Sie sind auf Seite 1von 9

This article has been accepted for inclusion in a future issue of this journal.

Content is final as presented, with the exception of pagination.

IEEE TRANSACTIONS ON ENERGY CONVERSION 1

Contribution of VSC-HVDC to Frequency Regulation


of Power Systems With Offshore Wind Generation
Hongzhi Liu and Zhe Chen, Senior Member, IEEE

Abstract—Modern large wind farms are required to provide tors (SGs). In the event of a sudden loss of a large power supply
frequency regulation service like conventional synchronous gen- or a sudden increase in power demand, SGs are able to extract
eration units. The frequency support capability of modern wind kinetic energy from their rotating masses (inertial response) to
farms has been widely investigated and implemented. Remotely
located large offshore wind farms are probably connected to the slow down the rate of change of frequency (ROCOF) at the very
onshore system grid through voltage-source converter-based–high instant of the event. Soon after the disturbance, SGs will pro-
voltage direct current (VSC-HVdc) transmission systems. Due to vide an additional power (primary control reserve) to stabilize
the decoupling of VSC-HVdc and signal transmission delay, off- the deviated frequency at a new steady-state level due to the
shore wind farms may not be able to respond to the onshore grid droop setting of governors. In contrast, VSWTs that are inter-
frequency excursion in time and, consequently, the stability and
security of the power system will be put at risk, especially for those faced with ac power grid via voltage source converters (VSCs)
with high wind penetration. This paper proposes a coordinated are naturally considered inertia-less to ac power systems [3],
control scheme to allow VSC-HVdc link to contribute to the sys- [4], and may have no primary control reserve as the wind is not
tem frequency regulation by adjusting its dc-link voltage. By means controllable [5]. Thus, the integration of large OWFs along with
of this approach, the dc capacitors of VSC-HVdc are controlled to the decommissioning of conventional power plants is bound to
absorb or release energy so as to provide frequency support. To fur-
ther enhance the system frequency response, the frequency support reduce the system inertia and primary control reserve. Without
from VSC-HVdc is also finely coordinated with that from offshore countermeasures, this would put power system security at high
wind farm according to the latency of offshore wind farm respond- risk. To solve this problem, ancillary frequency support schemes
ing to onshore grid frequency excursion. The control scheme is have been equipped to VSWTs for active power control. In [6]–
evaluated for both underfrequency and overfrequency events, and
[8], control methods for converters were proposed to provide
results are presented to demonstrate its effectiveness.
short-term frequency support by utilizing the rotational kinetic
Index Terms—Frequency support, inertial response, offshore energy of VSWT’s generator. The implementation of energy
wind generation, voltage-source converter-based–high voltage di- reserve was also reported in [9] and [10] by forcing VSWT to
rect current (VSC-HVdc).
operate in a deloading mode by means of converter control and
pitch angle control.
I. INTRODUCTION Large OWFs are probably far away from onshore connection
INCE the beginning of this century, the installation of large point. To integrate a long-distance large-scale OWF into the on-
S offshore wind farms (OWFs) is speeding up, especially in
Europe. The generation of a large offshore wind farm could
shore power grid, voltage-source converter-based–high voltage
direct current (VSC-HVdc) transmission is more attractive and
be dozens of megawatt or even hundreds of megawatt, which applicable compared to HVAC transmission system [11]–[15].
well matches the generation of conventional power plants. With For transferring the same amount of power, dc cables are smaller
the increasing integration of large OWFs into power grids, it with lower losses and have no limitations in length owing to the
inevitably leads to the retirement of conventional power plants. immunity from charging current. VSC-HVdc transmission also
Therefore, to maintain the stability of power systems with high has other advantages, such as fully controlled power flow, inde-
wind penetration, modern large OWFs are required to be op- pendent reactive power control at each ac end, and independently
erated like conventional power plants. They need not only to controlled active and reactive power [13]–[16]. However, on one
supply energy, but also to provide ancillary services, such as hand, OWFs would not be directly affected by onshore system
voltage control and frequency regulation [1], [2]. disturbances due to the decoupling of VSC-HVdc. On the other
However, the electromechanical behavior of variable-speed hand, this decoupling would prevent OWFs from immediate re-
wind turbines (VSWTs), which comprise modern OWFs, differs sponding to system disturbances of the onshore ac network. For
fundamentally from that of conventional synchronous genera- a system frequency deviation, it is apparent that OWFs cannot
provide immediate frequency support following the frequency
Manuscript received June 5, 2014; revised January 18, 2015; accepted March
transient due to communication delay. VSC-HVdc, which per-
20, 2015. This work was supported in part by the Norwegian Centre for Offshore forms well on voltage support [17], [18], does not generally re-
Wind Energy (NORCOWE) under Grant 193821/S60 from the Research Council spond to the frequency deviation. In [19]–[21], the participation
of Norway. NORCOWE is a consortium with partners from industry and science,
hosted by the Christian Michelsen Research. Paper no. TEC-00409-2014.
of VSC-HVdc-connected OWFs in the system frequency regula-
The authors are with the Department of Energy Technology, Aalborg Univer- tion was investigated. However, all these studies focused only on
sity, 9100 Aalborg, Denmark (e-mail: liuhzer@hotmail.com; zch@et.aau.dk). developing artificial coupling methods between offshore and on-
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org.
shore networks using the VSC-HVdc link, but did not probe into
Digital Object Identifier 10.1109/TEC.2015.2417130 the potential frequency support capability of VSC-HVdc itself.

