR MOTOR
267110 REMOTE CONTROLLER ASSY 6711A20043A 1 1 1 1
738290 MANUAL,OWNERS 3828A20151A 1 1 1 1
738281 MANUAL,SERVICE 3828A30014P 1 1 1 1

— 78 —
Exploded View and Replacement Parts List
6. LK-05B0CC
• Exploded View

359012
435311
349610

753010

346810
354212

559010

330870
546810
552102
549610

W6920

554031
249950
W0CZZ
219140

261704
566001

554160

566000

websit
e http://w
e-mail
http://w ww.LG
Eservi
ww.LG
ce.com
Eservi
ce.com
/techsu
p.html

website
e-mail http://ww
http://ww w.LGEse
w.LGEse rvice.com
rvice.com

/techsup.h

tml

738281 738290
— 79 —
Exploded View and Replacement Parts List

• Replacement Parts List(LK-05B0CC) (Units:mm)

NO. PART NAME PART NO. LK-05B0CC REMARKS


330870 DRAIN PAN ASSY 3087A30002F 1
346810 MOTOR ASSEMBLY,INDOOR 4681A20022G 1 0.75Hp
349610 MOUNT ASSEMBLY,MOTOR(INDOOR) 3G00788W 3
359012 FAN ASSY,BLOWER 2A00578M 1 D280 x W280
354212 EVAPORATOR ASSY 5421A10002C 1 3Rx28Cx18FPIxL550
552102 TUBE CAPILLARY,BEND 5424AP3074F 7 ID1.4xOD2.6xL700
554160 COMPRESSOR ASSEMBLY 5417A20008B 1 H25A62QDBLA
554031 CONDENSER ASSY 5403A10006F 2 2Rx14Cx18FPIxL1380
566000 SWITCH,PRESSURE 6600A20004D 1 OFF:2.0kgf,ON:3.5kgf
249950 CONTROL BOX ASSEMBLY,SINGLE 4995A10013D 1
269140 TIMER 3Q01017B 1
261704 TRANSFORMER,POWER 6171AQ2138F 1
566001 SWITCH,MAGNET 2A01031F 1 200V,30A,24V CONTROL
W6920 RELAY 6920AP3194B 1 220VAC,25A
W0CZZ CAPACITOR,DRAWING(15µF,450VAC) 0CZZA20001B 1 FOR INDOOR MOTOR
CAPACITOR,DRAWING(6µF,370VAC) 2H00841J 2 FOR OUTDOOR MOTOR
549610 MOUNT ASSY MOTOR(OUTDOOR) 3A00434B 2
546810 MOTOR ASSEMBLY OUTDOOR 4681A20013G 2 1,000RPM/0.15Hp
559010 FAN ASSY,PROPELLER 1A00195B 2 OD 460
435311 GRILLE ASSY,DISCHARGE(OUTDOOR) 3530A20007B 2
753010 HEATER ELECTRIC 5300A10003G 1 5Kw
738290 MANUAL,OWNERS 3828A30037Q 1
738281 MANUAL,SERVICE 3828A30014P 1

