ELECTRICAL NOTES

GENERAL CONDITIONS SHEATHS ARE NOT DAMAGED IN ANY WAY. CABLE PITS SHALL CONSIST OF HIGH DENSITY POLYETHYLENE PITS WITH
THIS DRAWING IS A SUMMARY OF THE GENERAL REQUIREMENTS FOR THE PROJECT, THE CABLES SHALL NOT BE BENT TO A RADIUS LESS THAN THAT RECOMMENDED BY THE CONCRETE/STEEL LIDS, UNLESS OTHERWISE INDICATED. PITS, LIDS AND THE METHOD OF
ASSOCIATED WORK/CO-ORDINATION
CONTRACTOR SHALL REFER TO THE TECHNICAL SPECIFICATION FOR FURTHER DETAILED MANUFACTURER. INSTALLATION SHALL BE SUITABLE FOR THE ANTICIPATED WHEEL LOADINGS IN THE AREA
INFORMATION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FULLY UNDERSTAND THE CO-ORDINATE ELECTRICAL REQUIREMENTS WITH MAIN CONTRACTOR AND ALL OTHER IN WHICH THEY ARE INSTALLED OR SHOWN IN THE DRAWINGS, WHICHEVER IS GREATER.
TRADES. BECOME FULLY INFORMED OF THE CONTRACT WORK BY INSPECTION OF THE SITE SHOULD ANY DAMAGE OCCUR TO ANY PART OF A CABLE (INCLUDING SERVING) DURING
WORKS PRIOR TO SUBMISSION OF TENDERS. THE CONTRACTOR MUST CONDUCT ALL LIDS TO ELECTRICAL PITS SHALL BE MARKED 'ELECTRICAL'. LIDS FOR COMMUNICATIONS
AND BY OTHER MEANS CONSIDERED NECESSARY. UNFORESEEN DIFFICULTIES DUE TO HANDLING OR INSTALLATION, THE SUPERINTENDENT SHALL BE INFORMED AND WORK
SURVEYS AND INSPECTIONS NECESSARY TO UNDERSTAND THE WORKS OUTLINED IN THE PITS SHALL BE MARKED 'COMMUNICATIONS'.
NEGLECT OF THIS PRECAUTION SHALL IN NO WAY RELIEVE THE RESPONSIBILITY FOR FULL SHALL ONLY PROCEED AFTER HIS INSPECTION AND AUTHORISATION TO CONTINUE HAS
DRAWINGS AND OTHER ASSOCIATED DOCUMENTATION. THE CONTRACTOR IS TO MAKE
PROPER EXECUTION OF THE WORKS. NO CLAIM FOR ADDITIONAL WORK ARISING FROM BEEN GIVEN.
ALLOWANCES IN THE SERVICES FOR ALL ASPECTS COVERED UNDER THIS SPECIFICATION
AND COORDINATE THE LOCATION OF ALL ELECTRICAL EQUIPMENT/SERVICES WITH OTHER NEGLECT OF A THOROUGH INSPECTION WILL BE APPROVED. CUT-OFFS AND JOINTING: CONTRACTORS DOCUMENTATION
TRADES, STRUCTURES, AND ALL OTHER SERVICES. DURING INSTALLATION, ALL CABLES SHALL BE CUT FROM DRUMS IN SUCH A MANNER THAT THE CONTRACTOR SHALL DEVELOP THE FOLLOWING DOCUMENTATION AS PART OF THE
TESTING AND COMMISSIONING CUT_OFFS ARE A MINIMUM AND ANY SURPLUS CABLE REMAINING IS IN A SINGLE LENGTH. WORK AND SUBMIT TO SITE SUPERINTENDENT DOCUMENTATION IN A COMPLETE
SCOPE OF WORK CABLES SHALL BE INSTALLED IN CONTINUOUS LENGTHS. CONSOLIDATED SET. THROUGHOUT THE PROGRESS OF THE WORKS THE CONTRACTOR
SUPPLY ALL NECESSARY LABOUR AND ASSISTANCE FOR TESTING, LIGHTING
THE SCOPE OF WORK INCLUDES THE SUPPLY, DELIVERY, INSTALLATION, TESTING, SHALL MAINTAIN RECORDS OF ANY CHANGE TO ITS DOCUMENTATION WHICH MAY HAVE
MEASUREMENT TEST (IN ACCORDANCE WITH VICTORIA GOVERNMENT COMMUNITY CABLE GLANDS:
COMMISSIONING AND DEFECT RECTIFICATION WORK OF THE FOLLOWING SYSTEMS AND BEEN APPROVED FOR CONSTRUCTION PURPOSES SUCH THAT ON COMPLETION OF THE
SPORTING FACILITY LIGHTING GUIDE) LOAD BALANCING, OPERATING AND ADJUSTING THE CABLE GLANDS SHALL BE OF AN APPROVED WEATHERPROOF TYPE OF A TYPE THAT IS
EQUIPMENT AND AS SHOWN ON THE ELECTRICAL SERVICES DRAWINGS AND WORKS ACCURATE "AS CONSTRUCTED" INFORMATION IS AVAILABLE.
SYSTEM AND EQUIPMENT, CERTIFICATE OF COMPLIANCE AND FOR FULLY INSTRUCTING CONSISTENT WITH THE IP RATING OF THE ENCLOSURE .
SPECIFICATION. SUPPLY ALL THE REQUIRED MATERIALS UNLESS OTHERWISE SPECIFIED.
THE CLIENT OR ITS REPRESENTATIVE IN THE OPERATION OF THE SYSTEM AND AS-CONSTRUCTION DRAWINGS
THE ELECTRICAL CONTRACTOR SHALL ALLOW FOR ANY INCIDENTAL ITEMS THAT HAVE AS A MINIMUM, GLANDS IN GENERAL AREAS SHALL BE CONSTRUCTED FROM:
EQUIPMENT. PROVIDE FULL OPERATORS MANUAL COMPLETE WITH AS-BUILT DRAWINGS PROVIDE A FULL SET AND A 'DWG' (AUTOCAD LATEST VERSION) DISK OF AS-BUILT
BEEN OMITTED TO PROVIDE A COMPLETE WORKING SYSTEM INCLUSIVE OF: · CABLES UP TO 25MM OVERALL DIA: NYLON OR PVC
AND ALL TESTS RESULTS. DRAWINGS, TO THE SATISFACTION OF THE SUPERINTENDENT, WITHIN 7 DAYS OF
- SWITCHBOARDS · CABLES LARGER THAN 25MM OVERALL DIA: NICKEL-PLATED BRASS
