POWER SYSTEM PROTECTION

COORDINATION REPORT

Client:
M/s. REXAM INDIA , SRI CITY,ANDHRA PRADESH

Report Compiled by:


Interface Electronics Pvt Ltd,Chennai
Email:ife@vsnl.com
Mobile no:9884370326
Executive Summary
Introduction
This document provides information about the various protective schemes for the transformer protection,motor
protection and generator protection . The document lists the particular protective functions as they overlap and
complement each other for back-up and outlines the philosophy about the selection of how the protection setting
values. Please note that the generator and transformer characteristics and capability curves and data are contained in
separate documents. Also the documentation with detailed descriptions of the various protection systems are provided
in separate relay documents.
We were requested to prepare a protection co-ordination report for 33 / 0.415 kV Electrical Distribution for the Plant
of REXAM India at SRI CITY, AP .
This report includes calculation results of the study 33/0.415 kV Switchgear.
The system data for calculation are based on the data provided by M/s REXAM,
The most important tool for documentation of over current protection co-ordination is Paladin Design Base 5. Typical
grading paths have been chosen in a single line and in a current/time diagram the selectivity of the characteristic curves
of the devices are shown.

2 Power System Data

It is stated the Power source is from a 33 kV substation some km away from this Plant and source Fault MVA is
assumed to be 1500 MVA sec and based on this value further calculations of short circuit currents for down stream
are calculated

3 Infeed Data  
In the absense of exact short circuit data of utility ,minimum Short-circuit power 3-phase @33 kV SS is taken as 750
MVA at 33 kV and that of maximum is taken to be 1500MVA for evaluation and study

4 Protection Coordination

The short circuit currents at various busbars are calculated .based on the above assumptions.
Based on the short circuit calculations, protection coordination study was carried out for this Project
Calculated Short circuit currents are tabulated in the report and also shown in the SLD.

Selectivity of relays have been worked out for all the relays in the 33 kV Switch Board, and 415 V PMCC Panel. The
tripping time selection of 0.415 kV Incomer is arrived at based on two motors starting simultaneously with acceleration
time of 1.5 sec.Keeping this time as reference other timing are worked out with time gradation of 150 mill sec.

5 Conclusion

Setting sketches for the over current devices have been performed for the 33/0.415 kV network The selectivity of the
protection settings for characteristic feeders was verified with the protection grading diagrams prepared with software
Paladin Design Base 5 Generally, attention was given to provide the largest possible safety clearance between the
individual protective devices.

The calculated relay settings are based on different data sheets available during the workout (e.g.generator data sheet,
CB data, and single line diagram) of the document. In case of any equipment modification or change of various
electrical characteristics, this document has to be revised. Therefore all the settings have to be checked and revised
during the commissioning on site. Generally the calculation of the settings is done according to our best knowledge and
conscience. So we can’t accept any responsibility for errors included in the document. Further we are not liable for any
incident or damage resulting from the content of this setting calculation. Some protection settings (e.g. frequency,
voltage) have to be checked and approved also from the power distribution owner.
Reference Documents / Drawings
Sl.No Document Title File reference Document No
1 Main Single Line Diagram EM_901 MAIN SINGLE LINE DIAGRAM - G .pdf 901/G
2 Single Line Diagram for HVAC Panel EM_901(2) HVAC SINGLE LINE DIAGRAM .pdf 901(2)/D
3 Single Line Diagram for Emergency & Lighting DB EM_901(3) LIghting & Emergency DB SINGLE LINE DIAGRAM..pdf 901(3)/D
4 Single Line Diagram for Power DB EM_901(4) Power DB SINGLE LINE DIAGRAM .pdf 901(4)/D
Device Details
2-Winding Transformers
Details of Equipment kVA rating High Voltage Low voltage Percentage Low High Grounding Vector Type of Supply Variation on
side side Impedance winding winding Mode Group Cooling Primary side
Transformers 1 2500 33000 V 433 V 8.00 Star Delta Direct Dyn11 ONAN -7.5% to +7.5%
Transformers 2 2500 33000 V 433 V 8.00 Star Delta Direct Dyn11 ONAN -7.5% to +7.5%
Diesel Generating Set
Details of Equipment kVA rating Output Voltage Sub transient Starting
Reactance
DG1 2500 415 V 9% Electric Manual
SINGLE LINE DIAGRAM
GRID MP_IC

