Beruflich Dokumente
Kultur Dokumente
ABB’s solutions are based on strong and stable architectures Sustainably manufactured in Switzerland to the highest of
that make sure your important application is supported by standards, ABB’s Power Protection products employ a variety
the very best power protection system, ready to step in and of technologies – from traditional designs to our leading range
take over at the first sign of trouble. of modular products that allow a power protection system to
be added to module by module, as and when required. This
This product catalogue provides details of ABB’s Power reduces initial capital outlay and simplifies maintenance.
Protection solutions and will guide you in choosing which
ones are suitable for your needs. ABB is always there to provide consultancy so that you
can choose the product that is exactly right for you.
Our uninterruptible power supplies (UPS) and ancillary And afterwards, our global, first-class service organization
products cover a wide range of applications and power – is at your disposal in more than 100 locations.
from small offices to large data centers. And for each
and every user ABB’s mission is to provide power protection Please browse the catalogue to learn more about the ABB
that ensures the highest availability and the lowest cost Power Protection group, our approach to power protection
of ownership. and details of our products. If you require guidance, we
are always ready to assist you in person, or you can visit
www.abb.com/ups.
About us 4
Connectivity solutions 56
The ABB Power Protection product group was formed the attention of the ABB Group, who acquired Newave in
from the combination of the three ABB product lines early 2012. This acquisition propelled ABB to the forefront
UPS, Power Conditioning and Power Solutions. The three of the power protection industry as the company’s portfolio
businesses have their roots in the formerly acquired complements the rest of ABB’s Power Protection offering to
companies Newave (UPS), Vectek and Cyberex. give a unique line-up of UPS, power conditioning and power
switching products designed to solve power quality issues in
Newave SA was founded in Ticino, Switzerland in 1993 to all sorts of commercial and industrial applications.
market innovative UPS technology. From the very start, the
company was a UPS innovator and by 1994 had designed, Through an expanding team of local business units and
manufactured and launched its first generation of three- channel partners – and an array of innovative products – ABB
phase, transformerless standalone UPS. Further innovation is well positioned for further growth in the global UPS and
followed and the UPS product portfolio grew through several power protection market. And there are innovative products
generations to cover three-phase applications and ever-higher to match: For example, the unique Decentralized Parallel
powers. Architecture (DPA™) featured in UPSs like the Conceptpower
DPA 500 is just one innovation from a pioneering company
In 1998, the first generation of modular UPSs was introduced. that has over 20 years of UPS design under its belt.
The modular approach delivers a low total cost of ownership
and has proven to be a runaway success with customers. www.abb.com/ups
The company’s innovation and accomplishments attracted
For a company to know its direction of travel and know in everything we do. Knowing our customers better, being
what it stands for, it has to have visions and values. perceived as having a clear focus on them and providing
high-quality offerings and services will make us the partner
“Power and productivity for a better world” describes what of choice.
ABB stands for. In power we are a leader in addressing
power infrastructure and control needs for utilities, industry, Innovation and speed
transport and infrastructure. In productivity – ABB is a leader Innovation is at the core of our value proposition and will
in operational asset effectiveness – we support our customers continue to be critical in strengthening and enhancing our
in achieving high uptime and speed while reducing waste. competitive position – in daily business, and as we expand
our offering towards engineering / consulting, software and
“… a better world” refers to our value proposition to decouple value-added services. Speed is essential in everything we do
economic growth from environmental pollution. Based on our – being efficient with a high quality and without haste is the
offering and technologies, we are well positioned to enable art that we are committed to mastering.
growth with less relative energy consumption and make the
still-needed energy supply cleaner and more sustainable. Ownership and performance
Strengthening clear lines of responsibility and accountability
Our vision is clear: our daily actions need to be built on across our organization is a key part of our Next Level
the right set of values – and not only for the world of today strategy. Institutional and individual performance are key to
but also for the world of tomorrow. continue to not only survive but succeed in a demanding
world. Performance is what is expected from all of us every
Our values can be summarized as five value pairs that day – not only continuing what we are doing, but also taking a
are both fundamental and inspirational: step forward.
