VER 27.X
INSTRUCTIONS FOR USE
1. IMPORTANT SAFETY INFORMATION Input group 2
(common for both inputs)
Thermocouple : B, C, D, E, G, J, K, N, R, S, T
1.1 Installation RTD : Pt100, 3-wire, Cu53
Check that the supply voltage given to the instrument is as Current : 0~20 mA, 4~20 mA,
specified on the terminals of the instrument. To avoid shock Square root (for input 1)
hazard prevent live parts being touched and follow wiring Voltage : 0~50 mV
diagram and regulations. Through DIP selection following
voltage inputs are available :
1.2 Warranty 0~1 V, 0~5 V, 0~10 V, 0~10 mV,
0~100 mV, 0~200 mV
Radix Electrosystems Pvt. Ltd. warrants this product to be Transmitter supply (VTX) : 22 V nominal, 30 mA max
free of defects in workmanship and materials for one year Range limits : See Table 1
from the date of purchase. Accuracy : See Table 1
Cold junction compensation : Automatic
1. Defects in workmanship and materials will be serviced Sensor break protection : User programmable
free of charge during the warranty period. Labour
required for rectifying the defects is also covered by this INDICATION
warranty. Any further claims are excluded. Process variable : Upper : 4 digit, 7 segment
0.56” (14.2 mm) red LED display
2. Warranty servicing does not extend the period of Setpoint : Middle : 4 digit, 7 segment
warranty for the entire instrument or for the parts that 0.56” (14.2 mm) green LED
have been replaced. display
% output power : Lower : 3 digit, 7 segment
3. From the warranty are excluded : 0.39” (9.9 mm) red LED display
a) all damage caused by improper handling, e.g. non- Status indication : LEDs for relay status
observance of the operating instructions, subjecting LEDs for setpoint indication
the product to excessive heat, moisture, corrosion, etc. LED for auto/manual power
b) damage caused by the intervention of the buyer or by status
unauthorised third parties LEDs for communication
c) transport damage from the manufacturer to the
OUTPUTS
dealer or user or on the way to servicing No. of relays :1/2/3/4
d) parts subject to normal wear, e.g. relays. Relay contact type : NO-C-NC
4. Any liability for direct or indirect consequential damages Relay contact rating : 5A / 230V AC, resistive
SSR drive : 12 V DC drive signal for
caused by the instrument is excluded, even if the defect
external SSR
of the instrument is covered by the warranty.
No. of analog outputs : 0 / 1 / 2 (current or voltage)
Radix liability for any breach of this agreement shall not Current output : 4~20 mA / 0~20 mA / 20~4 mA /
exceed the purchase price paid. 20~0 mA isolated from input)
Maximum load for current : 500 ohms
5. Any further claims, based on any title, are excluded. output
Voltage output : 0-10 V / user specified
6. In case repair service is required under this factory Load for voltage output : >10 Kohms
warranty, please send the instrument, indicating the
exact address of the sender and defect, carefully AUTO/MANUAL OPERATION
packed, postage paid, to : Radix Microsystems, B-1, 2nd Function : Output power is increased /
Floor, Ghanshyam Indl. Estate, Off Veera Desai Road, decreased by UP/DOWN keys
in manual mode
Andheri (West), Mumbai - 400 053.
Auto / Manual transfer : Bumpless
2. OVERVIEW COMMUNICATION
Port : RS485
2.1 Introduction Protocol : Modbus RTU
X96P is a microcontroller based user programmable Slave ID : User programmable (1~256)
PID/ONOFF/Time proportional controller with 4 digit LED
upper display for displaying measured values, 4-digit LED OTHER
middle display for displaying settings and 3-digit LED lower Programming : Through 3 tactile keys
display for displaying output percentage power. Dimensions (in mm) : 96(H) x 96(W) x 100(D)
Mounting : Panel mount
X96P has two universal inputs, upto 4 relays upto 2 analog Panel cutout : 92 x 92 mm
outputs. It is operated by 4 user friendly keys. Supply voltage : a) 85~265 V AC, 50/60 Hz
b) 20~35 V DC (optional)
Power consumption : 4 watts maximum
2.2 Specifications Operating ambient
INPUTS temperature : 0~50 °C
No. of inputs : 2 (input 1, input 2) Relative humidity : Below 90%, non condensing
Input group 1
2.3 Power On
MAN#161R4/P1/26/311211/A
1
Displays setpoints (SPC, SP1, SP2,
2 Setpoint
(2) (5) (2) SP3 or SP4) or measured input2 value
3
SP
(SP) Display
(as selected by user)
4
MAN (7) Relay status When the relays get ON or OFF, the
(4)
indicator LEDs respective LEDs become, ON or OFF
A/M
P A
+
TRANSMITTER
+
X X
mV/VIN value of parameter.