HG FUSE

CAB_IC

OD VCB
50
51

CAB_IC1

MP_IC
50
51

33kV Main HT PNL


16 17 18 MP_OG1-TR2 MP_OG1-TR1
50 50 50 50 50
51 51 51 51 51
DG SET
GEN

DG PNL OG
CAB:TR2HV CAB:TR1HV
33

32

26 25 TR2 TR1

BD 3
BD2 BD1

T2_F1

T1_F9
LVMD-T1_IC LVMD-G_IC
LVMD-T2 LVMD-T1 LVMD-G
T2_F2

T2_F12 T2_F11
T2_F10 T2_F9 T2_F8 T2_F7 T2_F6 T2_F5 T2_F4 T2_F3 T1_F2 T1_F3 T1_F4 T1_F5 T1_F6 T1_F7 G_F10 G_F11 G_F12 G_F13 G_F14 G_F15 G_F16 G_F18 G_F19 G_F20
cab: bms5
cab:sd_md

cab:1016

cab: bms6

cab: cap

cab: bms2

cab: 1001

cab: 1010

cab: wash1
cab:aircomp

cab: bms7

cab: 1006

cab: 1008

cab: ups

cab: 1011

cab: wash2

cab: fp
cab:1007

cab:1003

cab: bms4

cab: 1014
cab:1002

cab: bms1

cab: bms3

cab: sdl

cab: 1012
Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel

PDP-1016 PDP-1007 PDP-1003 PDP-1002 HVAC BMS-7 HVAC BMS6 HVAC BMS-5 CAP PNL
HVAC BMS-1 HVAC BMS-3 PDP 1006 PDP1001 PDP1008 PDP1010 PDP1011 PDP1012 PDP1014 WASHER 1 WASHER 2 FP
HVAC BMS-2 HVAC BMS-4
SD MD PWR IC AC_IC SD MD LIGHT IC UPS DB IC
Air COMP PNL
SD MD PWR SD MD LIGHT UPS DB
AC_OG1 AC_OG2 REV. DATE ECO# DWN APP DESCRIPTION
THIS DRAW ING IS PROPRIETARY INFORMATION

Your Company Name


Address
Address
Phone and web site
cab:aircomp1 CAB:AIRCOMP2
Electrical One-Line Diagram for System
Study
DRAWN BY/DATE: DWG No.: REV.
AC1 AC2
I

ENG. APP./DATE:
MFG. APP./DATE: PART No.:
SCALE: DWG SIZE:
Short Circuit Current Details
Short Circuit Report
Bus Name : Air COMP PNL 04/05/2107
Branch Flow ( A ) IEC60909 Method
Fault At Bus: Air COMP PNL
System Volt: 433 Base Volt: 433V
Fault Type : Pre Fault 3-phase L-L L-G L-L-G
voltage

Bus R RMS ( A ): 433 67250 0 54063 0


Bus Y RMS ( A ): 433 67250 58470 0 64843
Bus B RMS ( A ): 433 67250 58470 0 60205
Bus Name : SD MD PWR 04/05/2107
Branch Flow ( A ) IEC60909 Method
Fault At Bus: SD MD PWR
System Volt: 433 Base Volt: 433V
Fault Type : Pre Fault 3-phase L-L L-G L-L-G
voltage

Bus R RMS ( A ): 433 28535 0 17687 0


Bus Y RMS ( A ): 433 28535 24748 0 25126
Bus B RMS ( A ): 433 28535 24748 0 25975
Bus Name : SD MD LIGHT 04/05/2107
Branch Flow ( A ) IEC60909 Method
Fault At Bus: SD MD LIGHT
System Volt: 433 Base Volt: 433V
Fault Type : Pre Fault 3-phase L-L L-G L-L-G
voltage

