Sie sind auf Seite 1von 10

Electric Power Systems Research 66 (2003) 5 /14

www.elsevier.com/locate/epsr

Review

What is power quality?


M.H.J. Bollen *
Department of Electric power Engineering, Chalmers University of Technology, Horsalsvagen 11, Gothenburg 412 96, Sweden

Abstract

This paper introduces the terminology and various issues related to ‘power quality’. The interest in power quality is explained in
the context of a number of much wider developments in power engineering: deregulation of the electricity industry, increased
customer-demands, and the integration of renewable energy sources. After an introduction of the different terminology two power
quality disturbances are discussed in detail: voltage dips and harmonic distortion. For each of these two disturbances, a number of
other issues are briefly discussed, which are characterisation, origin, mitigation, and the need for future research.
# 2003 Elsevier Science B.V. All rights reserved.

Keywords: Power quality; Harmonic distortion; Voltage dips

1. Introduction Various developments have led to a different view at


the power system. These developments are strongly
Classically, the aim of the electric power system is to interrelated, but the three main ones are:
generate electrical energy and to deliver this energy to
the end-user equipment at an acceptable voltage. The . The deregulation of the electricity industry makes
constraint that was traditionally mentioned is that the that there is no longer one single system but a number
technical aim should be achieved for reasonable costs. of independent companies with customers.
The optimal level of investment was to be obtained by . Electricity customers have become more aware of
means of a trade-off between reliability and costs. A their rights and demand low-cost electricity of high
recurring argument with industrial customers concerned reliability and quality, where the priorities are
the definition of reliability: should it include only long different for different (types of) customers. Custo-
interruptions or also short interruptions or even voltage mers are certainly no longer willing to accept their
dips. The term power quality came in use referring to the position as merely one parameter in a global optimi-
other characteristics of the supply voltage (i.e. other sation.
than long interruptions). But, immediately, the first . Generation of electricity is shifting away from large
power stations connected to the transmission system
confusion started as utilities included the disturbances
towards smaller units connected at lower voltage
generated by the customers in the term ‘power quality’.
levels. Examples are combined-heat-and-power and
This difference in emphasis will be discussed in more
renewable sources of energy like sun and wind.
detail below. The main complaint of domestic customers
concerned the costs which were perceived too high, Because of this the power system can no longer be
especially where cross-subsidising was used to keep seen as one entity but as an electricity network with
prices low for industrial or agricultural customers. customers. This new model is shown in Fig. 2. Note that
This classical model of the power system, as it can be the physical structure of the power system/network has
found in many textbooks, is found in Fig. 1. The not changed, it is only the way of viewing it that has
customers are traditionally referred to as loads. changed.
In Fig. 2 the electric power network connects some or
many customers. Customers may generate or consume
* Tel.: /46-31-772-3832; fax: /46-31-772-1633.
E-mail address: mathias.bollen@elteknik.chalmers.se electrical energy, or even both albeit at different
(M.H.J. Bollen). moments in time. Different customers have different
0378-7796/03/$ - see front matter # 2003 Elsevier Science B.V. All rights reserved.
doi:10.1016/S0378-7796(03)00067-1
6 M.H.J. Bollen / Electric Power Systems Research 66 (2003) 5 /14

boundary condition that limits e.g. the amount of wind


power that can be produced at a certain location.
Instead the power network’s task becomes to enable
the transport of the amount of wind power that is
produced. It will be clear to the reader that the final
solution should be found in co-operation between the
customer and the network operator considering various
technical and economic constrains.
Fig. 1. Classical model of the power system.
There are many aspects to the limitations set by the
network on the market. A much discussed one is the
limited ability of the network to transport energy. Note
that lack of generation capacity is not a deficiency of the
network but a deficiency of the market.
In this modern way of looking at power systems, the
utility no longer buys and sells energy, but instead sells
transport capacity and access to the network.
This paper will give a short overview of power quality
with emphasis on the two issues that currently receive
Fig. 2. Modern model of the power system. most attention: harmonic distortion and voltage dips.
But first another attempt will be made at defining the
demands on voltage magnitude, frequency, waveform, term ‘power quality’.
etc. Different customers have different patterns of
current variation, fluctuation and distortion, thus pol-
luting the voltage for other customers in different ways. 2. Definitions
The power network in Fig. 2 could be a transmission
network, a distribution network, an industrial network, There is a lot of confusion on the meaning of the term
or any other network owned by one single company. ‘power quality’, not in the least because ‘power’ is used
For a transmission network, the customers are, e.g., as a synonym for ‘electricity’ in American English
generator stations, distribution networks, large indus- whereas it is also the energy transport per unit of time.
trial customers (who could be generating or consuming Different authors use different definitions. A consistent
electricity at different times, based on the electricity set of definitions is given as follows:
price at that moment), and other transmission networks.
For a distribution network, the customers are currently . Voltage quality is concerned with deviations of the
mainly end-users that only consume electricity, but also voltage from the ideal. The ideal voltage is a single-
the transmission network and smaller generator stations frequency sine wave of constant amplitude and
are customers. Note that all customers are equal, even frequency.
though some may be producing energy while others are . Current quality is the complementary term to voltage
consuming it. The aim of the network company is only quality: it is concerned with the deviation of the
to transport the energy, or in economic terms: to enable current from the ideal. The ideal current is again a
transactions between customers. single-frequency sine wave of constant amplitude and
The technical aim of the power network becomes one frequency, with the additional requirement that the
of allowing the transport of electrical energy between current sine wave is in phase with the voltage sine
wave.
the different customers, guaranteeing an acceptable
. Power quality is the combination of voltage quality
voltage and allowing the currents taken by the custo-
and current quality.
mers.
. Quality of supply is a combination of voltage quality
With an ideal network each customer should perceive
and the non-technical aspects of the interaction from
the electricity supply as an ideal voltage source with a
the power network to its customers.
zero impedance. Whatever the current is, the voltage
. Quality of consumption is the complementary term to
should be constant. As always, reality is not ideal. quality of supply.
Power quality concerns this deviation between reality
and ideal. Note that not all these terms are equally commonly
Note that this same model also becomes attractive used, especially current quality and quality of consump-
when considering the integration of renewable or other tion are used more frequently. Also note that other
environmentally /friendly sources of energy into the sources give other, often conflicting, definitions. All
power system. The power network is no longer the definitions given above apply to the interface between
M.H.J. Bollen / Electric Power Systems Research 66 (2003) 5 /14 7

the network (company) and the customer. This may be that power quality remains in most cases as a part of the
for example a domestic customer and the public low- phrase ‘bad power quality’. A power quality disturbance
voltage distribution network, an individual plant and is only seen as an issue when it causes problems, either
the industrial medium-voltage distribution network, a for the customer or for the network operator. Voltage
power station and a transmission network, or a trans- dips and harmonics are seen as a power quality issue by
mission network and a distribution network. The term many; but voltage and frequency variations are not seen
power quality is certainly not restricted to the interac- as a power quality issue because the latter were
tion between the power grid and end-user equipment. incorporated in the design of power systems many years
The term electromagnetic compatibility (EMC) has in ago.
this context a more restricted meaning: it applies only to
the interaction between equipment and its electromag-
netic environment (e.g. the power system). Strictly
3. Harmonic distortion
speaking it would thus only apply to low-voltage
networks but the terminology is also being applied to
The term harmonics refers to the decomposition of a
higher voltage levels. Note that in the international
non-sinusoidal but periodic signal into a sum of
(IEC) standards power quality is treated as a subset of
sinusoidal components:
EMC.
Power quality disturbances (i.e. deviations of voltage X


