Economic Analysis of

Hybrid Chiller Plants


By Brian Smith

raditionally, chiller plants in large facilities consisted of constant-speed, ated because they use multiple energy
T electric-drive centrifugal chillers because they were the least ex-
pensive and most efficient option. Although natural gas was cheaper
sources. In markets where high on-peak
electricity rates exist and natural gas
prices are low, a combination of electric
than electricity on a $/Btu basis, the price difference wasn’t sufficient and non-electric chillers may make the
most sense from a long-term economic
to offset the efficiency and capital-cost differences between electric
perspective.
and non-electric chillers. This article tries to answer the ques-
tion, “How high must electric-
In the past few years, the IPLV1
ity prices be to justify a hybrid
Capital
metrics have changed. Today, Chiller Type (COP
Cost ∆2
chiller plant?” In the following
hybrid chiller plants using basis) economic analysis of hybrid
Electric-Driven, Constant-Speed
multiple chillers and different Centrifugal
7.0 Base chiller plants, we first estab-
energy sources are being con- Electric-Driven, Variable-Speed Centrifugal 9.9 +25% lished a baseline of relative
sidered in many applications. Electric-Driven Screw 7.5 0% chiller efficiencies and capital
Gas-Engine-Driven Centrifugal 2.4 +280%
What has changed? costs, according to data from
Steam-Turbine-Driven Centrifugal 1.5 +285%
A significant factor is the Steam-Driven, Single-Stage Absorption 0.8 +35% multiple manufacturers. Next,
new time-of-use rate structures Gas-Driven, Two-Stage Absorption 1.1 +220% we selected an industrial user
that electric utilities are imple- 1. IPLV values are general indicators of chiller efficiency at both rate for natural gas, which we
menting. While these new rate design and off-design conditions and offered for comparison held constant throughout the
only. In the actual analysis, specific energy consumption values
structures vary among utilities, for each operating condition were used. analysis. Then, we varied the
users generally pay a lower rate 2. Capital Cost ∆ includes chiller, pumps and tower, but not boiler. peak price of electricity to test
when electricity demand is low Table 1: Typical water-cooled chiller efficiencies and costs. the sensitivity of various chiller
(off-peak periods) and a much combinations to progressively
higher rate when demand is high (on- market demand and the weather, because higher on-peak electric prices. Finally,
peak periods). high demand for electricity and warm we analyzed life-cycle costs, compar-
For example, some utilities have weather tend to be synchronous. ing the operating cost savings to the
moved to real-time pricing (RTP), which Thus, owners, managers, and design- additional capital costs. From these cal-
is a pricing schedule where rates are de- ers of large facilities exposed to these culations, we drew some general con-
termined a day or two in advance of their rate structures are recognizing that the clusions about hybrid chiller plants that
use. RTP rates eliminate or reduce de- biggest opportunity to reduce energy will help engineers evaluate their feasi-
mand charges. However, their presence costs is to reduce the high-cost, on-peak bility from a long-term economic per-
is felt in the peak pricing of electricity. use of electricity by their HVAC systems. spective.
High on-peak prices are the primary In non-residential facilities, chillers are
About the Author
means for electricity producers to recoup one of the largest energy users, so they
Brian Smith is a product manager for the
the cost of their peaking plants. With RTP, are receiving a lot of attention. Engineered Systems group of York International,
the price of electricity fluctuates with Hybrid chiller-plants are being evalu- York, Pa.
Hybrid Chillers

$0.70 $0.60 Peak 1500


Electric Price ($/kWh)

$0.60 $0.65 Peak CH3

Cooling Load (TR)


CH2
$0.50 $0.70 Peak
CH1
$0.40 1000
$0.30
$0.20 500
$0.10
$0.00

7.5
97.5

87.5

77.5

67.5

57.5

47.5

37.5

27.5

17.5
0

7.5
97.5

87.5

77.5

67.5

57.5

47.5

37.5

27.5

17.5
Outside-Air Temperature (°F)
Outside-Air Temperature (°F)

Figure 1: Temperature-based rate structures.* Figure 2: Chiller-plant load profile.*

