Sie sind auf Seite 1von 17

4-1312

4-1312

Application Engineering Bulletin


AE-1312 (Replaces AE -1280, 1293 & 1300) Revised April, 2001

APPLICATION GUIDELINES FOR 1.5 TO 6.75 TON


ZR16K4 to ZR81KC
COPELAND SCROLLTM COMPRESSORS

Introduction sure exceeds 375 to 450 psid (26 – 32 kg/cm2). When


the valve opens, hot discharge gas is routed back into
The ZR*KC, ZR*KL, ZR*K3, & ZR*K4 Copeland Scroll the area of the motor protector to cause a trip. During
compressors include a wide range of capacities, elec- developmental blocked fan testing, it is sometimes
trical options, and features. Typical model numbers are noted that the valve opens, but the compressor does
ZR24K3-PFV and ZR81KC-TF5. This bulletin de- not shut off while the discharge pressure continues to
scribes the operating characteristics, design features, climb. This condition is normally caused by floodback
and application requirements for these models. For and may be corrected by using a more restrictive
additional information, please refer to the online prod- expansion device or reducing the refrigerant charge.
uct information accessible from the Copeland website
at www.copeland-corp.com. Operating principles of Internal Temperature Protection: The Therm-
the Copeland Scroll are described in Figure 7 at the end O-Disc® or TOD is a temperature-sensitive snap disc
of this Application Engineering Bulletin. device located at the scroll discharge port. It is de-
signed to open and route excessively hot discharge gas
The ZR*K3 and K4 are models designed for 11+ SEER back to the motor protector. During a situation such as
A/C and heat pump usage ranging in size from 16,000 loss of charge, the compressor will be protected for
to 61,000 Btu/hr (4.7 to 17.9 kw). some time while it trips on the protector. However, as
refrigerant leaks out, the mass flow and the amperage
The ZR*KC are models designed for 10+ SEER A/C draw are reduced and the scrolls will start to overheat.
and heat pump usage ranging in size from 16,000 to Normally, during air conditioning operation the problem
81,000 Btu/hr (4.7 to 23.7 kw). is detected because of rising indoor temperatures
before damage is done. This may not be the case
The ZR*KL are identical to the ZR*KC models with the
during heat pump operation since backup heat will
exception of thicker shells to further reduce sound.
make up the deficit. A low pressure control is recom-
They range in size from 24,000 to 34,000 Btu/hr (7.0 to
mended for loss of charge protection in heat pumps for
10.0 kw).
the highest level of system protection. A cut out setting
The models include a number of features outlined in the no lower than 25 psig (2 kg/cm2) for air conditioning and
matrix below: 7 psig (0.5 kg/cm2) for heat pumps is recommended.
The low pressure cut-out, if installed in the suction line
Quiet Discharge to the compressor, can provide additional protection
Shut Check Motor against a TXV failed in the closed position, outdoor fan
IPR TOD Down Valve Protector failure in heating, a closed liquid line or suction line
ZR16-24KC/4 None X X X X service valve, or a blocked liquid line screen, filter,
ZR16-61K3 X X X X X orifice, or TXV. All of these can starve the compressor
ZR26-81KC X X X X X for refrigerant and result in compressor failure. The low
pressure cut-out should have a manual reset feature for
IPR Valve-Internal Pressure Relief Valve: The internal the highest level of system protection. If a compressor
pressure relief valve is located between the high side is allowed to cycle after a fault is detected, there is a
and the low side of the compressor. It is designed to high probability that the compressor will be damaged
open when the discharge-to-suction differential pres- and the system contaminated with debris from the

