AUTOTUNE PID CONTROLLER X96P

VER 27.X
INSTRUCTIONS FOR USE
1. IMPORTANT SAFETY INFORMATION Input group 2
(common for both inputs)
Thermocouple : B, C, D, E, G, J, K, N, R, S, T
1.1 Installation RTD : Pt100, 3-wire, Cu53
Check that the supply voltage given to the instrument is as Current : 0~20 mA, 4~20 mA,
specified on the terminals of the instrument. To avoid shock Square root (for input 1)
hazard prevent live parts being touched and follow wiring Voltage : 0~50 mV
diagram and regulations. Through DIP selection following
voltage inputs are available :
1.2 Warranty 0~1 V, 0~5 V, 0~10 V, 0~10 mV,
0~100 mV, 0~200 mV
Radix Electrosystems Pvt. Ltd. warrants this product to be Transmitter supply (VTX) : 22 V nominal, 30 mA max
free of defects in workmanship and materials for one year Range limits : See Table 1
from the date of purchase. Accuracy : See Table 1
Cold junction compensation : Automatic
1. Defects in workmanship and materials will be serviced Sensor break protection : User programmable
free of charge during the warranty period. Labour
required for rectifying the defects is also covered by this INDICATION
warranty. Any further claims are excluded. Process variable : Upper : 4 digit, 7 segment
0.56” (14.2 mm) red LED display
2. Warranty servicing does not extend the period of Setpoint : Middle : 4 digit, 7 segment
warranty for the entire instrument or for the parts that 0.56” (14.2 mm) green LED
have been replaced. display
% output power : Lower : 3 digit, 7 segment
3. From the warranty are excluded : 0.39” (9.9 mm) red LED display
a) all damage caused by improper handling, e.g. non- Status indication : LEDs for relay status
observance of the operating instructions, subjecting LEDs for setpoint indication
the product to excessive heat, moisture, corrosion, etc. LED for auto/manual power
b) damage caused by the intervention of the buyer or by status
unauthorised third parties LEDs for communication
c) transport damage from the manufacturer to the
OUTPUTS
dealer or user or on the way to servicing No. of relays :1/2/3/4
d) parts subject to normal wear, e.g. relays. Relay contact type : NO-C-NC
4. Any liability for direct or indirect consequential damages Relay contact rating : 5A / 230V AC, resistive
SSR drive : 12 V DC drive signal for
caused by the instrument is excluded, even if the defect
external SSR
of the instrument is covered by the warranty.
No. of analog outputs : 0 / 1 / 2 (current or voltage)
Radix liability for any breach of this agreement shall not Current output : 4~20 mA / 0~20 mA / 20~4 mA /
exceed the purchase price paid. 20~0 mA isolated from input)
Maximum load for current : 500 ohms
5. Any further claims, based on any title, are excluded. output
Voltage output : 0-10 V / user specified
6. In case repair service is required under this factory Load for voltage output : >10 Kohms
warranty, please send the instrument, indicating the
exact address of the sender and defect, carefully AUTO/MANUAL OPERATION
packed, postage paid, to : Radix Microsystems, B-1, 2nd Function : Output power is increased /
Floor, Ghanshyam Indl. Estate, Off Veera Desai Road, decreased by UP/DOWN keys
in manual mode
Andheri (West), Mumbai - 400 053.
Auto / Manual transfer : Bumpless
2. OVERVIEW COMMUNICATION
Port : RS485
2.1 Introduction Protocol : Modbus RTU
X96P is a microcontroller based user programmable Slave ID : User programmable (1~256)
PID/ONOFF/Time proportional controller with 4 digit LED
upper display for displaying measured values, 4-digit LED OTHER
middle display for displaying settings and 3-digit LED lower Programming : Through 3 tactile keys
display for displaying output percentage power. Dimensions (in mm) : 96(H) x 96(W) x 100(D)
Mounting : Panel mount
X96P has two universal inputs, upto 4 relays upto 2 analog Panel cutout : 92 x 92 mm
outputs. It is operated by 4 user friendly keys. Supply voltage : a) 85~265 V AC, 50/60 Hz
b) 20~35 V DC (optional)
Power consumption : 4 watts maximum
2.2 Specifications Operating ambient
INPUTS temperature : 0~50 °C
No. of inputs : 2 (input 1, input 2) Relative humidity : Below 90%, non condensing
Input group 1
2.3 Power On
MAN#161R4/P1/26/311211/A

(common for both inputs)


Thermocouple : B, E, J, K, N, R, S, T
RTD : Pt100, 3-wire On application of power to the instrument, version number
Voltage : 0~50 mV is displayed.
Current : 0~20 mA, 4~20 mA
2.4 Front Panel 2.5 Display & Control Key Functions (Refer 2.4)
Refer Indicator/
Fig 1 Fig 1 Display Function

Displays the measured input value


Measured
1 (PV) or the error message if an error
(1) input value
(1)
X96P 2 occurs. Displays a parameter symbol in
RLY (4) (PV) Display
3
program mode.
4

1
Displays setpoints (SPC, SP1, SP2,
2 Setpoint
(2) (5) (2) SP3 or SP4) or measured input2 value
3
SP
(SP) Display
(as selected by user)
4

(3) (6) Output power


(3) It displays the output power in percent.
Rx Tx display (O/P)

MAN (7) Relay status When the relays get ON or OFF, the
(4)
indicator LEDs respective LEDs become, ON or OFF
A/M

(5) Setpoint status Indicate which setpoint is displayed


indicator LEDs on 2nd row

(8) Serial Indicate that serial communication is


(6) communication in process.
status indicator

(7) Manual mode


Indicates manual mode.
indicator
2.6 Connection Diagram
In run mode, allows to enter setpoint
mode.
EXT SSR* RELAY 2-WIRE INPUT In program mode, allows to change
+

P A
+

TRANSMITTER
+
X X
mV/VIN value of parameter.
S
SSR
NO Q B In program mode, at parameter “VEr” if
Y RLY Y pressed for 6 sec, allows to enter
C R B' mA INPUT
calibration level.
+