0885-8969 © 2015 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications standards/publications/rights/index.html for more information.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

2 IEEE TRANSACTIONS ON ENERGY CONVERSION

To fulfill the frequency support capability, an ancillary fre-


quency controller is designed and shown in Fig. 2. It can be
divided into two parts: underfrequency controller, that is, ac-
tivated if the measured frequency is under 49.8 Hz, and over-
frequency controller that is activated if the measured frequency
is over 50.2 Hz. In Fig. 2, the active power reference Pω ref is
determined by the wind turbine generator speed via a maximum
power tracking. The active power reference Punder (p.u.) and
Pover (%) are generated by the under- and over-frequency con-
trollers, respectively. The total active power reference value Pg∗
to the wind turbine generator is then given as
Pg∗ = Pω ref × Pover + Punder . (1)
Fig. 1. Structure and control of FCWT.

1) Underfrequency Controller: The underfrequency con-


An inertia emulation control (INEC) strategy for VSC-HVdc troller is used to enable the FCWT to provide inertial response
transmission systems is proposed in [22] and [23]. It used stored and release active power reserve if applicable, when the system
energy in the HVdc dc capacitors to provide an inertial response frequency drops lower than 49.8 Hz (nominal 50 Hz) that is
and contribute to primary frequency control of the studied ac determined by the author in the simulation experiments. From
network. However, the performance of the INEC was evaluated Fig. 2, it can be seen that the underfrequency controller is also
only in a relatively weak ac network with only one conventional composed of two components: inertia controller and droop con-
SG. Besides, the DFIG-based wind farm connected via the VSC- troller. A demonstrative diagram of the underfrequency con-
HVdc did not participate in system frequency regulation, and troller is shown in Fig. 3.
the dc capacitors employed in this study was relatively larger The inertia controller is applied to emulate the inertial re-
than common configuration. sponse of SGs and its output active power reference Pinertia
This paper explores the frequency regulation capability of is proportional to the derivative of the system frequency. The
VSC-HVdc that is used to integrate a large OWF into the on- droop controller is applied to emulate the response of the speed
shore power grid. A coordinated control strategy is proposed governor of a SG, and its output active power reference Pdro op
to simplify the transmission of onshore frequency signal to off- is proportional to the absolute deviation of the system nomi-
shore wind turbines, and to enable VSC-HVdc to provide inertial nal frequency. Hence, the output Punder of the underfrequency
response by means of partially charging/discharging of its dc ca- controller can be given as
pacitors. To further improve the system frequency response, the
cooperation with the frequency support from OWF is also con- dfm eas fnom − fm eas
Punder = −Kinertia · + (2)
sidered with respect to the latency of OWF responding to the dt R
onshore grid frequency disturbances. where Kinertia is the gain of the inertia controller, R is the
The organization of this paper is as follows. Section II adjusting coefficient of the droop controller, fm eas is the mea-
introduces the frequency support strategies for VSWTs and sured system frequency, and fnom is the nominal frequency of
VSC-HVdc. Section III presents the test power system and the power system.
methodology adopted in this study. Section IV reports a se- 2) Overfrequency Controller: Fundamentally, the overfre-
ries of case studies and simulation results. Section V presents quency controller reduces the current active power generation
the conclusions of this study. with a 40% gradient of the presently available power per hertz if
the measured frequency exceeds 50.2 Hz in terms of E.ON Grid
II. FREQUENCY SUPPORT STRATEGIES Code [27]. While coordinated with the ancillary frequency con-
A. Frequency Support Strategy for Wind Turbine trol of VSC-HVdc, a participation coefficient Kover has been
employed to offset the influence of regulation of VSC-HVdc
In this study, full-converter wind turbine (FCWT) is used on the peak frequency during overfrequency disturbances. The
and its detailed modeling can be found in [24]–[26]. Fig. 1 il- control is described as
lustrates the structure and control diagram of the FCWT that
is modeled in DIgSILENT/PowerFactory. The generator-side yo = 1 − Kgrad · (f − fup ) · Kover (3)
converter regulates the generator active power through the d-
where yo is the output control signal, f is the system frequency,
axis current controller and the generator voltage through q-axis
and fup is equal to 50.2 Hz, which is the activating threshold
current controller. The controller of the grid-side converter sta-
value. The value of Kover is determined according to the wind
bilizes the dc capacitor voltage, and maintains a unity power
capacity penetration level (WCPL), which is defined as
factor operation through d- and q-axis currents, respectively,
as well. In Fig. 1, Pm d and Pm q are the d-axis and q-axis total installed wind capacity (MW)
WCPL = × 100%.
pulse width indices, respectively, and the asterisked variables are total load capacity (MW)
references. (4)
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

