Beruflich Dokumente
Kultur Dokumente
00 30-Jun-18
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
Fire Alarm System - Control Panel - Pre-Commissioning Test SATR-B-6101 24-Jul-18 INST
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
TEST PROCEDURE ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
Review Factory Acceptance Test (FAT) documents detailing the set-up 34-SAMSS-820
A2
and procedures for the Functional Test to be provided. Sec. 8(a)
Verify that manufactured items have been inspected by the Saudi Aramco
34-SAMSS-820
A3 Inspection representative, per the Saudi Aramco Inspection Requirement
Sec. 8
175-343100 attached to the Purchase Order.
Specific tools and equipment shall be identified to make and perform tests Schedule Q
A9
in the field with instructions for their use, calibration and storage. Att. IV Sec. 7.1
Discharge Test: With the battery charger disconnected, load test the
batteries following the manufacturer’s recommendations. Verify the
voltage level does not fall below the levels specified. Load testing can be SAES-B-014
C5
by means of an artificial load equal to the full fire alarm load connected to Sec. 3.2
the battery.
[NFPA 72-2013 Table14.4.3.2 Sec.9(a)(3)]
Load Voltage Test: With the battery charger disconnected, the terminal
voltage shall be measured while supplying the maximum load required by
its application. The voltage level shall not fall below the levels specified for
the specific type of battery. If the voltage falls below the level specified, SAES-B-014
C6
corrective action shall be taken and the batteries shall be retested. Sec. 3.2
Exception: An artificial load equal to the full fire alarm load connected to
the battery shall be permitted to be used in conducting this test.
[NFPA 72-2013 Table14.4.3.2 Sec.9(a)(4)]
Lead-Acid Type; Charger Test: With the batteries fully charged and
connected to the charger, the voltage across the batteries shall be
SAES-B-014
C8 measured with a voltmeter. The voltage shall be 2.30 volts per cell +0.02
Sec. 3.2
volts at 25°C (77°F) or as specified by the equipment manufacturer.
[NFPA72-2013 Table14.4.3.2 Sec.9(a)(2)]
Lead-Acid Type: Load Voltage Test: Under load, the battery shall not SAES-B-014
C9
fall below 2.05 volts per cell. [NFPA 72-2013 Table14.4.3.2 Sec.9(a)(3)] Sec. 3.2
Nickel-Cadmium Type: Load Voltage Test: Under load, the float voltage
for the entire battery shall be 1.42 volts per cell, nominal. If possible, cells SAES-B-014
C12
shall be measured individually. Sec. 3.2
[NFPA 72-2013 Table14.4.3.2 Sec.9(b)(4)]
Sealed Lead-Acid Type: Charger Test: With the batteries fully charged
and connected to the charger, the voltage across the batteries shall be
SAES-B-014
C13 measured with a voltmeter. The voltage shall be 2.30 volts per cell +0.02
Sec. 3.2
volts at 25°C (77°F) or as specified by the equipment manufacturer.
[NFPA 72-2013 Table14.4.3.2 Sec.9(c)(2)]
Sealed Lead-Acid Type: Load Voltage Test: Under load, the battery
SAES-B-014
C14 shall perform in accordance with the battery manufacturer's specifications.
Sec. 3.2
[NFPA 72-2013 Table14.4.3.2 Sec.9(c)(4)]
REMARKS:
REFERENCE DOCUMENTS:
1. Schedule G - Material, Tools and Equipment (Pro Forma MP-IK-LS Contract)
2. Schedule Q - Quality Requirements (Pro Forma Contract), Project Specific
3. SAES-B-014 - Safety Requirements for Plant and Operations Support Buildings,2 January 2018
4. 34-SAMSS-820 - Instrument Control Cabinets - Indoor, 13 July 2016
5. 34-SAMSS-831 - Instrumentation for Packaged Units,14 May 2018
6. NFPA 70 - National Electrical Code (NEC), 2017 Edition
7. NFPA 72 - National Fire Alarm Code, 2013 Edition
ATTACHMENTS:
1. Attachment 1: NFPA 72 Table 14.3.1 - Visual Inspection Frequencies
2. Attachment 2: NFPA 72 Tables A.12.3(a), A.12.3(b), A.12.3©
3. Attachment 3: Functional Test of Fire Alarm Panel (as one system) Page 1 of 3
4. Attachment 4: Functional Test of Fire Alarm Panel (as one system) Page 2 of 3
5. Attachment 5: Functional Test of Fire Alarm Panel (as one system) Page 3 of 3
NOTES:
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling).
3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products or
services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states
that the equipment, material or services either meets appropriate designated standards or has been tested and found suitable for a specified purpose.
4. Labeled - Equipment or materials to which has been attached a label, symbol or other identifying mark of an approved qualified organization
concerned with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the
manufacturer indicates compliance with appropriate standards or performance in a specified manner.
*Person Responsible for Implementation of Test and Analysis of Results Y = YES N = NO F = FAILED
Attachment 3: Functional Test of Fire Alarm Panel (as one system) Page 1 of 3
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
Panel or Enclosure Tag No: EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
Ref. Mfr. Instruction Manual REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
Visual Inspection of Cabinet done Yes / No All loops continuity check done Yes / No
SYSTEM PREPARATION AND PRELIMINARY CHECKS
Internal wiring Cold Test done Yes / No Grounding Systems connected & Checked Yes / No
Internal Components Cold check : Yes / No Cabinet Segregation from Field Signals done Yes / No
Attachment 4: Functional Test of Fire Alarm Panel (as one system) Page 2 of 3
SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUIT INFORMATION
Quantity Circuit Style
Building Temp.
Site Water Temp.
Site water Level
Fire Pump Power
Fire Pump Running
Fire Pump Auto Position
Fire Pump or Pump Controller Trouble
Fire Pump Running
Generator In Auto Position
Generator or Controller Trouble
Switch Transfer
Generator Engine Running
Others (Specify) …………………………………………….
Attachment 5: Functional Test of Fire Alarm Panel (as one system) Page 3 of 3
SYSTEM TESTS AND INSPECTIONS
Secondary Power Type Visual Functional Comments
Battery Condition
Load Voltage N/A
Discharge Test N/A
Charger Test N/A
Specific Gravity N/A
TRANSIENT SUPPRESSORS N/A
REMOTE ANNUNCIATOR
NOTIFICATIONS APPLIANCES
Audible
Visible
Speakers
Voice Clarity N/A
INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS
Loc. & S/N Device Type Visual Check Functional Test Factory Setting Measured Setting Pass Fail
Comments:
Comments:
Comments: