HARTline • 2004, Number 3

Moore Industries’ HIM HART Enhanced DDL Validation Project Underway


HART Loop Monitor In an effort to unify the Device Description Language across the major fieldbus
Facilitates Partial Valve technologies, HCF member companies from around the world are working in
Stroke Testing cooperation with HCF engineers on a validation project for new HART Device
Description Language enhancements (eDDL). The project is under the direction of
Moore Industries’ HIM HART Loop
Ed Ladd, HCF Technology Programs.
Monitor now has the ability to confirm
“We are enhancing Device Description Language with an improved user inter-
that the Fisher® FIELDVUE® DVC6000
face that includies support for menus, windows, tabs and groups and added graph-
Series Digital Valve Controller is per-
ic support for graphs, trends, charts and dial indicators,” says Ladd. “We are also
forming a partial valve stroke test to
providing added support for pervasive data storage and improved diagnostics for
validate proper Emergency Shutdown
complex devices like radar level and the tracking of valve signatures.”
(ESD) valve operation and, if the test
Member companies participating in the eDDL Validation project are Berthold
has failed, to alert the user that the ESD
Technologies, Germany; Endress+Hauser, Germany; Endress+Hauser Flowtec AG,
valve is stuck.
Switzerland; Fisher Rosemount Systems, US; Flowserve, US; Fluke, US; Fuji Electric,
As part of its unique HART diagnos-
Japan; Honeywell, US and India; M-Systems, Japan; Meriam Process Technologies,
tic data, the DVC6000 Digital Valve
US; Rosemount Analytical, US; SAAB Rosemount Tank Radar, Sweden; Siemens AG,
Controller sends digital information
Germany; Siemens Milltornics, Canada; and Westlock Controls, US.
on the HART loop when a partial valve
stroke test is in progress or if the ESD
valve is stuck. Mounted transparently Cebrace Uses HART Functionality to Increase Plant Productivity
on the HART loop, the HIM continu- By Rogerio Souza da Mata, SMAR, Brazil
ously monitors the HART data from A year ago, Cebrace Cristal Plano, a large glass manufacturer in Sao Paulo, Brazil,
the DVC6000. completed a major plant upgrade using HART Communication to enhance data
When a valve stroke test is initiated, retrieval in their maintenance and diagnostic system. Their goal was improving
the HIM sends an alarm trip (relay) overall plant maintenance quality by increasing the volume and quality of data
output to confirm that the test is in received from plant equipment.
progress. Should the valve be stuck “Even though a Foundation fieldbus network was already in place in the plant, we
shut, the HIM initiates a second alarm chose to rely on a technology our plant technicians are more familiar with and feel
to alert operator and maintenance per- more comfortable relying on in critical situations,” says Benedito Adalberto Pestana,
sonnel of the valve’s potentially dan- maintenance coordinator of Cebrace’s engineering and automation department.
gerous condition. “Using all the available functionality of HART instrumentation, we have increased
The HIM can also be set to send productivity and availability with better product quality at a competitive cost.”
alarm trips outputs based on any of According to Pestana, the benefits to Cebrace of using the full capabilities of
the DVC6000’s diagnostic Field their HART-enabled instruments include: an easy and quick way to monitor
Device Status Byte data including if process conditions; reliability in the indicated and controlled process values; and
the standard HART fault conditions productivity while diagnosing casual problems.
are detected: Smart Device Pestana also notes that before the retrofit (from analog to HART) plant person-
Configuration Changed; Primary and nel had difficulties diagnosing and evaluating instruments real conditions. “In fact
Non-Primary Variable Out of we only found a problem during regular preventive maintenance stops every three
Limits; Primary Variable Analog to six months,” he says. “Using HART diagnostic capabilities, we now check instru-
Output Out of Limits or Fixed; Cold ments’ health during daily maintenance routines.”
Start; Field Device Malfunction and Cebrace utilizes the Smar HART-to-FF gateway (HI302), AssetView® interface,
More Status Available. and portable HART configurator (Palm HPC301/HPI311) to view and control
The HIM’s two or three analog instruments on both networks. The plant is built around a huge linear machine
outputs allow valve parameters, such hundreds of meters long. Any disturbance can cause a major shutdown or, even
as valve travel and output pressure, worse, destroy the main oven.
to be monitored and reported to the “If this occurs, set up and restart lasts a minimum of 60 hours, which represents a cost
DCS via standard 4-20mA signals. of about $30,000US in lost product,” Pestana adds. “Through the use of HART technol-
www.miinet.com Continued on Page 3

pg. 2 w w w. h a r t
2004, Number 3 • HARTline
Unleash the Power!
H ART Experts Show You the Way at ISA 2004
In one stop at the HART Booth (#1342), visitors to ISA can see new HART-based products from more than 20 of the world’s
leading process automation suppliers – control system interfaces, remote I/O systems and software solutions that make it easy
and cost-effective to unleash the Power of HART and realize benefits in all phases of the plant life cycle.
The HART booth features interactive displays and a wide array of new HART-enabled instruments, systems and migration
solutions that demonstrate how HART Communication can help users optimize the intelligence in the millions of HART
devices currently installed in plants around the world.
The interactive HART booth features a wide array of new HART-enabled instruments, systems and solutions...showing prac-
tical ways to leverage the intelligence in HART-smart devices (using both 4-20mA and digital communication channels) to
deliver continuous, real-time device diagnostics and process information.
Magician Paul Gertner performs in the HART booth every hour. His captivating show both entertains and educates attendees
on the value and benefits of HART Communication. Gertner has appeared at The White House, on HBO, NBC’s World’s Greatest
Magicians, and The Tonight Show.
Free copies of the newly updated 4th Edition Complete HART Guide CD-ROM are available to all visitors to the HART booth.