THE CONTRACTOR SHALL CARRY OUT TESTING AND COMMISSIONING OF THE NEW PRACTICAL COMPLETION. THE AS BUILT DRAWINGS SHALL COMPREHENSIVELY
- LIGHTING AND ASSOCIATED WIRING LIGHTING SYSTEM INCLUSIVE OF: NICKEL-PLATED BRASS GLANDS SHALL NOT BE USED IN CONJUNCTION WITH ALUMINIUM REFLECT DETAILS OF ALL INSTALLED SYSTEMS AND COMPONENTS, AS DETAILED IN
- POWER AND ASSOCIATED WIRING - NIGHT TIME COMMSSIONING TO TEST OPERATION AND FUNCTIONALITY OF LUMINAIRES. ALLOY BOXES OR ALUMINIUM GLAND PLATES. THE SCOPE OF WORK.
- COORDINATION OF LIGHTING POLE, FOOTING, CROSSARM ETC - RECORDING AND PROVIDING PRINCIPAL OF FIELD OF PLAY HORIZONTAL ILLUMINANCE DAMAGE AND REINSTATEMENT: OPERATION AND MAINTENANCE MANUALS
LEVELS AT ALL SWITCHING LEVELS (TRAINING AND COMPETITION) IN ACCORDANCE WITH ANY DAMAGE TO CIVIL WORKS OR STEEL, INCLUDING PAINTWORK CAUSED BY ELECTRICAL PROVIDE TWO SETS OF OPERATION AND MAINTENANCE MANUALS, THE AIM OF THESE
AS2560 SERIES INSTALLATION WORK SHALL BE MADE GOOD BY THE CONTRACTOR. BEING TO PROVIDE A DETAILED UNDERSTANDING OF THE ITEMS OF EQUIPMENT, TESTS
ENVIRONMENTAL CONDITIONS
- ONE NIGHT OF SPORTSLIGHTING COMMISSIONING FOR FINAL ADJUSTMENT OF RESULTS AND ITS OPERATION. AN AID FOR TRAINING OF OPERATORS, A REFERENCE
THE EQUIPMENT SUPPLIED BY THE CONTRACTOR SHALL BE SUITABLE FOR CONTINUOUS AFTER ERECTION ALL HOLES IN FLOORS AND WALLS AND IN CABLE PIPES THROUGH
LUMINAIRE AIMING TO ACHIEVE COMPLIANCE AND TO INCREASE PERFORMANCE IN WHICH PASS CABLES, CONDUITS OR EARTH BARS SHALL BE SEALED. ALL PENETRATIONS FOR FAULT DIAGNOSIS AND A FRAMEWORK FOR PREVENTIVE AND BREAKDOWN
OPERATION IN AN INDOOR OR OUTDOOR ENVIRONMENT AS APPLICABLE. THE MAINTENANCE THE MANUALS SHALL INCLUDE AS A MINIMUM.
ACCORDANCE WITH AS2560 SERIES ILLUMINANCE AND UNIFORMITY REQUIREMENTS. SHALL BE SEALED WITH A FIRE RESISTANT TWO PART EXPANDING SILICON RUBBER. THE
CONTRACTOR IS WHOLLY RESPONSIBLE FOR ENSURING THAT THE EQUIPMENT SUPPLIED
UNDER THIS CONTRACT SHALL BE CAPABLE OF DELIVERING CONTINUOUS FULL RATED IN ADDITION, AS PART OF COMMISSIONING THE CONTRACTOR SHALL TAKE HIGH CONTRACTOR SHALL ENSURE THAT ALL PENETRATIONS ARE FIRE, WEATHER AND RODENT NAME, ADDRESS, TELEPHONE NUMBERS, EMAIL ADDRESS AND WEB PAGE ADDRESS OF
LOAD UNDER THE SITE CONDITIONS LISTED BELOW: RESOLUTION PHOTOS (MIN. 4MP) CLEARLY DETAILING: PROOF. THE MANUFACTURER AND SUPPLIER OF ITEMS OF EQUIPMENT INSTALLED, TOGETHER
WITH CATALOGUE LIST NUMBERS. INCLUDE DETAILS FOR ALL CONSULTANTS AND
MAXIMUM AMBIENT TEMPERATURE 45°C · LOCALITY AND POSITION OF LIGHTING POLE FOOTINGS
CONTRACTORS INVOLVED IN THE DESIGN AND CONSTRUCTION PHASE.
MINIMUM AMBIENT TEMPERATURE -5°C · LIGHTING POLE FOOTING EXCAVATION PRIOR TO CAGE/REO INSTALLATION UNDERGROUND ELECTRICAL INSTALLATION
TECHNICAL DESCRIPTION AND MODES OF OPERATION OF THE SYSTEMS INSTALLED.
RELATIVE HUMIDITY 80% (MAX), 10% (MIN) · LIGHTING POLE FOOTING PRIOR TO CONCRETE POUR TRENCHING:
PRODUCT LITERATURE FOR THE SYSTEMS INSTALLED AND CONTACT DETAILS FOR
ALTITUDE 1000m (NOT EXCEEDING) · REPRESENTATIVE PHOTOS OF UNDERGROUND CONDUIT INSTALLATION SHOWING ALL TRENCHES, UNLESS OTHERWISE DIRECTED BY THE SUPERINTENDENT, SHALL BE SUPPLIERS AND MANUFACTURERS OF THESE SYSTEMS.
NUMBER/SIZE CONDUITS INSTALLED AND BURY DEPTH EXCAVATED IN GROUND AS FOUND ALONG THE LINE AND TO THE DEPTHS AND WIDTHS
CONTROL AND SWITCHING SEQUENCES AND FLOW DIAGRAMS FOR THE SYSTEM
· PRIOR STANDING EACH LIGHT TOWER, A PHOTO OF EACH LIGHTING POLE HEADMAST SHOWN ON THE DRAWINGS. FINAL LOCATIONS OF UNDERGROUND INFRASTRUCTURE TO INSTALLED, INCLUDING SAFETY FEATURES. ALSO PROVIDE INSTRUCTIONS FOR FOR
REGULATIONS, STANDARDS AND CODES BE SURVEYED AND ALIGNMENTS SHALL BE ACCURATELY PRESENTED IN AS-BUILT
INSTALLATION SHOWING ALL INSTALLED LUMINAIRES AND THEIR CONNECTION.S OPERATING AND ADJUSTING CONTROL SYSTEMS.
ALL MATERIALS, SUPPLIES AND ALL WORK INSTALLED SHALL COMPLY WITH THE CURRENT · DRAWINGS
CLOSE UP OF LUMINAIRE MOUNTING TO HEADMAST MANUFACTURER'S OPERATIONAL AND SAFETY LITERATURE, AS APPROPRIATE.
