Sie sind auf Seite 1von 90

Australia Products

Since 1973
A Member of The Elta Group U.K 

FANS SELECTION

Documents included:

- Fan Performance Curve & Drawing for Each Fan

- General catalogue
FAF-2F-VP

FANTECH
CBS SERIES
Small Cabinet Fans

TECHNICAL DATA 

Fan
Power Noise
Model Speed
(W) (dBA @ 3m)
(rpm)
CBS200C 220 1100 38
CBS200D 320 1250 39
CBS250B 400 1150 44

DIMENSIONS

FEATURES 

ELTAFANTECH’s CBS Series is designed for


ceiling mounting and is suitable for domestics
and commercial applications such as houses, office
premises, bedroom, hotel etc. where require low
noise for small duty and low ceiling height (less than
Dimension in mm
400 mm).
Duct Weight
Construction Model L H W A B I J ØD
size (Kg)
The housing and impeller are made by galvanized CBS200C 650 365 400 478 65 182.5 445 195 Ø 200 21.1
sheet. CBS200D 650 365 400 478 65 182.5 445 195 Ø 200 21.1
Forward inclined impeller wheel with direct driven. CBS250B 740 380 400 548 75 190 445 245 Ø 250 24.1

Motors
Type – squirrel cage induction motors. WIRING DIAGRAM 
Electrical supply – 220-240V, single phase,
50/60Hz Bearings – sealed-for-life, ball
Internal Thermal Protection
Thermal fuse is equipped to cut-out for overload.
How to order
Select the model that meets your air flow
and application requirements from the graph.

450 
Pressure (Pa) 

400 

350 

300 
CBS250B

250 

200 
CBS200C 
CBS200D
150 

100 

50 


0  200  400  600 800 1000 1200 1400 1600  1800  2000

Air Volume (m /h) 

The specifications may be changed. All rights are reserved by ELTAFANTECH ASIA SDN BHD.
FAF-3F-VP

FANTECH
CBS SERIES
Small Cabinet Fans

TECHNICAL DATA 

Fan
Power Noise
Model Speed
(W) (dBA @ 3m)
(rpm)
CBS200C 220 1100 38
CBS200D 320 1250 39
CBS250B 400 1150 44

DIMENSIONS

FEATURES 

ELTAFANTECH’s CBS Series is designed for


ceiling mounting and is suitable for domestics
and commercial applications such as houses, office
premises, bedroom, hotel etc. where require low
noise for small duty and low ceiling height (less than
Dimension in mm
400 mm).
Duct Weight
Construction Model L H W A B I J ØD
size (Kg)
The housing and impeller are made by galvanized CBS200C 650 365 400 478 65 182.5 445 195 Ø 200 21.1
sheet. CBS200D 650 365 400 478 65 182.5 445 195 Ø 200 21.1
Forward inclined impeller wheel with direct driven. CBS250B 740 380 400 548 75 190 445 245 Ø 250 24.1

Motors
Type – squirrel cage induction motors. WIRING DIAGRAM 
Electrical supply – 220-240V, single phase,
50/60Hz Bearings – sealed-for-life, ball
Internal Thermal Protection
Thermal fuse is equipped to cut-out for overload.
How to order
Select the model that meets your air flow
and application requirements from the graph.

450 
Pressure (Pa) 

400 

350 

300 
CBS250B

250 

200 
CBS200C 
CBS200D
150 

100 

50 


0  200  400  600 800 1000 1200 1400 1600  1800  2000

Air Volume (m /h) 

The specifications may be changed. All rights are reserved by ELTAFANTECH ASIA SDN BHD.
FAF-3F-CQ
IMF SERIES
200 250

200
150

10 150

150
0
100 hi
gh

high
100

15
10

0l
0
low

ow
50
50

0 0
0 0.02 0.04 0.06 0.08 0 0.05 0.10 0.15 0.20

200

Technical Data
150
Model
12 Number Free Air FanSpeed Avg. dB(A)
5h IMF... m3/sec rev/sec Watts @ 3m
igh
100 High 0.065 38 27 45
12 100
5 Low 0.057 33 27 41
low
High 0.098 38 34 43
50 125 H
Low 0.082 33 34 38
High 0.163 40 67 48
150
0 Low 0.123 32 67 43
0 0.02 0.04 0.06 0.08 0.10 0.12 High 0.258 41 120 57
200
Low 0.222 38 120 53
High 0.390 40 225 66
250
Low 0.295 30 165 58

250 High 0.612 39 390 69


315
Low 0.486 27 275 61

200
20
0h
igh

150
20
0 lo

100
w

50

0
0 0.05 0.10 0.15 0.20 0.25 0.30

Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication.
Confirmation of dimensions and data will be supplied on request. 3
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Technical Data - Fan Model AP0504AA10/26

Location: FAF-4F-FA Designation:

Performance - Required Actual


Air Flow : 1500 L/s Air Flow: 1503 L/s
Static Pressure : 200 Pa Static Pressure: 201 Pa
Selection Pressure: 200 Pa Total Pressure: 236 Pa
Installation Type: TYPE D
Air Density: 1.204 kg/m³
- Atmos. Temp: 20 °C
- Altitude: 0m
- Humidity: 0.0 %

Fan Data
Catalogue Code: AP0504AA10/26 (AP0504AA10B007)
Description: AP Series In-Line Direct Drive

Diameter: 500 mm Hub: 150 mm


Impeller Type: Axial Pitch: 26°
Blade Material: Aluminium Blades: 10
Speed: 1440 r/min @50 Hz Form: B
Power, Abs: 0.58 kW Peak: 0.58 kW
Input Power: 0.70 kW
Efficiency Total: 61.5% Static: 52.3%
Fan Weight: 39.3 kg

Motor Data (at STP)


Motor Type: Standard
Electrical Supply: 380V 3ph 50Hz
Motor Frame: D80
Motor Power: 0.75kW
FLC/Start: 2.29A / 13.76A
Motor Speed: 4 pole
Motor Efficiency:

Energy Efficiency, NCC/BCA Vol. 1, Table J5.2 compliant


+ 2006 - 2009
+ 2010 - 2012
+ 2013 - 2016
+ 2015 - 2016 Carpark
+ 2019
Sound Data
Spectrum (Hz): 63 125 250 500 1K 2K 4K 8K dBW dB(A) @ 3m
Inlet (dB): 76 78 80 81 82 78 74 60 88 65
Outlet (dB): 76 78 82 81 80 78 74 64 88 64

Sound levels are quoted as in-duct values. dB(A) values are average spherical free-field for comparative use only.

Energy Sustainability Data


Hours Per Day: 10 Annual Electricity Cost ($): 338.0
DaysPerYear: 300 Annual GH Gas (Tonnes): 3.1
CO2 per kWh (kg): 1.467 Annual Carbon Usage (Tonnes): 0.8
Cost per kWh ($): 0.16

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:25 PM
make changes in design or specification to products without notice.
Page 1 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Drawing for Fan Model AP0504AA10/26

Location: FAF-4F-FA Designation:

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:25 PM
make changes in design or specification to products without notice.
Page 2 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Technical Data - Fan Model AP0804AA5/29

Location: EAF-1F-XL.01~02 Designation:

Performance - Required Actual


Air Flow : 6750 L/s Air Flow: 6798 L/s
Static Pressure : 150 Pa Static Pressure: 152 Pa
Selection Pressure: 150 Pa Total Pressure: 262 Pa
Installation Type: TYPE D
Air Density: 1.204 kg/m³
- Atmos. Temp: 20 °C
- Altitude: 0m
- Humidity: 0.0 %

Fan Data
Catalogue Code: AP0804AA5/29 (AP0804AA5B030)
Description: AP Series In-Line Direct Drive

Diameter: 800 mm Hub: 150 mm


Impeller Type: Axial Pitch: 29°
Blade Material: Aluminium Blades: 5
Speed: 1440 r/min @50 Hz Form: B
Power, Abs: 2.45 kW Peak: 2.45 kW
Input Power: 2.79 kW
Efficiency Total: 72.7% Static: 42.2%
Fan Weight: 89.6 kg

Motor Data (at STP)


Motor Type: Standard
Electrical Supply: 380V 3ph 50Hz
Motor Frame: D100L
Motor Power: 3.00kW
FLC/Start: 6.77A / 39.27A
Motor Speed: 4 pole
Motor Efficiency:

Energy Efficiency, NCC/BCA Vol. 1, Table J5.2 compliant


+ 2006 - 2009
+ 2010 - 2012
+ 2013 - 2016
+ 2015 - 2016 Carpark
+ 2019
Sound Data
Spectrum (Hz): 63 125 250 500 1K 2K 4K 8K dBW dB(A) @ 3m
Inlet (dB): 90 90 84 83 82 81 79 68 95 67
Outlet (dB): 85 93 87 84 85 82 80 75 96 69

Sound levels are quoted as in-duct values. dB(A) values are average spherical free-field for comparative use only.