Bus R RMS ( A ): 433 14110 0 12936 0


Bus Y RMS ( A ): 433 14110 12224 0 11149
Bus B RMS ( A ): 433 14110 12224 0 15493
Bus Name : LVMD-T2 04/05/2107
Branch Flow ( A ) IEC60909 Method
Fault At Bus: LVMD-T2
System Volt: 433 Base Volt: 433V
Fault Type : Pre Fault 3-phase L-L L-G L-L-G
voltage

Bus R RMS ( A ): 433 81557 0 76090 0


Bus Y RMS ( A ): 433 81557 70991 0 84393
Bus B RMS ( A ): 433 81557 70991 0 73404
Bus Name : Air COMP PNL DG feed only 04/05/2107
Branch Flow ( A ) IEC60909 Method
Fault At Bus: Air COMP PNL
System Volt: 415 Base Volt: 433V
Fault Type : Pre Fault 3-phase L-L L-G L-L-G
voltage

Bus R RMS ( A ): 415 36890 0 29040 0


Bus Y RMS ( A ): 415 36890 36668 0 37213
Bus B RMS ( A ): 415 36890 36668 0 36981
GRID MP_IC

HG FUSE

CAB_IC

OD VCB
50
51

CAB_IC1

MP_IC
50
51

33kV Main HT PNL


16 17 18 MP_OG1-TR2 MP_OG1-TR1
50 50 50 50 50
51 51 51 51 51
DG SET
GEN

DG PNL OG
Ik": 34274A
CAB:TR2HV CAB:TR1HV
33

32

26 25 TR2 TR1

Ik": 34274A
BD 3
BD2 BD1

Ik": 34273.99A
LVMD-G_IC

T1_F9
T2_F1 LVMD-T1_IC Ik": 34274A
T2_F2 LVMD-T1 LVMD-G
LVMD-T2
Ik": 34273.99A
T2_F11
T2_F12 Ik": 34273.99A
T2_F10 T2_F9 T2_F8 T2_F7 T2_F6 T2_F5 T2_F4 T2_F3 T1_F2 T1_F3 T1_F4 T1_F5 T1_F6 T1_F7 G_F10 G_F11 G_F12 G_F13 G_F14 G_F15 G_F16 G_F18 G_F19 G_F20
cab: bms5
cab:sd_md

cab:1016

cab: bms6

cab: cap

cab: bms2

cab: 1001

cab: 1010

cab: wash1
Ik": 34273.99A
cab:aircomp

cab: bms7

cab: 1006

cab: 1008

cab: ups

cab: 1011

cab: wash2

cab: fp
cab:1007

cab:1003

cab: bms4

cab: 1014
cab:1002

cab: bms1

cab: bms3

cab: sdl

cab: 1012
Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel

PDP-1016 PDP-1007 PDP-1003 PDP-1002 HVAC BMS-7 HVAC BMS6 HVAC BMS-5 CAP PNL
HVAC BMS-1 HVAC BMS-3 PDP 1006 PDP1001 PDP1008 PDP1010 PDP1011 PDP1012 PDP1014 WASHER 1 WASHER 2 FP
AC_IC HVAC BMS-2
SD MD PWR IC Ik": 34273.99A HVAC BMS-4
SD MD LIGHT IC UPS DB IC
Air COMP PNL
Ik" : 36889.82A

SD MD PWR AC_OG1 AC_OG2 SD MD LIGHT UPS DB


Ik": 1318.25A Ik": 1318.25A REV. DATE ECO# DWN APP DESCRIPTION
THIS DRAW ING IS PROPRIETARY INFORMATION

Your Company Name


Address
Address

cab:aircomp1 CAB:AIRCOMP2 Phone and web site

Ik": 1318.25A Ik": 1318.25A


FLOW OF SHORT CIRCUIT CURRENT FOR A FAULT AT AC
COMPRESSOR PANEL WHEN DG SET ALONE FEEDING THE Electrical One-Line Diagram for System
SYSTEM Study
DRAWN BY/DATE: DWG No.: REV.
AC1 AC2
I

