Sie sind auf Seite 1von 16

SAUDI ARAMCO ID/PIEU-24-July-2018 - REV.2018.06.00 (Standards Cutoff - June 30,2018) Rev.2018.06.

00 30-Jun-18
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
Fire Alarm System - Control Panel - Pre-Commissioning Test SATR-B-6101 24-Jul-18 INST
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
TEST PROCEDURE ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.

A General Conformance of Tests


Documented test procedures shall be submitted to Saudi Aramco for 34-SAMSS-820
A1
approval not less than thirty (30) days before commencement of test. Sec. 8

Review Factory Acceptance Test (FAT) documents detailing the set-up 34-SAMSS-820
A2
and procedures for the Functional Test to be provided. Sec. 8(a)

Verify that manufactured items have been inspected by the Saudi Aramco
34-SAMSS-820
A3 Inspection representative, per the Saudi Aramco Inspection Requirement
Sec. 8
175-343100 attached to the Purchase Order.

A certificate of compliance to the RFI requirements of IEC 61000-4-3,


Level 3. The certificate(s) shall be for either the entire cabinet or for all the
electronic equipment installed within the cabinet.
EMI/RFI Interference (Radiated Susceptibility):
The cabinet electronic equipment shall perform within the normal limits
without loss of function or degradation of performance when subjected to
34-SAMSS-820
A4 radiated electromagnetic fields in accordance with IEC 61000-4-3, Level
Sec. 8(b)
3, (at a 10 V/m power level), with cabinet doors open.
If certificates are not available, the equipment in the cabinet shall function
within the normal limit when tested with a 5 watt radio transceivers
operating at 5 Watts within the frequency ranges, 50-174 MHz, 406-
470MHz, and 800-870 MHz and held at a distance of 1.0 meter from the
cabinet, with cabinet doors open.

Service Personnel Qualifications and Experience: Service personnel


SAES-B-014 Sec.
A5 shall be qualified and experienced in the inspection, testing, and
3.2
maintenance of fire alarm systems. (NFPA 72-2010 Sec. 10.4.3.1)

Inspection: Visual inspections shall be performed in accordance with the


SAES-B-014 Sec.
A6 schedules in Table 14.3.1 or more often if required by the authority having
3.2
jurisdiction. (NFPA 72 Sec. 14.3.1)

Test Methods: Systems and associated equipment shall be tested


SAES-B-014 Sec.
A7 according to Table 14.4.2.2 and figure 10.6.2.3. (Attachment 2-5).
3.2
[NFPA 72 Sec. 14.4.2.2]

The Vendor is responsible for providing all test equipment required to


Schedule G
perform the tests described in this section. In addition, he shall perform
Sec. 2.5
A8 full functional tests and confirm that any problems have been resolved
SAES-B-014
prior to inviting Buyer's representative for the Buyer-witnessed functional
Sec. 7.9
test.

Specific tools and equipment shall be identified to make and perform tests Schedule Q
A9
in the field with instructions for their use, calibration and storage. Att. IV Sec. 7.1

Saudi Aramco: Company General Use


The CONTRACTOR shall identify, maintain, control, adjust and calibrate
Schedule Q
A10 all tools, gauges, instruments and other measuring and testing devices
Att. IV Sec. 7.1
used for controlling quality.

Calibration shall be performed at established periods as specified in


the most stringent of SAUDI ARAMCO standards, other applicable Schedule Q
A11
standards or manufacturer recommendations; if no standards apply, Att. IV Sec. 7.1
the calibration cycle shall not exceed six months.