Energy Sustainability Data


Hours Per Day: 10 Annual Electricity Cost ($): 1338.9
DaysPerYear: 300 Annual GH Gas (Tonnes): 12.3
CO2 per kWh (kg): 1.467 Annual Carbon Usage (Tonnes): 3.3
Cost per kWh ($): 0.16

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:25 PM
make changes in design or specification to products without notice.
Page 3 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Drawing for Fan Model AP0804AA5/29

Location: EAF-1F-XL.01~02 Designation:

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:25 PM
make changes in design or specification to products without notice.
Page 4 of 36
EAF-1F-WC, EAF-1F-RT

OUT LET

IN LET
EAF-1F-LK

OUT LET

IN LET
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Technical Data - Fan Model CPD0454F

Location: EAF-1F-TP.01~04 Designation:

Performance - Required Actual


Air Flow : 1500 L/s Air Flow: 1503 L/s
Static Pressure : 29 Pa Static Pressure: 29 Pa
Selection Pressure: 29 Pa Total Pressure: 29 Pa
Installation Type: n/a
Air Density: 1.204 kg/m³
- Atmos. Temp: 20 °C
- Altitude: 0m
- Humidity: 0.0 %

Fan Data
Catalogue Code: CPD0454F
Description: Compact 2000 Series

Diameter: 450 mm
Impeller Type: Axial
Blade Material: -
Speed: 1320 r/min @50 Hz
Power, Abs: 0.21 kW Peak: 0.22 kW
Input Power: -
Efficiency Total: - Static: 20.7%
Fan Weight: 17.0 kg

Motor Data (at STP)


Motor Type:
Electrical Supply: 380V 3ph 50Hz
Motor Frame: E80
Motor Power: 0.37kW
FLC/Start: 1.40A / 4.20A
Motor Speed: 4 pole
Motor Efficiency: -

Energy Efficiency, NCC/BCA Vol. 1, Table J5.2 compliant


+ 2006 - 2009
+ 2010 - 2012

Sound Data
Spectrum (Hz): 63 125 250 500 1K 2K 4K 8K dBW dB(A) @ 3m
Inlet (dB): 74 75 72 71 70 67 64 56 80 54

Sound levels are quoted as in-duct values. dB(A) values are average spherical free-field for comparative use only.

Energy Sustainability Data


Hours Per Day: 10 Annual Electricity Cost ($): 177.6
DaysPerYear: 300 Annual GH Gas (Tonnes): 1.6
CO2 per kWh (kg): 1.467 Annual Carbon Usage (Tonnes): 0.4
Cost per kWh ($): 0.16

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:25 PM
make changes in design or specification to products without notice.
Page 5 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Drawing for Fan Model CPD0454F

Location: EAF-1F-TP.01~04 Designation:

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:25 PM
make changes in design or specification to products without notice.
Page 6 of 36
EAF-1F-BT

HPA Performance Curves & Performance Data


EAF-1F-NVL

HPA Performance Curves & Performance Data


EAF-1F-ND

HPA Performance Curves & Performance Data


EAF-1F-TM

HPA Performance Curves & Performance Data


Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Technical Data - Fan Model AP0804AA5/27

Location: EAF-2F-LN.01~02 Designation:

Performance - Required Actual


Air Flow : 6400 L/s Air Flow: 6429 L/s
Static Pressure : 150 Pa Static Pressure: 151 Pa
Selection Pressure: 150 Pa Total Pressure: 250 Pa
Installation Type: TYPE D
Air Density: 1.204 kg/m³
- Atmos. Temp: 20 °C
- Altitude: 0m
- Humidity: 0.0 %

Fan Data
Catalogue Code: AP0804AA5/27 (AP0804AA5B022)
Description: AP Series In-Line Direct Drive

Diameter: 800 mm Hub: 150 mm


Impeller Type: Axial Pitch: 27°
Blade Material: Aluminium Blades: 5
Speed: 1440 r/min @50 Hz Form: B
Power, Abs: 2.17 kW Peak: 2.17 kW
Input Power: 2.50 kW
Efficiency Total: 74.2% Static: 44.9%
Fan Weight: 68.6 kg

Motor Data (at STP)


Motor Type: Standard
Electrical Supply: 380V 3ph 50Hz
Motor Frame: D100L
Motor Power: 2.20kW
FLC/Start: 4.70A / 25.36A
Motor Speed: 4 pole
Motor Efficiency:

Energy Efficiency, NCC/BCA Vol. 1, Table J5.2 compliant


+ 2006 - 2009
+ 2010 - 2012
+ 2013 - 2016
+ 2015 - 2016 Carpark
+ 2019
Sound Data
Spectrum (Hz): 63 125 250 500 1K 2K 4K 8K dBW dB(A) @ 3m
Inlet (dB): 90 90 84 83 82 81 79 68 95 67
Outlet (dB): 85 93 87 84 85 82 80 75 96 69

Sound levels are quoted as in-duct values. dB(A) values are average spherical free-field for comparative use only.

Energy Sustainability Data


Hours Per Day: 10 Annual Electricity Cost ($): 1201.0
DaysPerYear: 300 Annual GH Gas (Tonnes): 11.0
CO2 per kWh (kg): 1.467 Annual Carbon Usage (Tonnes): 3.0
Cost per kWh ($): 0.16

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:25 PM
make changes in design or specification to products without notice.
Page 7 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Drawing for Fan Model AP0804AA5/27

Location: EAF-2F-LN.01~02 Designation:

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:25 PM
make changes in design or specification to products without notice.
Page 8 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Technical Data - Fan Model CPD0504F

Location: EAF-2F-DT.01~02 Designation:

Performance - Required Actual


Air Flow : 2250 L/s Air Flow: 2261 L/s
Static Pressure : 40 Pa Static Pressure: 40 Pa
Selection Pressure: 40 Pa Total Pressure: 40 Pa
Installation Type: n/a
Air Density: 1.204 kg/m³
- Atmos. Temp: 20 °C
- Altitude: 0m
- Humidity: 0.0 %

Fan Data
Catalogue Code: CPD0504F
Description: Compact 2000 Series

Diameter: 500 mm
Impeller Type: Axial
Blade Material: -
Speed: 1320 r/min @50 Hz
Power, Abs: 0.38 kW Peak: 0.38 kW
Input Power: -
Efficiency Total: - Static: 24.3%
Fan Weight: 24.0 kg

Motor Data (at STP)


Motor Type:
Electrical Supply: 380V 3ph 50Hz
Motor Frame: E90
Motor Power: 0.55kW
FLC/Start: 1.75A / 5.25A
Motor Speed: 4 pole
Motor Efficiency: -

Energy Efficiency, NCC/BCA Vol. 1, Table J5.2 compliant


+ 2006 - 2009
+ 2010 - 2012

Sound Data
Spectrum (Hz): 63 125 250 500 1K 2K 4K 8K dBW dB(A) @ 3m
Inlet (dB): 77 81 78 73 72 72 69 62 85 58

Sound levels are quoted as in-duct values. dB(A) values are average spherical free-field for comparative use only.

Energy Sustainability Data


Hours Per Day: 10 Annual Electricity Cost ($): 264.0
DaysPerYear: 300 Annual GH Gas (Tonnes): 2.4
CO2 per kWh (kg): 1.467 Annual Carbon Usage (Tonnes): 0.7
Cost per kWh ($): 0.16

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:25 PM
make changes in design or specification to products without notice.
Page 9 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Drawing for Fan Model CPD0504F

Location: EAF-2F-DT.01~02 Designation:

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:25 PM
make changes in design or specification to products without notice.
Page 10 of 36
EAF-2F-HLF

HPA Performance Curves & Performance Data


Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Technical Data - Fan Model CPD0504F

Location: EAF-2F-NL Designation:

Performance - Required Actual


Air Flow : 2083 L/s Air Flow: 2099 L/s
Static Pressure : 60 Pa Static Pressure: 61 Pa
Selection Pressure: 60 Pa Total Pressure: 61 Pa
Installation Type: n/a
Air Density: 1.204 kg/m³
- Atmos. Temp: 20 °C
- Altitude: 0m
- Humidity: 0.0 %

Fan Data
Catalogue Code: CPD0504F
Description: Compact 2000 Series

Diameter: 500 mm
Impeller Type: Axial
Blade Material: -
Speed: 1320 r/min @50 Hz
Power, Abs: 0.38 kW Peak: 0.38 kW
Input Power: -
Efficiency Total: - Static: 34.0%
Fan Weight: 24.0 kg

Motor Data (at STP)


Motor Type:
Electrical Supply: 380V 3ph 50Hz
Motor Frame: E90
Motor Power: 0.55kW
FLC/Start: 1.75A / 5.25A
Motor Speed: 4 pole
Motor Efficiency: -

Energy Efficiency, NCC/BCA Vol. 1, Table J5.2 compliant


+ 2006 - 2009
+ 2010 - 2012

Sound Data
Spectrum (Hz): 63 125 250 500 1K 2K 4K 8K dBW dB(A) @ 3m
Inlet (dB): 77 81 78 73 72 72 69 62 85 58

Sound levels are quoted as in-duct values. dB(A) values are average spherical free-field for comparative use only.

Energy Sustainability Data


Hours Per Day: 10 Annual Electricity Cost ($): 264.0
DaysPerYear: 300 Annual GH Gas (Tonnes): 2.4
CO2 per kWh (kg): 1.467 Annual Carbon Usage (Tonnes): 0.7
Cost per kWh ($): 0.16

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:25 PM
make changes in design or specification to products without notice.
Page 11 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Drawing for Fan Model CPD0504F

Location: EAF-2F-NL Designation:

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:25 PM
make changes in design or specification to products without notice.
Page 12 of 36
EAF-2F-PR

HPA Performance Curves & Performance Data


EAF-2F-RT

HPA Performance Curves & Performance Data


EAF-2F-CQ

HPA Performance Curves & Performance Data


Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Technical Data - Fan Model AP0804AA5/27

Location: EAF-3F-LN.01~02 Designation:

Performance - Required Actual


Air Flow : 6400 L/s Air Flow: 6429 L/s
Static Pressure : 150 Pa Static Pressure: 151 Pa
Selection Pressure: 150 Pa Total Pressure: 250 Pa
Installation Type: TYPE D
Air Density: 1.204 kg/m³
- Atmos. Temp: 20 °C
- Altitude: 0m
- Humidity: 0.0 %

Fan Data
Catalogue Code: AP0804AA5/27 (AP0804AA5B022)
Description: AP Series In-Line Direct Drive

Diameter: 800 mm Hub: 150 mm


Impeller Type: Axial Pitch: 27°
Blade Material: Aluminium Blades: 5
Speed: 1440 r/min @50 Hz Form: B
Power, Abs: 2.17 kW Peak: 2.17 kW
Input Power: 2.50 kW
Efficiency Total: 74.2% Static: 44.9%
Fan Weight: 68.6 kg

Motor Data (at STP)


Motor Type: Standard
Electrical Supply: 380V 3ph 50Hz
Motor Frame: D100L
Motor Power: 2.20kW
FLC/Start: 4.70A / 25.36A
Motor Speed: 4 pole
Motor Efficiency:

Energy Efficiency, NCC/BCA Vol. 1, Table J5.2 compliant


+ 2006 - 2009
+ 2010 - 2012
+ 2013 - 2016
+ 2015 - 2016 Carpark
+ 2019
Sound Data
Spectrum (Hz): 63 125 250 500 1K 2K 4K 8K dBW dB(A) @ 3m
Inlet (dB): 90 90 84 83 82 81 79 68 95 67
Outlet (dB): 85 93 87 84 85 82 80 75 96 69

Sound levels are quoted as in-duct values. dB(A) values are average spherical free-field for comparative use only.