S
SSR
NO Q B In program mode, at parameter “VEr” if
Y RLY Y pressed for 6 sec, allows to enter
C R B' mA INPUT
calibration level.
+
9
Z +
NC FOR 2-WIRE S
TRANSMITTER USING Scrolls forward through the
2-WIRE RTD : SHORT Q & R
INTERNAL SUPPLY programmable parameters in program
mode.
1 21 31 P 11 P
85~265 V
V AC/DC S
(8) Allows to increment the value of the
2 22 32 Q 12 Q
INPUT2* INPUT1 selected parameter.
3 X 23 X 33 R 13 R
*
In run mode, resets alarm when in latch
RLY1 4 Y RLY3* 24 Y 34 S 14 S
D+
alarm mode.
5 Z 25 Z 35 15
RS485*
6 X 26 X 36 16 Scrolls backward through the
D
RLY2
* 7 Y RLY4* 27 Y 37 CJC 17
programmable parameters in program
8 Z 28 Z 38
+
18
mode.
V/Iout2 * + Allows to decrement the value of the
VTX* 9 29 39 19
V/Iout1 * selected parameter.
10 30 20
STK-710
(9) Toggles between Automatic & manual
* - FACTORY OPTION A/M
control mode
TABLE 1
RANGE LIMITS RANGE IN WHICH TYPICAL ACCURACY WORST CASE
SENSOR / INPUT (°C / EU) ACCURACY IS SPECIFIED AT 30 °C ACCURACY
LOW SCALE HIGH SCALE LOW SCALE HIGH SCALE (°C / EU) (°C / EU)
Input Group 1
Pt - 6% Rh / Pt - 30% Rh (B) 400 1820 400 1820 ±3 ±5
Chromel / Constantan (E) -270 1000 0 1000 ±1 ±3
Iron / Constantan (J) -210 760 0 760 ±1 ±3
Chromel / Alumel (K) -270 1372 -50 1200 ±1 ±3
Nicrosil / Nisil (N) -270 1300 -50 1200 ±1 ±3
Pt / Pt - 13% Rh (R) 0 1760 400 1760 ±2 ±5
Pt / Pt - 10% Rh (S) 0 1760 400 1760 ±2 ±5
Copper / Constantan (T) -270 400 -200 400 ±1 ±3
Pt100, 3-wire -200 850 -200 600 ± 0.3 ± 1.0
Linear (0~50 mV, 0~20 mA, 4~20 mA) -1999 9999 -1999 9999 ± 5 EU ± 20 EU
Input Group 2
The following inputs are available in Input Group 2 in addition to inputs of Input Group 1.
Tungsten - 5% Rh / Tungsten - 26% Rh (C) 0 2320 0 2320 ±3 ±5
Tungsten - 3% Rh / Tungsten - 25% Rh (D) 0 2310 0 2310 ±3 ±5
Tungsten / Tungsten - 26% Rh (G) 0 2310 0 2310 ±3 ±5
MAN#161R3/P2/26/311211/A
LEVEL PID
STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION
+ PV
Selection of level PID from option
1 Selection of level PID OR
SP, inp, iout, init, PID
+ SP
PV
MAN#161R4/P3/26/311211/A
Cont...