CODES, STANDARDS, RULES AND REGULATIONS OF ALL STANDARD AUTHORITIES THE LINE OF THE TRENCH MUST BE KEPT PERFECTLY STRAIGHT AND PARALLEL TO THE
INCLUDING, BUT NOT NECESSARILY LIMITED TO: · CLOSE UP OF ARMOURED CONDUIT CONNECTION BETWEEN LUMINAIRE AND PLANNED ALIGNMENT. THE BOTTOM MUST BE KEPT LEVEL ACROSS THE TRENCH AND THE EMERGENCY MAINTENANCE PROCEDURES, INCLUDING TELEPHONE NUMBERS FOR
HEADMAST SIDES AS NEAR THE VERTICAL AS IS PRACTICABLE. ANY CAVITIES IN THE BOTTOM OF THE EMERGENCY SERVICES AND AFTER HOURS CONTACTS FOR SUPPLIERS AND
NATIONAL CONSTRUCTION CODE 2019
· INSIDE EACH ACCESS PANEL SHOWING SWITCHGEAR AND DRIVER INSTALLATIONS TRENCH MUST BE FILLED WITH SELECTED STONE FREE MATERIAL, PROPERLY COMPACTED CONTRACTORS AND PROCEDURE FOR FAULT FINDING.
AS/NZS 3000, AS/NZS 3008 (LV POWER RETICULATION)
· FINAL INSTALLATION OF SWITCHGEAR AND CONTROL PANEL INSTALLATIONS TO THE PROPER GRADE. STATUTORY CERTIFICATES OF COMPLIANCE FOR ALL ELECTRICAL AND
AS 3017 ELECTRICAL INSTALLATIONS - TESTING GUIDELINES THE CONTRACTOR SHALL TAKE CARE TO ERECT SHORING AS NECESSARY TO COMMUNICATION WORK, COPIES OF MANUFACTURER'S WARRANTIES.
AS 61439 (LV SWITCHBOARDS) EFFECTIVELY PREVENT THE SIDES OF THE TRENCH FROM RUNNING OR FALLING INTO THE
CABLE SUPPORT AND PROTECTION CERTIFICATES FROM AUTHORITIES AND UTILITIES, PRODUCT CERTIFICATION, COPIES
AS 2560.2.3 FOOTBALL (ALL CODES) LIGHTING EXCAVATION AND TO KEEP TRENCHES FREE FROM WATER DURING ALL CABLE/CONDUIT OF TEST CERTIFICATES, ETC.
- CABLES SHALL BE ADEQUATELY SUPPORTED ALONG THEIR ENTIRE LENGTH TO THE LAYING OPERATIONS. SPOIL FROM THE TRENCH EXCAVATION NOT REQUIRED FOR
AS 4282 CONTROL OF OBTRUSIVE LIGHTING APPROVAL OF THE SUPERINTENDENT. SUPPORTS SHALL BE INSTALLED AT MAXIMUM COMMISSIONING PHOTOS
BACKFILL IN THE TRENCH SHALL BE MOUNDED ABOVE THE BACKFILLED TRENCH. WHERE
VICTORIAN BUILDING REGULATIONS INTERVALS OF 1000 MM AND AT LESSER INTERVALS WHERE REQUIRED TO PREVENT ELECTRICAL TRENCHES ARE TO BE EXCAVATED ACROSS SPORTING FIELD OF PLAY, THE AS-BUILT DRAWINGS, SYSTEM SCHEMATICS, ETC.
VICTORIAN SUPPLY AND INSTALLATION RULES (VSIR) UNDUE SAGGING. CABLES IN VERTICAL RUNS SHALL BE SUPPORTED EVERY 600 MM. CONTRACTOR SHALL ENSURE THAT THE BACKFILL DOES NOT INTERFERE WITH SPORTING INSPECTION AND TEST PLANS, TEST SHEETS AND COMMISSIONING RECORDS.
- WHERE NOT INSTALLED ON CABLE TRAY, CABLES SHALL BE SADDLED TO CONCRETE PLAY SURFACES AND SUB-SURFACES.
MAKE ALL APPLICATIONS AND PAY ALL FEES REQUIRED TO COMPLY WITH RELEVANT
AUTHORITY AND REGULATORY REQUIREMENTS INCLUDING METERING COSTS, BUILDING MASONRY OR STEELWORK OR CLIPPED BY CABLE CLAMPS TO UNISTRUT CHANNELS. THE CONTRACTOR SHALL TAKE EVERY PRECAUTION THAT IS NECESSARY FOR THE
PERMITS AND SELF-CERTIFICATION COSTS FOR ELECTRICAL AND COMMUNICATION CHANNELS SHALL BE OF SUFFICIENT WIDTH TO ACCOMMODATE ALL CABLES IN THE RUN PROTECTION FROM INJURY OF ALL EXISTING DRAIN PIPES, ELECTRIC AND
SYSTEMS, AND ALL WORKS REQUIRED FOR BUILDING PERMIT APPROVAL. PLUS A 20% SPARE CAPACITY. COMMUNICATIONS CONDUITS AND OTHER EXISTING WORKS AND SERVICES WHEREVER
- STRUCTURAL STEELWORK SHALL NOT BE DRILLED, WELDED OR CUT TO FACILITATE MET WITH, OR WHICH ARE ADJACENT TO THE WORK, AND TO AVOID DAMAGING SUCH
CABLE INSTALLATION WITHOUT THE SUPERINTENDENT'S WRITTEN PERMISSION. DRAINS, CONDUITS OR SERVICE CONNECTIONS OR ANY FITTINGS ATTACHED THERETO.
INSPECTION AND LOCATION OF SERVICES
THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR THE KEEPING CLEAN AND THE
THE LOCATION AND MOUNTING HEIGHTS OF THE SERVICES SHOWN ON THE DRAWING/S MAINTENANCE OF THE TRENCHES IN GOOD ORDER AND CONDITION BETWEEN THE TIME
ARE APPROXIMATE ONLY. FINAL LOCATIONS AND MOUNTING HEIGHTS SHALL BE CABLES
OF EXCAVATION AND LAYING AND SHALL OBTAIN THE SUPERINTENDENT'S APPROVAL
DETERMINED ON SITE TO SUIT THE PRINCIPAL/CLIENT AND TO PROVIDE OPTIMUM CABLES SHALL COMPLY WITH AS/NZS 5000.1 'ELECTRIC CABLES - POLYMERIC INSULATED - BEFORE COMMENCING TO LAY CABLES.