9
Z +
NC FOR 2-WIRE S
TRANSMITTER USING Scrolls forward through the
2-WIRE RTD : SHORT Q & R
INTERNAL SUPPLY programmable parameters in program
mode.
1 21 31 P 11 P
85~265 V
V AC/DC S
(8) Allows to increment the value of the
2 22 32 Q 12 Q
INPUT2* INPUT1 selected parameter.
3 X 23 X 33 R 13 R
*
In run mode, resets alarm when in latch
RLY1 4 Y RLY3* 24 Y 34 S 14 S
D+
alarm mode.
5 Z 25 Z 35 15
RS485*
6 X 26 X 36 16 Scrolls backward through the
D
RLY2
* 7 Y RLY4* 27 Y 37 CJC 17
programmable parameters in program
8 Z 28 Z 38
+
18
mode.
V/Iout2 * + Allows to decrement the value of the
VTX* 9 29 39 19
V/Iout1 * selected parameter.
10 30 20

STK-710
(9) Toggles between Automatic & manual
* - FACTORY OPTION A/M
control mode

TABLE 1
RANGE LIMITS RANGE IN WHICH TYPICAL ACCURACY WORST CASE
SENSOR / INPUT (°C / EU) ACCURACY IS SPECIFIED AT 30 °C ACCURACY
LOW SCALE HIGH SCALE LOW SCALE HIGH SCALE (°C / EU) (°C / EU)
Input Group 1
Pt - 6% Rh / Pt - 30% Rh (B) 400 1820 400 1820 ±3 ±5
Chromel / Constantan (E) -270 1000 0 1000 ±1 ±3
Iron / Constantan (J) -210 760 0 760 ±1 ±3
Chromel / Alumel (K) -270 1372 -50 1200 ±1 ±3
Nicrosil / Nisil (N) -270 1300 -50 1200 ±1 ±3
Pt / Pt - 13% Rh (R) 0 1760 400 1760 ±2 ±5
Pt / Pt - 10% Rh (S) 0 1760 400 1760 ±2 ±5
Copper / Constantan (T) -270 400 -200 400 ±1 ±3
Pt100, 3-wire -200 850 -200 600 ± 0.3 ± 1.0
Linear (0~50 mV, 0~20 mA, 4~20 mA) -1999 9999 -1999 9999 ± 5 EU ± 20 EU
Input Group 2
The following inputs are available in Input Group 2 in addition to inputs of Input Group 1.
Tungsten - 5% Rh / Tungsten - 26% Rh (C) 0 2320 0 2320 ±3 ±5
Tungsten - 3% Rh / Tungsten - 25% Rh (D) 0 2310 0 2310 ±3 ±5
Tungsten / Tungsten - 26% Rh (G) 0 2310 0 2310 ±3 ±5
MAN#161R3/P2/26/311211/A

Cu53 0 180 0 180 ± 0.3 ± 0.5


Linear (0~10 mV, 0~100 mV, 0~200 mV,
-1999 9999 -1999 9999 ± 5 EU ± 20 EU
0~1 V, 0~5 V, 0~10 V)
Linear (4~20 mA) with square root 0 9999 0 9999 ± 10 EU ± 40 EU
3. RELAY LOGIC 3.2 TIME PROPORTIONAL CONTROL
3.1 Onoff Control Note : To convert PID to Time Proportional control make I & D
ON
Note : To convert PID to ONOFF control parameters OFF.
make I & D parameters OFF & CYCT = ONOFF
OFF
SP1A/SP2A = SP1A/SP2A = COOL
SP1A/SP2A = HEAT
SP1A/SP2A/SP3A/SP4A = FsHi SP1A/SP2A/SP3A/SP4A = HEAT COOL SP1b/SP2b = n.Lin

PLL PHL PHL

SP SP BAND BAND BAND


HYST HYST
SP 50% SP 50% SP 10%

PHL PLL PLL

SP1A/SP2A/SP3A/SP4A = FSLO SP1A/SP2A/SP3A/SP4A = COOL


IF SP2A=dvhi IF SP2A=COOL IF SP2A=COOL
then, SP=SPC+SP2 then, then,
bAnd bAnd
If SP2A=dvLo SP=SPC+SP2+ 2 SP=SPC+SP2+ 2
HYST HYST then, SP=SP1-SP2
SP SP

3.3 Alarm Output


a) Latch (Ltch)
SP2A = dvhi SP2A = dvLo In latch output, once relay gets ON, it remains 'ON' until
SP = SPC+ SP2 SP2 = SPC - SP2 alarm is acknowledged by key. If alarm condition is
Similarly for SP3A & SP4A Similarly for SP3A & SP4A present and alarm is acknowledged the latched relay will
turn off but led will remain on to indicate the alarm condition
b) Hold
If the instrument is turned on in alarm condition,alarm
HYST
SP
HYST
SP output will be disabled. The alarm output will only activated
in the second occurance of the alarm.
c) Ltch.Hold
It is the combination of latch & Hold outputs.
SP2A = bnd.o SP2A = bnd.i
3.4 Auto/manual Operation
1. Press A/M key in run mode. The control enters manual
bnd2 bnd2 mode, MAN LED glows
SP2 SP2 2. To change the output power manually
SP SP1
1. Press key to increase power by 0.1%
2. Without releasing key, press + keys
SP2 SP2
to increase power by 1%
bnd2 bnd2 3. Release key without releasing key to
increase power by 10%
4. Similar operation by & to decrease power
manually
Similarly for SP3A/SP4A
5. To enter auto mode again press A/M key, MAN LED
goes off.
4. PROGRAM MODE GUIDE
To enter program mode, press & hold
· & keys together, in run mode.
Press
· + keys to increment the value of the selected parameter or go to next level, & press + keys to
decrement the value of the selected parameter, or go to previous level.
Use
· key to go to next parameter.
Use
· key to go to previous parameter.
To exit from the program mode & enter run mode, press
· & keys together.