PRODUCT SP TLIGHT HART Plant of the Year Recipients to Be Announced at ISA


The Dresser Masoneilan HART- Recipients of the 2004 HART Plant candidates. If you are aware of a plant
based SVI II Digital Positioner fully of the Year Award will be announced to that is using HART Communication for
integrates with AMS™ Suite software. the world press at the HCF ISA Press more than configuration and calibration,
By using the Emerson Process Conference in Houston, Texas or a plant that is using the real-time diag-
Management device driver (that is (Tuesday October 5). This is the first nostics and process variables of HART-
available for download at both the time the names of the selected plants enabled devices with its control system,
Emerson and Masoneilan websites), have been withheld until the ISA show. then you have a candidate!
users can configure, calibrate and diag- The award is presented annually by the The HCF encourages nominations
nose any control valve equipped with HCF to recognize innovative use of for HART Plant of the Year from all
HART Communication in real-time world areas. Nominations are accepted
the Masoneilan SVI II.
process applications. through May of each year. For more
By supporting features such as audit
Even as the 2004 recipients are recog- information on the HART Plant of the
trail and calibration management, the
nized, the HCF begins its search for 2005 Year, go to www.hartcomm.org.
driver provides the benefits of tracking
the calibration history of valves and Cont. . .Cebrace Uses HART
effectively planning resources for
ogy, we are able to maintain online pre- rely on invaluable support from our
upcoming shutdowns.
ventive maintenance full time and reduce partnership with SMAR.”
The integration of AMS Suite and SVI
maintenance costs at least 50 percent.” HART integration via Smar
is further enhanced with AMS ValVue2
“Our next goal is to have a link between AssetView allows Cebrace to monitor
SNAP-ON™ connectivity. This HART
our maintenance database software and process-related variables, diagnostic
Communication software is launched
the HART field device management tool status, and information 24 hours a day,
from the AMS environment providing (Smar Assetview),” Pestana adds. “Then seven days a week, and to access all
in-depth valve diagnostic capabilities we’ll be able to automatically generate field devices from every station
and a user-friendly interface to com- service orders for calibration or any plantwide (even worldwide if an
mission control valves. maintenance action and ultimately real- Internet connection is available) in a
Features such as Setup Wizard, ize more and more availability.” single, web-based, integrated software
process trending, valve signatures, and Pestana also notes that Cebrace per- environment (www.smar.com).
device cloning are among the more sonnel are very satisfied with their For a more information on the
powerful benefits of AMS ValVue2 HART-based upgrade because “we Cebrace application, look for HARTLine
SNAP-ON functionality. know we are using the most advanced 2003 No. 4 at www.hartcomm.org/news-
www.masoneilan.com instrumentation in the market and can main/newslettermain.html.