LIU AND CHEN: CONTRIBUTION OF VSC-HVDC TO FREQUENCY REGULATION OF POWER SYSTEMS WITH OFFSHORE WIND GENERATION 3

Fig. 2. Ancillary frequency control for FCWT.

Fig. 4. Modified pitch angle controller.

Fig. 3. Demonstrative diagram of the underfrequency controller. wind turbine generator speed control and/or a pitch angle control
[9], [10].
Since the VSC-HVdc capacity as well as its dc capacitance In this study, rated wind speed is applied, and only pitch angle
is directly related to the connected wind farm rating, the WCPL control is implemented to realize primary frequency reserve of
can then be thought as an index to reflect the frequency support FCWT. To enable FCWT to provide an active power reserve
level of the VSC-HVdc using the proposed control. In this study, margin for frequency support, an angle increment Δβ is added
the WCPL is around 40% and, thus, Kover is assigned to “1.4.” to force the FCWT to operate in the deloading mode. The value
The reduction of generation of FCWT is achieved by increasing of Δβ determines the deloading level, namely the capacity of
the pitch angle. an active power reserve. A 10% deloading level (Δβ ≈ 1.7◦ ) is
3) Primary Frequency Reserve Implementation: Conven- set for frequency regulation study, and the modified pitch angle
tional synchronous generating units are able to provide primary controller is shown in Fig. 4.
frequency reserve within 30 s. As mentioned above, when a
frequency disruption occurs, the governor of a convention SG
B. Frequency Support Strategy for VSC-HVdc
detects the frequency decline, and then increases its mechani-
cal power output to drive the SG to generate additional active VSC-HVdc transmission system is attractive for connecting
power. As a result, the imbalance between the power demand remotely located OWFs to the onshore main grid. From the point
and supply is reduced or eliminated, and the system frequency of view of a power system, it acts as a zero-inertia generator
is stabilized at an off-nominal point. that can control active and reactive power instantaneously. The
Dissimilarly, VSWTs are inherently noncapable of providing scheme of the VSC-HVdc used in this study is shown in Fig. 5.
primary frequency reserve due to the uncontrollability of the The offshore VSC is responsible for collecting power gen-
wind speed. However, with customized control strategies, the erated by the OWF. Due to the decoupling of VSC-HVdc, it
FCWT can generate less active power than its available capa- operates as a reference machine to set reference frequency, volt-
bility. The margin between the actual generation and available age amplitude, and phase angle for the offshore network. The
generation can be considered as a primary frequency reserve. onshore VSC controls the power flow to the onshore grid by
To obtain the active power reserve margin, the FCWT must op- controlling the dc-link voltage and voltage amplitude at the
erate in a deloading mode instead of in the maximum power connection point. A constant dc-link voltage indicates an ac-
extraction mode. The deloading operation can be achieved by a tive power balance between onshore and offshore VSCs, which
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

4 IEEE TRANSACTIONS ON ENERGY CONVERSION

Fig. 7. Equivalent circuit of a VSC. (a) AC side. (b) DC side.

Fig. 5. Generic scheme of the VSC-HVdc. [28]. The two sides are coupled each other with a controlled
voltage source and a controlled current source
    