LEVEL PID
STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

+ PV
Selection of level PID from option
1 Selection of level PID OR
SP, inp, iout, init, PID
+ SP

PV
MAN#161R4/P3/26/311211/A

2 Enter level PID First parameter is displayed


SP

Cont...
Cont... LEVEL PID

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION


Control output device for PID is
SP selected from options :
+ or rly : Relay output in control
Selection of control output
3 OR SP SSR : SSR output in control
device + or Ao.1 : Analog ouput1 in control
SP Ao.2 : Analog output2 in control
or Ao.1.2: Both analog outputs in control
SP
or
SP

PV
Control device is stored & next
4 Storing of control output device parameter is displayed
SP

+ Control output mode is selected from


or SP
Selection of control output options
5 OR
heat : For heat type of application
mode + SP
cooL : For cool type of application

PV
Control output mode is stored &
6 Storing of control output mode next para is displayed.
SP

SP
or Tuning options is selected from
+ SP Off : Tune off
7 Setting of tuning parameter OR or On : Tune on
+ SP At.Sp : Tune at setpoint
or
Park : All output’s disabled
SP

PV
Tuning parameter is stored & next
8 Storing of tuning parameter parameter is displayed.
SP

Unit of proportional band is selected


SP from options:
+
Abs : Band as absolute value
9 Selection of unit of proportional OR SP
Perc : Band as percentage of input
band +
SP span
gain : Band as gain

PV
PB unit is stored & next parameter
10 Storing of band unit is displayed.
SP

Integral time for SPC . It Auto corrects


+ proportional control offset error
PV
OFF - Integral is disabled
11 Set the integral time OR
+ SP A - Autotune calculated
1-9999 - User selectable
unit - sec

PV
Integral time is stored & next
12 Storing of Integral time parameter is displayed
SP
MAN#161R3/P4/26/311211/A

Cont...
Cont... LEVEL PID

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

Derivative time for SPC. It


suppresses overshoot & speeds
+ PV response to disturbances.
13 Setting of derivative time OR OFF - Derivative is disabled
+ SP A - Autotune calculated
1-9999 - User selectable
unit - sec

PV
Derivative time is stored & next
14 Storing of derivative time parameter is displayed.
SP

Adjust the approach control


+ PV factor - 1 to 10. Greater the value,
15 Set the approach control factor OR faster approach to setpoint but
+ SP possibility of overshoot and vice
versa

PV
Approach control factor is stored &
16 Storing of approach control next parameter is stored.
SP

Cycle time for SPC is selected from


+ options :
PV
onoF - Onoff mode
17 Setting of cycle time OR
+ SP A - Autotune calculated
1-640 - User selectable
unit - sec

PV
Cycle time is stored & next parameter
18 Storing of cycle time is displayed.
SP

Offset to SP1 when integral time is


+ PV OFF
19 Setting of offset OR Range : -10.0 to 10.0
+ PV

PV
Offset is stored & level pid is
20 Storing of offset displayed.
SP

LEVEL init
STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

+ PV
Selection of level init from options :
21 Selection of level init OR
SP, inp, iout, PID
+ SP

PV
First parameter of level init is
22 Enter level init displayed
SP
MAN#161R4/P5/26/311211/A

Cont...
Cont... LEVEL init

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

Status of relay o/p when sensor fail


MSB LSB
+ occurs is selected from options
Selection of burn option u -up scale : At sensor fail condition
23 for relays
OR SP relays remain on
+ to d - down scale : At sensor fail
SP condition relays remain off
LSB - Relay 1
MSB - Relay 4

PV
Burn option for relays is stored &
24 Storing of burn option for relays next parameter is displayed
SP

Status of analog o/p when sensor


burnout occurs
+ for eg : For 4 - 20mA type
Selection of burn option for SP
25 OR u : up scale : At sensor fail
analog output to
analog o/p is 20mA
+ SP
d : Downscale : At sensor fail analog
o/p is 4 mA
(Seen only if analog output is
configured)

PV
Storing of burn option for analog Burn option for analog o/p is stored &
26 output next parameter is displayed
SP

% o/p for first current o/p when


+
sensor fail occurs. For eg. for 4-20mA
PV
type
27 Setting of Pr.o1 OR
OFF : According to burn option brn.o
+ SP
50% : 12mA
100% : 20mA
(Seen only if analog output is
configured)

PV
Pr.o1 is stored & next parameter
28 Storing of Pr.o1 is displayed
SP

% o/p for second current o/p when


sensor fail occurs for eg : for 4~20mA
+ type
PV
29 Setting of Pr.o2 OR OFF : According to burn option brn.o
+ SP 50% : 12mA
100% : 20mA
(Seen only if analog output is
configured)

PV
Pr.o2 is stored & next parameter
30 Storing of Pr.o2 is displayed
SP

MSB LSB Output relay mode


+ d - direct action of relay
Selection of reverse / direct OR r - reverse action of relay
31 SP
mode + to LSB - Relay 1
SP MSB - Relay 4

PV
32 Storing of reverse / direct mode Next parameter is displayed
SP
MAN#161R4/P6/26/311211/A

+ SP Select lock for setpoint from options


33 Selection of setpoint lock OR Off : SP can be changed
+ SP On : SP cannot be changed

Cont...
Cont... LEVEL init

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

PV
Setpoint lock is stored & next
34 Storing of setpoint lock parameter is displayed
SP

Parameter lock is selected from


+ SP
options :
35 Selection of parameter lock OR
Off : Parameters can be changed
+ SP
On : Parameters cannot be changed

PV
Parameter lock is stored & next
36 Storing of parameter lock parameter is displayed
SP

Software Input Filter


FL A - no filtering (no-averaging)
+ SP FL B - averaging of 1 samples of ADC
Selection of software filter
37 OR to FL C - averaging of 2 samples of ADC
for input
+ SP FL d - averaging of 4 samples of ADC
FL E - averaging of 6 samples of ADC
FL F - averaging of 8 samples of ADC

PV
Software filter is stored & next
38 Storing of software filter parameter is displayed
SP

+ PV
39 Set serial ID for communication OR Adjust serial id for commn
+ SP

Serial id is stored & next parameter


40 Storing of serial ID Version No. is displayed

41 To enter calibration level Version No.

PV
42 To access next parameter Next parameter is displayed
SP

Select options for reset function


+ SP none : No reset
43 Selection of reset function OR All : Press & keys together
+ SP to reset the instrument to factory
set value.

