Sie sind auf Seite 1von 2

Electro-Pneumatic Positioners YT-1000 / YT-1050

Design features
• Simple zero and span adjustment. Internal hand dials • Internal feedback option. Available on weatherproof
and locking screws for adjustments. model only.
• Reverse & Direct Acting Settings. Full and 1/2 split • Auto / Manual switch. Internal adjustment with lock
range setting by simple adjustment. screw safety.
• High vibration resistant. No resonance between
5 to 200 Hz.

YT-1000 Aluminum Enclosure


33.
45.5 45.5
(1.32
2-M8*1.25P
2-M8*1.25P
Tap Tap (1.79) (1.79)

(1.06)
(1.06)
27
27

(1.04) (1.3)
(1.04) (1.3)
26.5 33
26.5 33
10~20 10~20
30 30
40 40

(0.9)
(0.9)
23
23

(1.71)
(1.71)
43.5
43.5
(6.57)
(6.57)
167
167

38.8 38.8
(1.53) (1.53)

(3.33)
(3.33)
84.5
84.5
4-M8*1.25P
4-M8*1.25P Tap Tap
224.3 224.3 116.7 116.7
(8.83) (8.83) (4.59) (4.59)

8
(0.31)

YT-1000L
YT-1000L
33.5 91.8
YT-1050 STS316
(1.32) Enclosure
(6.31) 45
33.5
(1.32)

(1.28)
32.5
2-M8*1.25P Tap (1.77)
(1.06)
27

(1.3)
33

(1.04) (1.34)
34
(1.04)
26.5

(1.06)

26.5
27
(0.9)
23

(1.71)

168.85
43.5

(6.65)

(1.71)
43.5
(0.91)
23
(3.33)
84.5

4-M8*1.25P Tap 4-M8*1.25P Tap

224.4
(8.83)

R YT-1050

Dimensions: mm (Inches ")

12 Valve Positioners and Accessories


Electro-Pneumatic Positioners YT-1000 / YT-1050

Item Type YT-1000 YT-1050


Product Code
YT-1000 - R - S - N - 1 - 1 - 4 - S - 0 - (0)
Input Signal 4 to 20 mA DC
Impedance 250 ± 15 Ω
Supply Pressure 0.14 to 0.7 MPa (1.4 to 7 bar)
Linear Type 10 to 150 mm Model
Stroke YT-1000 = Aluminum
Rotary Type 0 to 90° YT-1050 = STS316
Air Connection PT(NPT,G)1/4 NPT 1/4
Motion Type
Gauge Connection PT(NPT)1/8 NPT 1/8 L = Linear
Conduit G(PF,NPT)1/2, M20 G 1/2 (PF 1/2) R = Rotary
ATEX Acting Type
(II 2 G) Ex dmb IIB T5 S = Single
IECEx D = Double
(II2 G) EEx mb IIB T5
Explosion Protection
KCs KCs N = Non-Explosion
Ex dmb IIB T5/T4 / Ex dmb IIB T5 M = ATEX, IECEx, TS, KCs
Ex d IIC T5 IP66 / A = CSA, FM (YT-1000 only)
Ex ia IIB T6 Gb C = Ex d KCs, NEPSI (YT-1000 only)
TS - I = Exia KCs (YT-1000 only)
X = TIIS (YT-1000 only)
Ex db mb IIB T5 Gb X
Lever Type
CSA
Explosion Protection Type Linear Rotary
(Class I, Zone 1) Ex dm
1 = 10 to 40 mm 1 = M6 X 34L
IIB T5 2 = 30 to 70 mm 2 = M6 X 63L
FM 3 = 60 to 100 mm 3 = M8 X 34L
XP-S/I/1/CD/T5 4 = 100 to 150 mm 4 = M8 X 63L
5 = NAMUR
Ta=60°C;
DIP/II,III/1/EFG/T5 Orifice Type
Ta=60°C; Type 4X 1 = Ф1
2 = Ф2
NEPSI 3 = None
Ex dmb IIC T6 Gb
Conduit & Air Connection
TIIS YT-1000 YT-1050
Ex dmb IIB T5 1 = G1/2 - PT1/4 2= G1/2 - NPT1/4
Ingress Protection IP66 2 = G1/2 - NPT1/4
3 = G1/2 - G1/4
Operating Operating -20 to 70 °C (-4 to 158 °F)
4 = M20 - NPT1/4
Temp. Explosion -20 to 60 °C (-4 to 140 °F) 5 = NPT1/2 - NPT1/4
Linearity Single ± 1% F.S.
Operating Temp.
Double ± 2% F.S. S = -20 to 60 °C
Hysteresis ±1% F.S. H = -20 to 120 °C
L = -40 to 60 °C
Sensitivity Single ± 0.2% F.S.
Double ± 0.5% F.S. Option 1
YT-1000L YT-1000R
Repeatability ± 0.5% F.S. 0 = None 0 = None (St'd)
Air Consumption 2.5 LPM (sup = 0.14 MPa) 2 = 4 to 20 mA feedback (Smart Type) 1 = Dome Cover
Flow Capacity 80 LPM (sup = 0.14 MPa) 3 = 4 to 20 mA feedback with LCD (Smart Type)
Material Aluminium Diecasting Stainless steel 316 Option 2 (YT-1000R only)
Weight YT-1000L: 2.7 kg (6.1 lb) 0 = None
YT-1000R: 2.8 kg (6.2 lb) 1 = 4 to 20 mA feedback (Internal - only for non-explosion area protection)
2 = 4 to 20 mA feedback (External)
YT-1050: 5.71 kg (12.6 lb)
3 = Limit Switch (Internal - only for non-explosion area protection)
4 = Limit Switch (External)
5 = 4 to 20 mA feedback + Limit Switch
(Internal - only for non-explosion area protection)
6 = SPTM + Limit Switch (External)

Keeping the World Flowing 13