ENG. APP./DATE:
MFG. APP./DATE: PART No.:
SCALE: DWG SIZE:
GRID MP_IC

HG FUSE
Ik": 1037.16A

CAB_IC
Ik": 1037.16A

OD VCB
Ik": 1037.16A
50
51

CAB_IC1
Ik": 1037.16A

MP_IC
Ik": 1037.16A
50
51

33kV Main HT PNL


MP_OG1-TR2 MP_OG1-TR1
16 17 18 Ik": 519.16A Ik": 518.01A
50 50 50 50 50
51 51 51 51 51
DG SET
GEN

CAB:TR2HV CAB:TR1HV DG PNL OG


Ik": 519.16A Ik": 518.01A
33

32

TR2 TR1
26 25 Ik": 519.16A Ik": 518.01A

BD 3
BD2 BD1
Ik": 39566.41A Ik": 39479.01A

T2_F1 LVMD-T1_IC

T1_F9
Ik": 39566.41A Ik": 39479.01A LVMD-G_IC
LVMD-T2
Ik" : 81556.81A T2_F2 LVMD-T1 LVMD-G
Ik": 39479.01A
T2_F11
T2_F12 Ik": 2512.72A
T2_F10 T2_F9 T2_F8 T2_F7 T2_F6 T2_F5 T2_F4 T2_F3 T1_F2 T1_F3 T1_F4 T1_F5 T1_F6 T1_F7 G_F10 G_F11 G_F12 G_F13 G_F14 G_F15 G_F16 G_F18 G_F19 G_F20
cab: bms5
cab:sd_md

cab:1016

cab: bms6

cab: cap

cab: bms2

cab: 1001

cab: 1010

cab: wash1
Ik": 2512.72A
cab:aircomp

cab: bms7

cab: 1006

cab: 1008

cab: ups

cab: 1011

cab: wash2

cab: fp
cab:1007

cab:1003

cab: bms4

cab: 1014
cab:1002

cab: bms1

cab: bms3

cab: sdl

cab: 1012
Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel

PDP-1016 PDP-1007 PDP-1003 PDP-1002 HVAC BMS-7 HVAC BMS6 HVAC BMS-5 CAP PNL
HVAC BMS-1 HVAC BMS-3 PDP 1006 PDP1001 PDP1008 PDP1010 PDP1011 PDP1012 PDP1014 WASHER 1 WASHER 2 FP
AC_IC HVAC BMS-2
SD MD PWR IC Ik": 2512.72A HVAC BMS-4
SD MD LIGHT IC UPS DB IC
Air COMP PNL
SD MD PWR AC_OG1 AC_OG2 SD MD LIGHT UPS DB
Ik": 1256.36A Ik": 1256.36A REV. DATE ECO# DWN APP DESCRIPTION
THIS DRAW ING IS PROPRIETARY INFORMATION

Your Company Name


Address
Address

cab:aircomp1 CAB:AIRCOMP2 Phone and web site

Ik": 1256.36A Ik": 1256.36A


FLOW OF SHORT CIRCUIT CURRENT FOR A FAULT AT MAIN
LVMD T2 PANEL Electrical One-Line Diagram for System
Study
DRAWN BY/DATE: DWG No.: REV.
AC1 AC2
I

ENG. APP./DATE:
MFG. APP./DATE: PART No.:
SCALE: DWG SIZE:
GRID MP_IC

HG FUSE
Ik": 179.45A

CAB_IC
Ik": 179.45A

OD VCB
Ik": 179.45A
50
51

CAB_IC1
Ik": 179.45A

MP_IC
Ik": 179.45A
50
51

33kV Main HT PNL


MP_OG1-TR2 MP_OG1-TR1
16 17 18 Ik": 89.62A Ik": 89.83A
50 50 50 50 50
51 51 51 51 51
DG SET
GEN

CAB:TR2HV CAB:TR1HV DG PNL OG


Ik": 89.62A Ik": 89.83A
33

32

TR2 TR1
26 25 Ik": 89.62A Ik": 89.83A

BD 3
BD2 BD1
Ik": 6830.08A Ik": 6846.18A

T2_F1 LVMD-T1_IC

T1_F9
Ik": 6830.08A Ik": 6846.18A LVMD-G_IC
T2_F2 LVMD-T1 LVMD-G
LVMD-T2
Ik": 7263.89A
T2_F11
T2_F12 Ik": 433.82A T1_F7
T2_F10 T2_F9 T2_F8 T2_F7 T2_F6 T2_F5 T2_F4 T2_F3 T1_F2 T1_F3 T1_F4 T1_F5 T1_F6 Ik": 14109.82A
G_F10 G_F11 G_F12 G_F13 G_F14 G_F15 G_F16 G_F18 G_F19 G_F20
cab: bms5
cab:sd_md