Cont... LEVEL PID
PV
Control device is stored & next
4 Storing of control output device parameter is displayed
SP
PV
Control output mode is stored &
6 Storing of control output mode next para is displayed.
SP
SP
or Tuning options is selected from
+ SP Off : Tune off
7 Setting of tuning parameter OR or On : Tune on
+ SP At.Sp : Tune at setpoint
or
Park : All output’s disabled
SP
PV
Tuning parameter is stored & next
8 Storing of tuning parameter parameter is displayed.
SP
PV
PB unit is stored & next parameter
10 Storing of band unit is displayed.
SP
PV
Integral time is stored & next
12 Storing of Integral time parameter is displayed
SP
MAN#161R3/P4/26/311211/A
Cont...
Cont... LEVEL PID
PV
Derivative time is stored & next
14 Storing of derivative time parameter is displayed.
SP
PV
Approach control factor is stored &
16 Storing of approach control next parameter is stored.
SP
PV
Cycle time is stored & next parameter
18 Storing of cycle time is displayed.
SP
PV
Offset is stored & level pid is
20 Storing of offset displayed.
SP
LEVEL init
STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION
+ PV
Selection of level init from options :
21 Selection of level init OR
SP, inp, iout, PID
+ SP
PV
First parameter of level init is
22 Enter level init displayed
SP
MAN#161R4/P5/26/311211/A
Cont...
Cont... LEVEL init
PV
Burn option for relays is stored &
24 Storing of burn option for relays next parameter is displayed
SP
PV
Storing of burn option for analog Burn option for analog o/p is stored &
26 output next parameter is displayed
SP
PV
Pr.o1 is stored & next parameter
28 Storing of Pr.o1 is displayed
SP
PV
Pr.o2 is stored & next parameter
30 Storing of Pr.o2 is displayed
SP
PV
32 Storing of reverse / direct mode Next parameter is displayed
SP
MAN#161R4/P6/26/311211/A
Cont...
Cont... LEVEL init
PV
Setpoint lock is stored & next
34 Storing of setpoint lock parameter is displayed
SP
PV
Parameter lock is stored & next
36 Storing of parameter lock parameter is displayed
SP
PV
Software filter is stored & next
38 Storing of software filter parameter is displayed
SP
+ PV
39 Set serial ID for communication OR Adjust serial id for commn
+ SP
PV
42 To access next parameter Next parameter is displayed
SP
PV
44 Level init is displayed
SP
PV
Selection of level init from option
45 Selection of level setpoint +
SP
SP, inp, iout, init
MAN#161R4/P7/26/311211/A
or SP
or SP
Parameter to be displayed on
+ or SP
Selection of parameter to be second row is selected from
47 displayed on second row
OR
options :
or SP
+
SP1, SP2, SP3, SP4, INP2
or SP
Options seen according to
or SP number of relays / input configured
SP
+ SP
Selection of assignment of Relay 1 is assigned to Input 1
49* relay1
OR
or Input 2
+ SP
PV
Relay 1 assignment is stored &
50* Storing of relay1 assignment next parameter is displayed
SP
SP
Alarm type for relay1 is selected
SP from options :
+
Selection of alarm type FS.hi : High alarm
51* for relay1
OR SP
+ FS.Lo : Low alarm
SP heat : Heat mode
cool : Cool mode
SP
SP
SP
SP
PV
Alarm mode from relay1 is
Storing of alarm mode
54* PV stored and next parameter is
for relay1
displayed.
SP
PV
+
Set hysterisis/band1 value
55* for relay1
OR PV Hysterisis 1 is adjusted.
+
SP
MAN#161R4/P8/26/311211/A
Cont...
Cont... Level Setpoint
+ PV
Set cycle time for
57* proportional mode
OR Adjust cycle time for relay1
+ SP
PV
Cycle time 1 is stored & next
58* Storing of cycle time1 parameter is displayed.