— 80 —
Specification of Components
LK-0320CC/AC LK-0420CC/AC LK-0520CC/AC LK-05B0CC/AC LK-06B0CH/AH LK-08B0CH/AH LK-09B0CH/AH
COMP P/NO. 2A01196A 5417A20009A 5417A20008A 5417A20008B 5417A20008C 5417A20007A 5417A20008D
Model name CR38K6-PFV-502 AVD5548EXN H25A62QCBCA H25A62QDBLA H26A72QDBLA H25G094DBDE H25A54QDBLA
*RLA 19 (A) 19.2 (A) 24.6 (A) 16.0 (A) 18.3 (A) 25.2 (A) 14 (A)
*LRA 105 (A) 110 (A) 147 (A) 150 (A) 158 (A) 190 (A) 137 (A)
QUANTITY 1EA 1EA 1EA 1EA 1EA 1EA 2EA
INDOOR MOTOR P/NO. 4681A20022A 4681A20022B 4681A20022A 4681A20022G 4681A20018A 4681A20018A 4681A20025A
OUTPUT 0.75 Hp(SF:1.0) 0.5 Hp(SF:1.0) 0.75 Hp(SF:1.0) 0.75 Hp(SF:1.0) 1.5 Hp(SF:1.0) 1.5 Hp(SF:1.0) 3 Hp(SF:1.0)
Shaft Dia. 15 mm 15 mm 15 mm 15 mm 22 mm 22 mm 22 mm
RPM 1080(Hi) 995(Hi) 1080(Hi) 1080(Hi) 1700 1700 1730
OUTDOOR MOTOR P/NO. 4681A20019A 4681A20019A 4681A20019A 4681A20013G 4681A20019B 4681A20019B 4681A20026A
OUTPUT 0.5 Hp 0.5 Hp 0.5 Hp 0.15 Hp 0.5 Hp 0.5 Hp 1.3 Hp
Shaft Dia. 15 mm 15 mm 15 mm 12 mm 15 mm 15 mm 19 mm
RPM 1080 1080 1080 1000 1130 1130 1130
quantity 1ea 1ea 1ea 2ea 1ea 1ea 1ea
OUTDOOR FAN P/NO. 1A00284A 1A00284A 1A00284A 1A00195B 1A00284A 1A00284A 5901A20004A
Diameter O.D. 600mm O.D. 600mm O.D. 600mm O.D. 460 mm O.D. 600mm O.D. 600mm O.D. 660mm
INDOOR BLOWER P/NO. 2A00578P 2A00578P 2A00578P 2A00578M 5835A20001A 5835A20001A 5835A20003A
Diameter*Width 280 (mm)*280(mm) 280 (mm)*280(mm) 280 (mm)*280(mm) 280 (mm)*280(mm) 320 (mm)*320(mm) 320 (mm)*320(mm) 380(mm)*280(mm)
MOTOR PULLY P/NO. - - - 6600A20004D 3A00217R 3A00217R 3A00217R
Type - - - VARIBLE VARIBLE VARIBLE
BLOWER PULLY P/NO. - - - 4561A30001K 4561A30001H 4561A30002D
Type - - - "A" Type "A" Type "B" Type
Outside Dia.(mm) - - - 180 159 230
V-VELT P/NO. - - - 4400A30001S 4400A30001Q 4400A30002B
Type - - - "A" Type "A" Type "REC-B" Type
Length - - - 51(in") 49 58
LOW PRESSURE SWITCH P/NO. 6600A20004D 6600A20004D 6600A20004D 6600A20004C 6600A20004C 6600A20004C