Energy Sustainability Data


Hours Per Day: 10 Annual Electricity Cost ($): 1201.0
DaysPerYear: 300 Annual GH Gas (Tonnes): 11.0
CO2 per kWh (kg): 1.467 Annual Carbon Usage (Tonnes): 3.0
Cost per kWh ($): 0.16

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:25 PM
make changes in design or specification to products without notice.
Page 13 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Drawing for Fan Model AP0804AA5/27

Location: EAF-3F-LN.01~02 Designation:

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:25 PM
make changes in design or specification to products without notice.
Page 14 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Technical Data - Fan Model CPD0504F

Location: EAF-3F-DT.01~02 Designation:

Performance - Required Actual


Air Flow : 2250 L/s Air Flow: 2261 L/s
Static Pressure : 40 Pa Static Pressure: 40 Pa
Selection Pressure: 40 Pa Total Pressure: 40 Pa
Installation Type: n/a
Air Density: 1.204 kg/m³
- Atmos. Temp: 20 °C
- Altitude: 0m
- Humidity: 0.0 %

Fan Data
Catalogue Code: CPD0504F
Description: Compact 2000 Series

Diameter: 500 mm
Impeller Type: Axial
Blade Material: -
Speed: 1320 r/min @50 Hz
Power, Abs: 0.38 kW Peak: 0.38 kW
Input Power: -
Efficiency Total: - Static: 24.3%
Fan Weight: 24.0 kg

Motor Data (at STP)


Motor Type:
Electrical Supply: 380V 3ph 50Hz
Motor Frame: E90
Motor Power: 0.55kW
FLC/Start: 1.75A / 5.25A
Motor Speed: 4 pole
Motor Efficiency: -

Energy Efficiency, NCC/BCA Vol. 1, Table J5.2 compliant


+ 2006 - 2009
+ 2010 - 2012

Sound Data
Spectrum (Hz): 63 125 250 500 1K 2K 4K 8K dBW dB(A) @ 3m
Inlet (dB): 77 81 78 73 72 72 69 62 85 58

Sound levels are quoted as in-duct values. dB(A) values are average spherical free-field for comparative use only.

Energy Sustainability Data


Hours Per Day: 10 Annual Electricity Cost ($): 264.0
DaysPerYear: 300 Annual GH Gas (Tonnes): 2.4
CO2 per kWh (kg): 1.467 Annual Carbon Usage (Tonnes): 0.7
Cost per kWh ($): 0.16

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:25 PM
make changes in design or specification to products without notice.
Page 15 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Drawing for Fan Model CPD0504F

Location: EAF-3F-DT.01~02 Designation:

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 16 of 36
EAF-3F-HLF

HPA Performance Curves & Performance Data


Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Technical Data - Fan Model CPD0504F

Location: EAF-3F-NL Designation:

Performance - Required Actual


Air Flow : 2083 L/s Air Flow: 2099 L/s
Static Pressure : 60 Pa Static Pressure: 61 Pa
Selection Pressure: 60 Pa Total Pressure: 61 Pa
Installation Type: n/a
Air Density: 1.204 kg/m³
- Atmos. Temp: 20 °C
- Altitude: 0m
- Humidity: 0.0 %

Fan Data
Catalogue Code: CPD0504F
Description: Compact 2000 Series

Diameter: 500 mm
Impeller Type: Axial
Blade Material: -
Speed: 1320 r/min @50 Hz
Power, Abs: 0.38 kW Peak: 0.38 kW
Input Power: -
Efficiency Total: - Static: 34.0%
Fan Weight: 24.0 kg

Motor Data (at STP)


Motor Type:
Electrical Supply: 380V 3ph 50Hz
Motor Frame: E90
Motor Power: 0.55kW
FLC/Start: 1.75A / 5.25A
Motor Speed: 4 pole
Motor Efficiency: -

Energy Efficiency, NCC/BCA Vol. 1, Table J5.2 compliant


+ 2006 - 2009
+ 2010 - 2012

Sound Data
Spectrum (Hz): 63 125 250 500 1K 2K 4K 8K dBW dB(A) @ 3m
Inlet (dB): 77 81 78 73 72 72 69 62 85 58

Sound levels are quoted as in-duct values. dB(A) values are average spherical free-field for comparative use only.

Energy Sustainability Data


Hours Per Day: 10 Annual Electricity Cost ($): 264.0
DaysPerYear: 300 Annual GH Gas (Tonnes): 2.4
CO2 per kWh (kg): 1.467 Annual Carbon Usage (Tonnes): 0.7
Cost per kWh ($): 0.16

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 17 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Drawing for Fan Model CPD0504F

Location: EAF-3F-NL Designation:

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 18 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Technical Data - Fan Model SCE314HP

Location: EAF-3F-PR Designation:

Performance - Required Actual


Air Flow : 320 L/s Air Flow: 342 L/s
Static Pressure : 100 Pa Static Pressure: 115 Pa
Selection Pressure: 100 Pa Total Pressure: 127 Pa
Installation Type: n/a
Air Density: 1.204 kg/m³
- Atmos. Temp: 20 °C
- Altitude: 0m
- Humidity: 0.0 %

Fan Data
Catalogue Code: SCE314HP
Description: Short Case Series

Diameter: 310 mm
Impeller Type: Axial
Blade Material: -
Speed: 1320 r/min @50 Hz
Power, Abs: - Peak: -
Input Power: -
Efficiency Total: - Static: -
Fan Weight: 8.5 kg

Motor Data (at STP)


Motor Type:
Electrical Supply: 240V 1ph 50Hz
Motor Frame: E63
Motor Power: 0.09kW
FLC/Start: 0.90A / 2.70A
Motor Speed: 4 pole
Motor Efficiency: -

Sound Data
Spectrum (Hz): 63 125 250 500 1K 2K 4K 8K dBW dB(A) @ 3m
Inlet (dB): 65 69 69 62 65 64 57 44 74 49

Sound levels are quoted as in-duct values. dB(A) values are average spherical free-field for comparative use only.

Energy Sustainability Data


Hours Per Day: 10 Annual Electricity Cost ($): 43.2
DaysPerYear: 300 Annual GH Gas (Tonnes): 0.4
CO2 per kWh (kg): 1.467 Annual Carbon Usage (Tonnes): 0.1
Cost per kWh ($): 0.16

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 19 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Drawing for Fan Model SCE314HP

Location: EAF-3F-PR Designation:

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 20 of 36
EAF-3F-LK.01
EAF-3F-LK.02
IMF SERIES
200 250

200
150

10 150

150
0
100 hi
gh

high
100

15
10

0l
0
low

ow
50
50

0 0
0 0.02 0.04 0.06 0.08 0 0.05 0.10 0.15 0.20

200

Technical Data
150
Model
12 Number Free Air FanSpeed Avg. dB(A)
5h IMF... m3/sec rev/sec Watts @ 3m
igh
100 High 0.065 38 27 45
12 100
5 Low 0.057 33 27 41
low
High 0.098 38 34 43
50 125 H
Low 0.082 33 34 38
High 0.163 40 67 48
150
0 Low 0.123 32 67 43
0 0.02 0.04 0.06 0.08 0.10 0.12 High 0.258 41 120 57
200
Low 0.222 38 120 53
High 0.390 40 225 66
250
Low 0.295 30 165 58

250 High 0.612 39 390 69


315
Low 0.486 27 275 61

200
20
0h
igh

150
20
0 lo

100
w

50

0
0 0.05 0.10 0.15 0.20 0.25 0.30

Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication.
Confirmation of dimensions and data will be supplied on request. 3
EAF-3F-CQ
IMF SERIES
200 250

200
150

10 150

150
0
100 hi
gh

high
100

15
10

0l
0
low

ow
50
50

0 0
0 0.02 0.04 0.06 0.08 0 0.05 0.10 0.15 0.20

200

Technical Data
150
Model
12 Number Free Air FanSpeed Avg. dB(A)
5h IMF... m3/sec rev/sec Watts @ 3m
igh
100 High 0.065 38 27 45
12 100
5 Low 0.057 33 27 41
low
High 0.098 38 34 43
50 125 H
Low 0.082 33 34 38
High 0.163 40 67 48
150
0 Low 0.123 32 67 43
0 0.02 0.04 0.06 0.08 0.10 0.12 High 0.258 41 120 57
200
Low 0.222 38 120 53
High 0.390 40 225 66
250
Low 0.295 30 165 58

250 High 0.612 39 390 69


315
Low 0.486 27 275 61

200
20
0h
igh

150
20
0 lo

100
w

50

0
0 0.05 0.10 0.15 0.20 0.25 0.30

Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication.
Confirmation of dimensions and data will be supplied on request. 3
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Technical Data - Fan Model AP0634AA5/22