SP
PV
Max limit is stored & next
60* Storing of maximum limit parameter is displayed
SP
+ SP
Selection of assignment of Relay 2 is assigned to
63 relay2
OR
Input 1 or Input 2
+ SP
PV
Relay 2 assignment is stored &
64 Storing of relay 2 assignment next parameter is displayed.
SP
SP
SP
Alarm type for relay2 is selected
from option :
SP FS.hi : High alarm
FS.Lo : Low alarm
+ SP
Selection of alarm type for du.hi : Deviation high alarm
65 relay2
OR
+ SP du.Lo : Deviation low alarm
bnd.i : Band in alarm
SP bnd.o : Band out alarm
SP
heat : heat mode
cool : cool mode
SP
PV
Alarm mode from relay2 is
MAN#161R4/P9/26/311211/A
* Parameters visible only if controlling device is analog output. (C.dev = Anlg in level PID) Cont...
Cont... Level Setpoint
PV
+
Set hysterisis/band value for
69 relay2
OR PV Hysterisis 2/band 2 is adjusted.
+
SP
+ PV
Set cycle time for
71 proportional mode
OR Adjust cycle time for relay2
+ SP
PV
Cycle time for relay2 is stored &
72 Storing of cycle time next parameter is displayed.
SP
PV
Maximum limit is stored &
74 Store max limit next parameter is displayed.
SP
+ SP
Selection of assignment of Relay 3 is assigned to
77 relay3
OR
Input 1 or Input 2
+ SP
PV
Storing of relay 3 Relay 3 assignment is stored &
78 assignment next parameter is displayed.
SP
SP
SP
Alarm type for relay3 is selected
from options :
SP FS.hi : High alarm
FS.Lo : Low alarm
+ SP
du.hi : Deviation high alarm
79 Select alarm type for relay3 OR
+ SP du.Lo : Deviation low alarm
bnd.i : Band in alarm
SP bnd.o : Band out alarm
SP
heat : heat mode
cool : cool mode
SP
Cont...
Cont... Level Setpoint
STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION
+ PV
83 Set hysterisis value for relay3 OR Hysterisis 3 is adjusted.
+ SP
PV
Hysterisis 3 is stored & next
84 Storing of hysterisis 3 parameter is displayed.
SP
(Seen only for 2 inputs)
+ SP
Selection of assignment of Relay 4 is assigned to
85 relay 4
OR
Input 1 or Input 2.
+ SP
PV
Relay 4 assignment is stored &
86 Storing of relay 4 assignment next parameter is displayed.
SP
SP
SP
Alarm type for relay4 is selected
from option :
SP FS.hi : High alarm
FS.Lo : Low alarm
+ SP
Select type of alarm for du.hi : Deviation high alarm
87 relay4
OR
+ SP du.Lo : Deviation low alarm
bnd.i : Band in alarm
SP bnd.o : Band out alarm
SP
heat : heat mode
cool : cool mode
SP
+ PV
91 Set hysterisis value for relay4 OR Hysterisis 4 is adjusted.
+ SP
MAN#161R4/P11/26/311211/A
PV
Hysterisis 4 is stored & next
92 Storing of hysterisis 4 parameter is displayed.
SP
LEVEL inP
STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION
+ PV
Select inP level from options :
93 Selection of level input OR
SP, PID, iout, init
+ SP
PV
First parameter of level inP is
94 Enter level inP displayed
SP
95 To select input1 + SP
Select input from options :
OR TCK : K type thermocouple
+ SP TCE : E type thermocouple
TCJ : J type thermocouple
SP TCB : B type thermocouple
TCR : R type thermocouple
SP
TCS : S type thermocouple
SP TCT : T type thermocouple
TCN : N type thermocouple
SP TCG : G type thermocouple
TCC : C type thermocouple
SP
TCD : D type thermocouple
SP RTD : Pt100
CU53:
SP V.10 : 0~10 mV input
V.50 : 0~50 mV input
SP V.100 : 0~100 mV input
SP
V.200 : 0~200 mV input
V.1K : 0~1 V input
SP V.5K : 0~5 V input
V.10K : 0~10 V input
SP 0-10 : 0~10 mA input
0-20 : 0~20 mA input
SP
4-20 : 4~20 mA input
SP 20-4 : 20~4 mA input
Sqrt : Square root input
SP
Note : TC S, TC G, TC C, TC D ,
SP
Cu53, 0~10 mV, 0~100 mV,
SP
0~200 mV, 0~1 V, 0~5 V,
0~10 V & square root inputs
SP are available only in input
group 2
SP
SP
SP
SP
SP
SP
PV
Input is stored & next parameter is
96 Storing of input1 displayed
SP
Cont...