and/or current from the ideal) come in two types, based f (t) Ah cos(2phf0  8 h )
h1
on the way a characteristic of voltage or current is
measured: with Ah and 8h amplitude and phase angle for harmonic
order h, f0 /1/T and T the period. For a power system
. Variations are small deviations of voltage or current operating at 50 Hz, any non-sinusoidal voltage or
characteristics from its nominal or ideal value, e.g. current can be decomposed into a fundamental (50
the variation of voltage r.m.s. value and frequency Hz) component plus a number of harmonic components
from their nominal values, or the harmonic distortion with frequencies that are a multiple integer of 50 Hz.
of voltage and current. Variations are disturbances The latter are called harmonic components. The 150-Hz
that are measured at any moment in time. Harmonic component (h /3) is referred to as the third harmonic,
distortion will be discussed as an example of a power etc.
quality variation. A more appropriate term would be ‘waveform
. Events are larger deviations that only occur occa- distortion’ where one could distinguish between:
sionally, e.g. voltage interruptions or load switching
currents. Events are disturbances that start and end . Harmonic distortion is distortion where the waveform
with a threshold crossing. Voltage dips will be treated is non-sinusoidal but periodic with a period equal to
below as an example. the period of the power system frequency (50 or 60
Hz). Most of the literature on waveform distortion
The difference between variations and events is not only considers this harmonic distortion, which is an
always obvious, and related to the way in which the acceptable approximation in many cases. However
disturbance is measured. The best way of distinguishing most power quality studies consider more or less
between the two is as follows: variations can be exceptional situations, so that we cannot limit
measured at any moment in time; events require waiting ourselves to harmonic distortion only.
for a voltage or current characteristic to exceed a pre- . The presence of a dc component can be seen as a
defined threshold. As the setting of a threshold is always special case of harmonic distortion, but is often
somewhat arbitrary there is no clear border between treated separately due to difference in measurement
variations and events. Still the distinction between them techniques and consequences.
remains useful and it is in fact done (implicitly of . Interharmonic distortion is mathematically the same
explicitly) in almost any power quality study. However, as harmonic distortion. The difference with harmonic
note that here also there is no consistency in terminol- distortion is that the period is a multiple of the period
ogy. For example, measurements of the r.m.s. voltage of the power system frequency. For example, a 50 Hz
can be the basis for a variation (when 10-min averages signal with a 180 Hz interharmonic component has a
are continuously recorded) but also for an event period of 100 ms (5 cycles of 50 Hz, 18 cycles of 180
(starting and ending when the r.m.s. voltage dips below Hz). Mathematically, a frequency component at an
90% of the nominal voltage). irrational multiple of the power system frequency
The definitions of power quality events and variations would lead to a non-periodic signal, but that case
as given here are much wider than the general inter- does not need to be considered in practice. Inter-
pretation of power quality. This has to do with the fact harmonic distortion is discussed in more detail in [1].
8 M.H.J. Bollen / Electric Power Systems Research 66 (2003) 5 /14

. Subharmonic components are components with a between the harmonic lines. In this case there are no
frequency less than the power system frequency. clear interharmonic components present, instead there is
They can be considered as interharmonic distortion, a significant amount of noise, especially below 100 Hz.
but are often treated separately because their con- Part of this noise is the cause of light flicker. Note that
sequences are different from those of higher fre- according to the IEC standard for measurement of
quency components. harmonic distortion (IEC 61000-4-7) all spectral content
. Voltage flicker , or more accurately, voltage fluctua- in between integer harmonics is counted as interharmo-
tions leading to light flicker , are mathematically nic distortion even if the term noise would be more
another special case of interharmonic distortion. appropriate.
The special interest in this type of disturbance is
again due to the consequences. Even very small
3.1. Origin of waveform distortion
fluctuations in the r.m.s. voltage with frequencies
between 1 and 15 Hz lead to light-intensity variation
Harmonic distortion is due to the presence of non-
for which our eyes are very sensitive.
linear elements in the power system (i.e. either in the
. Noise , are all non-periodic frequency components.
network or in the loads). The main distortion is due to
The power system is not a static entity but it changes power-electronic loads like computers, televisions, en-
all the time, so that strictly applying the above defini- ergy-saving lamps. Such loads can be found in increas-
tions would imply that everything is noise. To distin- ing numbers with domestic and commercial customers
guish between the different types of distortion is indeed leading to an increasing level of distortion in the
network. An example of the non-sinusoidal current
not always possible. A way of distinguishing would be
due to a normal computer is shown in Fig. 4. This
by taking the spectrum of the signal over a reasonable
waveform is typical for many loads at home and in the
number of cycles, e.g. 50 cycles (1 s). Harmonics and
office.
interharmonics show up as sharp lines in the spectrum
Also adjustable-speed drives and arc furnaces are
whereas noise is seen as a continuous spectrum. Light
famous for the distortion they cause. But these loads are
flicker cannot be observed directly from the spectrum,
mainly found with large industrial customers where
although the presence of frequency components within mitigation methods are applied to limit the resulting
10 Hz of the fundamental component is a good voltage distortion. Therefore the resulting voltage dis-
indication. For the analysis of light flicker, the flicker- tortion is mainly determined by small non-linear loads
meter algorithm has been developed. and not by the large ones, although large non-linear
Fig. 3 shows the spectrum of a current signal contain- loads sometimes cause local problems. The daily varia-
ing several types of waveform distortion. The spectrum tion of the harmonic distortion shows clearly the pattern
was obtained by applying a discrete Fourier transform of domestic load, mainly televisions. This pattern is
to a 20-s window of the measured current to an arc visible round the globe as shown in Figs. 5 and 6, where
furnace. The harmonic distortion shows up as the each figure shows the 5th harmonic and the THD
spectral lines at integer multiples of 50 Hz. The spectral obtained as averages over 10-min intervals.
components close to the spectral lines are due to time Interharmonic distortion is much more related to
variations in the amplitude of these harmonics. Inter- industrial loads, so is the noise component of waveform
harmonic distortion shows up as spectral lines in distortion.
Capacitor banks are often incorrectly mentioned as a
source of harmonic distortion. They are not a cause of