Location: EAF-4F-LT Designation:

Performance - Required Actual


Air Flow : 2600 L/s Air Flow: 2629 L/s
Static Pressure : 150 Pa Static Pressure: 153 Pa
Selection Pressure: 150 Pa Total Pressure: 196 Pa
Installation Type: TYPE D
Air Density: 1.204 kg/m³
- Atmos. Temp: 20 °C
- Altitude: 0m
- Humidity: 0.0 %

Fan Data
Catalogue Code: AP0634AA5/22 (AP0634AA5B007)
Description: AP Series In-Line Direct Drive

Diameter: 630 mm Hub: 150 mm


Impeller Type: Axial Pitch: 22°
Blade Material: Aluminium Blades: 5
Speed: 1440 r/min @50 Hz Form: B
Power, Abs: 0.69 kW Peak: 0.69 kW
Input Power: 0.84 kW
Efficiency Total: 74.7% Static: 58.4%
Fan Weight: 44.3 kg

Motor Data (at STP)


Motor Type: Standard
Electrical Supply: 380V 3ph 50Hz
Motor Frame: D80
Motor Power: 0.75kW
FLC/Start: 2.29A / 13.76A
Motor Speed: 4 pole
Motor Efficiency:

Energy Efficiency, NCC/BCA Vol. 1, Table J5.2 compliant


+ 2006 - 2009
+ 2010 - 2012
+ 2013 - 2016
+ 2015 - 2016 Carpark
+ 2019
Sound Data
Spectrum (Hz): 63 125 250 500 1K 2K 4K 8K dBW dB(A) @ 3m
Inlet (dB): 88 88 81 83 83 81 78 69 93 67
Outlet (dB): 83 82 79 78 80 79 78 70 89 65

Sound levels are quoted as in-duct values. dB(A) values are average spherical free-field for comparative use only.

Energy Sustainability Data


Hours Per Day: 10 Annual Electricity Cost ($): 402.1
DaysPerYear: 300 Annual GH Gas (Tonnes): 3.7
CO2 per kWh (kg): 1.467 Annual Carbon Usage (Tonnes): 1.0
Cost per kWh ($): 0.16

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 21 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Drawing for Fan Model AP0634AA5/22

Location: EAF-4F-LT Designation:

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 22 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Technical Data - Fan Model BFA0804AA10/26

Location: EAF-4F-ND.01~10 Designation:

Performance - Required Actual


Air Flow : 6668 L/s Air Flow: 6707 L/s
Static Pressure : 150 Pa Static Pressure: 152 Pa
Selection Pressure: 150 Pa Total Pressure: 259 Pa
Installation Type: TYPE D
Air Density: 1.204 kg/m³
- Atmos. Temp: 20 °C
- Altitude: 0m
- Humidity: 0.0 %

Fan Data
Catalogue Code: BFA0804AA10/26 (BFA0804AA10B040)
Description: BFA Series In-Line Bifurcated

Diameter: 800 mm Hub: 150 mm


Impeller Type: Axial Pitch: 26°
Blade Material: Aluminium Blades: 10
Speed: 1440 r/min @50 Hz Form: B
Power, Abs: 3.37 kW Peak: 3.53 kW
Input Power: 3.80 kW
Efficiency Total: 51.6% Static: 30.2%
Fan Weight: 163.3 kg

Motor Data (at STP)


Motor Type: Standard
Electrical Supply: 380V 3ph 50Hz
Motor Frame: D112M
Motor Power: 4.00kW
FLC/Start: 8.96A / 53.73A
Motor Speed: 4 pole
Motor Efficiency:

Energy Efficiency, NCC/BCA Vol. 1, Table J5.2 compliant


+ 2006 - 2009
+ 2013 - 2016
+ 2015 - 2016 Carpark
+ 2019
Sound Data
Spectrum (Hz): 63 125 250 500 1K 2K 4K 8K dBW dB(A) @ 3m
Inlet (dB): 92 83 89 90 90 87 83 76 97 73
Outlet (dB): 89 85 90 89 88 87 84 78 96 73

Sound levels are quoted as in-duct values. dB(A) values are average spherical free-field for comparative use only.

Energy Sustainability Data


Hours Per Day: 10 Annual Electricity Cost ($): 1824.0
DaysPerYear: 300 Annual GH Gas (Tonnes): 16.7
CO2 per kWh (kg): 1.467 Annual Carbon Usage (Tonnes): 4.5
Cost per kWh ($): 0.16

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 23 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Drawing for Fan Model BFA0804AA10/26

Location: EAF-4F-ND.01~10 Designation:

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 24 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Technical Data - Fan Model BFA0804AA10/28

Location: EAF-4F-BTP.01~02 Designation:

Performance - Required Actual


Air Flow : 7000 L/s Air Flow: 7081 L/s
Static Pressure : 150 Pa Static Pressure: 153 Pa
Selection Pressure: 150 Pa Total Pressure: 273 Pa
Installation Type: TYPE D
Air Density: 1.204 kg/m³
- Atmos. Temp: 20 °C
- Altitude: 0m
- Humidity: 0.0 %

Fan Data
Catalogue Code: BFA0804AA10/28 (BFA0804AA10B040)
Description: BFA Series In-Line Bifurcated

Diameter: 800 mm Hub: 150 mm


Impeller Type: Axial Pitch: 28°
Blade Material: Aluminium Blades: 10
Speed: 1440 r/min @50 Hz Form: B
Power, Abs: 3.88 kW Peak: 4.00 kW
Input Power: 4.38 kW
Efficiency Total: 49.8% Static: 28.0%
Fan Weight: 163.3 kg

Motor Data (at STP)


Motor Type: Standard
Electrical Supply: 380V 3ph 50Hz
Motor Frame: D112M
Motor Power: 4.00kW
FLC/Start: 8.96A / 53.73A
Motor Speed: 4 pole
Motor Efficiency:

Energy Efficiency, NCC/BCA Vol. 1, Table J5.2 compliant


+ 2006 - 2009
+ 2013 - 2016
+ 2015 - 2016 Carpark
+ 2019
Sound Data
Spectrum (Hz): 63 125 250 500 1K 2K 4K 8K dBW dB(A) @ 3m
Inlet (dB): 92 83 89 90 90 87 83 76 97 73
Outlet (dB): 89 85 90 89 88 87 84 78 96 73

Sound levels are quoted as in-duct values. dB(A) values are average spherical free-field for comparative use only.

Energy Sustainability Data


Hours Per Day: 10 Annual Electricity Cost ($): 2101.6
DaysPerYear: 300 Annual GH Gas (Tonnes): 19.3
CO2 per kWh (kg): 1.467 Annual Carbon Usage (Tonnes): 5.2
Cost per kWh ($): 0.16

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 25 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Drawing for Fan Model BFA0804AA10/28

Location: EAF-4F-BTP.01~02 Designation:

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 26 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Technical Data - Fan Model AP0564AP5/14

Location: EAF-4F-CIP, EAF-4F-PR Designation:

Performance - Required Actual


Air Flow : 1000 L/s Air Flow: 1016 L/s
Static Pressure : 150 Pa Static Pressure: 155 Pa
Selection Pressure: 150 Pa Total Pressure: 165 Pa
Installation Type: TYPE D
Air Density: 1.204 kg/m³
- Atmos. Temp: 20 °C
- Altitude: 0m
- Humidity: 0.0 %

Fan Data
Catalogue Code: AP0564AP5/14 (AP0564AP5B003)
Description: AP Series In-Line Direct Drive

Diameter: 560 mm Hub: 150 mm


Impeller Type: Axial Pitch: 14°
Blade Material: GRP Blades: 5
Speed: 1440 r/min @50 Hz Form: B
Power, Abs: 0.28 kW Peak: 0.28 kW
Input Power: 0.39 kW
Efficiency Total: 60.3% Static: 56.6%
Fan Weight: 31.3 kg

Motor Data (at STP)


Motor Type: Standard
Electrical Supply: 380V 3ph 50Hz
Motor Frame: D71
Motor Power: 0.37kW
FLC/Start: 1.11A / 5.68A
Motor Speed: 4 pole
Motor Efficiency:

Energy Efficiency, NCC/BCA Vol. 1, Table J5.2 compliant


+ 2006 - 2009
+ 2010 - 2012
+ 2013 - 2016
+ 2015 - 2016 Carpark
+ 2019
Sound Data
Spectrum (Hz): 63 125 250 500 1K 2K 4K 8K dBW dB(A) @ 3m
Inlet (dB): 75 82 79 79 78 74 66 59 86 61
Outlet (dB): 77 79 79 82 76 75 72 68 87 62

Sound levels are quoted as in-duct values. dB(A) values are average spherical free-field for comparative use only.