© 2001 Copeland Corporation 1


Printed in U.S.A.
4-1312
failed compressor and decomposed oil. If current Application Considerations
monitoring to the compressor is available, the system
controller can take advantage of the compressor TOD The Copeland Scroll compressor has a number of
and internal protector operation. The controller can application characteristics that are different from those
lock out the compressor if current draw is not coincident of the traditional reciprocating compressor. These are
with the contactor energizing, implying that the com- detailed below.
pressor has shut off on its internal protector. This will
Accumulators
prevent unnecessary compressor cycling on a fault
condition until corrective action can be taken. Due to the Copeland Scroll’s inherent ability to handle
liquid refrigerant in flooded start and defrost cycle
Quiet Shut down: All scrolls in this size range have
operation, no accumulator is required for durability
one of two types of “quiet” shutdown solutions. Scrolls
below system charge levels listed in Table 5. However,
up to four tons use a cam-type device that separates
large volumes of liquid refrigerant which repeatedly
the scrolls as they run backward during shutdown when
flood back to the compressor during normal off cycles
high-pressure gas equalizes from the high side of the
or excessive liquid refrigerant floodback during steady
compressor to the low side. The larger scrolls use a
operation can dilute the oil. As a result, the bearings
different type of cam that stops backward rotation
are inadequately lubricated, and wear may occur. To
during shut down. Both of these quiet shut down
test for these conditions, see the section entitled
solutions allow the scroll compressor to restart imme-
Excessive Liquid Floodback Tests at the end of this
diately even if the system is not equalized. Models
bulletin. The accumlator oil return orifice should be
ZR68KC through ZR81KC will continue to be built with
from .040 to .055 inches (1 – 1.4 mm) in diameter
the fluid brake design, so a momentary reverse rotation
depending on compressor size and compressor
sound will be heard from these compressors. Devel-
floodback results. A large-area protective screen no
opment testing should include a review of the shutoff
finer than 30 x 30 mesh (0.6 mm openings) is required
sound for acceptability in a particular system. No time
to protect this small orifice from plugging. Tests have
delay is required with any of these compressors.
shown that a small screen with a fine mesh can easily
Discharge Check Valve: A low mass, disc-type check become plugged causing oil starvation to the compres-
valve in the discharge fitting of the compressor pre- sor bearings.
vents the high side, high pressure discharge gas from
Screens
flowing rapidly back through the compressor. This
check valve was not designed to be used with recycling The use of screens finer than 30 x 30 mesh (0.6mm
pumpdown because it is not entirely leak-proof. openings) anywhere in the system is not recom-
mended. Field experience has shown that finer mesh
Motor Protector: Conventional internal line break
screens used to protect thermal expansion valves,
motor protection is provided. The protector opens the
capillary tubes, or accumulators can become tempo-
common connection of a single-phase motor. It opens
rarily or permanently plugged with normal system
the center of the Y connection on three-phase motors.
debris and block the flow of either oil or refrigerant to
The three-phase protector provides primary single-
the compressor. Such blockage can result in compres-
phase protection. Both types of protectors react to
sor failure.
current and to motor winding temperature.
Crankcase Heat - Single Phase
Field Replacement of Single Phase ZR*K1 or ZR*K2
With Equivalent Capacity ZR*K3/K4 or KC Scroll No crankcase heater is required for single-phase
Compressors compressors, but when the system charge exceeds
the recommended limit, the compressor may fill with
The discharge and the suction fitting sizes and mount-
refrigerant under certain circumstances and configura-
ing foot pattern of the new models are identical to the
tions. This may cause excessive clearing noise, or the
ZR*K1 or ZR*K2. Tubing location is identical in most
compressor may lock up and trip on protector several
cases for easy field replacement. The ZR*K1 has an
times before starting. A crankcase heater is strongly
external top cap thermostat to limit discharge tempera-
recommended for systems containing more than 120%
ture. This feature has been moved to the inside of the
of the refrigerant charge limit listed in Table 5. A
new scrolls. When replacing the ZR*K1, the top cap
crankcase heater will lower start-up sound under these
thermostat wires must be removed and the control
conditions since the compressor will no longer be
circuit wires spliced together. See section on Com-
required to clear out liquid. Table 6 lists the crankcase
pressor Replacement after Motor Burn for further
heaters recommended for the various models and
tips on field replacement. See Table 4 for recom-
voltages.
mended run capacitor replacement.

© 2001 Copeland Corporation 2


Printed in U.S.A.
4-1312
Crankcase Heat – Three-Phase The reversing valve solenoid should be wired so that
the valve does not reverse when the system is shut off
A crankcase heater is required for three-phase com- by the operating thermostat in the heating or cooling
pressors when the system charge exceeds the charge mode. If the valve is allowed to reverse at system
limit listed in Table 5 and an accumulator cannot be shutoff, suction and discharge pressures are reversed
piped to provide free liquid drainage into the accumu- to the compressor. This results in pressures equalizing
lator during the off cycle (See Figure 2 and Table 6). through the compressor which can cause the compres-
sor to slowly rotate until the pressures equalize. This
Pumpdown Cycle
condition does not affect compressor durability but can
A pumpdown cycle for control of refrigerant migration cause unexpected sound after the compressor is turned
is not recommended for scroll compressors of this off.
size. If a pumpdown cycle is used, a separate
Low Ambient Cut-Out
external check valve must be added. The scroll
discharge check valve is designed to stop extended A low ambient cut-out is not required to limit air-to-air
reverse rotation and prevent high-pressure gas from heat pump operation. Air-to-water heat pumps must be
leaking rapidly into the low side after shut off. The check reviewed since this configuration could possibly run
valve will in some cases leak more than reciprocating outside of the approved operating envelope (Figure 5)
compressor discharge reeds, normally used with causing overheating or excessive pressure ratio opera-
pumpdown, causing the scroll compressor to recycle tion.
more frequently. Repeated short-cycling of this nature
can result in a low oil situation and consequent damage Oil Type
to the compressor. The low-pressure control differen-
tial has to be reviewed since a relatively large volume Conventional white oil (Sontex 200 LT) is used in these
of gas will re-expand from the high side of the compres- compressors. White oil is compatible with 3GS, and
sor into the low side on shut down. 3GS oil may be used if the addition of oil in the field is
required. See the compressor nameplate for original oil
Minimum Run Time charge. A complete recharge should be four fluid
ounces (118 ml) less than the nameplate value. Some
There is no set answer to how often scroll compressors models have been released for use with R407C and use
can be started and stopped in an hour, since it is highly polyol ester oil, identified as POE, along with the charge
dependent on system configuration. Other than the quantity on the nameplate. These models have an “E”
considerations in the section on Brief Power Interrup- in the 7th place of the model number. An example would
tions, there is no minimum off time. This is because the be the ZR24K3E-PFJ compressor. Copeland Ultra 22
scrolls start unloaded, even if the system has unbal- CC should be used if additional oil is needed in the field.
anced pressures. The most critical consideration is the Mobil Arctic EAL22CC or ICI Emkarate RL32CF oil may
minimum run time required to return oil to the be used to recharge these compressors if Ultra 22 is not
compressor after startup. This is most easily deter- available.
mined using a sample compressor equipped with a
sight glass (available from Copeland) and configured Discharge Mufflers
with the longest connecting lines that are approved for
the system. The minimum on time becomes the time Flow through Copeland Scroll Compressors is semi-
required for oil lost on compressor startup to return to continuous with relatively low pulsation. External muf-
the compressor sump and restore a normal level in the flers, where they are normally applied to piston com-
sight glass. Cycling the compressor for a shorter period pressors today, may not be required for Copeland
than this, for instance to maintain very tight tempera- Scroll. Because of variability between systems, how-
ture control, will result in progressive loss of oil and ever, individual system tests should be performed to
damage to the compressor. See Application Engineer- verify acceptability of sound performance. When no
ing Bulletin 17-1262 for more information on preventing testing is performed, mufflers are recommended in
compressor short cycling. heat pumps. A hollow shell muffler such as the Alco
APD-1 will work quite well. The muffler should be
Reversing Valves located a minimum of six inches (15 cm) to a maximum
of 18 inches (46 cm) from the compressor for most
Since Copeland Scroll compressors have very high effective operation. The further the muffler is placed
volumetric efficiency, their displacements are lower from the compressor within these ranges the more
than those of comparable capacity reciprocating com- effective it may be. If adequate attenuation is not
pressors. As a result, Copeland recommends that the achieved, use a muffler with a larger cross-sectional
capacity rating on reversing valves be no more than 2 area to inlet-area ratio. The ratio should be a minimum
times the nominal capacity of the compressor with of 20 to 1 with a 30 to 1 ratio recommended. The muffler
which it will be used in order to ensure proper operation should be from four to six inches (10-15 cm) long.
of the reversing valve under all operating conditions.