spec. OFF:2.0kgf/ON:3.5kgf OFF:2.0kgf/ON:3.5kgf OFF:2.0kgf/ON:3.5kgf OFF:2.0kgf/ON:3.5kgf OFF:2.0kgf/ON:3.5kgf OFF:2.0kgf/ON:3.5kgf OFF:2.0kgf/ON:3.5kgf
Rated volt. AC 24 AC 24 AC 24 AC 24 DC 24 DC 24 DC 24
Maker saginomiya saginomiya saginomiya saginomiya saginomiya saginomiya saginomiya
CAPACITOR for COMP. P/NO. 2A00986B 2A00986A 0CZZA20001D - - - -
SPEC. 40µF/400VAC 45µF/400VAC 60µF/450VAC - - - -
CAPACITOR for IDM. P/NO. 2A00986D 0CZZA20001B 0CZZA20001B 0CZZA20001B - - -
SPEC. 6µF/400VAC 15µF/450VAC 15µF/450VAC 15µF/450VAC - - -
CAPACITOR for ODM. P/NO. 0CZZA20001C 0CZZA20001C 0CZZA20001C 2H00841J 0CZZA20001C 0CZZA20001C 0CZZA20001E
SPEC. 12µF/450VAC 12µF/450VAC 12µF/450VAC 6µF/370VAC 12µF/450VAC 12µF/450VAC 20µF/450VAC
FILTER P/NO. 5230A20003B 5230A20003B 5230A20003B 5230A20003A & (C) 5230A20003A & (C) 5230A20003D
Size 716mm*696mm 716mm*696mm 716mm*696mm 668mm*742(500)mm 668mm*742(500)mm 938mm*408mm
Quantity 1 1 1 1+1 1+1 2
CAPILLARY TUBE P/NO. 3E92334G 5424AP3074D 5424AP3074G 5424AP3074F 3E92334G 3H03750K 5424AP3074D
Spec. I.D 1.4*1200mm I.D 1.2*1000mm I.D 1.4*1600mm I.D 1.4 * 700 mm I.D 1.4*1200mm I.D 1.4*700mm I.D 1.2*1000mm
Quantity 6 10 10 7 10 10 18
TRANSFORMER P/NO. 6171AQ2165C 6171AQ2165C 6171AQ2165C 6171AQ2165C 6171AQ2138D 6171AQ2138D 6171AQ2138D
Spec. AC220V,1.5A AC220V,1.5A AC220V,1.5A AC220V,1.5A AC220V,450mA AC220V,450mA AC220V,450mA
CONTACTOR for COMP. P/NO. 2A00771F 2A00771F 2A00771F 2A01031F 2A01031C 2A01031C 2A01031A
Spec. 40A,24V CONTROL 40A,24V CONTROL 40A,24V CONTROL 30A,24V CONTROL 40A,220V CONTROL 40A,220V CONTROL 30A,220V CONTROL
RELAY for IDM. P/NO. 6920AP3194B 6920AP3194B 6920AP3194B 6920AP3194B 6920AP3400A 6920AP3400A 6920AP3400A
Spec. AC 24V,25A AC 24V,25A AC 24V,25A AC 24V,25A 220V,25A 220V,25A 220V,25A
RELAY for ODM. P/NO. - - - - - - 6920AP3194A
Spec. - - - - - - 220V, 25A, 1POLE
*IDM : INDOOR MOTOR *RLA : RATED LOAD AMPERE
*ODM : OUTDOOR MOTOR *LRA : LOCK LOAD AMPERE