Fig. 3. Spectrum of a signal with different types of waveform Fig. 4. Example of voltage at the terminals of a computer (sine wave)
distortion. (Current in A, Frequency in Hz.) and the resulting non-sinusoidal current.
M.H.J. Bollen / Electric Power Systems Research 66 (2003) 5 /14 9

harmonic components are obtained by applying a


Fourier transform to the waveforms.
. Frequency domain study : a separate system model is
made for each frequency component included in the
study. Each single-frequency model is relatively
simple as it only needs to be valid for that specific
frequency. The resulting models are the same as used
for fundamental-frequency analysis resulting in com-
plex voltages and currents. The main difference, and
also the main difficulty, is in the choice of the
impedance values. Especially for higher frequency
components different models are needed because
various capacitive currents become significant, but
the calculation methods remain the same. More
details of frequency-domain studies are found in [3]
Fig. 5. Harmonic voltage distortion (5th harmonic and THD)
measured over a 6-day period in Gothenburg, Sweden. The term ‘harmonic analysis’ is normally used for the
second method, but the first method will equally result
in a harmonic spectrum. The reason that the second
method is most commonly used is its simplicity: the
same analysis methods can be applied to harmonic
components as to the fundamental frequency. The basic
assumptions behind this method are that the non-
linearity is restricted to a limited number of components
(in most cases loads) and that the current waveform of a
non-linear component is not significantly affected by the
voltage waveform. Harmonic analysis studies for large
transmission systems are discussed in detail in [3].

3.3. Consequences

Harmonic voltage distortion leads to harmonic cur-


Fig. 6. Harmonic voltage distortion (5th harmonic and THD)
rents through linear loads. These harmonic currents may
measured over a 6-day period in Shanghai, China.
cause extra losses in the loads which in turn requires de-
rating of the load. The effect is especially severe for
lower-order voltage harmonics at the terminals of
harmonic distortion but their resonance with (mainly
rotating machines. Negative-sequence voltages have
transformer) impedances leads to an amplification of the
the same effect. Rotating machines are designed for a
harmonic currents and voltages generated by non-linear
given maximum amount of voltage unbalance. The
loads.
presence of voltage distortion limits the immunity of
The harmonic distortion due to rotating machines is
the machine for voltage unbalance. The effect of
discussed in detail in [2].
harmonic distortion in rotation machines is discussed
in detail in [2].
3.2. Harmonic analysis Whereas machines are mainly affected by lower-order
harmonics, capacitor banks are mainly affected by
Harmonic analysis aims at predicting the harmonic higher-order harmonics.
distortion at one or more locations in the power Some sensitive electronic loads are negatively affected
network. Such a study can be done to estimate the by high harmonic voltage distortion. The effect on such
effect of a new non-linear load or of the installation of a loads is however not so much related to the harmonic
harmonic filter. There are two distinctly different spectrum but to the actual waveform, e.g. notching and
methods of harmonic analysis. multiple zero-crossings. An indirect effect of harmonic
voltage distortion is that the efficiency of rectifiers
. Time domain study : the system (i.e. network and load) becomes less when the crest factor (the maximum of
are modelled in detail after which a time-domain the voltage waveform) decreases. Loads also become
study is done resulting in the actual waveforms. The more sensitive to voltage dips.
10 M.H.J. Bollen / Electric Power Systems Research 66 (2003) 5 /14