This is a theoretical analysis based on broad market trends, For the purpose of our analysis, we made additional assump-
and is not intended as a study of actual utility rate structures. It tions: zero inflation and zero energy escalation; average weather
is offered as a design guide, not as definitive criteria for hybrid data for the United States; the chillers are piped in a parallel
chiller plant specifications. arrangement; there is no airside economizer, so the chillers run
year-round; the plant runs 24-hours-a-day and seven-days-a-
Inputs Used in the Analysis week, typical of large institutional and industrial facilities
First, let’s look at the inputs used in this analysis, starting that might consider a hybrid chiller plant; the electricity rate
with the types of chillers examined. In the analysis, we used a structures are in effect on weekends and holidays, as well as
plant consisting of three 500-ton (1760 kW) chillers, with as- during the week; and each plant has a full-service mainte-
sociated pumps and towers. The chiller types used are listed in nance contract that is based on the components it contains.
Table 1. The chiller plant load profile, shown in Figure 2, is hypotheti-
Note the wide differences in efficiency, represented by the cal but typical of many buildings.
integrated part-load value (IPLV, as described in ARI Standards
550/590 and 560). IPLV, originally developed as a performance Energy Analysis
measure for single-chiller plants, has also been shown to apply Based on these assumptions, chiller plant performance was
equally well to multiple-chiller plants.1,2 To simplify compari- analyzed using a chiller plant energy-estimating software tool
son among various chiller types, we converted all IPLVs to a that uses the ASHRAE temperature-bin method, plus equip-
coefficient of performance (COP) value, with the higher val- ment efficiencies from a number of manufacturers, to estimate
ues equating to higher efficiency and lower energy consump- chiller-plant energy consumption for each temperature bin,
tion. Also, note the significant range in capital costs (purchase which is then summed to establish the total energy
and install) of the various chiller types. This table shows why consumption.
electric-driven chillers have been a popular choice in large-
tonnage chiller plants for many years. Financial Analysis
However, as we know from field experience, on-peak elec- The chiller plants were analyzed on a life-cycle-cost basis.
tricity prices that are much higher than the cost of natural gas Plants with higher efficiencies usually had an added capital
on a $/Btu basis can make non-electric chillers a viable cost, which we compared to their energy and maintenance
option. costs. Since costs and savings occur at various times during
In our analysis, we used four hypothetical electricity rate the life of the chiller plant, we calculated them based on net
structures. We looked at a traditional structure, with a usage present value (NPV), which brings all cash flows back to present
price of $0.07/kWh and a demand price of $10.00/kW. Then, dollars. For the NPV calculations, we assumed a 10% discount
we undertook the sensitivity analysis by looking at the impact rate and a 25-year chiller-plant life.
of three progressively higher rate structures related to outdoor
temperature, illustrated in Figure 1. Sample Analysis
While we know of no real-life electricity rate structures that Using our traditional rate structure ($0.07 kWh usage and
are explicitly temperature-based such as ours, we believe the $10.00 kWh demand), we compared a base plant consisting of
correlation between outdoor temperature and on-peak demand three electric-driven, constant-speed centrifugal chillers to a
for electricity is implicit in all RTP rate schedules. So we have hybrid plant which uses two electric-driven, constant-speed
created these hypothetical, temperature-based rate structures
to predict how often on-peak prices will be charged. * (°F – 32) ÷ 1.8 = °C
25-Year NPV ($000, @ 10% Disc. Rate)

1000

25-Year NPV ($000, @ 10% Disc. Rate)


All Electric 1000 All Electric
2 Electric, 1 Non-Electric 2 Electric, 1 Non-Electric
1 Electric, 2 Non-Electric
1 Electric, 2 Non-Electric
750
750

500
500

250
250

0
0 200 400 600 800 1000 0
0 200 400 600 800 1000
Added Capital Cost ($000) Added Capital Cost ($000)

Figure 3: Case A, $0.07/kWh usage and $10.00/kW demand for Figure 4: Case B, $0.60/kWh temperature-based rate for electricity
electricity and $0.40/therm for gas. and $0.40/therm for gas.
25-Year NPV ($000, @ 10% Disc. Rate)

25-Year NPV ($000, @ 10% Disc. Rate)


1000 1000
All Electric All Electric
2 Electric, 1 Non-Electric 2 Electric, 1 Non-Electric
1 Electric, 2 Non-Electric 1 Electric, 2 Non-Electric
750 750

500 500

250 250

0 0
0 200 400 600 800 1000 0 200 400 600 800 1000
Added Capital Cost ($000) Added Capital Cost ($000)

Figure 5: Case C, $0.65/kWh temperature-based rate for electricity Figure 6: Case D, $0.70/kWh temperature-based rate for electricity
and $0.40/therm for gas. and $0.40/therm for gas.