Factory certification
– – ISO 9001 and 14001
–– OHSAS18001
Good customer service is the lifeblood of any business or Customers can contact their local ABB representative or
organization. This fact is well understood by ABB and the nominated ABB partner for assistance. A local field service
is the fundamental reason why good customer service is engineer will help the customer to solve the issue, either
driven by ABB management and is of equal importance by phone or by going on-site. If the field service engineer is in
for all staff. need of assistance, they are able to contact the round-the-
clock, 24 × 365 ABB support line in Switzerland. The support
ABB’s service footprint for the UPS product line is global and line expert assists the local field service engineer in solving
is provided by ABB itself or by members of ABB’s partner the issue by phone and electronic ticketing system as well as
network. All ABB and partner service engineers go through local intervention when required. The support team experts
intense product-specific training before they are allowed are always on duty and will return any call at any time.
to carry out service work at a customer site.
ABB’s approach to modular power protection Some modular UPS systems with a centralized parallel
Despite all the precautions taken during the design and architecture (CPA) have centralized control or hardware.
operation of data centers and related control processes, This renders them very vulnerable should a fault occur on
situations can arise in which external power is compromised one of these centralized components; one fault can bring
– either in terms of quality or availability. Such events could down the entire UPS system.
result in data loss, nonavailability of essential services, risk to
hardware and very high financial losses. This makes a highly With DPA, on the other hand, the UPS is modularized and
dependable UPS mission-critical. Therefore, the most critical each module has all the hardware and software needed for
loads should be protected by the very best UPS design – autonomous operation – rectifier, inverter, battery converter,
Decentralized Parallel Architecture (DPA™). static bypass switch, back-feed protection, control logic,
display, and mimic diagram for monitoring and control.
ABB, a pioneer and leader in large, modular UPSs, provides With all the critical components duplicated and distributed
a full range of modular DPA power protection products as between individual units, potential single points of failure
well a standalone solutions. In the following four pages, we are eliminated. In the unlikely event of one UPS module
will focus on our approach to modular power protection and failing, the failed module will be automatically isolated and
describe how these modular solutions can help ensure a the overall system will continue to operate normally.
supply of clean, reliable power to the customer’s application.
Power module Output to the UPS module Control logic Output to the
critical load display critical load
In DPA, each UPS module has all the hardware and software it
needs for autonomous operation.
True “online-swap” modularity enables the safe removal and The ability to scale the system means the UPS can be sized
insertion of UPS modules without risk to the critical load exactly to fit prevailing needs and modules can simply be
and without the need to either transfer it onto raw mains or added as requirements grow. This means that you only power,
remove power from it. Modules can therefore be replaced or cable and cool what you need.
added without any system downtime. It is simple to upgrade
power capability as critical load power requirements grow. The Conceptpower DPA 500, for example, allows five 100 kW
Additionally, modules can easily be removed for service or modules to be mounted in one cabinet and six cabinets
replaced if faulty, without compromising the availability of to be configured in parallel to provide a top rating of 3 MW.
the system. Only a truly redundant architecture like DPA Power consumption is the topic of greatest concern for
allows online modules to be swapped out while the system is data center operators and the energy savings made by this
running. modular approach over the service life time of the UPS are
substantial. Human error is reduced too: Because things are
This unique aspect of modularity directly addresses so simple, wiring errors are eliminated, and configuration
continuous uptime requirements, significantly reduces mean and reconfiguration are child’s play.
time to repair (MTTR), reduces inventory levels of spare
parts and simplifies system upgrades. This approach pays
off too when it comes to serviceability and availability, as
there is no downtime and the service personnel do not need
special skills.
Scalability up to 3 MW
Horizontal scalability: cabinets in
parallel configuration up to 3 MW
Efficiency
100%
Eco-mode
98%
95.8% 96.1% 96.0% 95.6%
96%
94%
92%
90%
0% 25% 50% 75% 100%
Load
kW
180 Standalone solution
kW
2 × 60 kW (N +1) UPS until year 1
160 180 3 × 60 kW (N +1) UPS years 1–4
140 160 Oversized capacity = saving potential
Oversized capacity
120 140 Oversized capacity = saving potential
Modularity lends itself well to keeping UPS footprint small, too Vertical modularity minimizes space requirements and
– ideal for data centers, where real estate can be restricted maximizes predictability of future space requirements. In the
example shown, 2 m2 is saved.
and expensive. A modular UPS rack has a small footprint and
when extra modules are added, no extra floor space is taken up. Total footprint
1.11 m2
But the advantages of DPA modularity go further as Clearance
Total footprint 3.2 m2
installation and servicing costs are also kept low: 0.16 m2
A straightforward modular concept simplifies and speeds
every step of the deployment process – from planning, UPS UPS UPS
through installation and commissioning to full use. DPA 0.7 m2 0.7 m2 0.4 m2
modularity also reduces costs as service engineers need
less training and spend less time on-site, and any risks
of data or production loss are minimized. Inventory levels
of spare parts are reduced.