Energy Sustainability Data


Hours Per Day: 10 Annual Electricity Cost ($): 186.2
DaysPerYear: 300 Annual GH Gas (Tonnes): 1.7
CO2 per kWh (kg): 1.467 Annual Carbon Usage (Tonnes): 0.5
Cost per kWh ($): 0.16

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 27 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Drawing for Fan Model AP0564AP5/14

Location: EAF-4F-CIP, EAF-4F-PR Designation:

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 28 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Technical Data - Fan Model CPD0504F

Location: EAF-4F-UT Designation:

Performance - Required Actual


Air Flow : 2250 L/s Air Flow: 2261 L/s
Static Pressure : 40 Pa Static Pressure: 40 Pa
Selection Pressure: 40 Pa Total Pressure: 40 Pa
Installation Type: n/a
Air Density: 1.204 kg/m³
- Atmos. Temp: 20 °C
- Altitude: 0m
- Humidity: 0.0 %

Fan Data
Catalogue Code: CPD0504F
Description: Compact 2000 Series

Diameter: 500 mm
Impeller Type: Axial
Blade Material: -
Speed: 1320 r/min @50 Hz
Power, Abs: 0.38 kW Peak: 0.38 kW
Input Power: -
Efficiency Total: - Static: 24.3%
Fan Weight: 24.0 kg

Motor Data (at STP)


Motor Type:
Electrical Supply: 380V 3ph 50Hz
Motor Frame: E90
Motor Power: 0.55kW
FLC/Start: 1.75A / 5.25A
Motor Speed: 4 pole
Motor Efficiency: -

Energy Efficiency, NCC/BCA Vol. 1, Table J5.2 compliant


+ 2006 - 2009
+ 2010 - 2012

Sound Data
Spectrum (Hz): 63 125 250 500 1K 2K 4K 8K dBW dB(A) @ 3m
Inlet (dB): 77 81 78 73 72 72 69 62 85 58

Sound levels are quoted as in-duct values. dB(A) values are average spherical free-field for comparative use only.

Energy Sustainability Data


Hours Per Day: 10 Annual Electricity Cost ($): 264.0
DaysPerYear: 300 Annual GH Gas (Tonnes): 2.4
CO2 per kWh (kg): 1.467 Annual Carbon Usage (Tonnes): 0.7
Cost per kWh ($): 0.16

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 29 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Drawing for Fan Model CPD0504F

Location: EAF-4F-UT Designation:

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 30 of 36
EAF-4F-HLF

HPA Performance Curves & Performance Data


Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Technical Data - Fan Model CPD0634F

Location: EAF-4F-NLT Designation:

Performance - Required Actual


Air Flow : 3500 L/s Air Flow: 4033 L/s
Static Pressure : 100 Pa Static Pressure: 133 Pa
Selection Pressure: 100 Pa Total Pressure: 133 Pa
Installation Type: n/a
Air Density: 1.204 kg/m³
- Atmos. Temp: 20 °C
- Altitude: 0m
- Humidity: 0.0 %

Fan Data
Catalogue Code: CPD0634F
Description: Compact 2000 Series

Diameter: 630 mm
Impeller Type: Axial
Blade Material: -
Speed: 1320 r/min @50 Hz
Power, Abs: 0.89 kW Peak: 0.89 kW
Input Power: -
Efficiency Total: - Static: 60.2%
Fan Weight: 34.0 kg

Motor Data (at STP)


Motor Type:
Electrical Supply: 380V 3ph 50Hz
Motor Frame: E90
Motor Power: 1.50kW
FLC/Start: 4.30A / 12.90A
Motor Speed: 4 pole
Motor Efficiency: -

Energy Efficiency, NCC/BCA Vol. 1, Table J5.2 compliant


+ 2006 - 2009
+ 2010 - 2012

Sound Data
Spectrum (Hz): 63 125 250 500 1K 2K 4K 8K dBW dB(A) @ 3m
Inlet (dB): 81 82 86 84 80 78 77 72 91 66

Sound levels are quoted as in-duct values. dB(A) values are average spherical free-field for comparative use only.

Energy Sustainability Data


Hours Per Day: 10 Annual Electricity Cost ($): 720.0
DaysPerYear: 300 Annual GH Gas (Tonnes): 6.6
CO2 per kWh (kg): 1.467 Annual Carbon Usage (Tonnes): 1.8
Cost per kWh ($): 0.16

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 31 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Drawing for Fan Model CPD0634F

Location: EAF-4F-NLT Designation:

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 32 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Technical Data - Fan Model CPD0504F

Location: EAF-4F-NLK Designation:

Performance - Required Actual


Air Flow : 1750 L/s Air Flow: 1811 L/s
Static Pressure : 100 Pa Static Pressure: 107 Pa
Selection Pressure: 100 Pa Total Pressure: 107 Pa
Installation Type: n/a
Air Density: 1.204 kg/m³
- Atmos. Temp: 20 °C
- Altitude: 0m
- Humidity: 0.0 %

Fan Data
Catalogue Code: CPD0504F
Description: Compact 2000 Series

Diameter: 500 mm
Impeller Type: Axial
Blade Material: -
Speed: 1320 r/min @50 Hz
Power, Abs: 0.37 kW Peak: 0.38 kW
Input Power: -
Efficiency Total: - Static: 52.4%
Fan Weight: 24.0 kg

Motor Data (at STP)


Motor Type:
Electrical Supply: 380V 3ph 50Hz
Motor Frame: E90
Motor Power: 0.55kW
FLC/Start: 1.75A / 5.25A
Motor Speed: 4 pole
Motor Efficiency: -

Energy Efficiency, NCC/BCA Vol. 1, Table J5.2 compliant


+ 2006 - 2009
+ 2010 - 2012

Sound Data
Spectrum (Hz): 63 125 250 500 1K 2K 4K 8K dBW dB(A) @ 3m
Inlet (dB): 77 81 78 73 72 72 69 62 85 58

Sound levels are quoted as in-duct values. dB(A) values are average spherical free-field for comparative use only.

Energy Sustainability Data


Hours Per Day: 10 Annual Electricity Cost ($): 264.0
DaysPerYear: 300 Annual GH Gas (Tonnes): 2.4
CO2 per kWh (kg): 1.467 Annual Carbon Usage (Tonnes): 0.7
Cost per kWh ($): 0.16

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 33 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Drawing for Fan Model CPD0504F

Location: EAF-4F-NLK Designation:

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 34 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Technical Data - Fan Model CPD0716/3

Location: EAF-4F-MN Designation:

Performance - Required Actual


Air Flow : 5000 L/s Air Flow: 5045 L/s
Static Pressure : 40 Pa Static Pressure: 41 Pa
Selection Pressure: 40 Pa Total Pressure: 41 Pa
Installation Type: n/a
Air Density: 1.204 kg/m³
- Atmos. Temp: 20 °C
- Altitude: 0m
- Humidity: 0.0 %

Fan Data
Catalogue Code: CPD0716/3
Description: Compact 2000 Series

Diameter: 710 mm
Impeller Type: Axial
Blade Material: -
Speed: 960 r/min @50 Hz
Power, Abs: 1.38 kW Peak: 1.50 kW
Input Power: 1.64 kW
Efficiency Total: - Static: 14.9%
Fan Weight: 61.0 kg

Motor Data (at STP)


Motor Type:
Electrical Supply: 380V 3ph 50Hz
Motor Frame: D100L
Motor Power: 1.50kW
FLC/Start: 3.70A / 20.35A
Motor Speed: 6 pole
Motor Efficiency:

Energy Efficiency, NCC/BCA Vol. 1, Table J5.2 compliant


+ 2006 - 2009
+ 2010 - 2012
+ 2013 - 2016
+ 2015 - 2016 Carpark
+ 2019
Sound Data
Spectrum (Hz): 63 125 250 500 1K 2K 4K 8K dBW dB(A) @ 3m
Inlet (dB): 90 84 85 89 86 79 72 68 95 69

Sound levels are quoted as in-duct values. dB(A) values are average spherical free-field for comparative use only.

Energy Sustainability Data


Hours Per Day: 10 Annual Electricity Cost ($): 786.4
DaysPerYear: 300 Annual GH Gas (Tonnes): 7.2
CO2 per kWh (kg): 1.467 Annual Carbon Usage (Tonnes): 2.0
Cost per kWh ($): 0.16

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 35 of 36
Represented by:
Fantech Pty. Ltd.
A.B.N. 11 005 434 024
42-62 Pound Road West
Dandenong South VIC 3175
Telephone: +61 (03) 9554 7845
Facsimile: +61 (03) 9554 7833
E-mail: info@fantech.com.au
Version 5.6.0 Copyright © 2010-20 Elta Group

Drawing for Fan Model CPD0716/3

Location: EAF-4F-MN Designation:

As part of our continuous improvement processes, Fantech reserves the right to Printed 7/10/2020 2:36:26 PM
make changes in design or specification to products without notice.
Page 36 of 36
EAF-4F-LK.01~02
EAF-4F-PĐ, EAF-4F-BB.01,02 IMF SERIES
200 250

200
150

10 150

150
0
100 hi
gh

high
100

15
10

0l
0
low

ow
50
50

0 0
0 0.02 0.04 0.06 0.08 0 0.05 0.10 0.15 0.20

200

Technical Data
150
Model
12 Number Free Air FanSpeed Avg. dB(A)
5h IMF... m3/sec rev/sec Watts @ 3m
igh
100 High 0.065 38 27 45
12 100
5 Low 0.057 33 27 41
low
High 0.098 38 34 43
50 125 H
Low 0.082 33 34 38
High 0.163 40 67 48
150
0 Low 0.123 32 67 43
0 0.02 0.04 0.06 0.08 0.10 0.12 High 0.258 41 120 57
200
Low 0.222 38 120 53
High 0.390 40 225 66
250
Low 0.295 30 165 58

250 High 0.612 39 390 69


315
Low 0.486 27 275 61

200
20
0h
igh

150
20
0 lo

100
w

50

0
0 0.05 0.10 0.15 0.20 0.25 0.30

Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication.
Confirmation of dimensions and data will be supplied on request. 3
GENERAL
CATALOGUE
FANTECH
CBS SERIES
Small Cabinet Fans

TECHNICAL DATA 

Fan
Power Noise
Model Speed
(W) (dBA @ 3m)
(rpm)
CBS200C 220 1100 38
CBS200D 320 1250 39
CBS250B 400 1150 44

DIMENSIONS

FEATURES 

ELTAFANTECH’s CBS Series is designed for


ceiling mounting and is suitable for domestics
and commercial applications such as houses, office
premises, bedroom, hotel etc. where require low
noise for small duty and low ceiling height (less than
Dimension in mm
400 mm).
Duct Weight
Construction Model L H W A B I J ØD
size (Kg)
The housing and impeller are made by galvanized CBS200C 650 365 400 478 65 182.5 445 195 Ø 200 21.1
sheet. CBS200D 650 365 400 478 65 182.5 445 195 Ø 200 21.1
Forward inclined impeller wheel with direct driven. CBS250B 740 380 400 548 75 190 445 245 Ø 250 24.1

Motors
Type – squirrel cage induction motors. WIRING DIAGRAM 
Electrical supply – 220-240V, single phase,
50/60Hz Bearings – sealed-for-life, ball
Internal Thermal Protection
Thermal fuse is equipped to cut-out for overload.
How to order
Select the model that meets your air flow
and application requirements from the graph.