MAN#161R4/P12/26/311211/A
LEVEL inP
STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION
SP
Unit is selected from options :
+ SP
Degree Centigrade
97 Selection of unit for display OR
Degree Farrenite
+ SP
Engineering unit for linear input only
SP
PV
Unit is stored & next parameter is
98 Storing of unit displayed
SP
SP
+ Resolution is selected from options :
Selection of resolution for 0.01 for linear input
99 display1 & input A
OR SP
+ 0.1
SP 1
PV
Resolution is stored and next
100 Storing of resolution parameter is displayed.
SP
+ PV
101 Set bias for input1 OR Adjust bias for input 1
+ SP
PV
Bias for input 1 is stored & next
102 Store bias for input 1 parameter is displayed.
SP
+ PV
Adjust the high scale value for
103 Set high scale value for input 1 OR
input1
+ SP
PV
Store high scale value for High scale for input1 is stored &
104 input1 next parameter is displayed
SP
+ PV
105 Set low scale value OR Adjust low scale value of input1
MAN#161R4/P13/26/311211/A
+ SP
Cont...
Cont... LEVEL inP
STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION
PV
Low scale value 1 is stored & next
106 Storing of low scale1 parameter is displayed
SP
PV
Storing of maximum range of Maximum range of input1 is stored
108 input1 & next parameter is displayed
SP
PV
Storing of minimum range of Minimum range of input1 is stored &
110 input1 next parameter is displayed
SP
PV
Second input function is stored &
112 Second input function is stored next parameter is displayed.
SP
+
Same as 95
113 To select input2 OR Same as 95 Except for square root input
+
PV
Input 2 is stored & next parameter
114 Storing of input 2 is displayed
SP
SP
Unit is selected from options :
SP
+ Degree Centigrade
115 Selection of unit for input 2 OR SP
Degree Farrenite
+ Engineering unit for linear input only
SP
PV
Unit 2 is stored & next parameter
116 Storing of unit for input 2 is displayed
SP
SP
+ Resolution is selected from options :
Selection of resolution for 0.01
117 input 2
OR SP
+ 0.1
SP 1
MAN#161R4/P14/26/311211/A
PV
Resolution 2 is stored & next
118 Storing of resolution 2 parameter is displayed
SP
Cont...
Cont... LEVEL inP
+ PV
119 Set bias of input2 OR Adjust bias for input 2
+ SP
PV
Bias for input 2 is stored & next
120 Store bias for input 2 parameter is displayed
SP
+ PV
121 Set high scale value for input2 OR Adjust high scale value for input2
+ SP
PV
Highscale2 is stored & next
122 Storing of high scale2 parameter is displayed
SP
+ PV
123 Set low scale value for input2 OR Adjust low scale value for input2
+ SP
PV
Low scale is stored & next
124 Storing of low scale2 parameter is displayed
SP
PV
Storing of minimum range of Minimum range is stored & next
128 input2 selected parameter is displayed
SP
MAN#161R4/P15/26/311211/A
Cont...
LEVEL iout
+ PV
Select iout from options:
129 Selection of output level OR
SP, inp, iout, init, PID
+ SP
PV
Output1 assignment is stored &
132 Store output 1 assignment next parameter is displayed
SP
SP
SP
+
Select from options
133 Selection of type of output1 OR SP
0-20, 4-20, 20-4, 20-0, Volt output
+
SP
SP
PV
Output 1 type is stored & next
134 Storing of type of output 1 PV
parameter is displayed
SP
PV
High scale output/maximum power
136 Store the parameter PV limit is stored & next parameter
is displayed
SP
i.e. C.dev=rLY/SSR
Cont...