© 2001 Copeland Corporation 3


Printed in U.S.A.
4-1312
Air Conditioning System Suction Line Noise and voltage where a poor power supply is encountered. The
Vibration low starting voltage reduces the starting torque of the
compressor and subsequently increases the start
Copeland Scroll compressors inherently have low time. This could cause light dimming or a buzzing noise
sound and vibration characteristics. However, the where wire is pulled through conduit. The start compo-
sound and vibration characteristics differ in some nents listed in Table 7 will substantially reduce start
respects from those of reciprocating compressors. In time and consequently the magnitude and duration of
rare instances, these could result in unexpected sound both light dimming and conduit buzzing.
complaints.
Electrical Connection
One difference is that the vibration characteristic of the
scroll compressor, although low, includes two very The orientation of the electrical connections on the
close frequencies, one of which is normally isolated Copeland Scroll compressors is shown in Figure 4.
from the shell by the suspension of an internally Three electrical connection options are available for
suspended compressor. These frequencies, which are these compressors. These include the “Molded Plug”
present in all compressors, may result in a low level one piece push-on connection, available in certain
“beat” frequency that may be detected as noise coming markets, and “Quick Connect” flag termination avail-
along the suction line into a house under some condi- able on all scrolls of this size. Some four-ton and larger
tions. Elimination of the “beat” can be achieved by models also offer “T-block Screw Connection” for ring
attenuating either of the contributing frequencies. The termination.
most important frequencies to avoid are line and twice-
line frequencies for single-phase compressors and line Deep Vacuum Operation
frequency for three phase compressors. This is easily
Very early models of Copeland Scroll compressors
done by using one of the common combinations of
could quickly achieve low vacuums if the suction side
design configurations described in Table 3. The scroll
of the compressor were closed or severely restricted.
compressor makes both a rocking and torsional motion,
This could cause arcing damage to the Fusite pins.
and enough flexibility must be provided in the line to
Models built after September 1991 (SN 91I) incorporate
prevent vibration transmission into any lines attached
internal low vacuum protection, and stop pumping
to the unit. In a split system the most important goal is
(unload) when the pressure ratio exceeds approxi-
to ensure minimal vibration in all directions at the
mately 10:1. There is an audible increase in sound
service valve to avoid transmitting vibrations to the
when the scrolls start unloading.
structure to which the lines are fastened.
Copeland Scroll compressors (as with any refriger-
A second difference of the Copeland Scroll is that under
ant compressor) should never be used to evacuate
some conditions the normal rotational starting motion
a refrigeration or air conditioning system. The scroll
of the compressor can transmit an “impact” noise along
compressor can be used to pump down refrigerant in
the suction line. This may be particularly pronounced
a unit as long as the pressures remain within the
in three-phase models due to their inherently higher
operating envelope shown in Figure 5. Prolonged
starting torque. This phenomenon, like the one de-
operation at low suction pressures will result in over-
scribed previously, also results from the lack of internal
heating of the scrolls and permanent damage to the
suspension, and can be easily avoided by using stan-
compressor drive bearing. (See Application Engineer-
dard suction line isolation techniques as described in
ing Bulletin 24-1105 for proper system evacuation
Table 3.
procedures.)
The sound phenomena described above are not usually
Nomenclature
associated with heat pump systems because of the
isolation and attenuation provided by the reversing The model numbers of the Copeland Scroll compres-
valve and tubing bends. sors include the approximate nominal 60 HZ capacity
at standard operating conditions. An example would be
Single Phase Starting Characteristics
the ZR24K3-TFD, which has 24,500 Btu/hr (7 kw)
Start assist devices are usually not required, even if a cooling capacity at the ARI high temperature air con-
system utilizes non-bleed expansion valves. Due to the ditioning rating point when operated on 60 Hz. Note that
inherent design of the Copeland Scroll, the internal the same compressor will have approximately 5/6 of
compression components always start unloaded even this capacity or 20,200 Btu/hr (5.9 kw) when operated
if system pressures are not balanced. In addition, since on 50 Hz current. Please refer to product literature for
internal compressor pressures are always balanced at details pertaining to other information contained in the
startup, low voltage starting characteristics are excel- model number.
lent for Copeland Scroll compressors. Starting current
on any compressor may result in a significant “sag” in