Clearance 1m Clearance
0.55 m2 1.8 m2
Highly dependable UPSs are mission-critical for many parts
of industry. DPA delivers unmatched UPS availability and
serviceability, scalability, flexibility and low energy usage.
Traditional 2×180 kW (2N) Modular up to
180 kW (N+1)
There are no better UPS architectures available to those users
whose critical electrical loads represent a valuable commercial
asset that must be kept powered at all costs.
At the core of our business is a technically advanced product equipment against all power problems: power failure, power
portfolio of high-quality and reliable three-phase and single- sag, power surge, undervoltage, overvoltage, switching
phase transformerless uninterruptible power supplies. All our transient, line noise, frequency variation and harmonic
UPSs provide online double conversion topology and are distortion.
designed for continuous power protection of critical
kVA
500
400
300
250
200
160
120
100
80
60
50
40
30
20
10
Product DPA UPScale ST DPA UPScale RI Conceptpower DPA Conceptpower DPA 500
kVA
500
400
300
250
200
160
120
100
80
60
50
40
30
20
10
System display
ABB’s DPA UPScale ST is available for high density mid-sized infrastructure, DPA UPScale ST can be paralleled
applications requiring an all-in-one power protection solution horizontally to increase the capacity up to 400 kW. This fully
that includes frame, UPS, battery and communications. The scalable and easily maintained UPS gives you unparalleled
solution delivers power protection from 10 kW to 200 kW uptime and energy efficiency.
in 10 kW or 20 kW modular steps. For a continuously growing
The DPA UPScale ST can be deployed in a variety of small- to productive and comfortable environment, thus increasing
medium-sized system architectures. In addition to traditional operational efficiency, decreasing the energy consumption
server load applications, the DPA UPScale ST is ideal to and ensuring the safety of personnel and equipment.
protect critical applications such as building management
systems (BMS). Large facilities are often provided with The DPA UPScale ST offers clean backup power for sensitive
BMS to control and monitor the building’s mechanical and electronic devices (controllers, I/O devices and user
electrical systems such as ventilation, lighting, fire alarms and interfaces) designed to monitor and control the infrastructure
security. The BMS is designed to create and maintain a safe, thus avoiding loss of data or damage to equipment.
Utility mains
Web server
User Interface 1 User Interface 2
Programmable Programmable
logic controller 1 logic controller 2
RS232
Battery breakers
The rack-independent DPA UPScale RI is one of the most is required. The DPA UPScale RI, including UPS, battery
compact UPS systems on the market that is suitable for and communication, can be integrated into any 19" rack
custom-designed solutions. Being modular and rack- (independent of manufacturer) and provides up to 80 kW
mountable, it provides an ideal system from the technical (60 kW N+1) making it ideal for integrated IT, telecom or other
and commercial point of view for when a flexible solution critical control processes.
Up to 5 UPS DPA
modules in one cabinet
DPA display
The Conceptpower DPA is a true double conversion modular – thus eliminating oversizing and minimizing upfront capital
UPS designed for medium-sized critical applications. The investment. Each DPA module is self-contained and can
Conceptpower DPA’s modular architecture provides very be online-swapped at any time, so nothing has to be ever
flexible power configuration based on 30 / 40 / 50 kVA transferred to bypass – making routine maintenance safe
modules that can be added as power requirements grow and easy.
DPA display in
each module
Battery breaker
Customer inputs
and potential-free
outputs
Inbuilt maintenance
Bypass fuses bypass switch (optional)
A data center with full uptime. That target is why ABB’s has to be ever switched off – making routine maintenance
Conceptpower DPA 500 is based on Decentralized Parallel safe and easy. And if you want to increase power, the UPS
Architecture (DPA). Only a truly redundant architecture like can be scaled vertically in 100 kW modular steps to provide up
DPA allows online modules to be swapped out while the to 500 kW power in a single frame. Horizontal scalability
system is running. Each high-reliability, standardized module is also given, with up to six frames in parallel, to increase total
is self-contained and can be swapped at any time, so nothing power up to 3 MW.