Cont... LEVEL iout
PV
Low scale value for output 1 is stored
138 Storing of low scale for output 1 & next parameter is displayed.
SP
+ SP
Selection of asignment of Output 2 is assigned to :
139 output 2
OR
Input 1, Input 2 or function selected
+ SP
PV
Output 2 assignment is stored &
140 Storing of output 2 assignment next parameter is displayed
SP
SP
SP
+
Select from options
141 Selection of type of output2 OR SP
0-20, 4-20, 20-4, 20-0, Volt output
+
SP
SP
PV
Output 2 type is stored & next
142 Storing of type of output2 parameter is displayed
SP
+ PV
143 Set high scale for output2 OR Adjust high scale for output 2
+ SP
PV
High scale value for output2 is
144 Storing of high scale for output2 stored & next parameter is displayed
SP
+ PV
145 Set low scale value for output2 OR Adjust lowscale value of output 2
+ SP
Cont...
LEVEL CAL
To enter calibration level press , when version number is being displayed in “init” level.
Note : Do not proceed through this section unless there is definite need to re-calibrate the instrument. All previous calibration data
will be lost. Do not attempt recalibration unless you have available appropriate calibration equipment. If calibration data is lost,
you will need to return the instrument to your supplier who may charge you a service fee to recalibrate the instrument.
The instrument will calculate the constants while exiting from program mode & store them in memory. Calibration should be
done with all parameters properly set (I/P, unit etc.)
A. INPUT CALIBRATION
Calibrate the displayed reading from the front panel. With this facility the zero & span calibration errors can be adjusted.
Select “input” correctly from level input. For eg. for rtd calibration select input “Pt100”, for mV/TC calibration select input “V50”
(0~50 mV). For CJC calibration select input “TC K”. For mA calibration select input either “0~20” or “4~20”.
For better accuracy select maximum range of high scale & low scale (level input)
PV
when version no.
147 Calibration level Level cal is selected
is displayed in level init SP
PV
First parameter of level cal
148 Enter level Cal
SP is displayed.
SP Select options
+
Calibration of 0~50mV Off : Calibration off
149 (input 1)
OR SP
+ On : Calibration on
SP Do : Allows to do calibration
PV
150 Calibration of input1
SP
PV
To calibrate higher limit, feed Uncalibrated high value is
151 50 mV through calibrator SP displayed.
+ PV
Adjust the display till it corresponds
152 Adjust the display OR
MAN#161R4/P18/26/311211/A
Cont...
Cont... Input Calibration
+ PV
Adjust the display till it corresponds
154 Adjust the display OR
to lower limit of input selected
+ SP
PV
+ Calibration is saved & program
155 To save calibration & exit
SP enters run mode
b) CJC (TC K calibration. Select “tc K” option of parameter “inp1” in level input) :For CJC calibration short the input terminals
(ter11 & ter12) with K type thermocouple wire.
PV
when version no.
156 Calibration level Level cal is selected
is displayed in level init SP
PV
First parameter of level Cal is
157 Enter level Cal
SP displayed.
PV
+ Select options
Off : Calibration off
158 Calibration of TC K (input1) OR SP
+ On : Calibration on
SP Do : Allows to do calibration
PV
159 Calibration of CJC
SP
PV
160 Calibrate CJC Uncalibrated CJC is displayed.
SP
+ PV
Adjust the CJC till it corresponds
161 Adjust the display OR
+ SP to the standard thermometer
PV
Calibration is saved & program
MAN#161R4/P19/26/311211/A
PV
when version no.
163 Calibration level Level cal is selected
is displayed in level init SP
PV
First parameter of level cal
164 Enter level Cal
SP is displayed.
SP Select options
+
Off : Calibration off
165 Calibration of Pt100 (input1) OR SP
+ On : Calibration on
SP Do : Allows to do calibration
PV
166 Calibration of Pt100
SP
+ PV
Adjust the display to the required
168 Adjust the display OR
temperature (400 °C)
+ SP
+ PV
Adjust the display to required
170 Adjust the display OR
temperature (0°C)
+ SP
PV
+ Calibration is saved & program
171 To save calibration & exit
SP enters run mode
d) 4~20 mA input calibration. (Select option “4~20” of parameter “inp1” in level inp)
PV
when version no.
172 Calibration level Level cal is selected
is displayed in level init SP
PV
First parameter of level cal
173 Enter level Cal
is displayed.