d isd −R/L ω isd
=
dt isq −ω −R/L isq
 
1 −vsd + vcd
+ (5)
L −vsq + vcq
3
Pac = (vcd · isd + vcq · isq ). (6)
2

and the dc-side can be given as


Fig. 6. Modified offshore VSC control with an ancillary frequency control. Pdc = Idc · Vdc . (7)
According to the law of energy conservation and from
means that the active power entering VSC-HVdc is equal to the Fig. 7(b), we can get
active power leaving it.
dVdc
Basically, in the mentioned scheme, the VSC-HVdc system Pdc = Pac + C · · Vdc . (8)
itself cannot provide addition active power to support an onshore dt
grid frequency excursion. It even blocks the OWF from directly Then, by substituting (6) and (7) into (8), we can have
responding to the state changes of the onshore grid. In other 3 dVdc
words, the existence of the VSC-HVdc actually deteriorates the Idc · Vdc = (vcd · isd + vcq · isq ) + C · · Vdc . (9)
2 dt
participation of FCWT-based OWFs in a system frequency reg-
From (9), it can be seen that to ensure the power balance
ulation. Hence, to cope with this impairment, a new frequency
between the offshore and onshore VSCs, the dc voltage must be
support strategy for VSC-HVdc is developed.
controlled constant. However, since the capacitor is an energy
1) Frequency Signaling: Generally, the control and measure-
storage element, it is obvious that it can be used to release or
ment data are transmitted to individual FCWTs via standard
absorb power by leveling down or up its voltage. The energy
SCADA link. However, this direct communication method has
change Wc and power change pc of a capacitor from t1 to t2 can
a relatively longer latency that is not suitable for events that
be expressed as
FCWTs are required to respond instantly.
 V d c (t 2 )
Therefore, instead of setting the reference frequency at a con-
stant value for the offshore grid, the offshore VSC is controlled Wc = C Vdc · dVdc (10)
V d c (t1)
to vary the reference frequency fwf along with the onshore grid
frequency fgrid by adding an ancillary control loop as shown in dWc (t1 , t2 )
Pc = . (11)
Fig. 6, in which Pm is the magnitude of the pulse width modula- dt
tion index, and F0 is the input frequency to VSC, which allows Therefore, it is realistic to exploit this characteristic of dc
varying the frequency of the output voltage. In the ancillary fre- capacitor of VSC-HVdc for grid frequency regulation. By means
quency signaling loop, the grid frequency fgrid is transmitted of adjusting the dc-link voltage, VSC-HVdc is able to inject
via the communication interface of the VSC-HVdc. In this way, more or less active power into the onshore grid than that it
the onshore grid frequency signal is contained in the offshore collects from the offshore wind farm.
electrical waveforms. Thus, individual offshore FCWTs can de- For this specific purpose, an ancillary dc voltage controller
tect the onshore grid frequency disturbance by monitoring the is proposed, and the modified onshore VSC control is shown in

offshore grid frequency and react swiftly. Fig. 8. The additional dc voltage reference Vdcf is determined
2) Ancillary DC Voltage Control: Fig. 7 shows the equivalent by the frequency deviation, which is passed to a first-order lag
ac-side and dc-side circuits of a VSC, in which R represents the with gain Kf . To control the energy-releasing speed of the dc
loss of the VSC and the VSC reactor, L is the reactor inductance, capacitors, the time constant Tf of the first-order lag is also
Vs is the grid bus voltage, and Vc is the VSC output voltage [13], tuned in terms of the latency of the communication interface of
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

LIU AND CHEN: CONTRIBUTION OF VSC-HVDC TO FREQUENCY REGULATION OF POWER SYSTEMS WITH OFFSHORE WIND GENERATION 5

Fig. 8. Modified onshore VSC control with ancillary frequency control.