A high crest factor (harmonic overvoltage) on the voltage distortion. Reduced emission is seen by many as
other hand may cause faster ageing of the insulation. the preferred long-term solution of the harmonic
The main effect of harmonic current distortion is distortion problem. One may however wonder if this is
overheating of series components like transformers indeed the cheapest solution. As the number of concrete
and cables. The heating is proportional to the r.m.s. problems due to harmonic distortion remains relatively
current; whereas, the transported energy is related to the small, keeping the distortion at its current level or even
fundamental component. For a given active power, the allowing a further increase may be a cheaper overall
heating increases with increasing current distortion. The solution.
effect, however, is more severe than would follow from An important component in addressing harmonic
this reasoning as the resistance of transformers increases problems is in defining limits to harmonic voltage and
with frequency. The higher order harmonics thus current distortion. The limits on harmonic voltage
produce more heating per Ampere than the fundamental distortion as mentioned in various national and inter-
component. Heavily distorted current waveforms re- national standards are mainly a formalisation of the
quire a de-rating of transformers. The effect is also already existing distortion. For harmonic current limits,
present for cables and lines, but to a lesser extent. IEC and IEEE use two principally different approaches.
The rating of power-electronic series components like The IEC standards set limits to the amount of emission
UPS and static transfer switch is determined mainly by of individual equipment, whereas the IEEE harmonic
the peak value of the current, not so much by its r.m.s. standard limits the emission per customer. Under the
value. A current with a high crest factor (as is very IEEE standard the responsibility lies with the customer
common with electronic load) will require a significant who may decide to install filters instead of buying better
derating. equipment. Under the IEC standards the responsibility
Third harmonic currents lead to a large sum current lies with the manufacturers of polluting equipment. The
through the neutral conductor. This current may cause difference can be traced back to the aim of the
overheating if the neutral conductor is designed not to documents: the IEEE standard aimed at regulating the
carry any significant current and is not equipped with connection of large industrial customers, whereas the
overload protection. Many single-phase loads cause a IEC document mainly aims at small customers that do
large third harmonic current which could lead to neutral not have the means to choose between mitigation
overload. The problem is especially present in low- options.
voltage installations with large amounts of computers or
energy-saving lighting. 3.5. Future research directions

3.4. Mitigation Most of the research on harmonic waveform distor-


tion has been done at universities, with emphasis on
Mitigation is in the harmonic context often seen as harmonic analysis studies in large transmission systems.
synonym to reduction of harmonic voltage or current Further calibration with measurements is required to
distortion. However the problem can also be mitigated test the various network and load models. The avail-
by improving the immunity of equipment. De-rating of ability of a growing amount of monitoring equipment
transformers and motors is a way of mitigating the make such studies feasible.
harmonic problem, albeit not necessarily the most An important question that remains to be answered is
economic solution. where the ‘optimal distortion level’ is. The consequences
A more common way of tackling the harmonic of harmonic distortion should be studied, both for
problem is by installing filters, typically LC-series existing distortion levels and for higher levels. The
connections that shunt the unwanted harmonic current discussion is ongoing about how much the distortion
components back to the load. The harmonic currents level may increase before serious problems occur.
remain high but they do not spread through the system Another direction of research is in improved equip-
and do not cause much harmonic voltage distortion. ment. Large PWM converters are not only able to
The disadvantages of these so-called passive filters (high produce a sinusoidal waveform, they are even able to
risk of overload, introduction of new resonances) has mitigate the distortion produced by other loads. The
led to the development of so-called active filters where installation of additional control algorithms on equip-
the current is fully controlled and adjusted to the ment with PWM converters (wind turbines, large drives)
existing voltage or current distortion. may lead to a reduction of harmonic distortion without
Other mitigation methods include improvements in much extra costs. The development of these algorithms
the network (de-rating of transformers, splitting sensi- may be encouraged by the network operators by setting
tive and polluting loads) and improvements in the load. up a harmonic-distortion market. Such a market
The latter includes a more sinusoidal current waveform requires some additional fundamental research in find-
(reduced emission) but also an increased immunity to ing adequate market mechanisms. Another develop-
M.H.J. Bollen / Electric Power Systems Research 66 (2003) 5 /14 11

ment-related research direction is on active harmonic


filters.

4. Voltage dips

Voltage dips are short-duration reductions in r.m.s.