centrifugal chillers and one steam-driven, single-stage absorp- 4. CH2 – CH3 – CH1
tion chiller as the peaking chiller (meaning “last on-line”). 5. CH3 – CH1 – CH2
When we ran the analysis, we found that the economics are 6. CH3 – CH2 – CH1
poor: an added capital cost of $48,000 and a 25-year NPV of In real-world operation, it is possible to use direct digital
$33,000. Obviously, this plant would never be considered. controls to sequence a chiller plant to take advantage of the
However, using the temperature-based rate structure, if the lowest energy rates and most efficient chiller. However, in this
maximum electricity price were $0.70/kWh, we found that we analysis, we chose to let the software-generated numbers pro-
would have a very compelling economic case: for the same vide an objective guide, rather than apply our own subjective
added capital cost of $48,000, the 25-year NPV is an impres- understanding.
sive $412,000. This plant would definitely be considered. In our sensitivity analysis, we used the traditional usage-
and-demand rate structure described earlier as Case A, and
Complete Analysis the three temperature-based electric rate structures as fol-
Using our analysis software, we evaluated more than 280 lows: $0.60/kWh maximum as Case B, $0.65/kWh maximum
equally sized chiller combinations, including constant- and vari- as Case C, and $0.70/kWh maximum as Case D. In all four
able-speed electric centrifugal, electric screw, steam-turbine cen- cases, to highlight the effect of changing electricity prices,
trifugal, gas-engine centrifugal, single- and two-stage absorption we assumed a constant rate for natural gas of $0.40/therm3
chillers. Every possible configuration of chiller sequencing was and a constant boiler efficiency of 80%. For each plant and
used, allowing six permutations of each chiller plant: rate structure, we calculated and plotted the 25-year NPV as
1. CH1 – CH2 – CH3 a function of added capital cost. In Figures 3–6, we can
2. CH1 – CH3 – CH2 quickly see the impact of varying the electricity costs, and
3. CH2 – CH1 – CH3 then draw some general conclusions. While 280 chiller com-
Hybrid Chillers

binations were analyzed, only those with positive NPV were rate structure with a $0.70/kWh maximum cost of electricity (a
plotted in Figures 3–6. price multiple more than 50). Here, the economics in favor of
Using our traditional rate structure (Case A), we see that hybrid chiller-plants would be extremely compelling. Hybrid
many of the hybrid plants have significantly higher added plants with two non-electric chillers could now offer tremen-
capital costs than the all-electric plants, but they do not offer dous NPVs — some approaching $1 million.
any real advantage in terms of better NPVs. Under this rate
structure, most designers and owners would choose to stay Conclusions
with an all-electric plant. While traditional usage-and-demand electricity rate structures
As we move to a temperature-based rate structure with a often do not favor hybrid chiller-plants, it is clear that a trend
$0.60/kWh maximum (Case B), we can see that some hybrid toward time-of-use rate structures would change the metrics. If
plants with one non-electric chiller can generate approxi- on-peak electricity prices exceed concurrent gas prices by a
mately $500,000 in NPV savings for an added capital cost of multiple of 40 or more on a $/Btu basis (which is not unheard
$100,000 or less. Under this rate structure, where the maxi- of), a hybrid plant should definitely be considered.
mum electricity price exceeds the gas price by a multiple of The financial performance of hybrid plants varies signifi-
44 on a $/Btu basis, some designers and owners might con- cantly with the types of chillers used. Note again the wide
sider a hybrid plant, depending on their operating and differences in COP and capital cost among the chillers used in
financial goals. our analysis. Fortunately, when it comes to selecting the opti-
In Case C, we raise the temperature-based rate structure to a mum chiller-plant combination, there are software tools avail-
$0.65/kWh maximum cost for electricity (an electricity-to-gas able that can simplify the process.
price multiple of 48). We now see that hybrid plants with two
non-electric chillers also offer attractive NPVs. Under this elec- References
tricity rate structure, hybrid plants would clearly deserve evalu- 1. Hubbard, R.S. 1999. “Forum on ARI Standard 550-590-98.” Heat-
ing, Piping, Air Conditioning Magazine May.
ation. There are now a variety of chiller combinations that
2. Hubbard, R.S. 1999. “Not-so-chilling results.” Engineered Sys-
could be considered, depending upon operating and financial tems September
objectives. 3. 2002. “Average price of natural gas sold to industrial consumers
In Case D, we consider the impact of a temperature-based ….” Energy Information Administration/Natural Gas Monthly March.

Copyright 2002 American Society of Heating, Refrigerating & Air-Conditioning Engineers, Inc., 1791 Tullie Circle NE, Atlanta, GA. 30329.
Reprinted by permission from the July 2002 Issue of ASHRAE Journal.