cab:1016

cab: bms6

cab: cap

cab: bms2

cab: 1001

cab: 1010

cab: wash1
Ik": 433.82A
cab:aircomp

cab: bms7

cab: 1006

cab: 1008

cab: ups

cab: 1011

cab: wash2

cab: fp
cab:1007

cab:1003

cab: bms4

cab: 1014
cab:1002

cab: bms1

cab: bms3

Ik": 14109.82A
cab: sdl

cab: 1012
Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel

PDP-1016 PDP-1007 PDP-1003 PDP-1002 HVAC BMS-7 HVAC BMS6 HVAC BMS-5 CAP PNL
HVAC BMS-1 HVAC BMS-3 PDP 1006 PDP1001 PDP1008 PDP1010 PDP1011 PDP1012 PDP1014 WASHER 1 WASHER 2 FP
AC_IC HVAC BMS-2 SD MD LIGHT IC
SD MD PWR IC Ik": 433.82A HVAC BMS-4
Ik": 14109.82A UPS DB IC
Air COMP PNL
SD MD LIGHT
SD MD PWR AC_OG1 AC_OG2 Ik" : 14109.82A UPS DB
Ik": 216.91A Ik": 216.91A REV. DATE ECO# DWN APP DESCRIPTION
THIS DRAW ING IS PROPRIETARY INFORMATION

Your Company Name


Address
Address

cab:aircomp1 CAB:AIRCOMP2 Phone and web site

Ik": 216.91A Ik": 216.91A


FLOW OF SHORT CIRCUIT CURRENT FOR A FAULT AT SD MD
LIGHTING PANEL Electrical One-Line Diagram for System
Study
DRAWN BY/DATE: DWG No.: REV.
AC1 AC2
I

ENG. APP./DATE:
MFG. APP./DATE: PART No.:
SCALE: DWG SIZE:
GRID MP_IC

HG FUSE
Ik": 362.88A

CAB_IC
Ik": 362.88A

OD VCB
Ik": 362.88A
50
51

CAB_IC1
Ik": 362.88A

MP_IC
Ik": 362.88A
50
51

33kV Main HT PNL


MP_OG1-TR2 MP_OG1-TR1
16 17 18 Ik": 181.65A Ik": 181.24A
50 50 50 50 50
51 51 51 51 51
DG SET
GEN

CAB:TR2HV CAB:TR1HV DG PNL OG


Ik": 181.65A Ik": 181.24A
33

32

TR2 TR1
26 25 Ik": 181.65A Ik": 181.24A

BD 3
BD2 BD1
Ik": 13843.63A Ik": 13813.06A

T2_F1 LVMD-T1_IC

T1_F9
Ik": 13843.63A Ik": 13813.06A LVMD-G_IC
T2_F2 LVMD-T1 LVMD-G
LVMD-T2
Ik": 13813.05A
T2_F12 T2_F11
Ik": 28535.39A
Ik": 879.16A
T2_F10 T2_F9 T2_F8 T2_F7 T2_F6 T2_F5 T2_F4 T2_F3 T1_F2 T1_F3 T1_F4 T1_F5 T1_F6 T1_F7 G_F10 G_F11 G_F12 G_F13 G_F14 G_F15 G_F16 G_F18 G_F19 G_F20
cab: bms5
Ik": 28535.39A
cab:sd_md