= 3 MW
configuration to build a system of up to 3 MW (horizontal
scalabiltiy).
+6
modules
The power demand of one row of server racks can vary from 100 kW
up to hundreds of kW. The building block concept of Conceptpower
DPA 500 allows adaption to the changes in power demand in a
growing infrastructure.
Extendable Extendable
SECTION A-A
BOTTOM CABLE ENTRY
81
General data
System power range 100 kW–3 MW
Nominal power / module 100 kW
Nominal power / frame 500 kW
Output power factor 1.0
Topology Online double conversion, Decentralized Parallel Architecture
Parallel configuration Up to 5 modules in one cabinet (500 kW) / up to 6 cabinets in parallel (3 MW)
Cable entry Bottom or top as standard
Serviceability Full front
Back-feed protection Built-in as standard
Input
Nominal input voltage 3 × 380 / 220 V + N, 3 × 400 / 230 V + N, 3 × 415 / 240 V + N
Voltage tolerance For loads <100% (−10%, +15%), <80% (−20%, +15%), <60% (−30%, +15%)
(referred to 400 / 230 V)
Input distortion THDi <3.5%
Frequency range 35 –70 Hz
Power factor 0.99
Walk in / soft start Yes
Output
Rated output voltage 3 × 380 / 220 V + N, 3 × 400 / 230 V + N, 3 × 415 / 240 V + N
Voltage tolerance <±1% with static load / <±4% with step load
(referred to 400 / 230 V)
Voltage distortion <2% with linear load / <4% with non linear load
Frequency 50 Hz or 60 Hz (selectable)
Efficiency
Overall efficiency Up to 96%
In eco-mode ≥ 99%
Environment
Protection rating IP 20
Storage temperature −25 °C to +70 °C
Operating temperature 0 °C to +40 °C
Altitude (above sea level) 1000 m without derating
Batteries
Types VRLA (vented lead-acid), NiCd
Battery charger Decentralized charger per module
Communications
User interface Graphical touch screen (one per frame as standard)
Decentralized LCD and mimic diagram (one per module as standard)
Communication ports USB, RS-232, potential-free contacts, SNMP (optional)
Customer interface Remote shutdown, gen-set interface, external bypass contact
Compliancy
Safety IEC / EN 62040-1
EMC IEC / EN 62040-2
Performance IEC / EN 62040-3
Manufacturing ISO 9001:2008, ISO 14001:2004, OHSAS18001
Weight, dimensions
Weight 975 kg (500 kW system)
Dimensions w × h × d 1580 × 1975 × 940 mm
ABB’s PowerValue 11 RT is a double-conversion online UPS The PowerValue 11 RT can be used as a standalone UPS
that guarantees up to 10 kVA of clean, reliable power for your device or installed into a standard "19 rack configuration, with
critical single-phase applications. As well as maintaining connectivity options available for each.
power to your servers, point-of-sale terminals, workstation
clusters, routers, switches, hubs and sensitive electronic Two units of the 6 or 10 kVA models can be configured in
equipment, the PowerValue 11 RT also conditions incoming parallel to provide redundancy or to increase the systems total
power to eliminate spikes, swells, sags, noise and harmonics. capacity up to 20 kVA. All units can be fitted with up to four
battery modules to extend runtime.
+ Rotatable
display + Rotatable
display + Rotatable
display
UPS
10 kVA
UPS
UPS 6 kVA
1– 3 kVA
Battery
Battery 6 / 10 kVA
1– 3 kVA
9 5
2 2 17
1
10
14
2
3 4
5 5 11
20 11 12
12
5 4 3 4 3 4
3
6 7 6 7
19
13
13
8
15 14
21
8 17
16 2
18
10
The PowerValue 11 / 31 T UPS delivers reliable power, low Three-phase or single-phase inputs can also be
running costs, long battery life, easy maintenance and high accommodated, as well as single- or dual-supply inputs –
levels of flexibility. Featuring double-conversion, voltage and allowing the customer to manage two independent power
frequency independent (VFI) topology, the PowerValue 11 / 31 sources. Simple to install and with a small footprint, the
T is available in both 10 and 20 kVA versions, with the option PowerValue 31 / 11 T provides stable, regulated, transient-free,
to configure up to four units in parallel to boost power pure sine wave AC power with extremely tight output voltage
capability or provide redundancy. regulation.