OPERATING PERFORMANCE AND FUNCTIONALITY. FOR WORKING VOLTAGES UP TO AND INCLUDING 0.6/1 KV'. UNLESS OTHERWISE INDICATED
INSTALLATION:
THE CONTRACTOR IS TO BE FULLY INFORMED OF THE CONTRACT WORK BY INSPECTION ALL CABLES SHALL HAVE STRANDED COPPER CONDUCTORS.
ALL CABLES SHALL BE INSTALLED IN THE PRESENCE OF THE SUPERINTENDENT OR ITS
OF THE SITE AND BY OTHER MEANS CONSIDERED NECESSARY. THE CONTRACTOR SHALL ALL CABLING AND WIRING SHALL BE SUPPLIED AND INSTALLED IN ACCORDANCE WITH THE REPRESENTATIVE AND THE CONTRACTOR SHALL GIVE A MINIMUM OF 48 HOURS NOTICE OF
BE RESPONSIBLE FOR OBTAINING FROM SITE ALL REQUIRED INFORMATION TO ALLOW THE APPLICABLE STANDARDS, IN PARTICULAR AS 3000 AND AS 3008. INTENTION TO PULL THE CABLES. ANY CABLES NOT INSTALLED TO THE ABOVE
NEW INSTALLATION TO BE COMPLETE AND CONSTRUCTIBLE. THIS INCLUDES, BUT IS NOT CABLING SHALL BE OF THE SIZE REQUIRED TO MEET THE CURRENT RATING AND VOLTAGE REQUIREMENTS MAY BE REQUIRED TO BE EXCAVATED AND RELAID. AFTER THE
LIMITED TO EXISTING EQUIPMENT LOCATIONS, SITE ACCESS LIMITATIONS, SUITABLE CABLE DROP REQUIREMENTS OF AS/NZS 3000 AND AS/NZS 3008 FOR THE ACTUAL CIRCUIT EXCAVATION HAS BEEN COMPLETED AND APPROVED THE TRENCH SHALL BE CLEARED OF
ROUTES AND ROUTE LENGTHS. THE CONTRACTOR SHALL ALLOW TO RECONNECT ALL LOADING AND METHOD OF INSTALLATION, OR AS SPECIFIED. ALL SHARP OBJECTS AND A FOUNDATION LAYER OF STONE-FREE BEDDING MATERIAL
EXISTING EQUIPMENT, WHERE THAT EQUIPMENT IS NOT BEING REPLACED OR REMOVED. SHALL BE PLACED.
CABLE INSTALLATION:
UNFORESEEN DIFFICULTIES DUE TO NEGLECT OF THIS PRECAUTION SHALL IN NO WAY
RELIEVE THE RESPONSIBILITY FOR FULL PROPER EXECUTION OF THE WORKS. UPON DELIVERY OF THE CABLE DRUMS, THEY SHALL BE VISUALLY INSPECTED FOR CABLE DRUMS SHALL BE ARRANGED SO THAT THE CABLE IS ALWAYS PULLED FROM THE
DAMAGE INCURRED DURING TRANSPORT OR STORAGE. THE SEAL ON THE INNER AND TOP OF THE DRUM USING SUITABLE SHOTTERS, HOOKS OR CUMALONGS AND A SWIVEL TO
OUTER CABLE END SHALL BE EXAMINED AND THE CONDITION OF ARMOURING, SERVING PREVENT DAMAGE TO THE CABLE. THE CABLE SHALL BE PULLED JUST FAST ENOUGH TO
WORKMANSHIP OR SHEATH INSPECTED FOR DAMAGE, CORROSION OR LEAKAGE OF IMPREGNATING OIL. KEEP THE DRUM ROTATING SMOOTHLY AND SUDDEN STOPPING SHALL BE AVOIDED.
ALL PERSONNEL SHALL BE APPROPRIATELY SKILLED AND LICENSED FOR THEIR ANY DAMAGE DISCOVERED SHALL BE REPORTED TO THE SUPERINTENDENT. WHEN PULLING CABLES INTO TRENCHES, ROLLERS SHALL BE SPACED TO PREVENT THE
PARTICULAR TASKS, AND ALL WORK SHALL BE IN ACCORDANCE WITH ACCEPTABLE TRADE DURING INSTALLATION CABLES SHALL BE HANDLED WITH DUE CARE. WHEN PULLING CABLE DRAGGING ON THE GROUND. AT BENDS AN ASSEMBLY OF ROLLERS AND SKIDS OR
PRACTICES FOR WORKS OF THIS KIND. LICENSES SHALL SATISFY THE REQUIREMENTS OF CABLES, ANY WINCH USED SHALL HAVE AUTOMATIC TENSION LIMITERS AND THE TENSION ROLLERS AND ANGLE ROLLERS SHALL BE USED AND THE CABLE SHALL NOT BE BENT TO
THE STATE OR TERRITORY AUTHORITY HAVING JURISDICTION OVER THE WORKS. LESS THAN 15 TIMES OD. ALL CHANGES IN DIRECTION OR GRADE SHALL BE IN EASY
SHALL NOT EXCEED THAT SPECIFIED BY THE MANUFACTURERS FOR THE PARTICULAR
STAGES.
ALL WORKMANSHIP AND MATERIALS SHALL BE OF A HIGH INDUSTRY STANDARD USING CABLE AND CONDITIONS OF INSTALLATION. WINCHING ROPES SHALL BE ATTACHED TO
NEW MATERIALS. ANY MATERIALS OR WORKMANSHIP, WHICH ARE CONSIDERED INFERIOR THE CABLE ARMOUR WITH STEEL MESH SLEEVES AND CARE SHALL BE TAKEN THAT CABLE PITS:
OR NON-CONFORMING, SHALL BE REPLACED AT THE CONTRACTOR COST. PRELIMINARY
DRAWN CHECKED
CITY OF GREATER GEELONG
- -
ESTUARY RESERVE SOCCER FIELD LIGHTING
DATE - DATE -
ELECTRICAL AND LIGHTING SERVICES
DESIGNED CHECKED
- - GENERAL NOTES
HARRIS KMON SOLUTIONS
A SCHEMATIC DESIGN 22/06/20 RO HKS DARWIN.GEELONG.CAIRNS DATE - DATE - -
admin@hksolutions.com.au PROJECT MANAGER AUTHORISED
No. DESCRIPTION DATE INIT. DEPT/COMPANY. www.hksolutions.com.au SHEET No. DRAWING No. AMEND. SHEET
- - SIZE
AMENDMENTS DATE - DATE - - OF - 20098-E01 A A1
N LEGEND:
ESTUARY BOULEVARD