cab:1016

cab: bms6

cab: cap

cab: bms2

cab: 1001

cab: 1010

cab: wash1
Ik": 879.16A
cab:aircomp

cab: bms7

cab: 1006

cab: 1008

cab: ups

cab: 1011

cab: wash2

cab: fp
cab:1007

cab:1003

cab: bms4

cab: 1014
cab:1002

cab: bms1

cab: bms3

cab: sdl

cab: 1012
Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel

PDP-1016 PDP-1007 PDP-1003 PDP-1002 HVAC BMS-7 HVAC BMS6 HVAC BMS-5 CAP PNL
HVAC BMS-1 HVAC BMS-3 PDP 1006 PDP1001 PDP1008 PDP1010 PDP1011 PDP1012 PDP1014 WASHER 1 WASHER 2 FP
SD MD PWR IC AC_IC HVAC BMS-2
Ik": 28535.39A Ik": 879.16A HVAC BMS-4
SD MD LIGHT IC UPS DB IC
Air COMP PNL
SD MD PWR
Ik" : 28535.39A AC_OG1 AC_OG2 SD MD LIGHT UPS DB
Ik": 439.58A Ik": 439.58A REV. DATE ECO# DWN APP DESCRIPTION
THIS DRAW ING IS PROPRIETARY INFORMATION

Your Company Name


Address
Address

cab:aircomp1 CAB:AIRCOMP2 Phone and web site

Ik": 439.58A Ik": 439.58A


FLOW OF SHORT CIRCUIT CURRENT FOR A FAULT AT SD MD
PWR PANEL Electrical One-Line Diagram for System
Study
DRAWN BY/DATE: DWG No.: REV.
AC1 AC2
I

ENG. APP./DATE:
MFG. APP./DATE: PART No.:
SCALE: DWG SIZE:
GRID MP_IC

HG FUSE
Ik": 850.04A

CAB_IC
Ik": 850.04A

OD VCB
Ik": 850.04A
50
51

CAB_IC1
Ik": 850.04A

MP_IC
Ik": 850.04A
50
51

33kV Main HT PNL


MP_OG1-TR2 MP_OG1-TR1
16 17 18 Ik": 425.5A Ik": 424.56A
50 50 50 50 50
51 51 51 51 51
DG SET
GEN

CAB:TR2HV CAB:TR1HV DG PNL OG


Ik": 425.5A Ik": 424.56A
33

32

TR2 TR1
26 25 Ik": 425.5A Ik": 424.56A

BD 3
BD2 BD1
Ik": 32428.25A Ik": 32356.62A

T2_F1 LVMD-T1_IC

T1_F9
Ik": 32428.25A Ik": 32356.62A LVMD-G_IC
T2_F2 LVMD-T1 LVMD-G
LVMD-T2
Ik": 32356.62A
T2_F11
T2_F12 Ik": 64783.84A
T2_F10 T2_F9 T2_F8 T2_F7 T2_F6 T2_F5 T2_F4 T2_F3 T1_F2 T1_F3 T1_F4 T1_F5 T1_F6 T1_F7 G_F10 G_F11 G_F12 G_F13 G_F14 G_F15 G_F16 G_F18 G_F19 G_F20
cab: bms5
cab:sd_md

cab:1016

cab: bms6

cab: cap

cab: bms2

cab: 1001

cab: 1010

cab: wash1
Ik": 64783.84A
cab:aircomp

cab: bms7

cab: 1006

cab: 1008

cab: ups

cab: 1011

cab: wash2

cab: fp
cab:1007

cab:1003

cab: bms4

cab: 1014
cab:1002

cab: bms1

cab: bms3

cab: sdl

cab: 1012
Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel Panel

PDP-1016 PDP-1007 PDP-1003 PDP-1002 HVAC BMS-7 HVAC BMS6 HVAC BMS-5 CAP PNL
HVAC BMS-1 HVAC BMS-3 PDP 1006 PDP1001 PDP1008 PDP1010 PDP1011 PDP1012 PDP1014 WASHER 1 WASHER 2 FP
AC_IC HVAC BMS-2
SD MD PWR IC Ik": 64783.84A HVAC BMS-4
SD MD LIGHT IC UPS DB IC
Air COMP PNL
Ik" : 67250.44A