© 2001 Copeland Corporation 4


Printed in U.S.A.
4-1312
Shell Temperature during shutdown when the compressor is reversed
through gas pressure. Should the compressor be
Certain types of system failures, such as condenser or powered in reverse, the anti-rotation device will not
evaporator fan blockage or loss of charge, may cause engage. In this case the compressor will continue to run
the top shell and discharge line to briefly but repeatedly in reverse until the protector opens.
reach temperatures above 350ºF (177ºC) as the com-
pressor cycles on its internal protection devices. Care Brief Power Interruptions
must be taken to ensure that wiring or other materials,
which could be damaged by these temperatures, do not Brief power interruptions (less than 1/2 second) may
come in contact with these potentially hot areas. result in powered reverse rotation of single-phase
Copeland Scroll compressors. This occurs because
Suction and Discharge Fittings high-pressure discharge gas expands backward through
the scrolls during power interruption, causing the scroll
Copeland Scroll compressors have copper plated steel to orbit in the reverse direction. When power is reap-
suction and discharge fittings. These fittings are far plied while reverse rotation is occurring, the compres-
more rugged and less prone to leaks than copper sor may continue to run in the reverse direction for
fittings used on other compressors. Due to the different some time before the compressor’s internal protector
thermal properties of steel and copper, brazing proce- trips. This has no effect on durability. When the protec-
dures may have to be changed from those commonly tor resets, the compressor will start and run normally.
used. See Figure 6 for assembly line and field brazing
procedures. To avoid disruption of operation, an electronic control
that can sense brief power interruptions may be used
Three Phase Scroll Compressors to lock out the compressor for a short time. This control
could be incorporated in other system controls (such
Scroll compressors, like several other types of com-
as defrost or thermostat), or be a stand-alone control.
pressors, will only compress in one rotational direction.
Functional specifications for this control as well as a
Direction of rotation is not an issue with single phase
suggested wiring diagram are shown in Figure 3.
compressors since they will always start and run in the
proper direction (except as described in the section Because three-phase models have high enough torque
“Brief Power Interruptions”). Three phase compres- to prevent reverse rotation after power interruptions no
sors will rotate in either direction depending upon time delay is necessary.
phasing of the power. Since there is a 50-50 chance of
connecting power in such a way as to cause rotation in Assembly Line Brazing Procedure
the reverse direction, it is important to include no-
tices and instructions in appropriate locations on Figure 6 discusses the proper procedures for brazing
the equipment to ensure proper rotation direction the suction and discharge lines to a scroll compressor.
is achieved when the system is installed and oper- It is important to flow nitrogen through the system
ated. Verification of proper rotation direction is made by while brazing all joints during the system assembly
observing that suction pressure drops and discharge process. Nitrogen displaces the air and prevents the
pressure rises when the compressor is energized. formation of copper oxides in the system. If allowed to
Reverse rotation will result in substantially-reduced form, the copper oxide flakes can later be swept
current draw compared to normal values. through the system and block screens such as those
protecting capillary tubes, thermal expansion valves,
There is no negative impact on durability caused by and accumulator oil return holes. The blockage –
operating three phase Copeland Scroll compressors in whether it be of oil or refrigerant – is capable of doing
the reversed direction for a short period of time (under damage resulting in compressor failure.
one hour) but oil may be lost. Oil loss can be prevented
during reverse rotation if the tubing is routed at least six Assembly Line System Charging Procedure
inches (15 cm) above the compressor. After several Systems should be charged on both the high and low
minutes of operation in reverse, the compressor’s sides simultaneously. The majority of the charge should
internal protector will trip. If allowed to repeatedly be placed in the high side of the system to prevent low
restart and run in reverse without correcting the situ- volt start difficulties, Hipot failures, and bearing wash-
ation, the compressor will be permanently damaged. out during first-time start on the assembly line. It is best
All three-phase scroll compressors are wired identi- to charge only vapor into the low side of the system. Do
cally internally. As a result, once the correct phasing not operate compressor without enough system
is determined for a specific system or installation, charge to maintain at least 7 psig (0.5kg/cm2)
connecting properly phased power leads to the same suction pressure. Do not operate with a restricted
Fusite terminals will maintain proper rotation direction. suction. Do not operate with the low pressure cut-
It should be noted that the “Quiet” shutdown device out jumpered. Allowing pressure to drop below 7 psig
used in the four and five-ton scroll will only engage (0.5 kg/cm2) for more than a few seconds may overheat