E T
nE80

IV
BURIED HD PVC ELECTRICAL CONDUITS INSTALLED WITH DRAW WIRE IN

R
M
TB
ACCORDANCE WITH TYPICAL CABLE TRENCH SECTION DETAIL AND
AS/NZS3000.

E
INDICATIVE LOCATION OF EXISTING
WM
I.S.
'n' DENOTES QUANTITY OF CONDUITS,
POWERCOR 3PH 150A CAPACITY SERVICE 'E' DENOTES ELECTRICAL ORANGE HD PVC

W
PIT. CONTRACTOR SHALL PROVIDE NEW LV NUMMER DENOTES DIA OF CONDUIT

E
CONSUMER MAINS TO THE NEW MSB FOR EXAMPLE:
1E100 2E80 - 2 x 80 DIA ELECTRICAL HD PVC CONDUITS

E
W
EP 710L x710Wx660D POLYETHELYNE PIT WITH AS3996 CLASS B PIT LID IN

E
OTHER AREAS. ALL LIDS SCRIBED WITH 'ELECTRICAL' .
DECOMMISSION AND REMOVE

W
TYPE: ACO TYPE 77 OR APPROVED EQUIVALENT.
EXISTING MAIN SWITCHBOARD AND

E
REPLACE WITH NEW GROUND ELECTRICAL SWITCHBOARD
MOUNTED MAIN SWITCHBOARD. MSB DENOTES NEW MAIN SWITCHBOARD
I.S.

CL
MSB GRAVEL CAR PARK Px 25m LIGHTING POLE STRUCTURE INCLUSIVE OF POLE, LED

UB
EXISTING FENCELINE

RO
LUMINAIRES, FOOTING, AND CROSSARM. CONTRACTOR TO DESIGN,

CL

O
CONSTRUCT AND CERTIFY LIGHTING POLE STRUCTURE AND FOOTING.

M
UB
RO
REFER SCHEDULES ON DRAWING E03 AND E05 FOR INFORMATION ON
TH

O
LUMINAIRES AND POLE GENERAL ARRANGEMENT RESPECTIVELY.

M
PA U SOCCER FIELD OF
/ / / /
U
PLAY BOUNDARY,
NOTES
/

CO
/ / U
/ U

NC
3E80
/
/
.
NC

.
/

CO
/
/

1. CONTRACTOR SHALL PROVIDE ALTERNATIVE DIRECTIONAL BORING


/

ET
GOAL POSTS E

IV
AC
/ /
SOLUTION OF EQUIVALENT PERFORMANCE AND ECONOMIC VALUE TO

R
TR

M
TB

PA
/ F
O TRADITIONAL TRENCH EXCAVATION AND BACKFILL SOLUTION.

TH
SS

SE
/ / / / /
LO
/

AT
/ / / / / / / / /
E

/
E

2. THE CONTRACTOR SHALL PRECISELY ORIENTATE IN ACCORDANCE

SE
AT
/
/

EP 2E80 WITH THE DIRECTION DIAGRAM DETAIL. ORIENTATION MAY NOT ALIGN

/
EP

E
/
P1 PRECISELY WITH TRUE NORTH.

/
/

/
P3

/
/

/
E

E
/
AC

/
TR
/

F
O

/
SS

E
LO
/

/
/

/
/
/
/

/
/

E
/

2E80

/
2E80

E
/

E
/
/

/
E
E

CONCRETE RETAINING WALL


/
/

/
E
E
SHELTER
/

/
E

/
/

STREET
CONCRETE RETAINING WALL

E
/

/
/

ET
E
IV /

/
/

R
M

E
EP

TB
EP
CRICKET PITCH

/
/

E
/

E
DIRECTION DIAGRAM LIGHTING POLE

TREEFERN
CONCRETE RETAINING WALL
/

/
E
/

SCHEDULE

SHELTER

/
/

90°
XARM

E
E
POLE POLE
/

XARM QTY ORIENTATION


ID HEIGHT

/
(NOTE 2)

E
/

E
180° 0°

/
2E80 1 25m 1 90°
/
E

/
2 25m 1 90°
/

2E80
ET
IV

270°
R

3 25m 1 90°
/

E
M
TB

/
/
/

4 25m 1 90°
E

/
/
/

/
REINSTATE EXISTING SUFACE
/
/

E
WHERE REQUIRED
E

/
/

/
/

E
SELECTED BACKFILL CLASS C STEEL
/

150 150
/
/

PIT LID

/
CENTRE LINE OF COMPACTED 85% MMDD TO

E
/

TRENCH COUNCIL REQUIREMENTS.