MAN#161R4/P20/26/311211/A
SP
Cont...
Cont... Input Calibration
SP Select options
+
Off : Calibration off
174 Calibration of 4~20 mA (input1) OR SP
+ On : Calibration on
SP Do : Allows to do calibration
PV
175 Calibration of 4~20 mA
SP
PV
To calibrate higher limit, feed Uncalibrated high value of input
176 20mA through calibrator SP is displayed.
+ PV
Adjust the display till it corresponds
179 Adjust the display OR
to the lower limit of input
+ SP
PV
+ Calibration is saved & program
180 To save calibration & exit
SP enters run mode
e) Calibration of Input2
i) Calibration of 0-50 mV. Select “v50” option of parameter “inp2” in level inp
STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION
PV
when version no.
181 Calibration level Level cal is selected
is displayed in level init SP
PV
First parameter of level cal
182 Enter level Cal is displayed.
SP
PV
Parameter for calibration of input 2
183 Calibration of input 2 is displayed
SP
SP
+ Select options
Off : Calibration off
184 Calibration of 0~50 mV (input2) OR SP
MAN#161R4/P21/26/311211/A
On : Calibration on
+
SP Do : Allows to do calibration
Cont...
Cont... Input Calibration
PV
185 Calibration of 0~50mV
SP
PV
To calibrate higher limit, feed
186 50 mV through calibrator Uncalibrated high value is displayed.
SP
+ PV
Adjust the display till it corresponds
187 Adjust the display OR
to the higher limit of input
+ SP
+ PV
Adjust the display till it corresponds
189 Adjust the display OR
to lower limit of input selected
+ SP
PV
+ Calibration is saved & program
190 To save calibration & exit
SP enters run mode
Follow steps 182 to 190 to do calibration for other inputs (rtd, 4~20) of input 2
Calibration of linear current / voltage output can be done through front panel. With this facility ZERO & SPAN calibration error in
current / voltage output can be adjusted.
Select “4-20” option of parameter “o1.ty” in level iout.
Connect current meter at the output terminal
PV
when version no.
191 Calibration level Level cal is selected
is displayed in level init SP
PV
First parameter of level cal
192 Enter level Cal is displayed.
SP
PV
Press key till Calibration parameter of output 1
193 Calibration of output 1 is displayed
display shows CL.01 SP
SP Select options
+
Off : Calbration off
194 Calibration of output 1 OR SP
+ On : Calibration on
SP Do : Allows to do calibration
PV
MAN#161R4/P22/26/311211/A
Cont...
Cont... Linear Output Calibration
+ PV
Adjust the display till current output
196 Calibrate higher limit OR
+ SP on meter is 20 mA
PV
197 Store higher limit.
SP
+ PV
Adjust the display till current output
198 Calibrate lower limit OR
+ SP on meter is 4mA
PV
+ Calibration is saved & program
199 To save calibration & exit
SP enters run mode
PV
200 Enter setpoint mode for 3 seconds While in run mode
SP
PV
202 Storing of SPC SPC is stored & next parameter is
SP displayed.
PV
Setpoint1 is adjusted
203 Set value of setpoint1 OR
(only seen if C.dev = Anlg)
SP
PV
Adjusted setpoint1gets stored &
204 Storing of setpoint1 next parameter is displayed.
SP
PV
205 Set value of setpoint2 OR Setpoint2 is adjusted.
SP
MAN#161R4/P23/26/311211/A
Cont...
Cont... Setpoint Mode Guide
PV
Adjusted setpoint2 gets stored
206 Storing of setpoint2 & next parameter is displayed.
SP
PV
207 Set value of setpoint3 OR Setpoint3 is adjusted.
SP
PV
Adjusted setpoint3 gets stored
208 Storing of setpoint3 & next parameter is displayed.
SP
PV
209 Set value of setpoint 4 OR Setpoint4 is adjusted.
SP
PV
Store setpoint4 & exit from
210 setpoint mode Enter run mode
SP
6. TROUBLE SHOOTING
6.1 Error Message
Display Cause Solution
This message can occur while exiting from program mode. Press key which will show the wrongly
The cause is improper selection of some parameter. selected parameters & its value. Correct it.