voltage caused by short-duration increases of the
current, typically at another location than where the
voltage dip is measured. The most common causes of
overcurrents leading to voltage dips are motor starting,
transformer energising and faults. Also capacitor en-
ergising and switching of electronic load lead to short-
duration overcurrents, but the duration of the over- Fig. 8. R.m.s. voltages for the voltage dip shown in Fig. 7.
current is too short to cause a significant reduction in
the r.m.s. voltage. These events are normally not zero. However many customers who would experience
referred to as voltage dips but as voltage notches or an interruption without protection now experience a
voltage transients. Voltage dips due to short circuit and voltage dip. This way of protection has been good
earth faults are the cause of the vast majority of enough for many years, but recently more and more
equipment problems. Most of the recent emphasis on problems with end-user equipment are reported due to
voltage dips is directed towards these fault-related dips. these voltage dips. Not only has, especially electronic,
An example of a measured voltage dip is shown in equipment become more susceptible to voltage dips,
Fig. 7, where the three voltage waveforms are given. A companies have also become less tolerant of production
more common way of presenting a voltage dip is stoppages.
through the r.m.s. voltages as a function of time. The
r.m.s. voltage is calculated over a window of typically
one cycle duration and updated one or more times per 4.1. Consequences
cycle. Fig. 8 shows the r.m.s. voltage for the dip in Fig.
7; the calculation is updated every sample in this As mentioned before, a voltage dip is a reduction in
example. The voltage dip shown is due to a phase-to- voltage. This reduction in voltage leads to a reduction in
phase fault in an underground cable that develops into a energy-transfer capability of the system. This has, for
three-phase fault within two cycles. long been, a well-known basis of transient-stability
Voltage dips are generally seen as undesired events, studies: the undervoltage due to a fault leads to a
but a more positive viewpoint could equally well see reduction of the power transfer from the generators to
them as a consequence of the high reliability of the the motors; motors slow down, generators speed up.
power supply. Without the wide-spread use of protec- This phenomenon limits e.g. the fault-clearing time in
tion equipment any fault would lead to the loss of transmission systems and also rules the connection of
supply for a large fraction of the customers. The wind farms to the grid. Motor-starting dips equally
protection significantly limits the numbers of customers become a concern when they lead to excess loss of speed
that experience a long interruption, in many cases to for neighbouring motors (or speed gain for generators).
Typical limits for stability concerns in distribution
systems are 70% voltage during 1 s. These events do
not occur very often in the public supply, and in
industrial power systems the stability issues are a
standard part of the design.
Many modern (power)-electronic devices like compu-
ters, process-controllers, and adjustable-speed drives
already experience operational problems when the
voltage drop below 85% for 40 ms. These events occur
ten times per year or more, causing a serious concern.
What most sensitive equipment has in common is that
it is connected to the power system through a rectifier
that converts a.c. to d.c. The d.c. voltage is then
converted to the actual application voltage. A voltage
dip on the a.c. side of the rectifier leads very fast to a
Fig. 7. Example of a voltage dip. drop in d.c. voltage. This in turn causes problems with
12 M.H.J. Bollen / Electric Power Systems Research 66 (2003) 5 /14

the application voltages. An additional problem is the events per year for different remaining voltage and
large inrush current that occurs when the voltage duration. There is an ongoing discussion about how
recovers after the dip (i.e. upon fault clearing). This to group remaining voltage and duration into bins.
recovery inrush may lead to damage in the rectifier Examples are the Unipede disdip table, IEC 61000-2-
components. For three-phase rectifiers, also the unba- 8 and IEEE Std. 493 and 1346.
lance of the currents through the rectifier and the ripple . The opposite principle ‘keep it simple’ , results in a
in the d.c. voltage are of concern. An example of the d.c. small number of indices, ideally just one index. The
bus voltage behind a three-phase diode rectifier is shown commonly-used SARFI indices belong to this school
in Fig. 9. The simulated event is a drop in the voltage as well as several proposals to quantify supply
between two phases to 50% of its pre-event value. The performance by just one number.
effect of voltage dip on adjustable-speed drives is
discussed in more detail in [4]. Important in the discussion on voltage-dip indices is
to consider that they can be obtained by measurements
as well as by simulations. Measurement (power quality
4.2. Characterisation and indices monitoring) is a good way of assessing the performance
of a site or system, in the end measurement is the only
To be able to characterise voltage dip events some exact method. But measurements have limited predictive
kind of processing of the sampled voltage waveforms is value due to the large year-to-year and site-to-site
needed. This is defined rather well in the standard differences. To predict voltage-dip performance a large
document IEC 61000-4-30, where remaining voltage and number of monitors are needed for a long period of
duration are defined as the two main characteristics to time. Stochastic prediction methods are much more
quantify a voltage dip. Both are obtained from the r.m.s. suitable for performance prediction, e.g. for comparing
voltage as a function of time (see Fig. 8). The different mitigation methods.
characterisation of three-phase measurements remains
a point of discussion. The current practice (using the
worst channel) is not very satisfactory. The character- 4.3. Mitigation methods
isation of three-phase measurements is discussed in
more detail in [5]. What has to be mitigated here is the tripping of
Having defined the characteristics of a single event, it equipment due to voltage dips. This can be done in a
becomes possible to describe the performance of a site number of ways:
and even of a whole network. For processing of event . Reducing the number of faults . There are several well-
indices into site and system-indices, there exist two known methods for this like tree-trimming, animal
different schools of thought which for the time being guards, and shielding wires, but also replacing over-
have shown incompatible. head lines by underground cables. As most of the
. The principle ‘don’t throw away too much informa- severe dips are due to faults, this will directly affect
tion’ , typically results in a table with the number of the dip frequency.
. Faster fault clearing . This requires improved protec-
tion techniques. Much gain can be obtained in
distribution networks, but at transmission level the
fault-clearing time is already very short. Further
improvement at transmission level would require
the development of a new generation of circuit
breakers and relays.
. Improved network design and operation . The network
can be changed such that a fault will not lead to a
severe dip at a certain location. This has been a
common practice in the design of industrial power
systems, but not in the public supply. Possible
options are to remove long overhead feeders from
busses supplying sensitive customers, and connecting
on-site generators at strategic locations. Also the use
of very fast transfer switches can be seen as a
network-based solution.
Fig. 9. Voltage at the d.c. bus of a three-phase adjustable-speed drive
. Mitigation equipment at the interface . The most
before and during a voltage dip. Solid curve: large capacitor; dashed commonly-used method of mitigating voltage dips
curve: small capacitor. is connecting a UPS or a constant-voltage transfor-
M.H.J. Bollen / Electric Power Systems Research 66 (2003) 5 /14 13