PV
44 Level init is displayed
SP

4.2 Level Setpoint

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

PV
Selection of level init from option
45 Selection of level setpoint +
SP
SP, inp, iout, init
MAN#161R4/P7/26/311211/A

PV First parameter in level SP is


46 To enter setpoint level displayed
SP
4.2 Level Setpoint

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

or SP

or SP
Parameter to be displayed on
+ or SP
Selection of parameter to be second row is selected from
47 displayed on second row
OR
options :
or SP
+
SP1, SP2, SP3, SP4, INP2
or SP
Options seen according to
or SP number of relays / input configured

SP

PV diS2 parameter is stored & next


48* Storing of diS2 parameter is displayed.
SP Seen only for 2 inputs

+ SP
Selection of assignment of Relay 1 is assigned to Input 1
49* relay1
OR
or Input 2
+ SP

PV
Relay 1 assignment is stored &
50* Storing of relay1 assignment next parameter is displayed
SP

SP
Alarm type for relay1 is selected
SP from options :
+
Selection of alarm type FS.hi : High alarm
51* for relay1
OR SP
+ FS.Lo : Low alarm
SP heat : Heat mode
cool : Cool mode
SP

SP

SP

SP

Storing of alarm type for PV Relay1 alarm type is stored &


52* relay1 next parameter is displayed.
SP
Seen only if SP1.A is alarm type

Alarm mode is selected from


SP
options :
+ SP nonE
Selection of mode of alarm
53* OR Ltch : Latch mode
for relay1
+ SP hold : Hold mode
SP
Lt.ho : Latch + hold mode
(n.Lin : Non linear mode for cool
relay type)

PV
Alarm mode from relay1 is
Storing of alarm mode
54* PV stored and next parameter is
for relay1
displayed.
SP

PV
+
Set hysterisis/band1 value
55* for relay1
OR PV Hysterisis 1 is adjusted.
+
SP
MAN#161R4/P8/26/311211/A

PV Hysterisis / band is stored. Cycle


56* Storing of hysterisis 1/band 1 time for relay 1 is displayed
SP (seen only if SP1.A=heat or cool)

Cont...
Cont... Level Setpoint

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

+ PV
Set cycle time for
57* proportional mode
OR Adjust cycle time for relay1
+ SP

PV
Cycle time 1 is stored & next
58* Storing of cycle time1 parameter is displayed.
SP

Max limit of output power for SP1


+ PV (Seen only if cycle time1 is set to
59* Set maximum limit OR
a numerical value -
+ SP
proportional mode)

PV
Max limit is stored & next
60* Storing of maximum limit parameter is displayed
SP

+ Min limit of output power for SP1


PV
61* Set minimum limit OR (Seen only if cycle time1 is set to
+ SP a numerical value -
proportional mode)

PV Minimum limit is stored & next


62 Storing of minimum limit parameter is displayed.
SP (Seen only for 2 inputs)

+ SP
Selection of assignment of Relay 2 is assigned to
63 relay2
OR
Input 1 or Input 2
+ SP

PV
Relay 2 assignment is stored &
64 Storing of relay 2 assignment next parameter is displayed.
SP

SP

SP
Alarm type for relay2 is selected
from option :
SP FS.hi : High alarm
FS.Lo : Low alarm
+ SP
Selection of alarm type for du.hi : Deviation high alarm
65 relay2
OR
+ SP du.Lo : Deviation low alarm
bnd.i : Band in alarm
SP bnd.o : Band out alarm
SP
heat : heat mode
cool : cool mode
SP

PV Relay2 alarm type is stored &


Storing of alarm type for next parameter is displayed.
66 relay2 SP (Seen only if SP2.A is alarm type)

Alarm mode for relay 2 is selected


from options :
SP
nonE
+ SP Ltch : Latch mode
Selection of alarm mode hold : Hold mode
67 for relay 2
OR
+ SP Lt.ho : Latch + hold mode
(n.Lin : Non linear mode for cool
SP
relay type)

PV
Alarm mode from relay2 is
MAN#161R4/P9/26/311211/A

Storing of alarm mode


68 PV stored and next parameter is
for relay2
displayed.
SP

* Parameters visible only if controlling device is analog output. (C.dev = Anlg in level PID) Cont...
Cont... Level Setpoint

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

PV
+
Set hysterisis/band value for
69 relay2
OR PV Hysterisis 2/band 2 is adjusted.
+
SP

PV Hysterisis 2 / band 2 is stored.


Storing of hysterisis 2/ Cycle time for relay 2 is displayed.
70
band 2 SP (Seen only if SP2.A=heat or cool)

+ PV
Set cycle time for
71 proportional mode
OR Adjust cycle time for relay2
+ SP

PV
Cycle time for relay2 is stored &
72 Storing of cycle time next parameter is displayed.
SP

Maximum limit of output power


+ PV for SP2
73 Adjust max limit OR (Seen only if cycle time1 is set to
+ SP
a numerical value -
proportional mode)

PV
Maximum limit is stored &
74 Store max limit next parameter is displayed.
SP

Minimum limit of output


+ PV power for SP2 is adjusted.
75 Adjust min limit OR
(Seen only if cycle time2 is set to
+ SP
a numerical value -
proportional mode)

PV Minimum limit is stored &


76 Storing of minimum limit next parameter is displayed.
SP Seen only for 2 inputs

+ SP
Selection of assignment of Relay 3 is assigned to
77 relay3
OR
Input 1 or Input 2
+ SP

PV
Storing of relay 3 Relay 3 assignment is stored &
78 assignment next parameter is displayed.
SP

SP

SP
Alarm type for relay3 is selected
from options :
SP FS.hi : High alarm
FS.Lo : Low alarm
+ SP
du.hi : Deviation high alarm
79 Select alarm type for relay3 OR
+ SP du.Lo : Deviation low alarm
bnd.i : Band in alarm
SP bnd.o : Band out alarm
SP
heat : heat mode
cool : cool mode
SP

PV Relay3 alarm type is stored &


Storing of alarm type for next parameter is displayed.
80
MAN#161R4/P10/26/311211/A

relay3 SP (Seen only if SP3.A is alarm type)

Cont...
Cont... Level Setpoint
STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

SP Alarm mode for relay 3 is selected


from options :
+ SP
Selection of alarm mode nonE
81 for relay 3
OR
+ SP Ltch : Latch mode
hold : Hold mode
SP Lt.ho : Latch + hold mode

PV Alarm mode for relay3 is


Storing of alarm mode
82 stored and next parameter is
for relay3 SP displayed.