CONTRACTOR shall provide backup equipment when the primary Schedule Q


A12
equipment is being calibrated or tested. Att. IV Sec. 7.1

CONTRACTOR personnel performing test and calibrations shall be Schedule Q


A13
trained per applicable international or manufacturer requirements. Att. IV Sec. 7.3

B Test Procedure / Methods for Control Equipment


Functions: At a minimum, control equipment shall be tested to verify
correct receipt of alarm, supervisory and trouble signals (inputs),
operation of evacuation signals and auxiliary functions (outputs), circuit
SAES-B-014
B1 supervision including detection of open circuits and ground faults, and
Sec. 3.2
power supply supervision for detection of loss of ac power and
disconnection of secondary batteries.
[NFPA 72-2013 Table14.4.3.2 Sec.2.(a)]

Fuses: The rating and supervision shall be verified. SAES-B-014


B2
[NFPA 72-2013 Table14.4.3.2 Sec.2.(b)] Sec. 3.2

Interfaced Equipment: Integrity of single or multiple circuits providing


interface between two or more control units shall be verified. Interfaced
equipment connections shall be tested by operating or simulating SAES-B-014
B3
operation of the equipment being supervised. Signals required to be Sec. 3.2
transmitted shall be verified at the control unit.
[NFPA 72-2013 Table14.4.3.2 Sec.2.(c)]

Lamps and LEDs: Lamps and LEDs shall be illuminated. SAES-B-014


B4
[NFPA 72-2013 Table 14.4.3.2 Sec.2.(d)] Sec. 3.2

Primary (Main) Power Supply: All secondary (standby) power shall be


disconnected and tested under maximum load, including all alarm
appliances requiring simultaneous operation. All secondary (standby) SAES-B-014
B5
power shall be reconnected at end of test. For redundant power supplies, Sec. 3.2
each shall be tested separately.
[NFPA72-2013 Table10.4.3.2 Sec.2(e)]

Secondary (Standby) Power Supply: Disconnect all primary (main)


power supplies and verify the occurrence of required trouble indication for
loss of primary power. Measure or verify the system’s standby and alarm
current demand and verify the ability of batteries to meet standby and
SAES-B-014
B6 alarm requirements using manufacturer’s data. Operate general alarm
Sec. 3.2
systems a minimum of 5 minutes and emergency voice communications
systems for a minimum of 15 minutes.Reconnect primary (main) power
supply at end of test.
(NFPA 72-2013 Table14.4.3.2 Sec.7)

Uninterrupted Power Supply (UPS): If a UPS system dedicated to the


fire alarm system is used as a required power source, operation of the
SAES-B-014
B7 UPS system shall be verified by the building owner in accordance with
Sec. 3.2
NFPA 111, Standard on stored Electrical Energy Emergency and Standby
Power Systems. (NFPA 72-2013Table14.4.3.2 Sec.8)

C Batteries - General Tests


General Tests: Prior to conducting any battery testing, the person
conducting the test shall ensure that all system software stored in volatile SAES-B-014
C1
memory is protected from loss. Sec. 3.2
(NFPA 72-2013 Table14.4.2.2 Sec.9)

Saudi Aramco: Company General Use


Visual Inspection: Batteries shall be inspected for corrosion or leakage.
Tightness of connections shall be checked and ensured. If necessary,
SAES-B-014
C2 battery terminals or connections shall be cleaned and coated. Electrolyte
Sec. 3.2
level in lead-acid batteries shall be visually inspected. [NFPA 72-2010
Table14.4.2.2 Sec.5.(a)]

Battery Replacement: Batteries shall be replaced in accordance with the


recommendations of the alarm equipment manufacturer or when the SAES-B-014
C3
recharged battery voltage or current falls below the manufacturer’s Sec. 3.2
recommendations. [NFPA 72-2010 Table14.4.2.2 Sec.5(b)]

Charger Test: Operation of battery charger shall be checked in


SAES-B-014
C4 accordance with charger test for the specific type of battery.
Sec. 3.2
[NFPA 72-2010 Table14.4.2.2 Sec.5(c)]

Discharge Test: With the battery charger disconnected, load test the
batteries following the manufacturer’s recommendations. Verify the
voltage level does not fall below the levels specified. Load testing can be SAES-B-014
C5
by means of an artificial load equal to the full fire alarm load connected to Sec. 3.2
the battery.
[NFPA 72-2013 Table14.4.3.2 Sec.9(a)(3)]