© 2001 Copeland Corporation 5


Printed in U.S.A.
4-1312
scrolls and cause early drive bearing damage. Do not Copeland Scroll Functional Check
use compressor to test opening setpoint of high pres-
sure cutout. Bearings are susceptible to damage before A functional compressor test during which the suction
they have had several hours of normal running for service valve is closed to check how low the compres-
proper break in. If a single-phase compressor fails to sor will pull suction pressure is not a good indication
start on the assembly line, the charging procedure may of how well a compressor is performing. Such a test
have resulted in scrolls that are sealed in the pumping will damage a scroll compressor. The following
position and difficult to start. These can either be set diagnostic procedure should be used to evaluate whether
aside for a short time while the internal pressures a Copeland Scroll compressor is functioning properly:
balance, making them easier to start; or they can be
1. Proper voltage to the unit should be verified.
started by temporarily attaching a high torque start kit.
Approved start components are listed in Table 7. 2. The normal checks of motor winding continuity and
Determine the starting voltage under locked rotor short to ground should be made to determine if the
conditions because there may be excessive voltage inherent overload motor protector has opened or if
sag during starting. an internal motor short or ground fault has devel-
oped. If the protector has opened, the compressor
“Hipot” (AC High Potential) Testing
must be allowed to cool sufficiently to allow it to
Copeland Scroll compressors are configured with the reset.
motor down and the pumping components at the top of
3. Proper indoor and outdoor fan/blower operation
the shell. As a result, the motor can be immersed in
should be verified.
refrigerant to a greater extent than hermetic reciprocat-
ing compressors when liquid refrigerant is present in the 4. With service gauges connected to suction and
shell. In this respect, the scroll is more like semi- discharge pressure fittings, turn on the compres-
hermetic compressors which can have horizontal mo- sor. If suction pressure falls below normal levels
tors partially submerged in oil and refrigerant. When the system is either low on charge or there is a flow
Copeland Scroll compressors are Hipot tested with blockage in the system.
liquid refrigerant in the shell, they can show higher
levels of leakage current than compressors with the 5. Single Phase Compressors
motor on top. This phenomenon can occur with any
compressor when the motor is immersed in refrigerant. If suction pressure does not drop and discharge
The level of current leakage does not present any safety pressure does not rise to normal levels, either the
issue. To lower the current leakage reading, the system reversing valve (if so equipped) or the compressor
should be operated for a brief period of time to redistrib- is faulty. Use normal diagnostic procedures to
ute the refrigerant to a more normal configuration and check operation of the reversing valve.
the system Hipot tested again. See AE Bulletin 4-1294 Three Phase Compressors
for Megohm testing recommendations. Under no cir-
cumstances should the Hipot test be performed while If suction pressure does not drop and discharge
the compressor is under a vacuum. pressure does not rise to normal levels, reverse
any two of the compressor power leads and reap-
Unbrazing System Components ply power to make sure the compressor was not
Caution! Before opening a system it is important to wired to run in reverse. If pressures still do not
remove all refrigerant from both the high and low move to normal values, either the reversing valve
side. If the refrigerant charge is removed from a scroll- (if so equipped) or the compressor is faulty. Recon-
equipped unit by bleeding one side only, it is very nect the compressor leads as originally configured
possible that either the high or low side of the system and use normal diagnostic procedures to check
remains pressurized. If a brazing torch is then used to operation of the reversing valve.
disconnect tubing, the pressurized refrigerant and oil 6. To test if the compressor is pumping properly, the
mixture could ignite when it escapes and contacts the compressor current draw must be compared to
brazing flame. It is important to check both the high published compressor performance curves using
pressure and low pressure side with manifold gauges the operating pressures and voltage of the system.
before unbrazing. Instructions should be provided in If the measured average current deviates more
appropriate product literature and assembly (line re- than ±15% from published values, a faulty com-
pair) areas. If compressor removal is required, the pressor may be indicated. A current imbalance
compressor should be cut out of system rather than exceeding 15% of the average on the three phases
unbrazed. See Figure 6 for proper compressor of a three-phase compressor should be investi-
removal procedure. gated further. A more comprehensive trouble-
shooting sequence for compressors and systems
can be found in Section H of the Copeland Electri-
cal Handbook.
© 2001 Copeland Corporation 6
Printed in U.S.A.
4-1312
7. Before replacing or returning a compressor: Be Start-up of a New or Replacement Compressor
certain that the compressor is actually defective.
As a minimum, recheck a compressor returned It is good service practice, when charging a system, to
from the field in the shop or depot for Hipot, winding charge liquid refrigerant into the high side only and
resistance, and ability to start before returning to charge the low side of the system with vapor only. It is
Copeland. More than one-third of compressors not good for any compressor to have liquid refrigerant
returned to Copeland for warranty analysis are dumped from a refrigerant cylinder into the crankcase
determined to have nothing found wrong. They of the compressor. Do not start the compressor
were mis-diagnosed in the field as being defective. while the system is in a deep vacuum. Internal arcing
Replacing working compressors unnecessarily may occur when a scroll compressor is started in a
costs everyone. vacuum. Do not operate compressor without enough
system charge to maintain at least 7 psig (0.5 kg/
Tandem 8 – 13.5 Ton Scroll Compressors cm2) suction pressure. Do not operate with a
restricted suction. Do not operate with the low
The refrigerant charge limit for an 8 to 13.5 ton tandem pressure cut-out jumpered. Allowing suction pres-
compressor is 12 pounds (5.4 kg). A three-phase unit sure to drop below 7 psig (0.5 kg/cm2) for more than a
with a charge over twelve pounds must have crankcase few seconds may overheat scrolls and cause early
heaters added to both compressors. The ZRT92 – drive bearing damage. Never install a system in the
ZRT122 compressors are mounted on rails using field and leave it unattended with no charge, a holding
rubber mounting parts. The ZRT136 – ZRT162 charge, or with the service valves closed without
compressors are rigidly mounted on rails using solid securely locking out the system. This will prevent
steel mounting parts. These mounts are installed at the unauthorized personnel from accidentally operating
factory and should not be loosened. Tighten to 125 inch the system for comfort cooling and potentially ruining
pounds (14 NM) if it becomes necessary to tighten the compressor by operating with no refrigerant flow.
these mounts. Holes in the mounting rails may be used
to mount isolation grommets under the entire tandem. Excessive Liquid Floodback Tests
A discharge check valve must be placed in the common The following tests are for those system configurations
discharge line when pumpdown is used. and charge levels identified in Table 1 that need special
testing to verify exemption from need of an accumulator.
Both compressors must be at the same level to prevent Figure 1 should be used to determine the effectiveness
oil from migrating to the lowest compressor through the of an accumulator. The compressor sump temperature
oil equalization line. during any test where the return gas superheat is near
zero must always meet the guidelines of Figure 1.
Compressors may be individually cycled.
To test for excessive continuous liquid refrigerant
Individual compressors should not be replaced in the
floodback, it is necessary to operate the system in a
field. The entire tandem compressor unit must be
test room at conditions where steady state floodback
replaced if it becomes necessary to replace one
may occur (low ambient heating operation). Thermo-
compressor. Individual compressors configured for
couples should be attached with glue or solder to the
tandem usage may not be available for field replace-
center of the bottom shell and to the suction and
ment. See section below for further tips on field
discharge lines approximately 6 inches (15 cm from the
replacement of compressors.
shell). These thermocouples should be insulated from
Compressor Replacement after Motor Burn the ambient air with Permagum® or other thermal
insulation to be able to record true shell and line
In the case of a motor burn, the majority of contami- temperatures. If the system is designed to be field
nated oil will be removed with the compressor. The rest charged, it should be overcharged by 15% in this test
of the oil is cleaned through use of suction and liquid line to simulate overcharging commonly found in field
filter dryers. A 100% activated alumina suction filter installations.
drier is recommended but must be removed after 72
hours. See Application Engineering bulletin 24-1105 The system should be operated at an indoor tempera-
for clean up procedures and AE bulletin 11-1297 for ture of 70°F (21°C). and outdoor temperature extremes
liquid line filter-drier recommendations. It is highly (0°F or -18°C or lower in heating) to produce floodback
recommended that the suction accumulator be conditions. The compressor suction and discharge
replaced if the system contains one. This is because pressures and temperatures as well as the sump
the accumulator oil return orifice or screen may be temperature should be recorded. The system should be
plugged with debris or may become plugged shortly allowed to frost up for several hours (disabling the
after a compressor failure. This will result in starvation defrost control and spraying water on the outdoor coil
of oil to the replacement compressor and a second may be necessary) to cause the saturated suction
failure. temperature to fall to below -10°F (-23°C). The com-