450 
Pressure (Pa) 

400 

350 

300 
CBS250B

250 

200 
CBS200C 
CBS200D
150 

100 

50 


0  200  400  600 800 1000 1200 1400 1600  1800  2000

Air Volume (m /h) 

The specifications may be changed. All rights are reserved by ELTA FANS MALAYSIA SDN BHD.
IMF
In-line Mixed Flow Fan
IMF SERIES How To Order IMF

IMF - IMF Series


100 to 315 - Fan size

100, 125, 150 & 200 Models


Motor
Type - 2 speed, induction.
Electricity supply - single phase 220-240V 50hz or 220V 60Hz.
Bearings - ball.
Maximum ambient temperature - 50℃.
Class F insulation, IP44 rated.

Internal Thermal Protection


Model 100, 125, 150 and 200 - one shot thermal fuse.

Testing

Description Airflow to ISO 5801:2007


Noise to BS 848 Part 2:1985
The IMF Series are a range of in-line mixed flow fans with
a compact profile. This means they offer excellent pressure
development characteristics. They have been designed specifically
Suggested Specification
for use with rigid or flexible ductwork and can be used for a wide The in-line fans shall be of the IMF Series as supplied by Elta Fans
variety of residential and commercial applications. Available in 6 and be of the models shown. It shall have single-phase induction
sizes to suit 100, 125, 150, 200, 250 and 315mm duct. motor with built in thermal protection and double insulated so no
earth connection is required. Fan housing and impeller are made
Typical Applications from high quality plastic. Motors and impellers are balanced to
ISO 14694 Grade G6.3. All models shall be fully tested to ISO
Exhaust from bathrooms, toilets, laundries, kitchens and other
5801:2007 for Airflow and BS848 Part 2:1985 for noise.
small to medium spaces in houses, hotels and apartments.

Features 250 & 315 Models


• All plastic casing provides a long lasting, robust and
non-corrosive construction. Motor
• Unique mixed flow impeller with fixed blade angles designed to
Type - 2 speed, induction.
overcome the resistances of long ducting systems and creates Electricity supply - single phase 230V 50Hz.
top silent operation. Bearings - ball.
• Units have been constructed from shockproof, heat resistant Maximum ambient temperature - 50℃.
white plastic, with both motor and impeller mounted within the Class F insulation, IP44 rated.
unit casing.
Internal Thermal Protection
• Single-phase induction motor with integral thermal protection,
mounted on sealed for life high quality sleeve bearings. Model 250, 315 - auto-reset integral thermal protection.
• Wired terminal box mounted on the outside of the unit casing,
Testing
for ease of connection
Data accurate to suspension free air test at 3m, contact your local
• Double insulated so no earth connection is required. Available
office for more information.
in Standard and run-on timer versions.
• Suitable for continuous and intermittent running.
• Comes with 2 year warranty.
• Mounting bracket is supplied as standard.

Construction
Fan housing and impeller are made from high quality plastic which
is shock proof and long lasting.
Finished in white RAL 9010 and UV resistant.

Ancillary Equipment

Ceiling Grilles Ducting, Louvres & Grilles


Ref. Section L Ref. Section L

2 Tel +603 7846 0340 Fax +603 7842 1132 Email info@eltafans.asia Website eltafans.asia
IMF SERIES
200 250

200
150

10 150

150
0
100 hi
gh

high
100

15
10

0l
0
low

ow
50
50

0 0
0 0.02 0.04 0.06 0.08 0 0.05 0.10 0.15 0.20

200

Technical Data
150
Model
12 Number Free Air FanSpeed Avg. dB(A)
5h IMF... m3/sec rev/sec Watts @ 3m
igh
100 High 0.065 38 27 45
12 100
5 Low 0.057 33 27 41
low
High 0.098 38 34 43
50 125 H
Low 0.082 33 34 38
High 0.163 40 67 48
150
0 Low 0.123 32 67 43
0 0.02 0.04 0.06 0.08 0.10 0.12 High 0.258 41 120 57
200
Low 0.222 38 120 53
High 0.390 40 225 66
250
Low 0.295 30 165 58

250 High 0.612 39 390 69


315
Low 0.486 27 275 61

200
20
0h
igh

150
20
0 lo

100
w

50

0
0 0.05 0.10 0.15 0.20 0.25 0.30

Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication.
Confirmation of dimensions and data will be supplied on request. 3
Dimensions

Model
100, 125, 150 & 200
Number Dimensions, mm
1800 IMF... A B CØ D E F G H I
100 140 296 97 154 - 179 202 217 190
C D H I
125 140 256 124 154 - 179 202 215 190
150 182 298 147 170 - 194 223 236 211
200 120 314 197 236 - 254 272 271 236
250 150 384 246 261 150 310 286 - -
A F
B G 315 181 446 311 325 178 386 357 - -

250 & 315



A E
B F

Elta Fans Malaysia Sdn Bhd


Tel +603 7846 0340
Fax +603 7842 1132
Email info@eltafans.asia

No. 147, Jalan TUDM Kampung


Baru Subang, 40150 Shah Alam,
Selangor West Malaysia, Malaysia

eltafans.asia

IMF-08-2019 Issue A

FS 676456
Duct Mounted.qxd 4/03/2008 3:55 PM Page 31

ADJUSTABLE PITCH AXIAL FLOW FANS

FEATURES ANCILLARY EQUIPMENT


The AP Series of duct mounted adjustable pitch axial flow fans is
available in the following variants:-
O
AP Series - direct-drive
O
APV Series - direct-drive vertical mounted
O
APS Series - direct-drive smoke-spill MF - Matching flange
C..P - Circular silencers Vibration isolators
O
APB Series - belt-drive Ref. H-4/8 Ref. I-1 Ref. J-4
O
BFA Series - bifurcated, direct-drive
Construction
The casings are of mild steel, hot-dip galvanised after
manufacture. Impeller blades shall have an aerofoil section and
be pressure die-cast aluminium, injection-moulded glass-
reinforced plastic or nylon. Anti-static blades for hazardous F - Mounting foot IC - Inlet cone FG - Finger guards
applications up to 1400mm diameter, are also available. Ref. J-6 Ref. J-7 Ref. J-9

Motors
Type - squirrel cage induction motor which can be selected to
suit virtually any specification.
Electricity supply - single or three-phase to suit a wide range of
voltages and frequencies. Inverter
Bearings - ball. Ref. L-9
See pages N-3/4 for details on motors.
Motors to meet Australian Ex e, Ex d, Ex n or D.I.P. Standards
can be fitted. SMOKE-SPILL APPLICATIONS
Internal Thermal Protection The APS Series has been tested to meet the air performance
Can be provided as an optional extra. and high temperature test requirements of Standards
AS/NZS1668.1:1998 and AS/NZS4429:1999; both tests are
Testing mandatory.
Air flow testing:- For advice on smoke-spill wiring requirements refer to the above
315-1000mm diameter - BS848:Part 1, 1980 Standards.
1250-2000mm diameter - ISO5801:1997
See page C-7 for details of the smoke-spill range available.
Noise testing all sizes to BS848:Part 2, 1985

Special Features
Suitable for a wide range of applications, ranging from handling
HOW TO ORDER
ambient filtered air to hot, toxic and noxious gases. -
Hazardous fume applications
AP Series fans can be made to accommodate requirements for AP - direct drive
APV - vertical
corrosive fume and explosion risk applications. Special coatings APS - smoke spill
and alternative materials, such as stainless steel, are available APB - belt drive
as well as increased safety motors and anti-static impellers. Our BFA - bifurcated
sales engineers are able to assist with requirements, which must Fan diameter in cm
be specified at time of quotation. Fan speed, no. of poles
Hub diameter code
Wiring Diagram A =150 D= 400
See pages M-6/7, diagrams DD 1, 2, 3, 7, 8, 9. B = 250 F = 550
C = 350 G = 255
Weights Aluminium blades, A
See pages C-112/113 to determine unit weights. GRP, P
Nylon, N
Dimensions Antistatic blades, E
See pages C-110/111 for dimensions. No. of blades
Blade pitch angle, deg.

© FANTECH 2008 DUCT MOUNTED FANS B-31


Duct Mounted.qxd 4/03/2008 3:55 PM Page 32

AXIAL FLOW FANS QUICK SELECTION GRAPHS


The quick selection curves on these pages are designed to SUGGESTED SPECIFICATION
assist users to determine the fan diameter, speed, approximate
noise level and dimensions of the fan to meet the specified duty. The axial fans shall be of the AP/APV/APS/APB/BFA design(s)
as manufactured by Fantech Pty. Ltd..
Refer to Section C for detailed selection information. All performances shall be based upon BS848:Part 1, 1980 or
Detail including the number of blades and power absorbed is ISO5801:1997 and BS848:Part 2, 1985.
shown on pages C-11/109 or is available from the Fantech CD
program. Casings shall be hot-dip galvanised mild steel. Impellers shall
be of aerofoil section glass-reinforced plastic (GRP), nylon, or
B Pages C-2/8 provide detailed information on these products.
An example of how to use the curves is shown on page C-9.
aluminium; GRP is standard where selection permits.