the VSC-HVdc system. This value of Vdcf is limited to ±0.1 p.u. In this study, the system frequency excursion is carried out by
of the nominal dc voltage, but in realistic applications, it should step increase/decrease of Load C. A step increase of 46% active
be determined with respect to insulation requirements, PWM power and 10% reactive power of Load C is simulated at 1.0 s
functionality etc. In such a way, when the frequency deviation is to cause an underfrequency event. This results in the system
recognized, the change rate of dc voltage is controlled according frequency to drop to nearly 49.0 Hz without frequency supports
to the communication latency between the stations of VSC- from OWF and VSC-HVdc. Similarly, the overfrequency event
HVdc. The voltage changes faster when the latency is shorter is resulted from a step decrease of 20% active power and 5%
and slower when the latency is longer. That also represents that reactive power of Load C at 1.0 s. During the event, the maxi-
the dc capacitors are able to release its energy continuously until mum frequency is around 50.4 Hz if the OWF and VSC-HVdc
wind turbines start to react to the grid frequency deviation. do not participate in the frequency regulation.
The ancillary dc voltage controller is activated when the grid To evaluate the proposed control strategies, a 10% reserve
frequency is out of the range 49.8–50.2 Hz. Once the grid fre- margin setting of FCWTs is implemented by pitch angle adjust-
quency is lower than 49.8 Hz, the dc voltage is controlled down ment. For different frequency events, cases listed in Table II are
to 0.9 p.u. to release a part of the stored energy in the dc ca- studied in the simulations.
pacitance. When the grid frequency is higher than 50.2 Hz, the
dc voltage is controlled up to 1.1 p.u. to absorb the energy IV SIMULATIONS
transmitted from the offshore VSC. Since the dc capacitance
and voltage variation for a certain VSC-HVdc are limited, the The modeling and simulations in this study are conducted in
power released/absorbed by the dc capacitance is also limited. DIgSILENT/PowerFactory 14.1.
Therefore, in this study, the VSC-HVdc is controlled to provide
efficient frequency support until the offshore FCWTs sense the A. Underfrequency Event
onshore grid frequency disturbance and start to respond to it. Fig. 10 presents the simulation results for the sudden load in-
crease with 300 ms latency of VSC-HVdc communication inter-
face. The frequency response of the ac power system is shown in
III. STUDIED SYSTEM
Fig. 10(a). It is observed that the frequency support from the off-
The power system presented in Fig. 9 has been used for this shore wind farm makes up active power for the load increase and
study. It is derived from [29]. It consists of three conventional reduces the frequency drop significantly. The frequency is also
power plants: one medium fast hydropower plant, one fast gas stabilized much faster at a higher steady-state value compared to
turbine, and one coal-fired power plant. The three plants are the case without offshore wind farm frequency support. More-
connected on the 230-kV level via a closed ring with overhead over, the participation of frequency support from VSC-HVdc
lines. Load A, B, and C are aggregated static loads and Load D improves the nadir frequency further. However, due to the la-
is composed of induction motors. tency of measurement and the VSC-HVdc communication, the
A large FCWT-based OWF rated at 135 MW is integrated initial ROCOF of the frequency decline is not ameliorated evi-
into the grid via VSC-HVdc on Bus 5 (PCC). That means that dently though both offshore wind farm and VSC-HVdc provide
wind power supplies about 40% of the grid’s load consumption. frequency support.
The OWF in this study operates at rated wind speed for the The offshore wind farm generation is shown in Fig. 10(b).
duration of the simulating time, and the power system operates It can be seen that if the ancillary frequency controller is not
at 50 Hz. The parameters of the simulated VSC-HVdc are listed activated, the operation of FCWTs is not affected due to the de-
in Table I. coupling of converters. In the cases that the frequency controller
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

6 IEEE TRANSACTIONS ON ENERGY CONVERSION

Fig. 9. Studied system.


TABLE II
TABLE I STUDY CASES
PARAMETERS OF THE SIMULATED VSC-HVdc

Case Description
VSC rated power 150 MVA
1 Without any frequency support
VSC-rated ac rms voltage 150 kV 2 Frequency support from offshore wind farm only
VSC-rated dc voltage ±150 kV 3 Frequency support from both offshore wind farm and VSC-HVdc
Copper loss 0 kW
No-load loss 0kW
DC capacitor 450 μF × 4

maintains at the rated level again. When the ancillary frequency


controller of VSC-HVdc is activated, the dc voltage is con-
of FCWTs is activated, it can be observed that at the instant that trolled to drop down to 0.9 p.u. quickly as shown in Fig. 10(c)
the frequency drop is detected by the FCWTs, there is a sudden to release part of the power stored in dc capacitance. In conse-
increase of the active power generation of the offshore wind farm quence, the onshore VSC is able to infeed more active power
as a result of the decrease of both turbine generator speed and into the onshore grid to support the frequency as illustrated in
pitch angle. The participation of VSC-HVdc in the frequency Fig. 10(d). This coordinated frequency regulation of offshore
regulation does not exert evident influence on the generation of wind farm and VSC-HVdc obtains better frequency response as
the OWF. mentioned above.
Fig. 10(c) and (d) presents the response of VSC-HVdc for The influence of frequency support from the offshore wind
the load increase. It can be seen from curves of Case 2 that the farm and VSC-HVdc on main grid spinning reserve is illustrated
onshore VSC increases its active power output [see Fig. 10(d)] in Fig. 10(e). The grid spinning reserve is the summation of the
as offshore wind farm starts to generate more power to sup- spinning reserve of all conventional SGs. It is obvious that en-
port the frequency [see Fig 10(b)], while only offshore wind abling frequency support from offshore wind farm has positive
farm responds to the frequency decline. Accordingly, the dc effect on the grid spinning reserve, whereas the frequency sup-
voltage in Fig. 10(c) fluctuates a bit at the time that the active port from VSC-HVdc barely affects the system spinning reserve
power output of the onshore VSC increases sharply and then due to its short activation time.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

LIU AND CHEN: CONTRIBUTION OF VSC-HVDC TO FREQUENCY REGULATION OF POWER SYSTEMS WITH OFFSHORE WIND GENERATION 7

Fig. 11. System response for sudden load decrease. (a) System frequency.
Fig. 10. System response for sudden load increase. (a) System frequency. (b) OWT active power. (c) HVdc dc-link voltage. (d) Onshore VSC active
(b) OWT active power. (c) HVdc dc-link voltage. (d) Onshore VSC active power. (e) Total spinning reserve of the grid.
power. (e) Total spinning reserve of the grid.

