Redundancy - Enhanced dependability


Visit us at
In our earlier articles, we have system breakdown in case of any
seen the benefits Intelligent fault.
Electronic Devices (IEDs) offer
when employed for plant For improving reliability of the
Elecrama
network, use of redundant
automation.
connections and integrating
2004
Modern automated process plants devices become all the more
have hundreds of such IEDs important.
Hall No. 6
controlling and monitoring the
Hence, redundancy is built to
entire plant. A large amount of data
ensure smooth and uninterrupted Stall No. R-3
is getting transferred on the data
flow of information including
bus. Continuous data monitoring
execution of commands that go
without interruption is the need of
on highest priority. Pragati Maidan
the hour. This requires a standby
system to take care of any In this issue, we have discussed
inadvertant failures or planned issues like :
shutdowns on the active network.
New Delhi
* What exactly is meant by
redundancy
Continuous process plants cannot * Different methods of achieving
face network breakdowns that can redundancy 3rd to 7th February,
disrupt the data acquisition and * Pros and cons of these 2004
control system and may result into methods

Wish all the readers a Very Happy New Year

Visit us at www.LNTEBG.com
FEATURE

Dual Redundant Communication System


- Mr. Anshuman Mallya
Electrical Systems & Equipment

Modern automated process plants just discuss here a few devices Redundancy
use numerous Intelligent available as data concentrators in If we perceive the literal meaning
Electronic Devices (IEDs) for the market. A star coupler (Fig. 1) of the word ‘redundant’, it says
remote monitoring and control. A is one of the options. It is used for ‘superfluous’ – something which
large amount of data is getting the connection in star topology to is extra. In our context, it shall
transferred to Remote Terminal a central master. In a modular star mean an additional path / backup
Unit (RTU). The risk of complete coupler, failure of a single module system for data and control
communication failure due to a leads to the loss of entire data of commands to / from the HMI /
single link is unacceptable. This the IEDs connected to that Supervisory Control & Data
calls for a standby / backup module. This cannot offer Acquisition (SCADA). Failure of
system in addition to the main or redundancy at data concentrator one of the components or paths
active network. Today’s trend, level which is a must for a critical is annunciated and taken care by
hence, demands a shift from non- process. the second one to preclude
redundant to redundant systems. complete failure. If we just sketch
a rough model of a redundant
Non Redundant systems Fig.1 system, it shall be as given in
When the IEDs are coupled to the Fig.2.
data monitoring system, there is
more than one arrangement
possible to achieve this. The A B B N e tw o r k P a rt n e r F E E D E R T E R M IN A L R EF54 1 A B B N e tw o r k P a rt n e r F E E D E R T E R M IN A L R EF54 1 A B B N e tw o r k P a rt n e r F E E D E R T E R M IN A L R EF54 1

simplest and easiest would be to O


I

O
I

O
I
Fig.2
connect all the relays to a single
A B B T ra n s m it O y A B B T ra n s m it O y A B B T ra n s m it O y
N e tw o rk P a r tn e r N e tw o rk P a r tn e r N e tw o rk P a r tn e r
L L L

F R L F R L F R L
R R R

running cable and hook the cable C


E
C
E
C
E

up to the PC via the interfacing


U a u x = 8 0 . ..2 6 5 V d c /a c I on = 1 /5 A ( Io ) 1 M R S x xx xx x
U a u x = 8 0 . ..2 6 5 V d c /a c I on = 1 /5 A ( Io ) 1 M R S x xx xx x U a u x = 8 0 . ..2 6 5 V d c /a c I on = 1 /5 A ( Io ) 1 M R S x xx xx x
fn = 5 0 H z U n = 1 00 /11 0 V (U ) 98 15 0
fn = 5 0 H z U n = 1 00 /11 0 V (U ) 98 15 0 fn = 5 0 H z U n = 1 00 /11 0 V (U ) 98 15 0
In = 1 /5 A (I) U o n = 1 0 0 /1 1 0 V ( U o ) 95 0 9
In = 1 /5 A (I) U o n = 1 0 0 /1 1 0 V ( U o ) 95 0 9 In = 1 /5 A (I) U o n = 1 0 0 /1 1 0 V ( U o ) 95 0 9