Up Up
4 + 4
to to
UPSs in battery
parallel cabinets in
parallel
in minutes at full/half load
Given runtimes are estimates and valid at 20 degrees Celsius. Actual runtime of the system will depend, among many variables, on the age of the batteries and environmental
conditions.
Frequency conversion
Operating as a frequency converter, PowerValue 11 / 31 T not The operation and installation is simple and consisys merely
only converts the power supply frequency (50 Hz to / from of correctly wiring the UPS and selecting the frequency
60 Hz), but it also protects the load from power disturbances conversion mode in the LCD.
and guarantees additional battery power in case of mains – – Input frequency range: 40–70 Hz
failure. – – Output frequency: 50 Hz or 60 Hz
– – Output derating:
– Single-phase input: 60%
10 11 10 11
12 12
9 9 9 9
2
1
3
8 8
4
7 7
6 6
5 5
13 13
General data 10 kVA 10 kVA (5 min) 10 kVA (16 min) 20 kVA 20 kVA (5 min)
Output rated power [W] 9 kW 18 kW
Output power factor 0.9
Topology Online double conversion
Parallel configuration Up to 4 units
Inbuilt batteries No Yes Yes No Yes
Input
Nominal input voltage 1 ph +N: 220 / 230 / 240 VAC
3 ph +N: 380 / 400 / 415 VAC
Input voltage tolerance 1 ph +N: 110–276 VAC
3 ph +N: 190–486 VAC
Input current THD <5% linear load, <7% non linear load
Frequency range 45–55 Hz for 50 Hz systems / 55–65 Hz for 60 Hz system
Power factor ≥0.99
Output
Rated output voltage 220 / 230 / 240 VAC
Voltage tolerance ±2%
Voltage distortion ≤2% linear load, ≤5% non linear load
Overload capability 1 min: 110–130% / 5 min: 105–110%
(linear load) 100 ms: >150% / 10 s: 130–150%
Nominal frequency 50 Hz or 60 Hz ±0.1 Hz
Crest factor 3 : 1 (load supported)
Efficiency
Overall efficiency Up to 93.1% Up to 93.9%
In eco-mode ≥97%
Environment
Protection rating IP 20
Storage temperature −15 °C to +60 °C for UPS, 0 °C to approx. +35 °C for battery
Operating temperature 0 °C to +40 °C
Relative humidity 0% to 95% (Non-condensing)
Altitude (above sea level) 1000 m without derating
Batteries
Type VRLA (vented lead-acid)
Inbuilt batteries – 1 × 24 2 × 24 – 2 × 24
Battery capacity – 9 Ah 9 Ah – 9 Ah
Charging current 4 A 4 A 4 A 4 A 4 A
Recharge time – 3 h to 90% 8 h to 90% – 8 h to 90%
Communications
User interface LCD
Communication cards Network interface (SNMP card), dry-contact card (AS400)
(option)
Standards
Safety IEC / EN 62040-1
EMC IEC / EN 62040-2
Performance IEC / EN 62040-3
Manufacturing ISO 9001:2008, ISO 14001:2004, OHSAS18001
Weight, dimensions
Weight 56 kg 116 kg 178 kg 67 kg 190 kg
Dimensions w × h × d 350 × 890 × 715 mm 350 × 890 × 715 mm 350 × 890 × 715 mm 350 × 890 × 715 mm 350 × 890 × 175 mm
Parallel isolator
Batteries
Maintenance
bypass switch
Battery fuses
PowerScale is an online, double-conversion, VFI (voltage with uncompromised system reliability and power availability.
frequency independent) UPS that provides enhanced power PowerScale is available in three cabinet sizes, enabling you
protection in a compact format. Its outstanding price / to choose the ideal capacity and required autonomy for your
performance delivers the best value for money in its category critical load.
Cooling fan
Maintenance
bypass isolator
PowerWave 33, an online double conversion UPS, delivers The PowerWave 33 is available over a model range of 60 kW
continuous power availability to network-critical infrastructures to 500 kW and can be configured to operate as a single,
of both data centers and process control environments. standalone UPS or as a multi-cabinet UPS system with up to
Offering maximum power protection, the PowerWave 33 ten UPS cabinets connected in parallel, achieving a total
has a small footprint and uses less energy than comparable power capacity of up to 5 MW.
products – thus delivering significant savings.