mer between the system and the sensitive load. For Fundamental research is also needed on stochastic
large loads the static series compensator of DVR prediction methods, including a large number of com-
(dynamic voltage restorer) is a possible solution. parisons with monitoring results to find the limitations
Power-electronic solutions are discussed in more of stochastic prediction.
detail in [6]. Most of the work on consequences of voltage dips has
. Improved end-user equipment . Making the equipment been directed towards adjustable-speed drives. With the
immune against all voltage dips would also solve the increase in embedded (renewable) generation more work
problem, but it is for most equipment not (yet) should be done on the effect of voltage dips on
feasible. Methods of improving equipment behaviour generation, especially on inverter-based interfaces.
will be discussed in more detail in [4].

The ongoing discussion on voltage-dip mitigation


concerns the responsibility sharing between the custo- 5. Conclusions
mer and network: should the solution be sought in the
network or with the customer. In some cases the costs of Power quality is a very wide and dispersed area that
mitigation equipment are shared or power quality somewhat accidentally became viewed as one subject.
contracts define the responsibility. In the long run an The two examples presented in this paper (harmonics
agreement has to be reached between what are ‘normal and voltage dips) show the variety of aspects related to
dips’ and what are ‘abnormal dips’. For normal dips even these two disturbances. Other disturbances that
end-user equipment is expected to be immune, whereas would deserve an equal amount of attention are (long
abnormal dips should have a small frequency of and short) interruptions, transients, and high-frequency
occurrence, see Fig. 10. waveform distortion. Note also that flicker is presented
here as a subset of waveform distortion, even though it
is commonly (and more correctly) treated as a separate
4.4. Future research disturbance.
For more information on these and other power-
Research on voltage dips includes development-re- quality disturbances, the reader is referred to the
lated research on mitigation equipment and improved extended literature on power quality. Good overviews
end-user equipment. It also includes education-related can be found in some of the books [8 /18], but also the
research on the relation between voltage-dip frequency IEC standards [19 /27] and the IEEE standards [28 /34]
and system design and operation. on power quality contain useful basic knowledge and
Fundamental research is needed on voltage dip overviews.
characteristics and indices, especially on methods for Harmonics, voltage dips and interruptions will be-
extracting system indices with a limited number of come a normal part of power system design and
monitors and on suitable single-index methods. Related operation and of the design of end-user equipment.
work is needed on the extraction of additional informa- Transients and high-frequency distortion will require
tion from voltage-dip recordings. This is one of the much more attention before they reach this stage.
possible applications for signal-processing techniques as The fact that power quality is becoming more mature
are discussed in [7]. does not mean that it will disappear as a subject that
deserves attention from academics. There remain inter-
esting research topics that await being taken up. Some
examples for harmonics and voltage dips are presented
in this paper. Another important task for academics is
to incorporate power quality issues in education.
Spreading knowledge on potential power quality pro-
blems (and not only to power engineers) will make it
more likely that future problems will be addressed
before they actually occur.