+ PV
83 Set hysterisis value for relay3 OR Hysterisis 3 is adjusted.
+ SP

PV
Hysterisis 3 is stored & next
84 Storing of hysterisis 3 parameter is displayed.
SP
(Seen only for 2 inputs)

+ SP
Selection of assignment of Relay 4 is assigned to
85 relay 4
OR
Input 1 or Input 2.
+ SP

PV
Relay 4 assignment is stored &
86 Storing of relay 4 assignment next parameter is displayed.
SP

SP

SP
Alarm type for relay4 is selected
from option :
SP FS.hi : High alarm
FS.Lo : Low alarm
+ SP
Select type of alarm for du.hi : Deviation high alarm
87 relay4
OR
+ SP du.Lo : Deviation low alarm
bnd.i : Band in alarm
SP bnd.o : Band out alarm
SP
heat : heat mode
cool : cool mode
SP

PV Alarm type is stored & next


Storing of alarm type for parameter is displayed
88 relay4 SP (Seen only if SP4.A is alarm type)

SP Alarm mode is selected from


options :
+ SP
nonE
89 Selection of alarm mode OR
+ SP Ltch : Latch mode
hold : Hold mode
SP Lt.ho : Latch + hold mode

PV Alarm mode for relay4


Storing of alarm mode
90 is stored and next parameter is
for relay4 SP displayed.

+ PV
91 Set hysterisis value for relay4 OR Hysterisis 4 is adjusted.
+ SP
MAN#161R4/P11/26/311211/A

PV
Hysterisis 4 is stored & next
92 Storing of hysterisis 4 parameter is displayed.
SP
LEVEL inP
STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

+ PV
Select inP level from options :
93 Selection of level input OR
SP, PID, iout, init
+ SP

PV
First parameter of level inP is
94 Enter level inP displayed
SP

95 To select input1 + SP
Select input from options :
OR TCK : K type thermocouple
+ SP TCE : E type thermocouple
TCJ : J type thermocouple
SP TCB : B type thermocouple
TCR : R type thermocouple
SP
TCS : S type thermocouple
SP TCT : T type thermocouple
TCN : N type thermocouple
SP TCG : G type thermocouple
TCC : C type thermocouple
SP
TCD : D type thermocouple
SP RTD : Pt100
CU53:
SP V.10 : 0~10 mV input
V.50 : 0~50 mV input
SP V.100 : 0~100 mV input
SP
V.200 : 0~200 mV input
V.1K : 0~1 V input
SP V.5K : 0~5 V input
V.10K : 0~10 V input
SP 0-10 : 0~10 mA input
0-20 : 0~20 mA input
SP
4-20 : 4~20 mA input
SP 20-4 : 20~4 mA input
Sqrt : Square root input
SP
Note : TC S, TC G, TC C, TC D ,
SP
Cu53, 0~10 mV, 0~100 mV,
SP
0~200 mV, 0~1 V, 0~5 V,
0~10 V & square root inputs
SP are available only in input
group 2
SP

SP

SP

SP

SP

SP

PV
Input is stored & next parameter is
96 Storing of input1 displayed
SP

Cont...
MAN#161R4/P12/26/311211/A
LEVEL inP
STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

SP
Unit is selected from options :
+ SP
Degree Centigrade
97 Selection of unit for display OR
Degree Farrenite
+ SP
Engineering unit for linear input only
SP

PV
Unit is stored & next parameter is
98 Storing of unit displayed
SP

SP
+ Resolution is selected from options :
Selection of resolution for 0.01 for linear input
99 display1 & input A
OR SP
+ 0.1
SP 1

PV
Resolution is stored and next
100 Storing of resolution parameter is displayed.
SP

+ PV
101 Set bias for input1 OR Adjust bias for input 1
+ SP

PV
Bias for input 1 is stored & next
102 Store bias for input 1 parameter is displayed.
SP

+ PV
Adjust the high scale value for
103 Set high scale value for input 1 OR
input1
+ SP

PV
Store high scale value for High scale for input1 is stored &
104 input1 next parameter is displayed
SP

+ PV
105 Set low scale value OR Adjust low scale value of input1
MAN#161R4/P13/26/311211/A

+ SP

Cont...
Cont... LEVEL inP
STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

PV
Low scale value 1 is stored & next
106 Storing of low scale1 parameter is displayed
SP

Maximum range of input is adjusted.


+ PV This parameter will be displayed only
Set maximum range of
107 OR if linear mV/V input type is selected
input1 selected
+ SP ( i.e. 0~50mV, 0~10 mV, 0~100mV,
0~1V, 0~5V, 0~10V)

PV
Storing of maximum range of Maximum range of input1 is stored
108 input1 & next parameter is displayed
SP

Minimum range of input is adjusted.