devices. This is basically a stand Quite often, one RS485/232


alone system or more popularly converter is connected as a data
known as a non redundant concentrator. It should be
system. understood that in no way a mere
485/232 signal converter can do
If we go into the innards of this the purpose of a data concentrator.
system, we will see that the The primary function of a data It can be seen that, there are ‘n’
deficiencies attached to the concentrator is fast and sequential number of paths from the source
system are plenty. There is no polling of the IED data. Additional "s" to destination "d" which employ
protection against the failure of one features in a modern day data d1 …. dn devices. Only one of the
of the interfacing devices between concentrator like discrimination devices / path will be active at a
IEDs and the data monitoring between the critical & non-critical specified time. The active device
software (HMI). In fact, there is no data makes it an ideal choice for is called the Master and its
backup even against the breakage an integrated system. Both the standby partners are dubbed as
of data cables. In addition to this, star coupler and converter are far Slave. The system runs smoothly
if one of the interfacing devices is from achieving these under a Master-Slave
taken out for repair / maintenance, specifications. configuration. In the event of failure
the complete data monitoring is of the Master device or the
disrupted. Seeing the intricacy and criticality connecting data cable up to the
attached to a modern plant, need Master device, the Slave becomes
Before we move further, we will for more reliable system is felt for. active. It starts polling the data and
transmitting it to the HMI/SCADA, between IEDs and data
thus ensuring continuous concentrator (Fig.3). Consider
availability of the IED data. the system below where DC1
Meanwhile, the fault in the main is acting as a master and
network can be identified and DC2 as slave.
rectified.
In case cable breakage at the
It should be noted that security point indicated occurs, the
should be provided both against DC1 polls the data for IEDs 1 Fig.4
data cable breakage and failure of & 2 and DC2 becomes active
interfacing device or its and starts doing the same for
accessories. Mere duplication of IEDs 3, 4 and 5 thus ensuring
connections / cables will not complete availability of all IEDs. available to achieve redundancy
suffice this requirement. This Additionally, if we connect an for the MMI. The less popular one
model can be called a ‘n’ degree additional communication cable is to have two separate PCs with
redundant system. When the between the relays, the above each one having its own MMI
number of paths in the above system can promise the security software. (Fig.4) Thus here, a
model is ‘‘two’’, it becomes a Dual of a quadruple redundant system complete PC with MMI is available
Redundant System. Critical at communication cable level. as a standby. This system is not
process like Nuclear Power Plants preferred much for the cost
even employ Triple or Quadruple Data Concentrator Redundancy: implication and space
redundant systems. Data concentrator is the second consideration it carries with it.
member in the communication
hierarchy. It is the sole mediator In the second architecture, two
For ensuring data and status
between the IEDs and upper level cables are laid from the data
change information from all IEDs
(MMI/DCS) system. Hence, concentrator to MMI and
plantwide, a data concentrator
redundancy at data concentrator connected to different ports of PC
facilitating parallel poling on all
is of utmost importance. (Fig.5). One port is configured as
drops is essential. Data bus and
Master and continuously polls the
data connections should be Dual
In Fig.3, either DC1 or DC2 is data. In case this port doesn’t
Redundant. In the event of one of
Master and in active state. If either receive any response from the
the conductors breaking, data
of them fails, the other becomes connected slaves for a preset
transmission changeover should
master/active and starts polling time, which may be either due to
be smooth, without any inadvertant
data and issuing commands the communication cable
operation i.e. bumpless.
received from MMI. Moreover, the
Redundancy can be achieved at redundancy of the power supply
the three levels: to data concentrator is as
important as the data concentrator
Data Cable Redundancy: This module itself. Hence, in the above
level of redundancy is applicable scheme, 2 PSUs are shown. If
one of them fails, the other
unit should drive the
necessary power for the
cards.