© 2001 Copeland Corporation 7


Printed in U.S.A.
4-1312
pressor sump temperature must remain above the twenty-five feet (8 meters) of connecting tubing with no
sump temperature shown in Figure 1 or design changes traps between the indoor and outdoor units. If the
must be made to reduce the amount of floodback. If an system is designed to be field charged, the system
accumulator is used, an oil return orifice size of 0.040 should be overcharged by 15% in this test to simulate
- .055” (1 - 1.4 mm) is recommended. (See information overcharging commonly found in field installations.
on Accumulators in Application Considerations and Operate the system in the cooling mode at the outdoor
also Copeland Application Engineering bulletin 11- ambients, on/off cycle times, and number of cycles
1247). Increasing indoor coil volume, increasing out- specified in Table 2. Record the height of the liquid in
door air flow, reducing refrigerant charge, decreasing the compressor at the start of each on cycle, any
capillary or orifice diameter, and adding a charge protector trips, or any compressor stalls during each
compensator can also be used to reduce excessive test. Review the results with Copeland Application
continuous liquid refrigerant floodback. Engineering to determine if an accumulator is required
for the application. The criteria for pass/fail is whether
To test for repeated excessive liquid floodback the liquid level reaches the height of the scroll compres-
during normal system off-cycles perform the “Field sor suction fitting on the side of the shell. Liquid levels
Application Test”. Obtain a sample compressor with higher than the suction fitting allow the compressor oil
a side sight tube to measure liquid level in the compres- floating on top of the refrigerant to be ingested by the
sor. Set the system up in a configuration with the indoor scrolls and pumped out of the compressor.
unit elevated several feet above the outdoor unit with