— 81 —
Specification of Components
LK-10B0CH/AH LK-13B0CH/AH LK-15B0CH/AH LK-18B0CH/AH LK-20B0CH/AH LK-25B0CH/AH
COMP P/NO. 5417A20008B 5417A20008C 5417A20007A 5417A20007B 5417A20007C 5417A20007D
Model name H25A62QDBLA H25A72QDBLA H25G094DBDE H25G104DBDE H25G124DBDE H25G144DBDE
RLA 16 (A) 18.3 (A) 25.2 (A) 29 (A) 33.5 (A) 43.1 (A)
LRA 150 (A) 158 (A) 190 (A) 228 (A) 264 (A) 252 (A)
QUANTITY 2EA 2EA 2EA 2EA 2EA 2EA
INDOOR MOTOR P/NO. 4681A20025A 4681A20025A 4681A20025B 4681A20031C 4681A20031B 4681A20031A
OUTPUT 3 Hp(SF:1.0) 3 Hp(SF:1.0) 4 Hp(SF:1.0) 5 Hp(SF:1.15) 5 Hp(SF:1.15) 7.5 Hp(SF:1.15)
Shaft Dia. 22 mm 22 mm 22 mm 28 mm 28 mm 28 mm
RPM 1,730 1,730 1,730 1,750 3,500 3,510
OUTDOOR MOTOR P/NO. 4681A20026A 4681A20026A 4681A20026A & B 4681A20026A & B 4681A20026B & C 4681A20032A & B
OUTPUT 1.3 Hp 1.3 Hp 1.3 Hp 1.3 Hp 1.3 Hp 2 Hp
Shaft Dia. 19 mm 19 mm 19 mm 19 mm 19 mm 19 mm
RPM 1130 1130 1130 1130 1130 1130
QUANTITY 1EA 1EA 2EA 2EA 2EA 2EA
OUTDOOR FAN P/NO. 5901A20004A 5901A20004A 5901A20004A 5901A20004A 5901A20004A 5901A20004D
Diameter O.D. 660mm O.D. 660mm O.D. 660mm O.D. 660mm O.D. 660mm O.D. 700mm
INDOOR BLOWER P/NO. 5835A20003A 5835A20003B 5835A20003B 5835A20003B 5835A20003D 5835A20003D
Diameter*Width 380(mm)*280(mm) 380(mm)*380(mm) 380(mm)*380(mm) 380(mm)*380(mm) 450(mm)*450(mm) 450(mm)*450(mm)
MOTOR PULLY P/NO. 3A00217R 3A00217R 3A00217R 3A00217S 3A00217S 3A00217S
Type VARIBLE VARIBLE VARIBLE VARIBLE VARIBLE VARIBLE
BLOWER PULLY P/NO. 4561A30002C 4561A30002C 4561A30002B 4561A30002B 4561A30003B 4561A30003A
Type "B" Type "B" Type "B" Type "B" Type "B" Type "B" Type
Outside Dia.(mm) 200 200 190 190 559 457
V-VELT P/NO. 4400A30002A 4400A30002A 4400A30002E 4400A30002F 4400A30002K 4400A30002J
Type "REC-B" Type "REC-B" Type "REC-B" Type "REC-B" Type "REC-B" Type "REC-B" Type
Length 57 57 56 55 88 81
LOW PRESSURE SWITCH P/NO. 66000A20004C 66000A20004C 66000A20004C 66000A20004C 66000A20004C 66000A20004C
SPEC. OFF:2.0kgf/ON:3.5kgf OFF:2.0kgf/ON:3.5kgf OFF:2.0kgf/ON:3.5kgf OFF:2.0kgf/ON:3.5kgf OFF:2.0kgf/ON:3.5kgf OFF:2.0kgf/ON:3.5kgf
RATED VOLT. DC 24 DC 24 DC 24 DC 24 DC 24 DC 24
Maker SAGINOMIYA SAGINOMIYA SAGINOMIYA SAGINOMIYA SAGINOMIYA SAGINOMIYA
CAPACITOR for COMP. P/NO. - - - - - -
SPEC. - - - - - -
CAPACITOR for IDM. P/NO. - - - - - -
SPEC. - - - - - -
CAPACITOR for ODM. P/NO. 0CZZA20001E 0CZZA20001E 0CZZA20001E 0CZZA20001E 0CZZA20001E -
SPEC. 20µF/450VAC 20µF/450VAC 20µF/450VAC 20µF/450VAC 20µF/450VAC -
FILTER P/NO. 5230A20003D 5230A20003E 5230A20003F 5230A20003F 5230A20003H 5230A20003H
Size 938mm*408mm 1110mm*408mm 1374mm*485mm 1374mm*485mm 750mm*717mm 750mm*717mm
Quantity 2 2 2 2 4 4
CAPILLARY TUBE P/NO. 3E92334G 3H03750H 5210A30040H 3H01535X 3H01535R 5210A30040J
Spec. I.D 1.4*1200mm I.D 1.4*1100mm I.D 1.6*1200mm I.D 1.6*1400mm I.D 1.6*1000mm I.D 1.6*1600mm
Quantity 18 18 20 20 20 30
TRANSFORMER P/NO. 6171AQ2138D 6171AQ2138D 6171AQ2138D 6171AQ2138D 6171AQ2138E 6171AQ2138E
Spec. AC220V,450mA AC220V,450mA AC220V,450mA AC220V,450mA AC220V,450mA AC220V,450mA
CONTACTOR for COMP. P/NO. 2A01031A 2A01031A 2A01031C 2A01031C 2A01031E 2A01031E
Spec. 30A,220V CONTROL 30A,220V CONTROL 40A,220V CONTROL 40A,220V CONTROL 60A,220V CONTROL 60A,220V CONTROL
RELAY for IDM. P/NO. 6920AP3400A 6920AP3400A 6920AP3400A 6920AP3400A 6920AP3400A 6920AP3400A
Spec. 220V,25A 220V,25A 220V,25A 220V,25A 220V,25A 220V,25A
RELAY for ODM. P/NO. 6920AP3194A 6920AP3194A 6920AP3194A 6920AP3194A 6920AP3194A 6920AP3400A
Spec. 220V, 25A,1POLE 220V, 25A,1POLE 220V, 25A,1POLE 220V, 25A,1POLE 220V, 25A,1POLE 220V, 25A, 2POLE
*IDM : INDOOR MOTOR *RLA : RATED LOAD AMPERE
*ODM : OUTDOOR MOTOR *LRA : LOCK LOAD AMPERE

— 82 —