Load Voltage Test: With the battery charger disconnected, the terminal
voltage shall be measured while supplying the maximum load required by
its application. The voltage level shall not fall below the levels specified for
the specific type of battery. If the voltage falls below the level specified, SAES-B-014
C6
corrective action shall be taken and the batteries shall be retested. Sec. 3.2
Exception: An artificial load equal to the full fire alarm load connected to
the battery shall be permitted to be used in conducting this test.
[NFPA 72-2013 Table14.4.3.2 Sec.9(a)(4)]

Battery - Tests (Specific Types)


Primary Battery Load Voltage Test: The maximum load for a No. 6
primary battery shall not be more than 2 amperes per cell. An individual
(1.5-volt) cell shall be replaced when a load of 1 ohm reduces the voltage SAES-B-014
C7
below 1 volt. A 6-volt assembly shall be replaced when a test load of 4 Sec. 3.2
ohms reduces the voltage below 4 volts.
[NFPA 72-2013 Table14.4.3.2 Sec.9]

Lead-Acid Type; Charger Test: With the batteries fully charged and
connected to the charger, the voltage across the batteries shall be
SAES-B-014
C8 measured with a voltmeter. The voltage shall be 2.30 volts per cell +0.02
Sec. 3.2
volts at 25°C (77°F) or as specified by the equipment manufacturer.
[NFPA72-2013 Table14.4.3.2 Sec.9(a)(2)]

Lead-Acid Type: Load Voltage Test: Under load, the battery shall not SAES-B-014
C9
fall below 2.05 volts per cell. [NFPA 72-2013 Table14.4.3.2 Sec.9(a)(3)] Sec. 3.2

Lead-Acid Type: Specific Gravity: The specific gravity of the liquid in


the pilot cell or all of the cells shall be measured as required. The specific
gravity shall be within the range specified by the manufacturer. Although
the specified specific gravity varies from manufacturer to manufacturer, a
range of 1.205-1.220 is typical for regular lead-acid batteries, while 1.240- SAES-B-014
C10
1.260 is typical for high-performance batteries. A hydrometer that shows Sec. 3.2
only a pass or fail condition of the battery and does not indicate the
specific gravity shall not be used, because such a reading does not give a
true indication of the battery condition.
[NFPA 72-2013 Table14.4.3.2 Sec.9(a)(5)]

Saudi Aramco: Company General Use


Nickel-cadmium type: Charger test: With the batteries fully charged and
connected to the charger, an ampere meter shall be placed in series with
the battery under charge. The charging current shall be in accordance SAES-B-014
C11
with the manufacturer's recommendations for the type of battery used. In Sec. 3.2
the absence of specific information, 1/30 to 1/25 of the battery rating shall
be used. (NFPA 72 2013 Table14.4.3.2 Sec.9.(b).(2))

Nickel-Cadmium Type: Load Voltage Test: Under load, the float voltage
for the entire battery shall be 1.42 volts per cell, nominal. If possible, cells SAES-B-014
C12
shall be measured individually. Sec. 3.2
[NFPA 72-2013 Table14.4.3.2 Sec.9(b)(4)]

Sealed Lead-Acid Type: Charger Test: With the batteries fully charged
and connected to the charger, the voltage across the batteries shall be
SAES-B-014
C13 measured with a voltmeter. The voltage shall be 2.30 volts per cell +0.02
Sec. 3.2
volts at 25°C (77°F) or as specified by the equipment manufacturer.
[NFPA 72-2013 Table14.4.3.2 Sec.9(c)(2)]

Sealed Lead-Acid Type: Load Voltage Test: Under load, the battery
SAES-B-014
C14 shall perform in accordance with the battery manufacturer's specifications.
Sec. 3.2
[NFPA 72-2013 Table14.4.3.2 Sec.9(c)(4)]