Oil Dilution Chart


200°F (93.3 °C) Max. Oil Temp.
Evaporating Temp. (°C)
-20 -15 -10 -5 0 5 10
100

90
30

80

OK
Safe Area

Compressor Sump Temp. (°C)


70
*See Note 1 20
Compressor Sump Temp. (°F)

60

50 10

40

Unsafe Area 0
30
(Too much refrigerant dilution)

20

-10

10

0
-10 0 10 20 30 40 50
Evaporating Temp. (°F)

Note 1: Operation in this refrigerant dilution area is safe in air-to-air heat pump heating mode. For other
applications, such as AC only, review expansion device to raise superheat. A cold sump may result in high refrigerant
migration after shut down.
Figure 1

© 2001 Copeland Corporation 8


Printed in U.S.A.
4-1312

To prevent flooded start damage on 3 phase Scrolls due to off cycle migration, the accumulator may be configured
on some systems to allow free drainage from the comressor to the accumulator during the off cycle. When the above
configuration is not possible and the unit charge is over the charge limit shown in Table 5, a crankcase hearer is
required.
Figure 2

230/240 VAC

Fuse Typical Solid State Timer


(if used)

Note: Wire A-B is


NOT required when
optional timer is used
Discharge Line Compressor Contactor
System Operating
Thermostat (if used)
Thermostat

Other Protective Condenser Fan Contactor


Devices (if used) (if used)

Time Delay Relay Specifications

Timer Opens 1 Electrical cycle Timer Closes Greater than 5 seconds later whether
(.016 sec. with 60 HZ operation) power is restored or not
after power is removed

Figure 3

© 2001 Copeland Corporation 9


Printed in U.S.A.
4-1312

Terminal (Fusite)
Terminal (Fusite)Connection
Connection

T1, C

T2, S

T3, R

Motor Terminal (Fusite) Connections

Figure 4

R22 & R407c Scroll Operating Envelope

Evaporating Temp. (°C)


-25 -20 -15 -10 -5 0 5 10 15
170

160
70

150
Condensing Temp. (°F)
)

140 60

130
Condensing Temp. (°C)
50
120

110
Safe Area
100 Safe Area 40
)

90
30

80

70
-20 -10 0 10 20 30 40 50 60

Evaporating Temp. (°F)

Figure 5

© 2001 Copeland Corporation 10


Printed in U.S.A.
4-1312

New Installations Field Service

• The copper-coated steel suction tube on scroll • To disconnect: Reclaim refrigerant from both
compressors can be brazed in approximately the high and low side of the system. Cut tubing
the same manner as any copper tube. near compressor.
• Recommended brazing materials: Any silfos • To reconnect:
material is recommended, preferably with a
minimum of 5% silver. However, 0% silver is • Recommended brazing materials: Silfos
acceptable. with minimum 5% silver or silver braze
material with flux.
• Be sure suction tube fitting I.D. and suction tube
O.D. are clean prior to assembly. If oil film is • Insert tubing stubs into fitting and connect
present wipe with denatured alcohol, Dichloro- to the system with tubing connectors.
Trifluoroethane or other suitable solvent.
• Follow New Installation brazing instruc-
• Using a double-tipped torch apply heat in Area 1. tions.
As tube approaches brazing temperature, move
torch flame to Area 2.

• Heat Area 2 until braze temperature is attained,


moving torch up and down and rotating around
tube as necessary to heat tube evenly. Add
braze material to the joint while moving torch
around joint to flow braze material around cir-
cumference.
• After braze material flows around joint, move
torch to heat Area 3. This will draw the braze
material down into the joint. The time spent
heating Area 3 should be minimal.

• As with any brazed joint, overheating may be


detrimental to the final result.

Figure 6

© 2001 Copeland Corporation 11


Printed in U.S.A.
4-1312

Operating Principle of Scroll

Figure 7

© 2001 Copeland Corporation 12


Printed in U.S.A.
Printed in U.S.A.
© 2001 Copeland Corporation
13
Table 1
* * * * * * * *

Scroll Compressor Application Diagram


(1) "Other" includes bleed-type TXVs, capillary tubes, and fixed orifices.
(2) "Nominal System Charge" is defined as the design charge for a system.
Note: See text for crankcase heater requirements.
*120% Times Compressor refrigerant charge limit in Table 5.
4-1312
4-1312
Table 2
Field Application Test
Operate the system as it would be operated in an actual field installation, cycling the unit on and off for the times
indicated at each ambient.

