Beruflich Dokumente
Kultur Dokumente
With the increase in size of industrial plant electrical systems, and the high
short-circuit levels encountered on electricity power systems, it is essential that the
electrical protection arrangements in any industrial installation are correctly designed
and have the appropriate settings applied to ensure the correct functioning of the plant
and continuity of supply within the installation. The importance of maintaining con-
tinuity of supply to industrial installations cannot be over emphasised and, in this
respect, the interconnectors to the public supply system play a vital role. It is crucial
that correct co-ordination is maintained between the protection on the main industrial
supply infeeds and the power system supply feeders.
In addition to the overcurrent relay, which has been covered in Chapter 5, moulded-
case circuit breakers (MCCBs) and thermal relay-contactor and fuse devices are
frequently used to protect elements of the industrial electrical system and these will
be covered in more detail in this chapter.
for operating breakers up to 600 V, but are sometimes used on breakers of a higher
voltage and, in these cases, are generally fed by current transformers.
These devices can be operated by:
1. An armature attracted by the electromagnetic force that is produced by the fault
current which flows through a trip coil.
2. A bimetallic strip that is actuated by the heat produced by the fault current.
The characteristic curves of these mechanisms are generally the result of com-
bining the curves of instantaneous relays with long or short time-delay relays. The
starting current of the long delay units can normally be set to 80, 100, 120, 140 and
160 per cent of the nominal value. The calibrations of short time-delay relays are
typically 5, 7.5 and 10 times the nominal value.
It is common to use breakers to protect circuits of low current capacity with
a combination of a single time-delay element plus an instantaneous unit normally
having a bimetallic or magnetic element. In this case, the curves are normally set in
the factory based on the nominal values.
The criteria normally used for the selection of the nominal values and the range of
settings of low voltage overcurrent devices such as thermal relays and moulded-case
breakers that are used frequently in industrial plants are similar to those for overcurrent
protection included in Chapter 5. An important consideration for these devices is that,
as for overcurrent relays, the selected settings can vary depending upon the criteria
adopted by the particular utility or plant operators, providing that the resultant settings
guarantee appropriate protection to the machines and the elements of the system under
analysis. Thus, the settings should be higher than the motor-locked rotor current and
below the motor thermal limit.
Coil rating
In order to determine the coil rating, manufacturers provide a range of maximum and
minimum current values for which the thermal relay has been designed. The rating of
the coil is somewhat above the maximum value of the motor secondary rated current.
The range of a thermal relay for a motor should overlap the motor manufacturer's
value of the motor nominal secondary current, in amperes. Using a thermal relay that
has a maximum current rating very close to the motor nominal secondary current (in
amperes) is not recommended; in this case it is better to use the next highest range
available.
Example 10.1
Consider a motor with the following characteristics:
power: 100 HP, p.f. = 0 . 8
voltage: 440 V
efficiency: 100 per cent
The thermal protection consists of three single-phase relays, fed from a set of
current transformers with 200/5 ratios. The setting range of the relays is given in
Table 10. l, and the operating characteristics are shown in Figure 10.1.
Inom = 122.36A, and Inom(sec) = 122.36 x 5 / 2 0 0 = 3.06A. In accordance with
the data in Table 10.1, a thermal coil with a rating of 3.87A, which has a current
range of 3.10 to 3.39 A, can be selected. A relay with a range of 2.82-3.09 A should
not be used since the maximum value is very close to the Inom(sec) of the motor.
(a) 800
700
\
\
600
<
500
~ 6 0 Hz
400
300
200
100
Time (s)
(b) 800
700
600
<
500
,fi
e.
400
300
200
100
Time (s)
Nominal current
The nominal value of the breaker is selected using the next higher available setting
to the value obtained from the following expression:
/breaker = 1.05 x SF x Inom.motor
where SF is the so-called service factor, which is an overload margin permitted by
the manufacturer.
In the case of breakers associated with motor control centres (MCCs), the nominal
current is selected using the following expression:
Inom = 1.2 x 1FL
where IFL is the full-load current taking into account the nominal power of all the
motors plus the other loads that are supplied by the feeder. To calculate this, the
nominal current of the largest motor, and the current for the rest of the load multiplied
by the demand factor, are added together.
E x a m p l e 10.2
Determine the settings for the thermal relay and the 200 and 600 A breakers, which
protect the system indicated in Figure 10.2, using the information given.
Induction motor
500 HP, 2400 V, power factor = 0.8
Service factor: 1.0
Code letter: G; thermal limit with locked rotor: 5.5 s
Direct start, duration: 1.0 s
Thermal relay
(See Figure 10.1.)
Coil: 3.87 A
Taps: 90-110 per cent o f coil rating
CT ratio: 150/5
232 Protection of electricity distribution networks
~ 1500kVA
13.8/2.4 kV
Thermo-magnetic N
/ 600 A
interrupter J
) 4kV
Thermo-magnetic 200 A
interrupter
Contactor : ' - - -- -- I
I
I
I
I
150/5 .2.____..__@
500 HP
Breakers
The setting values and characteristic curve are shown in Table 10.3 and Figure 10.3
respectively.
Solution
Nominal motor current
500 x 0.746 k W
1N= =112.16A
v/3 x 0.8 x 2 . 4 k V
1000
800
600
400
200
100
80
60
40
20
1
0.8
0.6
0.4
0.2
0.1
0.08
0.06
0.04
0.02
0.01
10 20 30 50 70 lO0 1 2 3 5 7 lO 20 30 50 70 100
Earth fault current in percent Current in multiples of pick-up
of tripping XFMR rating
5 1
Setting---- 117.8 x - - x -- x 100%= 101.46%
150 3.87
With a setting o f 100 per cent,
lstartl = 6 x ( 1 1 2 . 1 6 A ) = 672.96A
Given that this value is less than the motor starting current, it is necessary to increase
the setting value. Try eight times, then
400
200
100
80
60
40
20
10
8
6
~ 2
1
0.8
0.6
0.4
0.2
0.1
0.08
0.06
0.04
0.02
0.01
A C B
Since there is no overlap with the short-time element of the motor, the intermediate
band is also selected.
(iii) Instantaneous element
The instantaneous element is cancelled in order to maintain co-ordination. The
co-ordination curves are shown in Figure 10.4.
It should be emphasised that, although the values selected for the protective
devices in this example ensure proper co-ordination, they are not unique. Other
settings could be chosen provided that the curves so obtained guarantee adequate
reliability and good selectivity.