C4962 – STS TRANSFORMERS

Multi-Tap Transformer

Crestchic Ltd.
2nd Avenue
Centrum 100
Burton upon Trent
Staffordshire
United Kingdom
DE14 2WF

Tel. +44 (0) 1283 531645


Fax. +44 (0) 1283 510103
Reproduction of this document, in part or whole, by any means, electrical, mechanical, optical, chemical,
manual or otherwise is prohibited without written permission from Crestchic Limited.

The information contained herein is believed to be accurate as of the date of publication, however,
Crestchic Limited will not be liable for any damages, including indirect or consequential, arising from use
of the hardware or software described within or reliance upon the accuracy of this documentation. The
information contained herein is subject to change without notice.

Revision: A
Date: 12th June 2014
8. GENERAL ARRANGEMENT

Transformer
9. WIRING DIAGRAMS

Transformer
10. 24V DC BATTERY CHARGER

Transformer
1. GENERAL TRANSFORMER INFORMATION

Customer Crestchic Ltd


United State of America

Equipment 8.0MVA Transformer unit (20ft)

MV Supply 8660-34641V, 50Hz, 3-Phase

LV Supply 400V, 50Hz, 3-Phase

Fan Auxiliary Supply 380-440V, 50Hz, 3-Phase, 3-Wire


440-480V, 60Hz, 3-Phase, 3-Wire

Control Auxiliary Supply 120V, 50/60Hz, 1-Phase, 2-Wire

Dimensions 6058 x 2438 x 2591mm (l, w, h) / 238.5” x 96.0” x 102.0”

Gross Weight 25400kg / 55880 lbs

Paint Specification White – BS4800 00E55

Transformer Serial No. C4818 Page 4


2. COMPONENT DESCRIPTION
2.1 MV Cable Termination Chamber
Cables enter the chamber through a gland plate to reduce the ingress of water and
dust.

Copper bus bars, fitted with M16 bolts, are provided for connecting the MV cables.
There is an earth bar which links all components throughout the enclosure.

2.2 MV Switchgear Cubicle


This is a 2-section module, manufactured by ABB to the following specification:-

H.1 C
SafePlus 36 C is a cable switch module with a two position load break switch and
earthing switch, bus bars, interlocking and earth bar.

1 SafePlus Type C: Cable switch 36kV, 630A, 20kA


1 Snap action mech. For manual operation
1 Cable bushings 400 Series bolted, 630A, standard
1 Cable cover standard
1 Capacitive voltage indication CAPDIS S1+ VDS – LR System
1 Aux. switch for load break switch position 2NO + 2NC

H.2 V / H.3V

SafePlus 36 V is a vacuum circuit breaker module with vacuum circuit breaker, two
position isolator/earthing switch, bus bars, interlocking, and earth bar and stored spring
energy mechanism (A-mech.).

1 SafePlus Type V: Vacuum circuit breaker 36kV, 630A, 20kA


1 Control voltage, motor operation 24 V DC
1 Optical indication of latch function
1 Protection relay type REJ603
3 Ring core current transformers Type CT4 57.6 / 0.075A (64A-224A)
1 Cable bushings 400 Series plug-in, 630A standard
1 Cable cover standard
1 Capacitive voltage indication CAPDIS S1+ VDS – LR System
1 Aux. switch for vacuum circuit breaker position 2NO + 2NC

Transformer Serial No. C4818 Page 6


Additional equipment delivered separately or mounted in respective panel.

1 Cable support bars, standard for 1-way unit


1 Manometer
1 Voltage tester Type VIM-3
1 Operating handle

2.3 Main Transformer


The transformer is housed at one end of the enclosure and accessed by removable
end. The base of the enclosure is continuously welded to form a ‘Bund’ in the event of
cooling oil leakage.

Additional cooling is provided by fans mounted in the side of the enclosure. Three tap
change switches are fitted to the top of the transformer, as shown in Drawing DP1062
or 14 CTMU 36 H 54292.

Protection devices for the transformer and access doors are wired to the control panel.

SPECIFICATION:-

THREE-PHASE OIL-IMMERSED DISTRIBUTION TRANSFORMER

Type CTMU 36 HM 3400


Rated power, kVA 4000 50Hz
Voltage ratio, V YN(YN)yn0 33000 (34641..15000) 50Hz
D(D)ynll 11000 (22000..8660) 50Hz
Frequency, cps 50
Connection YN(YN)yn0
D(D)yn11
No Load Loss (50Hz) 3800W
Load Loss (50Hz) 28000W (33.0kV)
Impedance Volt (50Hz) 7.0% (33.0kV)
Oil Weight 1720kg
Total Weight 8000kg

Transformer Serial No. C4818 Page 7


The transformer protection circuit consists of:-

Transformer Access Door Open – L1

Gas/Oil Trip – L2

Over Pressure Trip – L3

Over Temperature Trip – L4

Activation of any of these signals will trip the MV.

Indication Only:-

Transformer Temperature Rising Alarm – L5

MV Breaker Tripped Indication – L6

LV Isolator 1 Open – L7

LV Isolator 2 Open – L8

LV Isolator 3 Open – L9

SAFETY

The access door into the transformer section is fitted with a door switch ‘DSW1’. If the
supplies are live this will activate the shunt trip and open the breaker MCB1 (2), should
the door be opened.

There is fitted an Emergency Stop button on the transformer control panel. Activation of
this button will activate the shunt trip and open the breakers MCB1 and MCB2, and stop
the rotation of the cooling fans.

Warning: - The Emergency Stop does not isolate the Test Supply or the
Auxiliary Supply; this must be done at source.

Note: - The 120V 1-Phase auxiliary supply for the internal lighting and heating, if
connected is not affected by the Emergency Stop.

Transformer Serial No. C4818 Page 10


2.8 Control Room
Lighting, anti-condensation heater and power sockets are located in the Control Room
and are powered from the auxiliary supply.

The Control Room also contains:-

MV Switchgear Cubicle
24V DC Battery Charger Unit
Control Interlock Panel
Access to MV Cable Connections
Rubber Mat.

Transformer Serial No. C4818 Page 11