The dimensions for all fans are on pages C-110/111.


Weights can be determined from details on pages C-112/113.

Model Numbers
O
AP - direct-driven; 315 to 2000mm diameter
O
APV - direct-driven; 315 to 2000mm diameter
O
APS - direct-driven; 315 to 2000mm diameter
O
APB - belt driven; 315 to 2000mm diameter
O
BFA - bifurcated; 400 to 1250mm diameter

2 Pole
3000 48 rev/sec
2000
95
91
1000 88
80 92
80 92
pSF - Fan Static Pressure, Pa

600 90
71 75
78 0802
400 65 0712
70 0632
0502 0562
200 0312 65 0402
em
st s
Sy ine
L
100

60 68 71 80 78 94 95 91

0.2 0.4 0.6 1.0 2.0 4.0 6.0 10.0 20.0 30.0
qV - Volume Flow, m /s3
dB(A) @ 3m: Inlet Side =

4 Pole
2000 24 rev/sec
92
87
1000
90
600 83 85
pSF - Fan Static Pressure, Pa

Lin stem

69 78
400
es

75
Sy

73 69
68 71
68
200 65 1254 1404
64 0804 1004
63 0634 0714
0564
56 52 0504
100 51 49 0404
0314 49 55 64 67 71 73 73 78 88 93
60
0.2 0.4 0.6 1.0 2.0 4.0 6.0 10.0 20.0 40.0 60.0
qV - Volume Flow, m /s
3
dB(A) @ 3m: Inlet Side =

B-32 DUCT MOUNTED FANS © FANTECH 2008


Duct Mounted.qxd 4/03/2008 3:55 PM Page 33

AXIAL FLOW FANS QUICK SELECTION GRAPHS

6 Pole
1000 96 16 rev/sec
86 90
82
600
78 95
400 88
81
Lin tem

80
pSF - Fan Static Pressure, Pa

B
es
s

72 75
Sy

200 63 67

66 59 1606 1806 2006


62 1406
63 1256
59 58 1006
100 54 0806
0716
56 56 0636
0566
60 48 0506
0406 45 51 57 61 67 65 70 76 81 83 88 92
0316 40
40
0.2 0.4 0.6 1.0 2.0 4.0 6.0 10.0 20.0 40.0 60.0 100.0
qV - Volume Flow, m /s
3
dB(A) @ 3m: Inlet Side =

8 Pole
600 12 rev/sec
86
400 78 82
74 77
72 74
71
Lin tem
pSF - Fan Static Pressure, Pa

71
200
es
s
Sy

63 61

1258 1408 1608 1808 2008


57 60
100 1008
58 58 0808
56 51 0718
60 0638
51 59 62 62 71 75 75 79 83
40
0.6 1.0 2.0 4.0 6.0 10.0 20.0 40.0 60.0 100.0
qV - Volume Flow, m /s 3
dB(A) @ 3m: Inlet Side =

10 Pole
400 10 rev/sec
81
78
78
72 75
70
200
pSF - Fan Static Pressure, Pa

em 1601 1801 2001


st s
Sy ine
100 L

60 71 75 78

50
6.0 10.0 20.0 40.0 60.0 80.0
qV - Volume Flow, m /s
3
dB(A) @ 3m: Inlet Side =

© FANTECH 2008 DUCT MOUNTED FANS B-33


CBB SERIES
IN LET

OUT LET
OUT LET

IN LET
OUT LET

IN LET
OUT LET

IN LET
WIRING DIAGRAMS FOR CBB FANS

N (Blue)

Lo (White)

Yellow / Green

Low Speed

N (Blue)

Med (Grey)

Yellow / Green

Medium Speed

N (Blue)

Hi (Brown)

Yellow / Green

High Speed
Wall Window & Ceiling.qxd 4/03/2008 3:20 PM Page 12

CPD, CPE SERIES


COMPACT 2000 SERIES

FEATURES ANCILLARY EQUIPMENT


The Compact 2000 Series of square plate axial fans can be
mounted in any position. They are a high quality product suitable
for a wide range of applications.

Construction
Metal construction with a high quality polyester epoxy finish as DG - Finger Guards WSK - Backdraft shutter Speed controllers
standard. Impellers have GRP blades; nylon and aluminium Ref. J-9 Ref. K-3 Ref. L-1

blades are an optional extra.

Motors
Type - squirrel cage induction motor.
Sizes 710 and 800 can be fitted with motors to suit virtually any SD - Star/Delta switch VZ - Run-on timer
specification. Ref. L-9 Ref. L-10
Electricity supply - 220-240V, single or 415V, three-phase, 50Hz.
Bearings - sealed-for-life, ball.
Speed-controllable using electronic or auto-transformer.
Weatherproof to IP55.
Operating temperature range -20ºC to +70ºC. Maximum SUGGESTED SPECIFICATION
ambient when being speed-controlled is 40ºC.
See pages N-3/4 for details of these motors. The Compact 2000 Series of plate mounted axial fans shall be
as supplied by Fantech Pty. Ltd.
Some fans are fitted with 2-speed star/delta motors.
The axial impellers shall be of GRP and fitted with TECH-LOCK®
Internal Thermal Protection bushes for easy removal and fitting.
Manual-reset protection is supplied as standard on models from Square plates shall be of metal construction with a polyester
025 to 063; they are an optional extra on the 071 and 80 models. epoxy finish.
All models shall be fully tested to BS848:Part 1, 1980 for air flow
Testing to BS848:Part 2, 1985 for noise.
Air flow tests to BS848:Part 1, 1980.
Noise tests to BS848:Part 2, 1985.

Special Features
Can be mounted at any angle.
HOW TO ORDER
A full guard is fitted as standard to 025. to 063. units only.
Guards on 071. to 080. units are an optional extra.
A flying lead with junction box and Ø20 flexible conduit is fitted
as standard with the 025. to 063. units only.
Derate the performance by at least 25% if air flow direction is
reverse to standard

Wiring Diagram
See page M-6/7, diagram DD 1, 4, 5, 6, 9.

A-12 WALL, WINDOW & CEILING MOUNTED FANS © FANTECH 2008


Wall Window & Ceiling.qxd 4/03/2008 3:20 PM Page 13

COMPACT 2000 SERIES


DIMENSIONS 4 Pole
400 24 rev/sec
C E F HP
G
200 A
4 x HØ

Lin stem
Holes

es
100

pSF - Fan Static Pressure, Pa

Sy

564 HP
504 HP
D AØ BØ

454 HP
404 HP
354 HP
314 H
60

40

P
Air Flow
Full guard ‘F’ fitted as standard NOTE: Flying lead fitted as standard
up to size 063. with Ø20 flexible conduit 20
49 52 54 57 62 63
App. App.
Model Dimensions, mm wt. vol. 10
0.2 0.4 0.6 1.0 2.0 4.0
CP.. AØ BØ C† D† E F G HØ kg m3
qV - Volume Flow, m /s 3
dB(A) @ 3m: Outlet Side =
025. 263 285 370 320 98 74 15 6 5.5 0.03
031. 325 330 430 380 95 85 10 9 10 0.04
035. 360 370 485 435 95 85 10 9 10 0.05 4 Pole
040. 410 420 540 490 95 95 12 9 15 0.07 400 24 rev/sec
045. 460 470 575 535 95 95 12 11 17 0.08
050. 510 535 655 615 145 100 15 11 24 0.13 200
Lin tem
pSF - Fan Static Pressure, Pa

714/3
056. 575 600 725 670 145 100 15 11 27 0.16

714/214/1
es
Sys

7
063. 645 670 805 750 140 105 20 11 34 0.22 100

804/1
634
071. 716 760 850 810 * 98 22 14.5 37/61 0.40

564
60

504
080. 809 860 970 910 * 133 22 14.5 0.63

804/2
50/99
454
404
354

40
314

Motor
254

73
Frame Size *E
71
D90S 222 20
68
D90L 238
42 45 49 52 54 58 62 66 78 79
D100L 304 10
D112M 346
0.2 0.4 0.6 1.0 2.0 4.0 6.0 10.0 20.0

D132S 367 qV - Volume Flow, m /s 3


dB(A) @ 3m: Outlet Side =

D132M 405
Note:-
6 Pole
The selections shown here are based on fixed pitch impellers. 150 16 rev/sec
If units with different performances than those shown here are
required, refer to the SQ Series on pages A-15/17.
100
716/3

806/1
806/2
Lin tem

716/
es
Sys

60
2
pSF - Fan Static Pressure, Pa

40
716/1
636
566
506
456
406

20
63
69
44 46 51 57 60 63 67 71
10
0.4 0.6 1.0 2.0 4.0 6.0 10.0
qV - Volume Flow, m /s 3
dB(A) @ 3m: Outlet Side =