+ PV This parameter will be displayed only
109 Set minimum range of input1 OR if linear mV/V input type is selected
+ SP ( i.e. 0~50mV, 0~10 mV, 0~100mV,
0~1V, 0~5V, 0~10V)

PV
Storing of minimum range of Minimum range of input1 is stored &
110 input1 next parameter is displayed
SP

+ Second input function is selected


SP
Select second input as remote from options:
111 setpoint or as a process value
OR
+ SP rm.SP - remote setpoint
PV2 - Process value

PV
Second input function is stored &
112 Second input function is stored next parameter is displayed.
SP

+
Same as 95
113 To select input2 OR Same as 95 Except for square root input
+

PV
Input 2 is stored & next parameter
114 Storing of input 2 is displayed
SP

SP
Unit is selected from options :
SP
+ Degree Centigrade
115 Selection of unit for input 2 OR SP
Degree Farrenite
+ Engineering unit for linear input only
SP

PV
Unit 2 is stored & next parameter
116 Storing of unit for input 2 is displayed
SP

SP
+ Resolution is selected from options :
Selection of resolution for 0.01
117 input 2
OR SP
+ 0.1
SP 1
MAN#161R4/P14/26/311211/A

PV
Resolution 2 is stored & next
118 Storing of resolution 2 parameter is displayed
SP

Cont...
Cont... LEVEL inP

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

+ PV
119 Set bias of input2 OR Adjust bias for input 2
+ SP

PV
Bias for input 2 is stored & next
120 Store bias for input 2 parameter is displayed
SP

+ PV
121 Set high scale value for input2 OR Adjust high scale value for input2
+ SP

PV
Highscale2 is stored & next
122 Storing of high scale2 parameter is displayed
SP

+ PV
123 Set low scale value for input2 OR Adjust low scale value for input2
+ SP

PV
Low scale is stored & next
124 Storing of low scale2 parameter is displayed
SP

Maximum range of input is adjusted.


+ PV This parameter will be displayed only
Set maximum range of
125 OR if linear mV/V input type is selected
input2
+ SP ( i.e. 0~50mV, 0~10 mV, 0~100mV,
0~1V, 0~5V, 0~10V)

PV Maximum range of input2 is


Storing of maximum range of
126 stored & next parameter is
input2 SP displayed

Minimum range of input2 is adjusted.


+ PV This parameter will be displayed only
127 Set minimum range of input2 OR if linear mV/V input type is selected
+ SP ( i.e. 0~50mV, 0~10 mV, 0~100mV,
0~2V, 0~5V, 0~10V)

PV
Storing of minimum range of Minimum range is stored & next
128 input2 selected parameter is displayed
SP
MAN#161R4/P15/26/311211/A

Cont...
LEVEL iout

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

+ PV
Select iout from options:
129 Selection of output level OR
SP, inp, iout, init, PID
+ SP

PV First parameter in level iout is


130 Enter level iout displayed.
SP Seen only if C.dev = rLY/SSR

Output 1 is assignment is selected


+ SP
Selection of assignment of from options :
131 output 1
OR
inp1 : Assigned to input1
+ SP
inp2 : Assigned to input2

PV
Output1 assignment is stored &
132 Store output 1 assignment next parameter is displayed
SP

SP

SP
+
Select from options
133 Selection of type of output1 OR SP
0-20, 4-20, 20-4, 20-0, Volt output
+
SP

SP

PV
Output 1 type is stored & next
134 Storing of type of output 1 PV
parameter is displayed
SP

Set maximum power limit for PV


SPC (if C.dev=Anlg) or set +
135 high scale if analog output in OR PV Adjust the parameter
retransmission : +
SP
ie C.dev=rLY/SSr

PV
High scale output/maximum power
136 Store the parameter PV limit is stored & next parameter
is displayed
SP

Set minimum limit of output


power for SPC (if C.dev=anlg) PV
+
or
137 OR PV Adjust the parameter
Set low scale if analog output +
is in retransmission mode SP
MAN#161R4/P16/26/311211/A

i.e. C.dev=rLY/SSR

Cont...
Cont... LEVEL iout

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

PV
Low scale value for output 1 is stored
138 Storing of low scale for output 1 & next parameter is displayed.
SP

+ SP
Selection of asignment of Output 2 is assigned to :
139 output 2
OR
Input 1, Input 2 or function selected
+ SP

PV
Output 2 assignment is stored &
140 Storing of output 2 assignment next parameter is displayed
SP

SP

SP
+
Select from options
141 Selection of type of output2 OR SP
0-20, 4-20, 20-4, 20-0, Volt output
+
SP

SP

PV
Output 2 type is stored & next
142 Storing of type of output2 parameter is displayed
SP

+ PV
143 Set high scale for output2 OR Adjust high scale for output 2
+ SP

PV
High scale value for output2 is
144 Storing of high scale for output2 stored & next parameter is displayed
SP

+ PV
145 Set low scale value for output2 OR Adjust lowscale value of output 2
+ SP

PV Low scale value of output 2 is


Storing of low scale value for
146 stored & next parameter is
output2 SP displayed
MAN#161R4/P17/26/311211/A

Cont...
LEVEL CAL

To enter calibration level press , when version number is being displayed in “init” level.
Note : Do not proceed through this section unless there is definite need to re-calibrate the instrument. All previous calibration data
will be lost. Do not attempt recalibration unless you have available appropriate calibration equipment. If calibration data is lost,
you will need to return the instrument to your supplier who may charge you a service fee to recalibrate the instrument.

The instrument will calculate the constants while exiting from program mode & store them in memory. Calibration should be
done with all parameters properly set (I/P, unit etc.)

Complete calibration of the instrument requires calibration of


A. INPUT CALIBRATION
a) 0~50 mV
b) CJC
c) RTD
d) 4~20 mA input
e) Calibration of Input2
B. OUTPUT CALIBRATION
e) 4~20 mA output1
f) 4~20 mA output2

A. INPUT CALIBRATION

Calibrate the displayed reading from the front panel. With this facility the zero & span calibration errors can be adjusted.

Select “input” correctly from level input. For eg. for rtd calibration select input “Pt100”, for mV/TC calibration select input “V50”
(0~50 mV). For CJC calibration select input “TC K”. For mA calibration select input either “0~20” or “4~20”.

For better accuracy select maximum range of high scale & low scale (level input)

a) 0~50 mV Calibration (Select option “V50” of parameter “inp1” in level input)

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

PV
when version no.
147 Calibration level Level cal is selected
is displayed in level init SP

PV
First parameter of level cal
148 Enter level Cal
SP is displayed.