Outdoor Ambient 85°F (29°C) 95°F (35°C) 105°F (40°C)


System On-Time (Minutes) 7 14 54
System Off-Time (Minutes) 13 8 6
Number of On/Off Cycles 5 5 4

Table 3
Recommended Configuration
Component Description
Tubing Configuration Shock loop
Service Valve “Angled valve” fastened to unit
Suction muffler Not required

Alternate Configuration
Component Description
Tubing Configuration Shock loop
Service Valve “Straight through” valve not fastened to unit
Suction muffler May be required (Acts as dampening mass)

Table 4
Recommended Run Capacitors for Field Replacement
of a ZR*K1 or K2 with a ZR*K3, K4, or KC

K1 K2 K3 K4 KC
ZR18 25µf/370 volt 30µf/370 volt 35µf/370 volt 30µf/370 volt
ZR23 30µf/370 volt 40µf/370 volt 35µf/370 volt 35µf/370 volt
ZR26 35µf/370 volt 40µf/370 volt 30µf/440 volt
ZR28 35µf/370 volt 45µf/370 volt 35µf/440 volt
ZR34 35µf/440 volt 50µf/370 volt 40µf/370 volt
ZR40 35µf/440 volt 55µf/370 volt 40µf/440 volt
ZR46 40µf/440 volt 60µf/370 volt
ZR49 40µf/440 volt 60µf/370 volt 45µf/440 volt
ZR57 55µf/440 volt 80µf/370 volt 60µf/370 volt
ZR61 55µf/440 volt 80µf/370 volt 60µf/370 volt

© 2001 Copeland Corporation 14


Printed in U.S.A.
4-1312

Table 5
Compressor Refrigerant Charge Limits

STAR (54 Frame) ZR16KC/4 to ZR24KC/4 6 pounds (2.7 kg)

QUANTUM (63 Frame) ZR18K3/28KC to ZR48KC/3 8 pounds (3.6 kg)

QUEST (70 Frame) ZR46KC/3 to ZR81KC 10 pounds (4.5 kg)

QUEST TANDEM ZRT92 to ZRT162 12 pounds (5.4 kg)

Table 6
Crank Case Heaters

Copeland Models: Copeland Part #: Tutco Part #: Volts: Watts: Lead Length:
Star: ZR16K4/KC - ZR24K4/KC 018-0052-00 02-6319-00 240 40 21”
018-0052-01 02-6319-02 120 40 21”
Quantum: ZR18K3 – ZR24K3 018-0053-00 02-6328-00 240 70 21”
ZR26K3/KC - ZR48K3/KC 018-0053-01 02-6329-03 480 70 21”
ZP23K3E - ZP41K3E 018-0053-02 02-6328-06 575 70 21”
Quest: ZR46K3/KC – ZR61K3/KC 018-0053-04 02-6330-00 240 70 48”
ZR67KC – ZR81KC 018-0053-05 02-6330-03 480 70 48”
ZP54K3E 018-0053-06 02-6330-06 575 70 48”

© 2001 Copeland Corporation 15


Printed in U.S.A.
4-1312

Table 7
Approved start components for Scroll Compressor

(ASPEN) ZR18K1 through ZR40K1


start capacitor 014-0036-03 88-108 mfd/330 vac
potential relay 040-0001-68 pu 240-260 volts GE: 3ARR3CT6V5
do 60-121 volts 420 coil volts

(STAR) ZR16K4/KC through ZR24K4/KC


(QUANTUM) ZR18K3/KC-PFV/PFJ through ZR42K3/KC-PFV/PFJ, ZR45KC-PFV
& ZR47KC-PFV, ZP23 to ZP44(PFV/PFJ)
start capacitor 014-0036-03 88-108 mfd/330 vac Use w/all Star and Quantum
models except (1)
014-0006-12 175-216 mfd/330 vac (1)Use w/ ZR40KC,ZR45KC,
ZR47KC/K3,ZR 48K3-PFV
potential relay 040-0001-79 pu 170-180 volts GE: 3ARR3CT3P5
do 40-90 volts 332 coil volts Use w/all models except (2)
040-0001-68 pu 240-260 volts GE: 3ARR3CT6V5
do 60-121 volts 420 coil volts (2)Use w/ ZR48KC-PFV

(QUEST) ZR46K2 through ZR61K2


start capacitor 014-0006-10 270-324 mfd/330 vac
potential relay 040-0001-69 pu 320-340 volts GE: 3ARR3CT4D5
do 60-135 volts 502 coil volts

(QUEST) ZR46K3/KC-PFV/PFJ through ZR68K3/KC-PFV/PFJ, ZP54K3E-PFV


start capacitor 014-0006-10 270-324 mfd/330 vac
potential relay 040-0001-69 pu 320-340 volts GE: 3ARR3CT4D5
do 60-160 volts 375 coil volts

© 2001 Copeland Corporation 16


Printed in U.S.A.
4-1312

© 2001 Copeland Corporation 17 Copeland Corporation


Printed in U.S.A. Sidney, OH 45365-0669

Das könnte Ihnen auch gefallen