This message occurs if input wires are not connected or Check input signal
broken
This message occurs in case of negative over range / Check input wiring
under range at input
This message occurs, if any parameter is corrupted Set the corrupted parameters to
their default values.
7. DATA CORRUPTION
In case of user programmed data corruption, a message 'dfLt' is given immediately on power on & the instrument does not
proceed further until the corrupted data is cleared by user.
The user has to reset the instrument by selecting “all” option of reset parameter in level init. Press & keys together
to go ahead. All parameters are set to their default values. Instrument now requires initial selection which includes input &
unit.
After pressing & keys together, it displays 'inpt none'. Select the desired input using + keys.
After selecting input, press key once, it displays 'unit none'. Select the desired unit using + keys.
MAN#161R4/P24/26/311211/A
When selection is over, press & keys together which will enable the instrument to enter 'run' mode.
8. DIP SETTING FOR NON STANDARD INPUT
1 2 3 4 5 6 7 8 1 2 3 4
SW1 SW2
INPUT
1 2 3 4 5 6 7 8 1 2 3 4
0~1 V OFF ON OFF ON OFF OFF OFF OFF ON ON OFF OFF
0~5 V OFF OFF ON ON OFF OFF OFF OFF ON ON OFF OFF
0~10 V ON OFF OFF ON OFF OFF OFF OFF ON ON OFF OFF
0~10 mV OFF OFF OFF OFF ON OFF OFF OFF OFF ON OFF OFF
0~100 mV OFF OFF OFF OFF ON OFF OFF OFF ON OFF ON OFF
0~200 mV OFF OFF OFF OFF ON OFF OFF OFF ON OFF OFF ON
TC/0~50 mV OFF OFF OFF OFF OFF OFF ON ON ON OFF OFF OFF
RTD/Cu53 OFF OFF OFF OFF OFF ON ON ON ON OFF OFF OFF
mA OFF OFF OFF OFF OFF OFF ON ON ON OFF OFF OFF
MAN#161R4/P25/26/311211/A
FOR COMMUNICATION PROTOCOL PLEASE REFER BELOW.
The MODBUS/RTU protocol is messaging structure, widely When a message is sent from a master to a slave device the
used to establish master - slave communications between function code tells the slave what kind of action to perform.
intelligent devices. A modbus message sent from a master to Generally, the following functions are implemented in Radix
slave tells the selected slave what to do and what MODBUS products :
information to send back. The MODBUS/RTU protocol
works with RS232, RS485 and RS422 standards. 03 READ HOLDING REGISTERS
16 PRESET MULTIPLE REGISTERS
10. SETTING THE SLAVE ADDRESS
14. ADDRESSES
Slave address (Serial ID) is programmable parameter. Refer
to instruction manual. Parameter Type Hex Absolute
address address
11. RADIX PRODUCTS INCORPORATING RO PV1-input1 Float 01 40001
MODBUS / RTU PROTOCOL
RO PV2-input2 Float 03 40003
At present, the following products have the MODBUS/RTU RW SPC Float 05 40005
protocol incorporated :
RW SP1 Float 07 40007
1. Programmable 16-channel scanner - ISOSCAN RW SP2 Float 09 40009
2. PID controller - X Series RW SP3 Float 0B 40011
3. Humidity & temperature controller - HX96A
RW SP4 Float 0D 40013
12. SETTINGS #RW
(write
Band rate 9600
Start bit 1 only in
Data bit 8 manual
Stop bit 1
Parity none mode) Output Power Float 11 40017
#RW AutoManual Integer 13 40019
status
RO Relay Status Integer 0F 40015
RO Alarm Status Integer 10 40016
RO 2nd row display Integer 14 40020
lndicator
a) Host computer
b) RS232 to RS485 convertor
c) Intelligent devices (ISOSCAN, X96P, HX96A etc.)
d) RS485 bus
VS GND
Upto 32 devices
LOCAL
D+ D- D+ D- D+ D-
MAN#161R4/P26/26/311211/A