SP Select options
+
Calibration of 0~50mV Off : Calibration off
149 (input 1)
OR SP
+ On : Calibration on
SP Do : Allows to do calibration

PV
150 Calibration of input1
SP

PV
To calibrate higher limit, feed Uncalibrated high value is
151 50 mV through calibrator SP displayed.

+ PV
Adjust the display till it corresponds
152 Adjust the display OR
MAN#161R4/P18/26/311211/A

to the higher limit of input


+ SP

Cont...
Cont... Input Calibration

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

Store higher limit. To calibrate PV


153 lower limit feed 0mV through Uncalibrated low value is displayed
calibrator SP

+ PV
Adjust the display till it corresponds
154 Adjust the display OR
to lower limit of input selected
+ SP

PV
+ Calibration is saved & program
155 To save calibration & exit
SP enters run mode

b) CJC (TC K calibration. Select “tc K” option of parameter “inp1” in level input) :For CJC calibration short the input terminals
(ter11 & ter12) with K type thermocouple wire.

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

PV
when version no.
156 Calibration level Level cal is selected
is displayed in level init SP

PV
First parameter of level Cal is
157 Enter level Cal
SP displayed.

PV
+ Select options
Off : Calibration off
158 Calibration of TC K (input1) OR SP
+ On : Calibration on
SP Do : Allows to do calibration

PV
159 Calibration of CJC
SP

PV
160 Calibrate CJC Uncalibrated CJC is displayed.
SP

+ PV
Adjust the CJC till it corresponds
161 Adjust the display OR
+ SP to the standard thermometer

PV
Calibration is saved & program
MAN#161R4/P19/26/311211/A

162 To save calibration & exit +


SP enters run mode
c) Pt100 calibration (select option “rtd” of parameter “inp1” in level inp)

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

PV
when version no.
163 Calibration level Level cal is selected
is displayed in level init SP

PV
First parameter of level cal
164 Enter level Cal
SP is displayed.

SP Select options
+
Off : Calibration off
165 Calibration of Pt100 (input1) OR SP
+ On : Calibration on
SP Do : Allows to do calibration

PV
166 Calibration of Pt100
SP

To calibrate higher limit, feed PV


167 247.06 ohm(corresponding Uncalibrated high value is displayed.
to 400 °C) from decade box SP

+ PV
Adjust the display to the required
168 Adjust the display OR
temperature (400 °C)
+ SP

Store higher limit. To calibrate


PV
lower limit, feed 100ohm
169 (corresponding to 0 °C) Uncalibrated low value is displayed
SP
through decade box

+ PV
Adjust the display to required
170 Adjust the display OR
temperature (0°C)
+ SP

PV
+ Calibration is saved & program
171 To save calibration & exit
SP enters run mode

d) 4~20 mA input calibration. (Select option “4~20” of parameter “inp1” in level inp)

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

PV
when version no.
172 Calibration level Level cal is selected
is displayed in level init SP

PV
First parameter of level cal
173 Enter level Cal
is displayed.
MAN#161R4/P20/26/311211/A

SP

Cont...
Cont... Input Calibration

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

SP Select options
+
Off : Calibration off
174 Calibration of 4~20 mA (input1) OR SP
+ On : Calibration on
SP Do : Allows to do calibration

PV
175 Calibration of 4~20 mA
SP

PV
To calibrate higher limit, feed Uncalibrated high value of input
176 20mA through calibrator SP is displayed.

+ PV Adjust the display till it


177 Adjust the display OR corresponds to the higher limit
+ SP of input

Store higher limit. To calibrate PV


178 lower limit, feed 4mA through Uncalibrated low value is displayed
calibrator SP

+ PV
Adjust the display till it corresponds
179 Adjust the display OR
to the lower limit of input
+ SP

PV
+ Calibration is saved & program
180 To save calibration & exit
SP enters run mode

e) Calibration of Input2

i) Calibration of 0-50 mV. Select “v50” option of parameter “inp2” in level inp
STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

PV
when version no.
181 Calibration level Level cal is selected
is displayed in level init SP

PV
First parameter of level cal
182 Enter level Cal is displayed.
SP

PV
Parameter for calibration of input 2
183 Calibration of input 2 is displayed
SP

SP
+ Select options
Off : Calibration off
184 Calibration of 0~50 mV (input2) OR SP
MAN#161R4/P21/26/311211/A

On : Calibration on
+
SP Do : Allows to do calibration

Cont...
Cont... Input Calibration

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

PV
185 Calibration of 0~50mV
SP

PV
To calibrate higher limit, feed
186 50 mV through calibrator Uncalibrated high value is displayed.
SP

+ PV
Adjust the display till it corresponds
187 Adjust the display OR
to the higher limit of input
+ SP

Store higher limit. To calibrate PV


188 lower limit, feed 0mV through Uncalibrated low value is displayed
calibrator SP

+ PV
Adjust the display till it corresponds
189 Adjust the display OR
to lower limit of input selected
+ SP

PV
+ Calibration is saved & program
190 To save calibration & exit
SP enters run mode

Follow steps 182 to 190 to do calibration for other inputs (rtd, 4~20) of input 2

B. LINEAR OUTPUT CALIBRATION

Calibration of linear current / voltage output can be done through front panel. With this facility ZERO & SPAN calibration error in
current / voltage output can be adjusted.
Select “4-20” option of parameter “o1.ty” in level iout.
Connect current meter at the output terminal

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

PV
when version no.
191 Calibration level Level cal is selected
is displayed in level init SP

PV
First parameter of level cal
192 Enter level Cal is displayed.
SP

PV
Press key till Calibration parameter of output 1
193 Calibration of output 1 is displayed
display shows CL.01 SP

SP Select options
+
Off : Calbration off
194 Calibration of output 1 OR SP
+ On : Calibration on
SP Do : Allows to do calibration

PV
MAN#161R4/P22/26/311211/A

195 To do calibration of output 1


SP

Cont...
Cont... Linear Output Calibration

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

+ PV
Adjust the display till current output
196 Calibrate higher limit OR
+ SP on meter is 20 mA

PV
197 Store higher limit.
SP

+ PV
Adjust the display till current output
198 Calibrate lower limit OR
+ SP on meter is 4mA

PV
+ Calibration is saved & program
199 To save calibration & exit
SP enters run mode

Follow the above steps for calibration of current output2

5. SETPOINT MODE GUIDE


Press key to increment the value of the selected parameter & press key to decrement the value of the selected
parameter.