/

P2
/
E

/
P4

100
N.S.L
/

/
E
/
/

/ COMPACTED SOIL

/
E E TO 85% MMDD
/

/ E E
E / / / / / /
E E E E
/ / / / / / E E E
E / / / / /
E

300
/

E E E E E E
CABLE MARKER TAPE
RC

E E E E E E
E E E E NATURAL
m

/ E
0m

SOIL
/

TYPICAL
30

600
/

WASHED STABILISED SAND


POLYETHYLENE
/

PIT COMPACTED
/

/
CLEAN SAND
/
/
/
GOAL POSTS
/
/
/
HD PVC CONDUITS AS REQUIRED. MIN.
E

/
/
/
/ 50mm HORIZONTAL SEPARATION.
/ /
E - SHOWN AS 80Ø LV ELECTRICAL.
SITE LAYOUT PLAN PROVISION ONE CONDUIT AS SPARE FOR

50

100
FUTURE.
SCALE 1:500 AT ORIGINAL SIZE E E
DRAW WIRES SHALL BE INSTALLED IN ALL

50
ELECTRICAL DUCTS AND THE ENDS
50 50
SEALED WITH A NON-SETTING MASTIC
COMPOUND.
WARNING
BEWARE OF UNDERGROUND SERVICES TYPICAL CABLE TRENCH SECTION TYPICAL CABLE PIT DETAIL
CHECK WITH ALL RELEVANT AUTHORITIES AND
NTS NOT TO SCALE
0 5000 10000 15000 20000 25000mm
CARRY OUT SITE INSPECTIONS TO DETERMINE
THE LOCATION OF ALL EXISTING SERVICES
SCALE 1:500 AT ORIGINAL SIZE
PRIOR TO STARTING ANY EXCAVATIONS

PRELIMINARY
DRAWN CHECKED
CITY OF GREATER GEELONG
- -
ESTUARY RESERVE SOCCER FIELD LIGHTING
DATE - DATE -
ELECTRICAL AND LIGHTING SERVICES
DESIGNED CHECKED
- - ELECTRICAL CABLE SUPPORT SYSTEMS
HARRIS KMON SOLUTIONS
A SCHEMATIC DESIGN 22/06/20 RO HKS DARWIN.GEELONG.CAIRNS DATE - DATE - PLAN
admin@hksolutions.com.au PROJECT MANAGER AUTHORISED
No. DESCRIPTION DATE INIT. DEPT/COMPANY. www.hksolutions.com.au SHEET No. DRAWING No. AMEND. SHEET
- - SIZE
AMENDMENTS DATE - DATE - - OF - 20098-E02 A A1
ET
IV
R
M
TB
N NOTES

E
INDICATIVE LOCATION OF EXISTING
WM
I.S.

POWERCOR 3PH 150A CAPACITY SERVICE 1. THE CONTRACTOR SHALL ALLOW FOR FINAL MEASUREMENT AND

W
PIT. CONTRACTOR SHALL PROVIDE NEW LV RECORDING OF HORIZONTAL ILLUMINANCE AND UNIFORMITIES ON MAIN 4. ISOLUX LINES ARE CALCULATED HORIZONTAL ILLUMINANCE VALUES

0
CONSUMER MAINS TO THE NEW MSB OVAL PPA IN ACCORDANCE WITH 2560.2.3 LIGHTING TECHNICAL AND SHOWN AT GROUND LEVEL.
1E100 PARAMETERS 100 LUX PERFORMANCE LEVEL. AS PART OF LIGHTING

E
W
MEASUREMENT THE CONTRACTOR SHALL ALLOW FOR ON-SITE NIGHT 5. ORIENTATION MAY NOT ALIGN PRECISELY WITH TRUE NORTH. REFER TO

0
AIMING OF LUMINAIRES TO PROVIDE TUNING AND IMPROVEMENTS TO DIRECTION DIAGRAM FOR ORIENTATION. THE CONTRACTOR SHALL

E
LIGHTING PERFORMANCE AND REDUCTION OF LIGHTING SPILL AS PART PRECISELY ORIENTATE IN ACCORDANCE WITH THE DIRECTION DIAGRAM.

0
DECOMMISSION AND REMOVE

W
OF ITS COMMISSIONING.
EXISTING MAIN SWITCHBOARD AND 6. TILT SHALL BE IN ACCORDANCE TO LUMINARIE TILT DIAGRAM.THE

E
REPLACE WITH NEW GROUND 2. OBTRUSIVE LIGHTING BOUNDARY SEGMENT WAS ASSESSED AT CONTRACTOR SHALL CALIBRATE LUMINARIE TILT 0 DEGREE ANGLE AS

0
FIELD OF PLAY HORIZONTAL
MOUNTED MAIN SWITCHBOARD. PROPERTY BOUNDARIES IN ACCORDANCE WITH AS4282-2019 ZONE 'A3' LEVEL AND IN ACCORDANCE TO MANUFACTURERS REQUIREMENTS.
ILLUMINANCE RESULTS. REFER TO
I.S.
NOTE 3. USING SOFTWARE AGI32. OBTRUSIVE LIGHTING WAS ASSESSED WITH

0
20m HIGH VERTICAL PLANE GRID (5M HORIZONTAL 2m VERTICAL POINT 7. CONTRACTOR SHALL ENGAGE AND INDEPENDENT EXPERIENCED AND

CL
MSB GRAVEL CAR PARK

UB
EXISTING FENCELINE GRID SPACING) ALONG THE IDENTIFIED PROPERTY BOUNDARIES IN COMPETENT PERSON WITH EXPERIENCE IN THE INSTALLATION AND

RO

0
COLOURED LINES REPRESENT COMPLIANCE WITH AS4282-2019. AIMING OF THE SPECIFIED LUMINAIRES TO UNDERTAKE FINAL LUMINAIRE
DIRECTION DIAGRAM LUMINAIRE TILT

CL

O
M
UB
HORIZONTAL ILLUMINANCE ISOLUX AIMING AND LIGHTING SURVEY. ALL AIMING SHALL BE UNDERTAKEN

RO
CONTOURS. REFER TO NOTE 4. 3. FIELD OF PLAY (PPA) CALCULATED POINTS ARE HORIZONTAL USING THE PROPRIETARY AIMING EQUIPMENT AND PROCESS SPECIFIED

