Sie sind auf Seite 1von 2

HARD & SOFT ADDRESSABLE FIRE ALARM SYSTEMS

Network LED Driver


(NET-LD20 Part No. 37-525)

Description
The NET-LD20 is a module to provide an LED
mimic of the Quatro control panel zonal fire or
fault LEDs, the module is placed on the network
loop and is able to mimic the Quatro panel
zonal LEDs of all panels on the network loop.
Each module can drive 20 LED outputs and up to 32
modules can be installed on the network loop.

The module has 4 switch inputs that can be used to


silence internal buzzer, silence sounders, start sounders
and reset function of all nodes on the network when
configured as a controller.

The module is equipped with an internal buzzer which will


Features sound when any fire LED is lit.

20 LED outputs
Up to 32 modules per network loop
Applications
4 switch inputs
The main use for this module is to construct a remote
Internal buzzer zonal LED indication and/or a mimic graphic LED
Can be configured as a master or a slave indicator. It can also be used to construct multiple LED
mimic indicators as part of a network loop.
On board facility for firmware upgrade when needed
Each LED indication can also be used with sharing
Separate 24Vdc is required
indications from a multiple panel Network.

Dimensions (mm) Configuration


282 Each
27module can be configured as a master or a slave.
134 133 A master will make use of the switch inputs and when
configured as slave, then the switch inputs cannot be
used.

For multiple of modules used, only one can be allowed to


be configured as master.
146
133

No special software is required but the module has an on


board facility for firmware upgrade when needed.

This module is not powered by the network loop, thus a


separate 24Vdc is required.

Doc No. GLT-275-6-1 Issue No. 002 Date: 11/08/2015


HARD & SOFT ADDRESSABLE FIRE ALARM SYSTEMS
Mimic Graphic LED Indicator
A mimic LED panel can be constructed to suit
any customer requirements, including sizes
utilizing one or more NET-LD20 boards
The NET-LD20 board can also be configured to not only
indicate fire but also fault. This option will give ten fire
LEDs (red) and ten fault LEDs (yellow).

Inter Connections

1 2 3 4

QT+QT-NC QT+QT-NC QT+QT-NC QT+QT-NC


ZONES 1-20 ZONES 21-40 ZONES 41-60 ZONES 61-80

LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
ON OFF RE- BUZZER
SND SND SET OFF

A
B IN
NET-LD20 BUZZER ZONES
1-20
A +
B OUT -

(MASTER)
IN 24V

1A F2
A ONLY
B 500mA F3
MASTER MASTER ADDRESS
+
OUT 24V -

USB

LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
ON OFF RE- BUZZER
SND SND SET OFF

A
B IN
NET-LD20 BUZZER ZONES
21-40
A +
B OUT -

(SLAVE 1)
IN 24V

The NET-LD20 can connect on a network of more


1A F2
A ONLY
B 500mA F3
MASTER MASTER ADDRESS
+
OUT 24V -

than one panel, one mimic construction containing the


USB

necessary number of boards will be able to mimic all


programmed zones of the total network.
LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
ON OFF RE- BUZZER
SND SND SET OFF

ZONES
A
B IN
NET-LD20 BUZZER

41-60
A +
B OUT -

(SLAVE 2)
IN 24V

1A F2
A ONLY
B 500mA F3
MASTER MASTER ADDRESS
+
OUT 24V -

USB

LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
ON OFF RE- BUZZER
SND SND SET OFF

A
B IN
NET-LD20 BUZZER ZONES
61-80
A +
B -

(SLAVE 3)
OUT
IN 24V

1A F2
A ONLY
B 500mA F3
MASTER MASTER ADDRESS
+
OUT 24V -

USB

Doc No. GLT-275-6-1 Issue No. 002 Date: 11/08/2015