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

PV
200 Enter setpoint mode for 3 seconds While in run mode
SP

Adjust value of setpoint for


PV
control (can be set only if
201 input2 is not assigned as
OR SPC is adjusted
SP
remote setpoint)

PV
202 Storing of SPC SPC is stored & next parameter is
SP displayed.

PV
Setpoint1 is adjusted
203 Set value of setpoint1 OR
(only seen if C.dev = Anlg)
SP

PV
Adjusted setpoint1gets stored &
204 Storing of setpoint1 next parameter is displayed.
SP

PV
205 Set value of setpoint2 OR Setpoint2 is adjusted.
SP
MAN#161R4/P23/26/311211/A

Cont...
Cont... Setpoint Mode Guide

STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION

PV
Adjusted setpoint2 gets stored
206 Storing of setpoint2 & next parameter is displayed.
SP

PV
207 Set value of setpoint3 OR Setpoint3 is adjusted.
SP

PV
Adjusted setpoint3 gets stored
208 Storing of setpoint3 & next parameter is displayed.
SP

PV
209 Set value of setpoint 4 OR Setpoint4 is adjusted.
SP

PV
Store setpoint4 & exit from
210 setpoint mode Enter run mode
SP

6. TROUBLE SHOOTING
6.1 Error Message
Display Cause Solution

This message can occur while exiting from program mode. Press key which will show the wrongly
The cause is improper selection of some parameter. selected parameters & its value. Correct it.

This message occurs if input wires are not connected or Check input signal
broken

This message occurs in case of negative over range / Check input wiring
under range at input

This message occurs, if any parameter is corrupted Set the corrupted parameters to
their default values.

7. DATA CORRUPTION
In case of user programmed data corruption, a message 'dfLt' is given immediately on power on & the instrument does not
proceed further until the corrupted data is cleared by user.

The user has to reset the instrument by selecting “all” option of reset parameter in level init. Press & keys together
to go ahead. All parameters are set to their default values. Instrument now requires initial selection which includes input &
unit.

After pressing & keys together, it displays 'inpt none'. Select the desired input using + keys.

After selecting input, press key once, it displays 'unit none'. Select the desired unit using + keys.
MAN#161R4/P24/26/311211/A

When selection is over, press & keys together which will enable the instrument to enter 'run' mode.
8. DIP SETTING FOR NON STANDARD INPUT

DIP SWA DIP SWB


ON ON

1 2 3 4 5 6 7 8 1 2 3 4

SW1 SW2
INPUT
1 2 3 4 5 6 7 8 1 2 3 4
0~1 V OFF ON OFF ON OFF OFF OFF OFF ON ON OFF OFF
0~5 V OFF OFF ON ON OFF OFF OFF OFF ON ON OFF OFF
0~10 V ON OFF OFF ON OFF OFF OFF OFF ON ON OFF OFF
0~10 mV OFF OFF OFF OFF ON OFF OFF OFF OFF ON OFF OFF
0~100 mV OFF OFF OFF OFF ON OFF OFF OFF ON OFF ON OFF
0~200 mV OFF OFF OFF OFF ON OFF OFF OFF ON OFF OFF ON
TC/0~50 mV OFF OFF OFF OFF OFF OFF ON ON ON OFF OFF OFF
RTD/Cu53 OFF OFF OFF OFF OFF ON ON ON ON OFF OFF OFF
mA OFF OFF OFF OFF OFF OFF ON ON ON OFF OFF OFF
MAN#161R4/P25/26/311211/A
FOR COMMUNICATION PROTOCOL PLEASE REFER BELOW.

9. INTRODUCTION 13. FUNCTIONS

The MODBUS/RTU protocol is messaging structure, widely When a message is sent from a master to a slave device the
used to establish master - slave communications between function code tells the slave what kind of action to perform.
intelligent devices. A modbus message sent from a master to Generally, the following functions are implemented in Radix
slave tells the selected slave what to do and what MODBUS products :
information to send back. The MODBUS/RTU protocol
works with RS232, RS485 and RS422 standards. 03 READ HOLDING REGISTERS
16 PRESET MULTIPLE REGISTERS
10. SETTING THE SLAVE ADDRESS
14. ADDRESSES
Slave address (Serial ID) is programmable parameter. Refer
to instruction manual. Parameter Type Hex Absolute
address address
11. RADIX PRODUCTS INCORPORATING RO PV1-input1 Float 01 40001
MODBUS / RTU PROTOCOL
RO PV2-input2 Float 03 40003
At present, the following products have the MODBUS/RTU RW SPC Float 05 40005
protocol incorporated :
RW SP1 Float 07 40007
1. Programmable 16-channel scanner - ISOSCAN RW SP2 Float 09 40009
2. PID controller - X Series RW SP3 Float 0B 40011
3. Humidity & temperature controller - HX96A
RW SP4 Float 0D 40013
12. SETTINGS #RW
(write
Band rate 9600
Start bit 1 only in
Data bit 8 manual
Stop bit 1
Parity none mode) Output Power Float 11 40017
#RW AutoManual Integer 13 40019
status
RO Relay Status Integer 0F 40015
RO Alarm Status Integer 10 40016
RO 2nd row display Integer 14 40020
lndicator

15. RS-485 SYSTEM CONFIGURATION

ISOSCAN / X96P / HX96A is connected on RS485 bus. This consists of :

a) Host computer
b) RS232 to RS485 convertor
c) Intelligent devices (ISOSCAN, X96P, HX96A etc.)
d) RS485 bus

RS232 - to - RS485 Bus


RS485 Converter
DATA+
RS232
DATA-

VS GND
Upto 32 devices

LOCAL
D+ D- D+ D- D+ D-
MAN#161R4/P26/26/311211/A