comm.org pg. 3
HARTline • 2004, Number 3
Cont. . .Troubleshooting Control Valves
The resulting graph depicts a stick- According to the chemical
and-slip problem induced by unwanted plant personnel, significant
friction in the control valve, inducing maintenance cost savings
instability in the control loop. were realized.
Identifying the underlying problem Case 3: Express assistance
eliminated the need for sending person- required from a factory expert
nel in the field, reduced the trou- in a secluded region.
bleshooting time and provided key Here, a control valve was
information to prepare the work order not behaving properly to a
(order parts, schedule maintenance, setpoint change, which pre-
etc). vented ramping up the
If this valve had not been fitted with a plant to its normal through-
HART-enabled positioner, it is likely that put. The site was in a seclud- Valve in secluded area; Factory expert , 4000 miles away;
a crew would have had to obtain work ed area in South America Secure website
permits, investigate using proper protec- that would require at least
tive equipment, and worst of all, go in 24 hours to access. troubleshooting packages are widely
with an uncertainty of the root cause. Using a secured Masoneilan website, available and waiting to be deployed in
Case 2: Utilizing diagnostic data to the factory expert and site technician were any environment.
establish predictive maintenance at a connected in seconds. The site technician
major chemical plant. was running ValVue2 software and was
A control valve maintenance budget connected to the HART-enabled position- NEW
is the second in importance for most er. The factory technician was remotely TH
industrial plants, mainly because of a viewing the software. In no time, the
4 EDITION
reactive and/or an unnecessary preven- problem was identified—inappropriate
tive approach. Using the diagnostic calibration of the positioner—and quick- FREE
data provided via the HART Protocol, a ly resolved.
chemical plant is predicting the life of As these cases illustrate, the HART
COPIES
bellow seal equipped valves. Protocol is a proven transport mecha- AT HART ISA
These engineered sealing mechanisms nism of field device information over an
are costly to replace in parts, time and in existing twisted pair of wires that allows
BOOTH #1342!
the procedure of handling dangerous users to assess the health of control
chemicals. Our SVI™ positioner family valves in a safe working environment.
maintains in its non-volatile memory, With the growing popularity of
real-time information such as time HART over the past 10 years, it is now
open, closed and near closed. easier than ever to take full advantage
Combining this data with the cycles and of the diagnostic data from HART- 9390 Research Blvd. Suite I-350
Austin, TX 78759-6540 U.S.A.
the travel odometer, this customer based devices. Software, hardware, sys- 512-794-0369, FAX 512-794-3904
obtains the remaining life of the bellow. tem integration and sophisticated HCF Europe +41(0)61-333-2275
www.hartcomm.org
Ron Helson, Executive Director
Jean-Luc Griessmann, HCF Europe
HCF Membership is open to anyone Welcome New Members Wally Pratt, Chief Engineer
interested in the use of HART tech- Paul Baker, Support Engineer
nology. Join now, share the benefits! Anderson Instrument Company Ed Ladd, Technology Programs
Manometr-Kharikiv Keith Kleinschmidt, Support Administrator
Organization… Not-for-profit
user funded. ROOST-95 Inc. Irina Kadukova, Training/Web Support
Melissa Boyd, Administration
Expertise… Vendor-neutral ShenZhen ExSaf Electronic Co. Ltd.
Liz Patranella, Media Relations
technical support, training. Shinho System Co. Ltd.
SPIRAX Sarco Italy HARTLine is published quarterly by HART
Standards… Best practices and Communication Foundation. Subscriptions can be
technology specifications. Thermo Electron Corp. obtained through the HCF offices.

© HART Communication Foundation, 2004. All rights reserved.


HART® is a registered trademark of the HART Communication Foundation.
All other trademarks are the property of their respective owners.
HART Communication News • 2004, Number 3

The Power of HART Communication. . . See What You Can Do


Continuous device monitoring, real- Life Cycle: planning and engineering, capabilities to improve operations,
time device diagnostics and multi-vari- installation and commissioning, reduce time from problem identifica-
able process information are within operations and maintenance, and asset tion to problem resolution, and
your grasp. Start using the HART-smart productivity improvement. continuously validate loop integrity
devices in your plant to their full poten- HART-enabled systems use both and control information. In addition,
tial and maximize your return – opti- communication channels to unlock the real-time diagnostic alerts provide early
mize assets, increase availability, lower value of intelligent device information warning to device or process problems.
costs and ensure compliance. and secure control loop
“HART devices are real-time data integrity. Real-time HART Growth Outlook
servers with two simultaneous commu- diagnostics and predic-
nication channels on the same wire – tive maintenance alerts
the 4-20mA analog channel and the enable problems to be
HART digital channel,” says HCF detected within seconds
Executive Director Ron Helson. “Real- and process disruptions
time integration with plant control, to be avoided.
safety and asset management systems By using the full
unlocks the Power of HART and allows potential of the tech-
users to realize the full potential of their nology, you are able to
HART-smart devices.” leverage intelligent device
HART-enabled control system inter-
faces, remote I/O systems and software Troubleshooting Control Valves Made Easy Using HART
solutions make it easy and cost-effective By Sandro Esposito, Dresser Masoneilan, Avon, MA
to unleash the Power of HART and real-
ize benefits in all phases of the Plant In this new era of plant management, two things are clear: many are continuous-
ly seeking methods for reducing the exposure of personnel to hazardous areas and
many continue to expect more from reduced staffing. Don’t you feel like trou-
Inside This Issue bleshooting control valves in a safe environment for a change? HART can help!
Pg. 2 Moore Industries’ HIM HART
After personally spending many years as a field service engineer, I know how often
Loop Monitor Facilitates Partial valves can be installed in the most inconvenient locations and how much their per-
Valve Stroke Testing formance can impact both the throughput and the safety of a plant. I think the fol-
Pg. 2 HART Enhanced DDL Validation lowing case studies effectively demonstrate the value and benefits of applying HART-
Project Underway enabled digital positioners in difficult environments.
Pg. 2 Cebrace Uses HART Functionality Case 1: Operations from a major refining company, are complaining of an unstable con-
to Increase Plant Productivity trol loop and suspect the valve as the problem.
Pg. 3 HART Experts Show You the Way This control valve is equipped with an advanced diagnostic version of the
at ISA 2004 Masoneilan SVI II™ digital valve positioner. Using Masoneilan’s ValVue2™ software
Pg. 3 Product Spotlight connected to the marshalling cabinet near the control room, the trending feature is
Pg. 3 HART Plant of the Year Recipients populated with the actual valve position, the control system’s setpoint, via the
to Be Announced at ISA HART Protocol.
BkPg Welcome New Members
Continued on Back Page