Acknowledgements

The measurements presented in this paper were


Fig. 10. Distinction between events that are the responsibility of the obtained with the help of Christian Roxenius (Göteborg
customer and those that are the responsibility of the network operator. Energi Nät), Mats Häger (STRI) and Gu Zengti.
14 M.H.J. Bollen / Electric Power Systems Research 66 (2003) 5 /14

References [16] W.E. Kazibwe, M.H. Sendaula, Electric Power Quality Control
Techniques, Van Norstad Reinhold, New York, 1995.
[17] G.J. Wakileh, Power Systems Harmonics */Fundamentals, Ana-
[1] C. Li, W. Xu, T. Tayjasanant, Interharmonics: basic concepts and
lysis and Filter Design, Springer, 2001.
techniques for their detection and measurement, Electric Power
[18] D. Blume, J. Schlabbach, T. Stephanblome, Voltage Quality in
Systems Research, this issue.
Electrical Power Systems, IEE, 2001.
[2] G.J. Wakileh, Harmonics and rotation machines, Electric Power
[19] IEC 61000-2-8, Voltage dips and short interruptions on public
Systems Research, this issue.
electric power supply systems with statistical measurement results,
[3] N. Watson, J. Arrillaga, Harmonics in large systems, Electric
in preparation.
Power Systems Research, this issue.
[20] IEC 61000-3-2, Limits on harmonic current emissions (equipment
[4] K. Stockman, F. D’hulster, K. Verhaege, M. Didden, R. Belmans,
input current 5/16 A per phase).
Ride-through of adjustable-speed drives during voltage dips,
[21] IEC 61000-3-4, Limits on harmonic current emissions for equip-
Electric Power Systems Research, this issue. ment with rated current greater than 16 A.
[5] M.H.J. Bollen, L.D. Zhang, Different methods for classification [22] IEC 61000-3-6, Assessment of emission limits for distorting loads
of three-phase unbalanced voltage dips due to faults, Electric in MV and HV power systems.
Power Systems Research, this issue. [23] IEC 61000-3-7. Assessment of emission limits for fluctuating loads
[6] A. Sannino, J. Svensson, T. Larsson, power-electronic solutions in MV and HV power systems.
to Power-quality problems, Electric Power Systems Research, [24] IEC 61000-4-7, General guide on harmonic distortion and
2003 this issue. interharmonics measurement and instrumentation, for power
[7] Y.H. Gu, E. Styvaktakis, Bridge the gap: signal-processing for systems and equipment connected thereto.
power-quality applications, Electric Power Systems Research, this [25] IEC 61000-4-11, Voltage dips, short interruptions and voltage
issue. variations immunity tests.
[8] E. Acha, M. Madrigal, Power System Harmonics, Computer [26] IEC 61000-4-15, Flickermeter */functional and design specifica-
Modelling and Analysis, Wiley, Chichester, 2001. tions.
[9] E. Acha, V.G. Agelidis, O. Anaya-Lara, T.J.E. Miller, Power [27] IEC 61000-4-30, Power quality measurement methods, in pre-
Electronic Control in Electrical Systems, Newnes, 2002. paration.
[10] P.M. Anderson, Analysis of faulted power systems, IEEE Press, [28] IEEE Std. 493, Recommended practice for the design of reliable
1995. industrial and commercial power systems.
[11] J. Arrillaga, D. Bradley, P.S. Bodger, Power System Harmonics, [29] IEEE Std. 1100, Recommended practice for powering and
Wiley, London, 1985. grounding sensitive electronic equipment.
[12] J. Arrillaga, B.C. Smith, N.R. Watson, A.R. Wood, Power [30] IEEE Std. 1159, Recommended practice for monitoring electric
System Harmonic Analysis, Wiley, Chichester, 1997. power quality.
[13] M.H.J. Bollen, Understanding Power Quality Problems: Voltage [31] IEEE Std. 1250, Guide for service to equipment sensitive to
Sags and Interruptions, IEEE Press, New York, 2000. momentary voltage disturbances.
[14] R.C. Dugan, M.F. McGranaghan, H.W. Beaty, Electric Power [32] IEEE Std. 1346, Recommended practice for evaluating electric
Systems Quality, McGraw-Hill, New York, 1996. power system compatibility with electronics process equipment.
[15] G.T. Heydt, Electric Power Quality, Stars in a Circle Publications, [33] IEEE Std. 1453, Voltage flicker, in preparation.
West LaFayette, 1991. [34] IEEE Std. 1564, Voltage sag indices, in preparation.

Das könnte Ihnen auch gefallen