Critical load
As your power requirements grow, the UPS system grows with them –
thanks to its scalability – even in the most confined spaces.
Optionally a top cable entry enclosure may be used for the Battery runtime can be optimized to match the exact needs.
400–500 kW UPS. This enclosure permits the connection of all The UPS supports usage of 42–48 batteries (60–120 kW units)
incoming power cables from the top and extends the overall or 44–50 batteries (160–500 kW units) in a single string, which
width of the UPS by 500 mm. minimizes the total cost of installation as an optimal configuration
can be used and so there is no need to oversize the battery.
ABB offers a line of battery cabinets for its modular and 1. Choose the UPS power and type (pages 14–49)
standalone UPS series. These battery cabinets with 2. Define the backup time required
integral overcurrent protection are compatible with a wide 3. Choose common or separate batteries
range of battery configurations and are optimized to meet (in case of modular UPS)
application runtime needs. 4. Check autonomy tables for appropriate battery
configuration and compatible battery cabinets (pages 53–55)
Appropriate battery sizing will ensure that the autonomy is of 5. Check technical specification of selected battery cabinets for
an adequate duration for the load supplied. The user should further information (pages 50–52)
first decide what battery autonomy is required, then select the
battery configuration and cabinets accordingly. This document
assists in this process, which may be broken down into the
following steps:
Availabel models
Type CBAT-DPA-120 C CBAT-DPA-120 S CBAT-DPA-200 C CBAT-DPA-200 S
Compatible UPS models Conceptpower DPA 150 kVA Conceptpower DPA 150 kVA
Conceptpower DPA 250 kVA Conceptpower DPA 250 kVA
Battery quantity / type / Up to 120 VRLA 24/28 Ah Up to 200 VRLA 24/28 Ah
capacity
Autonomy Depends on UPS rated power, see detailed autonomy tables (pages 53–55)
Battery arrangement Common (C) Separate (S) Common (C) Separate (S)
common / separate
Dimensions w × h × d 730 × 1975 × 796 mm 1200 × 1975 × 796 mm
Color Front (doors) RAL 9007; side walls graphite grey (similar to RAL 7024)
Available models
Type CBAT-DPA UPSCALE-120 C CBAT-DPA UPSCALE-120 S CBAT-DPA UPSCALE-200 C CBAT-DPA UPSCALE-200 S
Compatible UPS models DPA UPScale ST40* | DPA UPScale ST80 DPA UPScale ST40* | DPA UPScale ST80
DPA UPScale ST60* | DPA UPScale ST120 DPA UPScale ST60* | DPA UPScale ST120 |
DPA UPScale ST200
PowerWave 33 S2 160 kW | PowerWave 33 S2 200 kW
Battery quantity / type / Up to 120 VRLA 24 / 28 Ah Up to 200 VRLA 24 / 28 Ah
capacity
Autonomy Depends on UPS rated power, see detailed autonomy tables (pages 53–55)
Battery arrangement Common (C) Separate (S) Common (C) Separate (S)
common / separate
Dimensions w × h × d 730 × 1975 × 796 mm 1200 × 1975 × 796 mm
Color Graphite grey (similar to RAL 7024)
Available models
Type CBAT-DPA UPSCALE-600 S CBAT-FLEX** CBAT-POWERSCALE-88
Compatible UPS models DPA UPScale ST120 DPA UPScale ST40* PowerScale 25 kVA Cab C*
DPA UPScale ST80 PowerScale 30 kVA Cab C*
DPA UPScale ST60* PowerScale 40 kVA Cab C*
DPA UPScale ST120 PowerScale 50 kVA Cab C*
PowerWave 33 S2 160 kW
PowerWave 33 S2 200 kW
PowerWave 33 S2 250 kW
PowerWave 33 S2 300 kW
Battery type & capacity Up to 600 VRLA 7 / 9 Ah VRLA up to 150 Ah VRLA up to 88 24 / 28 Ah
Autonomy Depends on UPS rated Not applicable Depends on UPS rated
power, see detailed power, see detailed
autonomy tables below autonomy tables below
Battery arrangement Separate (S) Not applicable Common (C)
common / separate
Dimensions w × h × d 1200 × 1975 × 796 mm 475 × 1400 × 940 mm
Color Graphite grey (similar to RAL 7024)
Battery configurations are for example purposes only and calculations are based
on an ambient temperature of 20 °C to 25 °C. ABB recommends that the user checks
or recalculates configurations according to the battery manufacturer’s datasheet.