0
H

O
T

M
PA SOCCER FIELD OF ILLUMINANCE AT GROUND LEVEL. CALCULATED POINTS SHOWN ARE FOR BY THE LUMINAIRE MANUFACTURER. IMPROPER AIMING SHALL BE
U

PLAY BOUNDARY,
90° RECTIFIED BY THE CONTRACTOR AT NO FURTHER COST.
/ / /
U
AFL COMPETITION PERFORMANCE LEVEL OF 100 LUX IN ACCORDANCE

0
/
/

CO
WITH AS2560.2.3. A LED LUMINAIRE MAINTENANCE FACTOR OF 0.85 WAS
/ / U
/ U

NC
3E80
/
/
. UTILISED.
NC + 0°

.
/

CO

0
/

/ 180° 0°

ET
GOAL POSTS E
LUMINAIRE TYPE AND AIMING SCHEDULE

IV
AC
/
10

R
TR

0
TB

PA
F
20 O

TH
SS

SE
/ / / / /
LO
/

AT
/ / / / / /

270°
E
/ /
HEADMAST

/
E

0
LUMINARE TILT ORIENTATION CONTROL

SE
MODEL POSITION OPTICS

AT
/
2E80 ID'S (NOTE 6) (NOTE 5) GROUP

/
(REFER DRG E05)

E
/
P1 50

0
/
P3

/
L1-1 3PH 400V PHILLIPS OPTIVISION BVP527 OUT T30 50K POS. 1 A35-NB +BL 35° 317° 100 LUX

0
63 76 85 91

/
E 94 95 95 94

E
91

/
AC 86 77 63 L1-2 3PH 400V PHILLIPS OPTIVISION BVP527 OUT T30 50K POS. 2 A35-NB +BL 35° 317° 150 LUX

/
TR
F
O

/
SS

0
/
76 89 96 99 101 101 101 101 99 L1-3 3PH 400V PHILLIPS OPTIVISION BVP527 OUT T30 50K POS. 3 A35-NB +BL 35° 317° 100 LUX

E
LO
96 89 77
L2-1 3PH 400V PHILLIPS OPTIVISION BVP527 OUT T30 50K POS. 1 A35-NB +BL 35° 39° 100 LUX

0
/
83 91

E
99 106 109 110 111 109 106 99

E
92 84

/
100 L2-2 3PH 400V PHILLIPS OPTIVISION BVP527 OUT T30 50K POS. 2 A35-NB +BL 35° 39° 150 LUX

/
/
GREY DENOTES FUTURE 150 LUX

1
0
87 94 20

E
103 112 119 121 121 119 112 103 94

/
87 PERFORMANCE LEVEL. LIGHTING POLE L2-3 3PH 400V PHILLIPS OPTIVISION BVP527 OUT T30 50K POS. 3 A35-NB +BL 35° 39° 100 LUX
/

E
2E80

/
STRUCTURES AND FOUNDATIONS SHALL

/
2E80

1
0
85 95 106 118 126 133 133 127 118 107 96 CONSIDER THESE LUMINAIRES AS PART OF L3-1 3PH 400V PHILLIPS OPTIVISION BVP527 OUT T30 50K POS. 1 A35-NB +BL 35° 220° 100 LUX
85

E
/

E
/
ITS STRUCTURAL DESIGN.
L3-2 3PH 400V PHILLIPS OPTIVISION BVP527 OUT T30 50K POS. 2 A35-NB +BL 35° 220° 150 LUX

1
0
81
/

94 109 120 133 142 143 134 121 109 95

/
E
82

OBTRUSIVELIGHT_RES_BOUNDARY 1 (NOTE 2)
L3-3 3PH 400V PHILLIPS OPTIVISION BVP527 OUT T30 50K POS. 3 A35-NB +BL 35° 220° 100 LUX

CONCRETE RETAINING WALL


/
/

1
0
76 92 107 121 135 146 147 135 122 108 93

E
10 77 L4-1 3PH 400V PHILLIPS OPTIVISION BVP527 OUT T30 50K POS. 1 A35-NB +BL 35° 139° 100 LUX

E
SHELTER
/

/
L4-2 3PH 400V PHILLIPS OPTIVISION BVP527 OUT T30 50K POS. 2 A35-NB +BL 35° 139° 150 LUX

1
0
74 90 103 119 134 142 142 135 120 104 91

E
75

/
/

L4-3 3PH 400V PHILLIPS OPTIVISION BVP527 OUT T30 50K POS. 3 A35-NB +BL 35° 139° 100 LUX

STREET
CONCRETE RETAINING WALL

1
0
73

E
86 99 116 129 136 136 130 117 100 87

E
/
74

/
/

50
ET

E
IV

1
/

0
72

/
82 98 113 125 132 132 126 114 99
/

R
M
83 73

E
TB
CRICKET PITCH

/
/

1
0
72 82 98
/

113 125 132 132 126 114 99 83 FIELD OF PLAY CALCULATION SUMMARY

E
73

TREEFERN
CONCRETE RETAINING WALL
/

/
E
/

1
0
72 86 99 115 129 135 135 130 116 100 87 APPLICABLE STANDARD: AS2560.2.3:2007
SHELTER

E
73 LEVEL OF PLAY: AMATUER CLUB COMPETITION 100 LUX

/
/

LUMINAIRE LLF: 0.85

1
0
74 89 102 118 133 141 141 134 119 104 90

E
75
E
/

SEGMENT LABEL CALC TYPE UNITS AVG MAX MIN U1 (MIN/AVG) U2 (MIN.MAX)