© FANTECH 2008 WALL, WINDOW & CEILING MOUNTED FANS A-13


Wall Window & Ceiling.qxd 4/03/2008 3:20 PM Page 14

COMPACT 2000 SERIES


TECHNICAL DATA & NOISE LEVELS
Nom. Avg. Max. In-duct Sound Power Levels
Model Speed dB(A) CPE.. 1 ph. CPD.. 3 ph. amb LwdB re 1pW
CP.. r/s @ 3m kW Amps* Frame** kW Amps* °C 63 125 250 500 1k 2k 4k 8k
A 0254 23 42 0.09 0.90 - 0.12 0.50 70∆ 66 64 61 60 56 55 51 45
0314 23 45 0.09 0.90 - 0.12 0.50 70∆ 69 67 63 63 60 57 53 49
0314HP 23 49 0.09 0.90 - 0.12 0.50 70 ∆
65 69 69 62 65 64 57 44
0354 23 49 0.09 0.90 - 0.12 0.50 70∆ 71 70 65 67 66 59 55 54
0354HP 23 52 0.09 0.90 - 0.12 0.50 70 ∆
68 72 72 65 68 67 60 47
0404 23 52 0.25 1.80 - 0.37 1.40 70 ∆
71 72 68 70 69 64 61 56
0404HP 23 54 0.25 1.80 - 0.37 1.40 70∆ 68 70 70 69 71 69 61 52
0406 15 44 0.12 1.05 - 0.16 0.93 70 ∆
67 63 66 63 61 53 48 43
0454 23 54 0.25 1.80 - 0.37 1.40 70∆ 74 75 72 71 70 67 64 56
0454HP 23 57 0.25 1.80 - 0.37 1.40 70 ∆
71 73 73 72 74 72 64 55
0456 14 46 0.12 1.05 - 0.18 0.68 70∆ 66 64 66 64 61 58 54 45
0504 23 58 0.55 3.60 - 0.55 1.75 70 ∆
77 81 78 73 72 72 69 62
0504HP 23 62 0.55 3.60 - 0.55 1.75 70∆ 73 74 74 76 79 76 74 62
0506 14 51 0.18 1.55 - 0.25 0.94 70 ∆
72 67 69 68 69 63 57 51
0564 23 62 0.75 4.90 - 0.75 2.00 70∆ 81 83 80 79 78 75 73 67
0564HP 23 63 0.75 4.90 - 0.75 2.00 70 ∆
76 74 77 78 80 77 75 66
0566 14 57 0.25 2.20 - 0.25 0.94 70∆ 76 73 76 76 73 71 60 56
0634 23 66 - - - 1.50 4.30 70 ∆
81 82 86 84 80 78 77 72
0636 14 60 0.55 6.00 - 0.55 2.00 70 ∆
83 80 78 77 76 73 68 59
0714/1 23 68 - - D100La 2.20 4.60 40 90 80 84 83 83 82 81 76
0714/2 23 71 - - D100Lb 3.00 6.20 40 87 84 87 87 86 84 84 75
0714/3 23 73 - - D112M 4.00 8.00 40 91 90 93 91 87 86 83 77
0716/1 16 63 - - D90S 0.75 2.20 40 85 79 77 83 78 73 71 63
0716/2 16 63 - - D90L 1.10 3.00 40 84 81 82 83 78 73 72 61
0716/3 16 69 - - D100L 1.50 3.30 40 90 84 85 89 86 79 72 68
0804/1 23 78 - - D132S 5.50 10.50 40 90 83 89 92 95 93 88 81
0804/2 23 79 - - D132M 7.50 15.80 40 96 93 94 95 94 93 89 82
0806/1 16 67 - - D100L 1.50 3.30 40 90 86 85 87 82 77 73 65
0806/2 16 71 - - D132S 3.00 6.30 40 92 84 88 89 87 84 78 69
* Amperages shown are a guide only, refer to our Sales Department for accurate figures at time of order.
** Use inverter controllers for variable speed.
Electrical data in bold type refers to fans that are fitted with 2-speed star/delta motors as standard. High speed data shown.

Maximum ambient is 50°C when being speed controlled.
The In-duct Sound Power Levels are for the Outlet Side of the fan; Inlet Side values are generally 1-2 dB lower. The levels are based on the fans operating at approximately
50% of peak pressure.

A-14 WALL, WINDOW & CEILING MOUNTED FANS © FANTECH 2008


HPA SERIES
ì
ì
HPA Performance Curves & Performance Data
HPA Performance Curves & Performance Data
Duct Mounted.qxd 4/03/2008 3:54 PM Page 14

SCD, SCE SERIES


SHORT CASE AXIAL SERIES

4 Pole
300 24 rev/sec

200

Lin tem
es
100

s
Sy

634
B

pSF - Fan Static Pressure, Pa

564
504
454
60

404
354
314
40

254
FEATURES 20

39 42 45 47 50 55 58 65
The Short Case Axial Series of fans is designed for duct
mounting. The fans are suitable for a wide range of applications. 10
0.2 0.4 0.6 1.0 2.0 4.0 6.0 8.0

Construction qV - Volume Flow, m /s 3


dB(A) @ 3m: Outlet Side =
Galvanised steel coated with polyester epoxy finish as standard.
Impellers are of injection moulded glass-reinforced plastic.
Aluminium blades are an optional extra. 4 Pole
24 rev/sec
300
Motors HP
Type - squirrel cage induction motor. 200
Electricity supply - 220-240V single or 415V three-phase, 50Hz.
Bearings - sealed-for-life ball.
Speed-controllable using electronic controllers or auto
Lin tem

100
transformers.

564 HP
es

504 HP
s
pSF - Fan Static Pressure, Pa

Sy

454 HP
Enclosure IP55.

404 HP
See pages N-3/4 for details of these motors. 60
354 HP
314 HP

40
Internal Thermal Protection
Manual reset protection is supplied as standard in these units.

Testing 20
Air flow tests to BS848:Part 1, 1980. 49 52 54 57 62 63
Noise tests BS848:Part 2, 1985.
10
0.2 0.4 0.6 1.0 2.0 4.0 6.0
Special Features
Can be mounted at any angle. qV - Volume Flow, m3/s dB(A) @ 3m: Outlet Side =

Can operate in ambients from -20°C up to 70°C, or maximum of


50°C when being speed controlled.
Most three-phase external rotor motors are 2-speed star/delta
design.
An electrical junction box is fitted as standard.

Wiring Diagram
See pages M-6/7, diagram DD 4, 5, 6, 9.

SUGGESTED SPECIFICATION HOW TO ORDER


The Short Case Axial Series of fans shall be as supplied by
SC
Fantech Pty Ltd. The axial impellers shall be of GRP and driven
by single-phase speed-controllable or three-phase motors with
SC - Short Case
integral thermal protection.
Cases shall be of galvanised construction with a polyester epoxy D - 3 phase
E - 1 phase
finish.
All models shall be fully tested to BS848:Part 1, 1980 for air flow Fan diameter in cm
and to BS848:Part 2, 1985 for noise. Fan speed no. of poles
HP - High Performance model

B-14 DUCT MOUNTED FANS © FANTECH 2008


Duct Mounted.qxd 4/03/2008 3:54 PM Page 15

SHORT CASE AXIAL SERIES


TECHNICAL DATA ANCILLARY EQUIPMENT
Model Fan. Avg. App.
SCD.. Speed dB(A) SCE.. 1 ph. SCD.. 3 ph. wt
SCE.. r/s @ 3m kW Amps kW Amps kg.
254 23 39 0.09 0.90 0.12 0.50 8.0
314 23 42 0.09 0.90 0.12 0.50 8.5
CC - Circular Attenuator Vibration Isolators CMF - Matching Flange
314HP 23 49 0.09 0.90 0.12 0.50 8.5
354 23 45 0.09 0.90 0.12 0.50 9.0
Ref. H-3 Ref. I-1 Ref. J-4
B
354HP 23 52 0.09 0.90 0.12 0.50 9.0
404 23 47 0.25 1.80 0.37 1.40 12.0
404HP 23 54 0.25 1.80 0.37 1.40 12.0
454 23 50 0.25 1.80 0.37 1.40 14.0 CFT - Mounting Feet CIC - Inlet Cone DG - Finger Guards
454HP 23 57 0.25 1.80 0.37 1.40 14.0 Ref. J-6 Ref. J-7 Ref. J-9

504 23 55 0.55 3.60 0.55 1.75 20.0


504HP 23 62 0.55 3.60 0.55 1.75 20.0
564 23 58 0.75 4.90 † 0.75 2.00 22.0
564HP 23 63 0.75 4.90 † 0.75 2.00 22.0
634 23 65 - - 1.50 4.30 24.0 Shutters VA - Speed controller TC3 - Speed controller
Ref. K-1 Ref. L-6 Ref. L-8
Electrical data in bold type denotes 2-speed star/delta motors are fitted.
Amperages shown are a guide only. Refer to our Sales Department for accurate
figures at time of order.
† Use auto transformer control only.

SD - Star/Delta switch VZ - Run-on timer


Ref. L-9 Ref. L-10

NOISE DATA DIMENSIONS


Model In-duct Sound Power Levels AØ
SCD.. LwdB re 1pW
SCE.. 63 125 250 500 1k 2k 4k 8k BØ C
254 63 61 57 57 55 52 48 43
314 64 63 60 60 58 55 51 46
314HP 65 69 69 62 65 64 57 44
354 67 66 63 63 61 58 54 49
354HP 68 72 72 65 68 67 60 47
404 69 68 65 64 64 60 56 50
404HP 68 70 70 69 71 69 61 52
454 72 71 68 67 67 63 59 53
454HP 71 73 73 72 74 72 64 55
504 75 75 71 72 71 68 62 57
D × EØ Holes
504HP 73 74 74 76 79 76 74 62 on F PCD
564 79 79 75 74 75 71 68 61 Model Dimensions, mm
564HP 76 74 77 78 80 77 75 66 SC.. AØ BØ* C D EØ F
634 85 77 81 82 80 79 76 70 254 305 250 180 8 7.0 285
The In-Duct Sound Power Levels are for the Outlet Side of the fan. Inlet Side levels 314 382 315 180 8 9.5 356
are generally 1-2dB lower. The levels are based on the fans operating at 354 421 350 180 8 9.5 395
approximately 50% of peak pressure.
404 466 400 190 12 9.5 438
454 515 450 190 12 9.5 487
504 567 500 250 12 9.5 541
564 636 560 250 16 11.5 605
634 709 630 250 16 11.5 674
* Dimension B is internal for the casing.

© FANTECH 2008 DUCT MOUNTED FANS B-15