Cabinet B
Load power in kW / Autonomy in minutes
5 min. 6 min. 8 min. 10 min. 12 min. 15 min. 20 min. 25 min. 30 min. 40 min. 60 min.
9 kW internal internal internal internal internal internal internal internal internal internal 1 × 40
batt. bat. bat. bat. bat. bat. bat. bat. bat. bat. × 28 Ah
13.5 kW internal internal internal internal internal internal internal 1 × 36 1 × 38 1 × 46 2 × 36
bat. bat. bat. bat. bat. bat. bat. × 28 Ah × 28 Ah × 28 Ah × 28 Ah
18 kW internal internal internal internal internal internal 1 × 44 1 × 44 1 × 48 2 × 44 2 × 44
bat. bat. bat. bat. bat. bat. × 28 Ah* × 28 Ah* x 28 Ah × 28 Ah* × 28 Ah*
22.5kW internal internal internal internal 1 × 48 1 × 48 1 × 48 n. a. n. a. n. a. n. a.
bat. bat. bat. bat. × 28 Ah* × 28 Ah* × 28 Ah*
Cabinet C
Load power in kW / Autonomy in minutes
5 min. 6 min. 8 min. 10 min. 12 min. 15 min. 20 min. 25 min. 30 min. 40 min. 60 min.
22.5kW internal internal internal internal internal internal internal n. a. n. a. n. a. n. a.
batt. bat. bat. bat. bat. bat. bat.
27 kW internal internal internal internal internal internal 2 × 28 2 × 32 2 × 38 n. a. n. a.
bat. bat. bat. bat. bat. bat. × 28 Ah × 28 Ah × 28 Ah
36 kW internal internal internal internal 2 × 36 2 × 36 2 × 36 2 × 42 n. a. n. a. n. a.
bat. bat. bat. bat. × 28 Ah* × 28 Ah* × 28 Ah × 28 Ah
45kW internal internal n. a. n. a. n. a. n. a. n. a. n. a. n. a. n. a. n. a.
bat. bat.
Slot format
Box format
CS121 ModBus USHA+
For interfacing UPS with the network and the ModBus RS485 For interfacing UPS with the network with an option to
with option to connect alarms buzzers or additional relay connect additional environmental sensors. Available in slot
board. Available in slot and box formats. format only.
Slot cards are UPS powered, while cards in box format require external power.
4 relay outputs
04-0594 Profibus converter External DIN rail mount device
00-6944 Temperature sensor −25 °C to +100 °C, ± 0.5% 1.8 m cable
04-3880 Combisensor for temperature and humidity −25 °C to +100 °C, ± 0.5% 1.8 m cable
CS121
0% to 100% RH, ± 5%
00-5915 Sensor manager Environmental interface
Sensor manager
0% to 100% RH, ± 5%
00-6945 Alarm buzzer 85 dB 5 m cable
00-6947 Relay box 1 input contact 5 m cable
1 output contact
04-3869 RCCMD license For Windows, Linux, MAC X, OS / 2, UNIX,
NOVELL
RCCMD
04-0210 USHA+ network interface card Web / SNMP interface ModBus TCP Sensor connections
interface**
Network
04-0212 EMD with temperature and humidity sensors 0 °C to +80 °C, ± 1 °C
USHA+
2 m cable
10% to 90% RH, ± 3%
Environmental
* All CS121 cards / boxes come with one free RCCMD client and a CD containing the monitoring software.
** All USHA+ cards come with RCCMD client and a CD containing the monitoring software.
SNMP SNMP
Modbus TCP Modbus TCP
Others Others
No peripherals
1 4
Peripheral options
Relay
Advanced board
04-0593
Buzzer
04-0592
LAN
SNMP
Modbus TCP
Others
CS121 Advanced
1 4
Peripheral options
ProfiBus 0101
Sensor manager ModBus
converter 1100
RS232
Relay Buzzer Temperature Temperature 00-5915 04-0594
board 04-0592 00-6944 and humidity
04-0593 04-3880
8
SMIO 2
00-6947
1
Temperature
00-5916
1 2
4NWP101485R0001_EN
without notice.
Specifications subject to change without notice.