CIRCUIT DRAWN WITH POWER SUPPLY OFF FOR TYPICAL REMOTE CONTROL
M 2 DETAILS, SEE DOCUMENT
3
3 V
3
PHASE
RWS122
SUPPLY
+
(OUTPUT) FUSE FS1=250mA ANTI-SURGE
SK14
0VDC 1 REFER TO SHEET 2 FOR NOTES
INTERNAL SUPPLY
FOR FOLO/CPT PCB & OPTION PCB'S IF FITTED
24VDC 2
SK13 THE ACTUATOR MUST BE
PROTECTED USING SUITABLY
26 WAY RATED HIGH SPEED
SEMI-CONDUCTOR FUSES ON THE
INCOMING SUPPLY.
SK3 SK13 SK14 SUGGESTED FUSES :-
6 1 42 IQ10-20:10 Amp FERRAZ G330010
MONITOR RELAY IQ25-35:20 Amp FERRAZ K330013
5 3 43 ALTERNATIVES =
4 2 44 IQ10-20:10 Amp SIBA 50-179-06/10A
TORQUE 3
SK7
IQ25-35:20 Amp SIBA 50-179-06/20A
2
SENSOR 1 1 6
OR EQUIVALENT PROTECTIVE
DEVICE.
SK8 MAKE AT FULLY SHUT S1 8 7
POSITION 10 WAY 2 8
SENSOR MAKE AT FULLY OPEN S2 7 9
SK9 BREAK AT FULLY SHUT
3 10
BATTERY - 4
S3 6 11
4 12
+
1 BREAK AT FULLY OPEN S4 5 13
FS2 (IF FITTED) 100mA SK4
CLOSE 9 33
STOP/ MAINTAIN 10 34
50% SK6 OPEN 8 35
COMMON -VE 1 36
18 WAY
ESD 12 25
STOP
CLOSE LOCAL OPEN INTERLOCK 13 37
OPEN REMOTE
CLOSE INTERLOCK 14 38
COMMON -VE 5 31
SK1 SK2
SLOT A SLOT B
Iss Date Chkd Revision Details IQM + FOLO & CPT + HART
1 041113 PJW First Issue. www. .com
2 121113 JC1 Hart demand idents added.
ROTORK CONTROLS LTD ROTORK CONTROLS INC Drawn by: JC1 Circuit Diagram Number Issue Sheet
3 270214 PJW WAS RWS102 Date : 041113 No
BATH, BA1 3JQ ROCHESTER
4 120614
5 040914
JBA Slot A PUB Ref. changed to 003
JC1 Note changed - sheet 2
ENGLAND NY 14624, USA
Base WD: 203H2000
Job No : - -
203H2000 6
1
of 2
6 130616 PW Updated notes on page 2. Tel:01225-733200 Tel:585-247-2304 MI No : - - B1 C1 B2 C2
IQ3
CIRCUIT DRAWN WITH POWER SUPPLY OFF
SLOT A
SK1
SLOT A SK3
-VE +VE
1 14 A
2 15
DEMAND +VE 3 16
COMMON -VE 4 17 } ANALOGUE INPUT SIGNAL
FOR FOLOMATIC
FOLOMATIC /
NO CONNECT 5
CPT
MANUAL/AUTO 6 39
COMMON -VE 24VDC 7 41
COMMON -VE 120VAC 8 45
SK6
1 0V
SUPPLY FROM SK14 ON POWER PCB
2 24V
SK8
1
2
SLOT B
SK2
SLOT B SK3
PUB092-003)
(REFER TO
26 DEMAND +
MANUAL
1
HART
2 27 DEMAND -
29 SCREEN
30
E
NOTE
Only 1 source of control can be enabled at one time.
As default the folomatic will have control, selection of the other control
source can be made using the manual / auto input on the folomatic card
NOTES
1.FUSES:
-PS1 is a self-resetting fuse. 3.INDICATION:
-Refer to publication PUB002-039 for approved fuses FS1 and FS2. -For typical position, status and alarm indication see PUB002-041.
-Actuator rated voltage specified on nameplate. Voltage tolerance +/-10%, -“S” contacts are user configurable and are shown in their default
applies for rated torque performance; duty cycle is not gauaranteed. setting.
2.REMOTE CONTROL: -Refer to PUB002-040 for functions and configuration instructions.
-For typical remote control circuits refer to: -Monitor Relay indicates actuator availability for remote control (shown
-RWS indicated or PUB002-041. “unavailable”). It can be configured to exclude local/remote selection.
-For DC and AC control, connect –ve/0V to terminal 36. -Refer to PUB002-040 for monitored functions and configuration
-(For negative switch / positive common, refer to RWS indicated). instructions.
-Control signal threshold voltages: -Voltage applied to indication contacts must not exceed 150Vac
-DC: “on” ≥16Vdc / “off” ≤8Vdc, max 60Vdc. -Individual Switch current must not exceed 3.5A inductive, 5A resistive
-Control signal duration to be 100ms minimum. and no more than 8A in total for all 4 contacts.
-Maximum current drawn from remote control signals is:
-8mA at 24Vdc . 4.BATTERY:
-Supply provided on terminals 4 & 5: -Battery maintains local and remote “S” contact indication only.
-Intended for remote control. -Refer to installation manual for approved replacement battery types.
-Max external load 5W at 24Vdc Issue Sheet
Circuit Diagram Number
No
2
See Sheet 1 for all Revision details/information 203H2000 6 of 2
IQ3