D Transient Suppressors, Control Unit Trouble Signals & Annunciator


Transient Suppressors: Lightning protection equipment shall be
inspected and maintained per the manufacturer's published instructions. SAES-B-014
D1
Additional inspections shall be required after any lightning strikes. Sec. 3.2
(NFPA 72-2013 )

Audible and visual: Operation of control unit trouble signals shall be


verified as well as ring-back feature for systems using a trouble-silencing SAES-B-014
D2
switch that requires resetting. Sec. 3.2
[NFPA 72-2013 Table14.4.3.2 Sec.3(a)]

Disconnect Switches: If control unit has disconnect or isolating switches,


verify performance of intended function of each switch. Verify receipt of SAES-B-014
D3
trouble signal when a supervised function is disconnected Sec. 3.2
[NFPA 72-2013 Table14.4.3.2 Sec.3(b)]

Ground-Fault Monitoring Circuit: If the system has a ground detection


feature, the occurrence of ground-fault indication shall be verified SAES-B-014
D4
whenever any installation conductor is grounded. Sec. 3.2
[NFPA 72-2013 Table14.4.3.2 Sec.3(c)]

Transmission of Signals to Off-Premises Location: An initiating device


shall be actuated and receipt of alarm signal at the off-premises location
shall be verified. A trouble condition shall be created and receipt of a
trouble signal at the off-premises location shall be verified. A supervisory
device shall be actuated and receipt of a supervisory signal at the off-
SAES-B-014
D5 premises location shall be verified. If a transmission carrier is capable of
Sec. 3.2
operation under a single- or multiple-fault condition, an initiating device
shall be activated during such fault condition and receipt of a trouble
signal at the off-premises location shall be verified, in addition to the alarm
signal.
[NFPA 72-2013 Table14.4.3.2 Sec.3(d)]

Remote Annunciator: The correct operation and identification of


annunciator shall be verified. If provided, the correct operation of SAES-B-014
D6
annunciator under a fault condition shall be verified. Sec. 3.2
(NFPA 72-2013 Table14.4.3.2 Sec.11)
E Conductors - Metallic
Stray Voltage: All installation conductors shall be tested with a
volt/ohmmeter to verify that there are no stray (unwanted) voltages
between installation conductors or between installation conductors and
SAES-B-014
E1 ground. Unless a different threshold is specified in the published
Sec. 3.2
manufacturer's instructions for the installed equipment, the maximum
allowable stray voltage shall not exceed 1 volt ac/dc.
[NFPA 72-2013 Table10.4.3.2 Sec.15(a)]

Saudi Aramco: Company General Use


Ground Faults: All installation conductors other than those intentionally
and permanently grounded shall be tested for isolation from ground per SAES-B-014
E2
the installed equipment manufacturer's published instructions. Sec. 3.2
[NFPA 72-2013 Table 14.4.3.2 Sec.15(b)]

Short-Circuit Faults: All installation conductors other than those


intentionally connected together shall be tested for conductor-to-conductor
SAES-B-014
E3 isolation per the published manufacturer's instructions for the installed
Sec. 3.2
equipment. These same circuits also shall be tested conductor-to-ground.
[NFPA 72-2013 Table14.4.3.2 Sec.15(c)]

Loop Resistance: With each initiating and indicating circuit installation


conductor pair short-circuited at the far end, the resistance of each circuit
shall be measured and recorded. It shall be verified that the loop SAES-B-014
E4
resistance does not exceed the limits specified in the published Sec. 3.2
manufacturer's instructions for the installed equpment.
[NFPA 72-2013 Table14.4.3.2 Sec.15(d)]

Circuit integrity: Introduction of a fault in any circuit monitored for


integrity shall result in a trouble indication at the fire alarm control unit.
One connection shall be opened at not less than 10 percent of the SAES-B-014
E5
initiating devices, notification appliances and controlled devices on every Sec. 3.2
initiating device circuit, notification appliance circuit, and signaling line
circuit. [NFPA 72-2013 Table14.4.3.2 Sec.15(e)]