obviously. However, without special coordination, the participa-


B. Overfrequency Event
tion of VSC-HVdc in overfrequency regulation aggravates the
A sudden decrease of Load C results in the frequency to be restoration of the frequency as observed by comparing “Case2”
over the upper acceptable limit (50.2 Hz). The simulation results with “Case3 without Kover .” By introducing the participation
for the sudden load decrease scenario are shown in Fig. 11, while coefficient Kover to the overfrequency controller of FCWTs
the communication delay of VSC-HVdc is also 300 ms. in the case “Case3 with Kover = 1.4,” it can be seen that the
The system frequency response is shown in Fig. 11(a). It negative impact of the support from VSC-HVdc on frequency
can be seen that the frequency support provided only by the restoration is alleviated.
offshore wind farm does not improve the initial frequency dy- Fig. 11(b) presents the offshore wind farm generation re-
namics but reduces the peak frequency and achieves signifi- garding the given overfrequency event. According to (3), the
cant enhancement on the frequency restoration. Comparably, reduction in the offshore wind farm generation is proportional
the joint frequency support provided by both offshore wind farm to the overfrequency deviation. As above mentioned, the VSC-
and VSC-HVdc further lowers down the peak frequency more HVdc support reduces the peak frequency. However, it, in turn,
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

8 IEEE TRANSACTIONS ON ENERGY CONVERSION

covers the actual severity of the frequency variation to FCWTs wind farm directly affects the strength of the inertial response
and, thus, weakens the FCWTs’ frequency support as the red from the VSC-HVdc.
curves illustrate in Fig. 11(a) and (b). The correction is done by This proposed control strategy could probably be adapted to
the employment of participation coefficient Kover . By compari- the VSC multiterminal HVdc system, which is of great interest
son between “Case2” and “Case3 with Kover = 1.4,” it is clear to many authorities these days. If this is the case, a dedicated
that the wind farm active power in “Case 3 with Kover = 1.4” communication system as well as a coordinated control strategy
is very close to that in “Case 2.” seems to be indispensable. The proposed scheme is to coordi-
Fig. 11(c) and (d) presents the response of VSC-HVdc for nately control a wind farm and a VSC-HVdc system that is used
the sudden load reduction. It can be observed from Fig. 11 that to connect the wind farm to an onshore power grid. It may also
in the frequency-rising period, the dc voltage is controlled to apply to other wind farm technologies, including DFIG systems.
increase to let the dc capacitors charge and absorb energy that In principle, the wind farm needs to have a relevant power con-
slows down the ROCOF and reduces the absolute frequency trol method adapted, if a VSC-HVdc is used for connecting it
deviation. After the offshore wind farm reduces its generation to the main power grid.
as a response to the overfrequency as shown in Fig. 11(b), the dc It is foreseeable that with the large-scale development and
voltage begins to drop [see Fig. 11(c)], and the dc capacitors then utilization of offshore wind power and VSC-HVdc interconnec-
begin to discharge and release energy that impairs the frequency tions, the participation of OWFs and VSC-HVdc transmissions
restoring. The charging and discharging of dc capacitance are in the system voltage and frequency regulation will play a sub-
reflected in the active power output of onshore VSC as shown stantial role. Hence, the significance of the method provided
in Fig. 11(d). The influence of the introduction of Kover on dc herein becomes more notable.
voltage and onshore VSC active power output are also clearly
presented in Fig. 11(c) and (d), respectively. REFERENCES
Fig. 11(e) shows the changes for the sudden load reduc-
[1] J. Matevosyan, T. Ackermann, and S. Bolik, “Technical regulations for
tion with respect to main grid spinning reserve. By com- the interconnection of wind farms to the power systems,” in Wind Power
parison, it is apparent from Fig. 11(e) that the frequency in Power Systems. Hoboken, NJ, USA: Wiley, 2005, pp. 115–142.
support from VSC-HVdc smoothes the fluctuations in spinning [2] G. Lalor, J. Ritchie, S. Rourke, D. Flynn, and M. J. O’Malley, “Dynamic
