Sie sind auf Seite 1von 5

PROJECT NO.

PO. 4500098732 / 10 / 01.01.2018


PROJECT TITLE

Supply of PF Process Calculation Spreadsheet (Excel


Forma)
E T
H
DOCUMENT TITLE
E
E S
L
Control Valve Sizing for Single Phase - Liquid Flow

M P
SA

DATE REV. REASON FOR REVISION PREP. CHKD. APPD. APPD.

DOC. NO. CEPL-PC-001-CA-001B PAGE 1 of 5 REV. 0


Control Valve Sizing for Single Phase - Liquid Flow
DOC. NO. CEPL-PC-001-CA-001B REV. 0
PROJECT NO. PO. 4500098732 / 10 / 01.01.2018 PAGE NO. 2 of 5
PROJECT TITLE Supply of PF Process Calculation Spreadsheet (Excel Forma)
BASIS

Calculation Objective

Calculation Basis

E T
Calculation Methodology

H E
E S
PL
M
SA
Assumptions

Software used

Conclusions

References

Attachments
Control Valve Sizing for Single Phase - Liquid Flow
DOC. NO. CEPL-PC-001-CA-001B REV. 0
PROJECT NO. PO. 4500098732 / 10 / 01.01.2018 PAGE NO. 3 of 5
PROJECT TITLE Supply of PF Process Calculation Spreadsheet (Excel Forma)
SCHEMATIC:

This spreadsheet provides the sizing calculations of control valve for Incompressible fluid.

INPUT
Case 1 Case 2 Case 3
3
100.10 80.00 40.00 m /h Q Liquid flow rate
5.00 5.00 5.00 barg P1 Inlet pressure
2
5.10 5.10 5.10 kg/cm g P1 Inlet pressure
0.50 1.00 1.50 bar ∆P Pressure drop

T
0.51 1.02 1.53 kg/cm2 ∆P Pressure drop

E
3
997 997 997 kg/m ρ Density

E
1 1 1 cSt v Kinematic viscosity

H
0.0 0.0 0.0 bara Pv Vapor pressure

S
221 221 221 bara Pc Critical pressure
4 4 4 inch d Control valve NB

E
6 6 6 inch D1 Inlet pipe ID

L
6 6 6 inch D2 Outlet pipe ID

P
FL Liquid pressure recovery factor of a control
0.80 0.80 0.80
valve without attached fittings.

0.80

M
0.80 0.80 Fd Valve style modifier

SA
xT Pressure differential ratio factor of a control
0.80 0.80 0.80
valve without attached fittings at choked flow.

80 66 49 % Valve output for maximum flow


Equal Percentage Equal Percentage Equal Percentage Valve characteristics

RESULTS
Case 1 Case 2 Case 3
The results are within The results are within The results are within
applicable scope of ANSI-ISA applicable scope of ANSI- applicable scope of ANSI-
75-01-01. ISA 75-01-01. ISA 75-01-01.
Flow is turbulent Flow is turbulent Flow is turbulent
It is NOT a choked flow It is NOT a choked flow It is NOT a choked flow
0.957 0.957 0.957 FF Liquid critical pressure ratio factor
0.973 0.991 0.973 FP Piping geometry factor
FLP Combined liquid pressure recovery factor and
0.771 0.791 0.771 piping geometry factor of a control valve with
attached fittings.

168.02 93.15 37.8 Cv Flow coefficient


328 324 321 Cv_D Design flow coefficient
Remarks
Control Valve Sizing for Single Phase - Liquid Flow
DOC. NO. CEPL-PC-001-CA-001B REV. 0
PROJECT NO. PO. 4500098732 / 10 / 01.01.2018 PAGE NO. 4 of 5
PROJECT TITLE Supply of PF Process Calculation Spreadsheet (Excel Forma)

To calculate Reynolds number:

E T
H E
E S
PL
M
SA
Control Valve Sizing for Single Phase - Liquid Flow
DOC. NO. CEPL-PC-001-CA-001B REV. 0
PROJECT NO. PO. 4500098732 / 10 / 01.01.2018 PAGE NO. 5 of 5
PROJECT TITLE Supply of PF Process Calculation Spreadsheet (Excel Forma)

E T
H E
E S
PL
M
SA

Das könnte Ihnen auch gefallen