Conductors - Non Metallic


Circuit Integrity: Each initiating device, notification appliances, and
controlled devices on every initiating device circuit, notification appliance
SAES-B-014
E6 circuit, and signaling line circuit. Confirm all circuits perform as indicated
Sec. 3.2
in Sections 23.5,23.6, and 23.7
[NFPA 72-2013 Table14.4.3.2 Sec.16(b)]

Fiber Optics: The fiber-optic transmission line shall be tested in


accordance with the manufacturer’s instructions by the use of an optical
power meter or by an optical time domain reflectometer used to measure
the relative power loss of the line. This relative figure for each fiber-optic
line shall be recorded in the fire alarm control panel. If the power level
SAES-B-014
E7 drops 2 percent or more from the value recorded during the initial
Sec. 3.2
acceptance test, the transmission line, section thereof, or connectors shall
be repaired or replaced by a qualified technician to bring the line back into
compliance with the accepted transmission level per the manufacturer’s
recommendations.
[NFPA 72-2013 Table14.4.3.2 Sec.16(b)]

Supervision: Introduction of a fault in any supervised circuit shall result in


a trouble indication at the control unit. One connection shall be opened at
not less than 10 percent of the initiating device, notification appliance, and
signaling line circuit. Each initiating device, notification appliance, and SAES-B-014
E8
signaling line circuit shall be tested for correct indication at the control Sec. 3.2
unit. All circuits shall perform as indicated in Table 6.5, Table 6.6.1, or
Table 6.7. (Attachment 2)
[NFPA 72-2013 Table14.4.3.2 Sec.13(6)]

Saudi Aramco: Company General Use


Shop Drawings: Control unit wiring diagrams should be provided for all
control equipment (i.e., equipment listed as either a control unit or control
unit accessory), power supplies, battery chargers and annunciators and
should include the following information:
(1) Identification of the control equipment depicted
(2) Location(s)
(3) All field wiring terminals and terminal identifications
(4) All circuits connected to field wiring terminals, and circuit
SAES-B-014
E9 identifications
Sec. 3.2
(5) All indicators and manual controls, including the full text of all
labels
(6) All field connections to supervising station signaling equipment,
releasing equipment, and fire safety control interfaces.
Typical wiring diagrams should be provided for all initiating devices,
notification appliances, remote alarm light emitting diodes (LEDs), remote
test stations, and end-of-line and power supervisory devices. (NFPA 72-
2013 Section 7.4.7)

REMARKS:

REFERENCE DOCUMENTS:
1. Schedule G - Material, Tools and Equipment (Pro Forma MP-IK-LS Contract)
2. Schedule Q - Quality Requirements (Pro Forma Contract), Project Specific
3. SAES-B-014 - Safety Requirements for Plant and Operations Support Buildings,2 January 2018
4. 34-SAMSS-820 - Instrument Control Cabinets - Indoor, 13 July 2016
5. 34-SAMSS-831 - Instrumentation for Packaged Units,14 May 2018
6. NFPA 70 - National Electrical Code (NEC), 2017 Edition
7. NFPA 72 - National Fire Alarm Code, 2013 Edition

ATTACHMENTS:
1. Attachment 1: NFPA 72 Table 14.3.1 - Visual Inspection Frequencies
2. Attachment 2: NFPA 72 Tables A.12.3(a), A.12.3(b), A.12.3©
3. Attachment 3: Functional Test of Fire Alarm Panel (as one system) Page 1 of 3
4. Attachment 4: Functional Test of Fire Alarm Panel (as one system) Page 2 of 3
5. Attachment 5: Functional Test of Fire Alarm Panel (as one system) Page 3 of 3
NOTES:
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling).

3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products or
services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states
that the equipment, material or services either meets appropriate designated standards or has been tested and found suitable for a specified purpose.

4. Labeled - Equipment or materials to which has been attached a label, symbol or other identifying mark of an approved qualified organization
concerned with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the
manufacturer indicates compliance with appropriate standards or performance in a specified manner.