frequency control with increasing wind generation,” in Proc. IEEE Power
reserve. Eng. Soc. Gen. Meet., 2004, vol. 2, pp. 1715–1720
[3] G. Lalor, A. Mullane, and M. O”Malley, “Frequency control and
wind turbine technologies,” IEEE Trans. Power Syst., vol. 20, no. 4,
V. CONCLUSION pp. 1905–1913, Nov. 2005.
[4] E. Vittal, J. D. McCalley, V. Ajjarapu, and T. Harbour, “Wind penetration
A new control strategy is developed in this paper to al- limited by thermal constraints and frequency stability,” in Proc. 39th North
low the VSC-HVdc transmission to contribute to the system Amer. Power Symp., 2007, pp. 353–359.
[5] J. Morren, S. W. H. De Haan, W. L. Kling, and J. A. Ferreira, “Wind
frequency regulation without additional investment. The ancil- turbines emulating inertia and supporting primary frequency control,”
lary frequency controller added to the offshore VSC simplifies IEEE Trans. Power Syst., vol. 21, no. 1, pp. 433–434, Feb. 2006.
frequency signal communicating and reduces the latency of off- [6] J. F. Conroy and R. Watson, “Frequency response capability of full con-
verter wind turbine generators in comparison to conventional generation,”
shore wind farm responding to the onshore grid frequency de- IEEE Trans. Power Syst., vol. 23, no. 2, pp. 649–656, May 2008.
viation. The ancillary frequency controller added to the onshore [7] S. E. Itani and G. Joos, “Assessment of inertial potential of variable-
VSC utilizes the dc capacitor banks to release/absorb energy by speed wind turbines,” in Proc. IEEE Energy Convers. Cong. Expo., 2011,
pp. 851–856.
adjusting its voltage to fluctuate in a certain range. As a conse- [8] G. C. Tarnowski, P. C. Kjar, P. E. Sorensen, and J. Ostergaard, “Variable
quence, the VSC-HVdc is able to respond to system frequency speed wind turbines capability for temporary over-production,” in Proc.
excursion almost immediately and vary its active power output IEEE Power Energy Soc. Gen. Meeting, 2009, pp. 1–7.
[9] Z. S. Zhang, Y. Z. Sun, J. Lin, and G. J. Li, “Coordinated frequency
to support the system frequency. regulation by doubly fed induction generator-based wind power plants,”
The implementation of the proposed control strategy is de- IET Renew. Power Gener., vol. 6, pp. 38–47, 2012.
liberately coupled with the frequency control of the FCWTs of [10] J. M. Mauricio, A. Marano, A. Gomez-Exposito, and J. L. Martinez
Ramos, “Frequency regulation contribution through variable-speed wind
the offshore wind farm, which is integrated into the onshore energy conversion systems,” IEEE Trans. Power Syst., vol. 24, no. 1,
power grid by the VSC-HVdc. Through simulations and anal- pp. 173–180, Feb. 2009.
ysis, it is shown that the proposed control strategy allows the [11] S. K. Chaudhary, R. Teodorescu, and P. Rodriguez, “Wind farm grid in-
tegration using VSC based HVDC transmission—An overview,” in Proc.
VSC-HVdc to provide effective inertial response without any IEEE Energy 2030 Conf., 2008, pp. 1–7.
extra investment. The coordination of the frequency control of [12] D. Jovcic and N. Strachan, “Offshore wind farm with centralised power
the VSC-HVdc and wind turbines obtains a significantly en- conversion and DC interconnection,” IET Gener. Transmiss. Distrib.,
vol. 3, pp. 586–595, 2009.
hanced frequency response for the studied power system. The [13] L. Xu, L. Z. Yao, and C. Sasse, “Grid integration of large DFIG-based
collective frequency support capability is comparable to that of wind farms using VSC transmission,” IEEE Trans. Power Syst., vol. 22,
conventional power plants. no. 3, pp. 976–984, Aug. 2007.
[14] A. Arulampalam, G. Ramtharan, N. Jenkins, V. K. Ramachandaramurthy,
However, subject to the VSC-HVdc dc-link voltage and dc J. B. Ekanayake, and G. Strbac, “Trends in wind power technology
capacitor capacity constraints, the amount of the energy re- and grid code requirements,” in Proc. Int. Conf. Ind. Inf. Syst., 2007,
leased/absorbed by the dc capacitors is limited and, therefore, pp. 129–134.
[15] A. Reidy and R. Watson, “Comparison of VSC based HVDC and HVAC
the frequency support from VSC-HVdc is only temporary. In interconnections to a large offshore wind farm,” in Proc. IEEE Power Eng.
view of this, the frequency-responding latency of the offshore Soc. Gen. Meeting, 2005, vol. 1, pp. 1–8 .
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