Redundancy at MMI level:


The software residing in the
PC which displays and Fig.5
stores the IED data forms a
breakage or PC port failure, the
part of MMI system. User can
second port of the PC becomes
also issue specific
active and automatically starts
commands to the IED
polling the data. This is a more
through the MMI. Two
economical solution and provides
Fig.3 primary configurations are
adequate redundancy at MMI level. easy to lay and its termination is desired to have this data at other
Before we move further, we will simple. Shielding provides places too, at the desk of the plant
discuss a few systems here which excellent immunity to interference manager for e.g. These auxiliary
are sometimes incorrectly and is a cost effective solution for PCs share the data on the same
considered as equivalent data transfer. network making the PC data
Redundant Systems. concentrators all the more
Use of shared processor vulnerable. Additional problems
Use of Optic Fibre cable Different system integrators like PC hanging do add to the
Often it is popularised that using suggest different ways of problems. Moreover, even an
an optic fibre cable between IEDs configuring a system. One of industrial PC requires a suitable
and data concentrator / star them is based on sharing of data environment to work with and a
coupler may be a replacement for between two processors. To good regular maintenance.
a dual redundant network. There elaborate it, consider a data of 2
have been cases reported about IEDs to be collected and With the advancement of
the breakage of such cables. transferred to MMI. For this, two technology, hardware based data
Though its immunity to noise is processors A & B will be used. concentrators have been
better when compared to STP Each shall poll a data of 1 IED introduced and have proven to be
and transmit it. In this more reliable and robust. Unlike
cable, its breakage cannot be
configuration, the data is shared PC based data concentrators,
prevented. Moreover, by just using
equally between the two
a more noise immune cable we these require minimum
processors. In the event a
are not ensuring a suitable backup maintenance and have a much
processor or link to the processor
against a part or complete failure longer life.
failing, 50% of the data shall be
of the data concentrator / star
lost. Hence, it is not a secure
coupler. One of the most powerful features
system. Considerable data is at
stake if either processor or link to only available with these advance
In all, for a network to provide the the processor fails. data concentrators is the facility
safety and security of dual of Hot Swapping of modules. It is
redundancy, it is mandatory that it This configuration is employed possible to take out one of the data
should have that additional path / basically where a PC based data concentrator cards for
standby setup for data concentrator is used. The maintenance and replace it with
transmission between the source reliability of the data concentrator another with the system running.
and destination. Moreover, optic system is always a question mark While the swapping of modules is
fibre cable laying and termination when we are going for PC based in operation, complete IED data is
calls for specified skills. Also, the data concentrator. The probability available to the monitoring system
cable is quite expensive and attached with the breakdown of PC and control can be accessed over
recommended only above 1 km is in turn attached to the failure of the IEDs without disruption. This
or when the environment is noise data concentrators. feature is unavailable with any PC
polluted and where high bandwidth data concentrator.
is required. When used under 1 Today, with entry of new viruses
km where STP can be used, it daily, the software in those PC Conclusion:
necessitates additional hardware concentrators tend to get corrupt Since numerous such options
such as converters to be used in the course of time. and configurations are available
even for smaller distances. This today, the user should be alert in
can cause further time delays and Generally PC based data selecting a system so that the
disturbance in communication. concentrators and MMI systems plant security meets the desired
On the other hand, STP cable is share data on TCP/IP. Often it is level.

For further details on this subject, please contact:


EBG - Electrical Systems & Equipment, Larsen & Toubro Limited, Saki-Vihar Road, P.O. Box 8901, Powai, Mumbai 400 072
Fax: 022-2858 1024 * E-mail: kotnisnd@Intebg.com

Printed by Printania Offset Pvt. Ltd.,D 20/21, Shalimar Industrial Estate, Matunga (East), Mumbai 400 019. Tel.: 2407 7996/
8866/4540 Fax : 2402 4703 Email: pds6@bol.net.in. The views expressed in this magazine are not necessarily those of the
management of Larsen & Toubro Limited. The contents of this magazine should not be reproduced without the written
ABCI permission of the Editor. Not for sale-only for circulation among the customers. Editorial Coordinators : R. S. Mahajan,
Neelam D. Kotnis, EBG-ESE, Powai .
Member

Das könnte Ihnen auch gefallen