Contractor / Third-Party Saudi Aramco


Technician Performing Test* PMT Representative
Test Performed Successfully and Results are Acceptable: T&I Witnessed QC Record Reviewed Work Verified
Name, Title, Department,
Name, Initials and Date:
Company, Initials and Date:

QC Inspector PID Representative

Saudi Aramco: Company General Use


Witnessed Test Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Implementation of Test and Analysis of Results Y = YES N = NO F = FAILED

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU-24-July-2018 - REV.2018.06.00 (Standards Cutoff - June 30,2018) Rev.2018.06.00 30-Jun-18
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
Fire Alarm System - Control Panel - Pre-Commissioning Test SATR-B-6101 24-Jul-18 INST

Attachment 1: NFPA 72, 2013 Table 14.3.1 - Visual Inspection Frequencies

Saudi Aramco: Company General Use


Saudi Aramco: Company General Use
SAUDI ARAMCO ID/PIEU-24-July-2018 - REV.2018.06.00 (Standards Cutoff - June 30,2018) Rev.2018.06.00 30-Jun-18
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
Fire Alarm System - Control Panel - Pre-Commissioning Test SATR-B-6101 24-Jul-18 INST

Attachment 2: NFPA 72 Tables A.12.3(a), A.12.3(b), A.12.3(c)

Saudi Aramco: Company General Use


Saudi Aramco: Company General Use
SAUDI ARAMCO ID/PIEU-24-July-2018 - REV.2018.06.00 (Standards Cutoff - June 30,2018) Rev.2018.06.00 30-Jun-18
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
Fire Alarm System - Control Panel - Pre-Commissioning Test SATR-B-6101 24-Jul-18 INST

Attachment 3: Functional Test of Fire Alarm Panel (as one system) Page 1 of 3
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

Panel or Enclosure Tag No: EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

Ref. Mfr. Instruction Manual REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

Visual Inspection of Cabinet done Yes / No All loops continuity check done Yes / No
SYSTEM PREPARATION AND PRELIMINARY CHECKS
Internal wiring Cold Test done Yes / No Grounding Systems connected & Checked Yes / No
Internal Components Cold check : Yes / No Cabinet Segregation from Field Signals done Yes / No

Type of Transmission: Service:


Multiplex Reverse Priority Weekly Monthly
Digital RF Quarterly Semi-annually
Other (Specify) Annually Others (specify)
Control Unit Manufacturer:……………………………………………………………Model No………………………………….
Circuits Styles:…………………………………… Number of Circuits:…………………………………………………………..
Software Rev:……………………………Last Date System Had Any Service Performed:…………………………………….
SYSTEM ENERGISATION
Last Date that any Software or Configuration was Revised:......................................................
Power Supplies Input Check: Yes / No Power Supplies on…………………………………………………..
Switching System Check :…………………….. Warm up Check …………………………………………….
Back-up Battery Check :…………………….. Others (Specify) …………………………………………….
ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION
Quantity Circuit Style
Manual Fire Alarm Boxes
Ion Detectors
Photo Detectors
Duct Detectors
Heat Detectors
Water flow Switches
Others (Specify) …………………………………………….

Alarm verification feature is disabled ------------------- enabled-------------


(NFPA Inspection and Testing , 1 of 4)

ALARM-NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION


Quantity Circuit Style
Bells
Horns
Chimes
Strobes
Speakers
Others (Specify) …………………………………………….

No of alarm notification appliance circuits:------------------------------------


Are Circuits monitored for integrity? Yes / No
(NFPA Inspection and Testing , 2 of 4)

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU-24-July-2018 - REV.2018.06.00 (Standards Cutoff - June 30,2018) Rev.2018.06.00 30-Jun-18
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
Fire Alarm System - Control Panel - Pre-Commissioning Test SATR-B-6101 24-Jul-18 INST

Attachment 4: Functional Test of Fire Alarm Panel (as one system) Page 2 of 3
SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUIT INFORMATION
Quantity Circuit Style
Building Temp.
Site Water Temp.
Site water Level
Fire Pump Power
Fire Pump Running
Fire Pump Auto Position
Fire Pump or Pump Controller Trouble
Fire Pump Running
Generator In Auto Position
Generator or Controller Trouble
Switch Transfer
Generator Engine Running
Others (Specify) …………………………………………….