LIU AND CHEN: CONTRIBUTION OF VSC-HVDC TO FREQUENCY REGULATION OF POWER SYSTEMS WITH OFFSHORE WIND GENERATION 9

[16] L. Xu and B. R. Andersen, “Grid connection of large offshore wind farms [28] Z. Guibin, Z. Xu, and Y. Cai, “An equivalent model for simulating VSC
using HVDC,” Wind Energy, vol. 9, pp. 371–382, 2006. based HVDC,” IEEE/PES Transmiss. Distrib. Conf. Expo., 2001, vol. 1,
[17] C. Feltes, H. Wrede, F. W. Koch, and I. Erlich, “Enhanced fault ride- pp. 20–24.
through method for wind farms connected to the grid through VSC- [29] Application Manual: Battery Energy Storing Systems in PowerFacory,
based HVDC transmission,” IEEE Trans. Power Syst., vol. 24, no. 1, DIgSILENT GmbH, Nov. 30, 2010.
pp. 1537–1546, Aug. 2009.
[18] X. Dawei, L. Ran, J. R. Bumby, P. J. Tavner, and S. Yang, “Coordinated
control of an HVDC link and doubly fed induction generators in a large
offshore wind farm,” IEEE Trans. Power Del., vol. 21, no. 1, pp. 463–471, Hongzhi Liu received the B.Eng. degree in electrical
Jan. 2006. engineering from the Taiyuan University of Tech-
[19] Y. Phulpin, “Communication-free inertia and frequency control for wind nology, Shanxi, China, in 2000; the M.Sc. degree in
generators connected by an HVDC-link,” IEEE Trans. Power Syst., vol. electrical engineering from Northwestern Polytech-
27, no. 1, pp. 1136–1137, May 2012. nical University, Shanxi, in 2004; the M.Phil. de-
[20] Y. Pipelzadeh, B. Chaudhuri, and T. C. Green, “Inertial response from gree in information technology from the University
remote offshore wind farms connected through VSC-HVDC links: A of Queensland, Brisbane, QLD, Australia, in 2009;
communication-less scheme,” in Proc. IEEE Power Energy Soc. Gen. and the Ph.D. degree in electrical engineering from
Meeting, 2012, pp. 1–6. the Department of Energy Technology, Aalborg Uni-
[21] T. M. Haileselassie, R. E. Torres-Olguin, T. K. Vrana, K. Uhlen, and T. Un- versity, Aalborg, Denmark, in 2014.
deland, “Main grid frequency support strategy for VSC-HVDC connected
wind farms with variable speed wind turbines,” in Proc. IEEE PowerTech
Conf., Trondheim, Norway, 2011, pp. 1–6.
[22] J. Zhu, C. D. Booth, G. P. Adam, and A. J. Roscoe, “Inertia emulation Zhe Chen (M’95–SM’98) received the B.Eng. and
control of VSC-HVDC transmission system,” in Proc. Int. Conf. Adv. M.Sc. degrees in electrical engineering from the
Power Syst. Autom. Protection, 2011, pp. 1–6. Northeast China Institute of Electric Power Engineer-
[23] J. Zhu, C. D. Booth, G. P. Adam, A. J. Roscoe, and C. G. Bright, “Inertia ing, Jilin City, China, in 1982 and 1986, respectively,
emulation control strategy for VSC-HVDC transmission systems,” IEEE and the Ph.D. degree in electrical engineering from
Trans. Power Syst., vol. 28, no. 2, pp. 1277–1287, May 2013. the University of Durham, Durham, U.K, in 1997.
[24] V. Akhmatova, A. H. Nielsenb, J. K. Pedersenc, and O. Nymannc, He is currently a Full Professor with the De-
“Variable-speed wind turbines with multi-pole synchronous permanent partment of Energy Technology, Aalborg University,
magnet generators. Part I: Modelling in dynamic simulation tools,” Wind Aalborg, Denmark, where he is also the Leader of
Eng., vol. 27, pp. 531–548, 2003. the Wind Power System Research Program in the
[25] A. D. Hansen and G. Michalke, “Multi-pole permanent magnet syn- Department of Energy Technology, and the Danish
chronous generator wind turbines’ grid support capability in uninter- Principle Investigator for the Wind Energy of Sino-Danish Centre for Education
rupted operation during grid faults,” IET Renew. Power Gener., vol. 3, and Research, Beijing, China. He has more than 300 publications in his techni-
pp. 333–348, 2009. cal field. His research interests include power systems, power electronics, and
[26] G. Michalke and A. D. Hansen, “Modelling and control of variable speed electric machines, and his main current research interests include wind energy
wind turbines for power system studies,” Wind Energy, vol. 13, no. 4, and modern power systems.
pp. 307–322, 2010. Dr. Chen is an Associate Editor of Renewable Energy of the IEEE TRANS-
[27] Grid Code: High and Extra High Voltage, E.ON Netz GmbH Tech. Rep., ACTIONS ON POWER ELECTRONICS; a Fellow of the Institution of Engineering
Status:1, Apr. 2006. and Technology, London, U.K.; and a Chartered Engineer in the U.K.

Das könnte Ihnen auch gefallen