/
/

1
0
76 92 106 120 134 145 146 135 121 108 93 10

E
/

78 HORIZONTAL
PPA_AFL OVAL LUX 104.02 147 63 0.61 0.43

/
2E80
/

ILLUMINANCE

1
0
81 94 108 119 132 142 142 133 120 109 95
E

20

E
82

/
/

OBTRUSIVE LIGHTING CALCULATION SUMMARY


/

2E80
ET

100
IV

1
0
84 95 105 117 126 132 133 126 118 106 96
R
/

E
M

85
TB

/
APPLICABLE STANDARD: AS/NZS 4282:2019
/
/

ENVIRONMENTAL ZONE: A3

1
0
85 93 102 111 118 120 120 118 112 103 93
E

/
86 CONDITIONS: NON-CURFEW L1
/

LUMINAIRE LLF: 1.0


50

1
0
83 91
/

98 105 108 109 109 108 106 99


/

E
100 92 83 AS4282
E

SEGMENT LABEL CALC TYPE UNITS CALC MAX AS4282 LIMIT

/
/

COMPLIANT?
/

0
77 88

E
95 98 99 99 99 99 98 95 89 78 LUMINOUS
/

8,300 12,500
/

Cd YES

/
INTENSITY

0
E
63 77 85 89 92 93
/

93 92 89 85 77 65 OBTRUSIVELIGHT_RES_BOUNDARY 1
P2
/
E

/
VERTICAL
P4 ILLUMINANCE
LUX 1 10 YES

0
/

/
E
/

50 20

0
/
E E E
E / / / E E
/ / / / / E E E
/ / / / / /
E E E
E / / / /
E
P

E E E E E

0
E
RC

E E E E E E
E E E E
m

/ E
0m

10
30

0
/
E

0
/

0
/

/
GOAL POSTS /
/
E

/
/ /

0
/ /
/

0
0
FIELD OF PLAY LIGHTING PLAN

0
AND CALCULATION SUMMARY
SCALE 1:500 AT ORIGINAL SIZE 0

0 5000 10000 15000 20000 25000mm

SCALE 1:500 AT ORIGINAL SIZE

PRELIMINARY
DRAWN CHECKED
CITY OF GREATER GEELONG
- -
ESTUARY RESERVE SOCCER FIELD LIGHTING
DATE - DATE -
ELECTRICAL AND LIGHTING SERVICES
DESIGNED CHECKED
- - FIELD OF PLAY LIGHTING - 100 LUX
HARRIS KMON SOLUTIONS
A SCHEMATIC DESIGN 22/06/20 RO HKS DARWIN.GEELONG.CAIRNS DATE - DATE - CALCULATION SUMMARY
admin@hksolutions.com.au PROJECT MANAGER AUTHORISED
No. DESCRIPTION DATE INIT. DEPT/COMPANY. www.hksolutions.com.au SHEET No. DRAWING No. AMEND. SHEET
- - SIZE
AMENDMENTS DATE - DATE - - OF - 20098-E03 A A1
NOTES:
1. POLE HEADFRAME TO BE DESIGNED TO CAUSE NO LIGHTING
INTERFERENCE OR SHADOWING FROM ADJACENT LUMINARIES
(INSTALLED AND FUTURE). COORDINATE LUMINAIRE HEADFRAME
SUPPLY AND INSTALL MOUNTING RECOMMENDATIONS WITH LUMINAIRE SUPPLIER.
MECHANICAL PROTECTION TO
EXPOSED LUMINAIRE CABLING. 2. SUPPLY AND INSTALL FLEXIBLE STEEL CONDUIT (ANACONDA OR
POSITION POSITION POSITION
REFER TO NOTE 2. APPROVED EQUAL) ON ALL EXPOSED SECTIONS OF LIGHTING CABLE
1 2 3
SPORTS FLOODLIGHT FROM LIGHTING POLE STRUCTURE TO LUMINARIES. COORDINATE
CROSSARM AND POLE TO BE WITH LIGHTING POLE SUPPLIER AND PROVIDE ALL NECESSARY
DESIGNED FOR MIN. 3 OFF WEATHERPROOF CONNECTIONS AND ACCESSORIES TO PREVENT
SPORTS LUMINAIRES WATER AND DUST INGRESS INTO LUMINAIRE AND POLE STRUCTURE.
POSITION POSITION POSITION
1 2 3

3. CONCEPT GENERAL ARRANGEMENTS SHOWN ONLY, THE


CONTRACTOR SHALL ENSURE SHOP DRAWINGS TO BE SUBMITTED
FOR ACCEPTANCE PRIOR TO MANUFACTURE.

4. FINAL EQUIPMENT SELECTION TO BE SUITABLE FOR APPLICATION

CABLE EXIT

TYPICAL AFL POLE HEADMAST


LUMINAIRE POSTION
(LOOKING FRONT ON AT POLE)

PLAN VIEW

PROPRIETARY POLE. VIC POLE OR


APPROVED EQUAL.

25m
CONCEPT ONLY

FRONT VIEW

LOCKABLE ACCESS DOORS (AS REQUIRED


FOR QTY OF CONTROL GEAR) INDICATIVE LIGHTING POLE
CROSS-ARM DETAIL
NOT TO SCALE
POLE FOOTING (BORED PIER TYPE
SHOWN). CONTRACTOR TO DESIGN AND CONCEPT ONLY
CONSTRUCT NEW POLE FOOTING TO BE
PAD OR BORED PIER TYPE. REFER TO
COUNCIL PROVIDED GEOTECHNICAL
REPORT FOR GROUND CONDITION
DETAILS.

INDICATIVE ELECTRICAL
CONDUITS

FRONT VIEW SIDE VIEW

INDICATIVE LIGHTING POLE DETAIL INDICATIVE LIGHTING POLE BASE


NOT TO SCALE
DETAIL
NOT TO SCALE
PRELIMINARY
DRAWN CHECKED
CITY OF GREATER GEELONG
- -
ESTUARY RESERVE SOCCER FIELD LIGHTING
DATE - DATE -
ELECTRICAL AND LIGHTING SERVICES
DESIGNED CHECKED
- - SPORTS LIGHTING POLE
HARRIS KMON SOLUTIONS
A SCHEMATIC DESIGN 22/06/20 RO HKS DARWIN.GEELONG.CAIRNS DATE - DATE - GENERAL ARRANGEMENT
admin@hksolutions.com.au PROJECT MANAGER AUTHORISED
No. DESCRIPTION DATE INIT. DEPT/COMPANY. www.hksolutions.com.au SHEET No. DRAWING No. AMEND. SHEET
- - SIZE
AMENDMENTS DATE - DATE - - OF - 20098-E05 A A1