SIGNALING LINE CIRCUITS:


Quantity and style of signaling line circuits connected to system ( NFPA 72, Table 6.6.1)
Quantity …………………………………………….. Style (s)……………………………………………………...

SYSTEM POWER SUPPLIES:


(a) Primary (Main): Nominal Voltage……………...…………………………Amps……………………………………………...
Overcurrent Protection : Type…………………………………………..Amps……………………………………….………
Location(of Primary Supply Panelboard)………………………………………………………………………….................
Disconnecting Means Location:........................................................................................................................
(b) Secondary (Standby):
..............................................................Storage Battery : Amp-Hr Rating.............................................................
Calculated capacity to operate sytem, in hours:...........................24...........................60...................................
......................................Engine-driven generator dedicated to fire alarm System:
Location of fuel storage:.................................................................................................................................
TYPE BATTERY
Dry Cell------------------------------- Nickle- Cadmium ............................ Sealed Lead- Acid............................................
Other (Specify)
(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:
.......................................Emergency System described in NFPA 70, Article 700
.......................................legally required standby described in NFPA 70, Article 701
.......................................Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or
701.

PRIOR TO ANY TESTING


NOTIFICATIONS ARE MADE Yes No Who Time
Monitoring Entity Yes No ………….. ………………
Building Occupants Yes No ………….. ………………
Building Management Yes No ………….. ………………
Other (Specify) Yes No ………….. ………………
Authorities Having Jurdiction Notified
of any Impairments Yes No ………….. ………………
SYSTEM TESTS AND INSPECTIONS
TYPE Visual Functional Comments
Control Unit
Interface Equipment
Lamps / LEDs
Fuses
Primary Power Supply
Trouble Signals

Saudi Aramco: Company General Use


Disconnect Switches
Ground-Fault Monitoring

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU-24-July-2018 - REV.2018.06.00 (Standards Cutoff - June 30,2018) Rev.2018.06.00 30-Jun-18
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
Fire Alarm System - Control Panel - Pre-Commissioning Test SATR-B-6101 24-Jul-18 INST

Attachment 5: Functional Test of Fire Alarm Panel (as one system) Page 3 of 3
SYSTEM TESTS AND INSPECTIONS
Secondary Power Type Visual Functional Comments
Battery Condition
Load Voltage N/A
Discharge Test N/A
Charger Test N/A
Specific Gravity N/A
TRANSIENT SUPPRESSORS N/A
REMOTE ANNUNCIATOR
NOTIFICATIONS APPLIANCES
Audible
Visible
Speakers
Voice Clarity N/A
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS
Loc. & S/N Device Type Visual Check Functional Test Factory Setting Measured Setting Pass Fail

Comments:

Emergency Communication Equipt. Visual Functional Comments


Phone Set
Phone Jacks
Off-Hook Indicator
Amplifier (s)
Tone Generator (s)
Call-in Signal
System Performance

INTERFACE EQUIPMENT Visual Device Operation Simulated Operation


(Specify)
(Specify)
(Specify)
SPECIAL HAZARD SYSTEMS Visual Device Operation Simulated Operation
(Specify)
(Specify)
(Specify)
Special Procedures:

Comments:

SUPERVISING STATION MONITORING


Yes No Time Comments
Alarm Signal Yes No ………….. ………………
Alarm Restoration Yes No ………….. ………………
Trouble Signal Yes No ………….. ………………
Supervisory Signal Yes No ………….. ………………
Supervisory Restoration Yes No ………….. ………………
The following did not operate correctly:

Comments:

Saudi Aramco: Company General Use


Saudi Aramco: Company General Use

Das könnte Ihnen auch gefallen