SD MD PWR AC_OG1 AC_OG2 SD MD LIGHT UPS DB


Ik": 1264.01A Ik": 1264.01A REV. DATE ECO# DWN APP DESCRIPTION
THIS DRAW ING IS PROPRIETARY INFORMATION

Your Company Name


Address
Address

cab:aircomp1 CAB:AIRCOMP2 Phone and web site

Ik": 1264.01A Ik": 1264.01A


FLOW OF SHORT CIRCUIT CURRENT FOR A FAULT AT AC
COMPRESSOR PANEL Electrical One-Line Diagram for System
Study
DRAWN BY/DATE: DWG No.: REV.
AC1 AC2
I

ENG. APP./DATE:
MFG. APP./DATE: PART No.:
SCALE: DWG SIZE:
Setting Calculation for 2500 kVA Transformers

33kV 0.433
CTHV:200/1 4000 A ACB
2500 kVA
Transformer capacity PT 2500 kVA
Primary Voltage Vp 33 kV
Secondary Voltage Vs 0.433 kV
Transformer HV side CT details CTHV 200/1
Turns Ratio CTR1 200
Transformer LV side ACB RATING 4000 Amps
Percentage Impedance of Transformer Z 8.00%
Transformer Full Load HV side Primary Current at 0% tapping Ipfl 2500/ (33x1.732) Amps
Transformer HV side current as per name plate (HV Current) 43.74 Amps
Relay drop off Ratio 0.95
HV Pick up Current 1.10 x HV Currrent/ Drop off ratio
=1.10 x 43.74/ 0.95
50.65
Transformer HV side CT Secondary Pick up Current Isfl 0.25
IDMT setting at 11 kV side 0.25
Setting proposed on HV side Ip 0.25
Curve Normal Inverse
Transformer Full Load LV side Current at 0% tapping 2500/ (0.433x1.732) Amps
Transformer LV side Primary current as per name plate 3333.53 Amps
Relay drop off Ratio 0.95
LV Pick up Current 1.1 x HV Currrent/ Drop off ratio
=1.10 x 3333.53/ 0.95
3859.88
Transformer LV side CT Secondary Pick up Current Isfl 0.96
ACB setting at 0.433 kV side 1
Setting proposed on LV side Ip 1
Through Fault Current on LV side 41669.11 Amps
Through Fault Current on HV side 546.75 Amps
High set setting Current on HV side 1.2 x546.75 Amps
656.1
High set setting on HV side relay 3.2805
Setting proposed on HV side I>> 3.3
Setting Calculation for 2500 kVA DG setset

0.415 kV
4000 A ACB
2500 kVA
GENERATOR Capacity PT 2500 kVA
Generator ACB Rating 4000 Amps
Synchronous Reactance 170.00%
Transient Reactance 15.00%
Sub Transient Reactance 9.00%
Generator Full Load Current Ipfl 3478.12 Amps
Relay drop off Ratio 0.95
HV Pick up Current 1.10 xFull Load Currrent/ Drop off ratio
=1.1 x 3478.12 / 0.95
4027.29
Generator ACB Pick up Current Isfl 1.01
Through Fault Current on from Generator 38645.73 Amps
Setting proposed for high set >> 4
Setting Details for
33 kV SwitchBoard
Setting Details 33 kV Switch Board
33kV Incomer 1
Relay type: Areva P121 Located in Panel 1
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
• Power System Data 1
Title Setting Range Setting
CTs CT Primary 10..50000 A 200
CT Secondary 1A/5A 1
PT PT Primary 110..132000V 33000/√3
PT Secondary 57-130,220-480 110/√3
• Phase over current Protection: 50/51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.1~40.00 A 4 x In 800
50-2 Delay T I>> 0.00..150.00 s 0.25 s
51-1Pickup I> 0.4~10.00 A 0.6 x In 120
51-1Delay tI> 0.00..150.00 s NA
Time dial I> TMS 0.02~1.5 0.2
IEC Curve IEC Standard IEC
Inverse(SI) ,IEC Standard
Very Inverse(VI) Inverse
,IEC Extremely
Inverse(EI)…
• Ground over current Protection: 50N/51 N
Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> 0.01 to 8 Ien 0.5 x In 100
50N-2 Delay Te>> 0.02..99.00 s 0.1
51N-1Pickup Ie> 0.002 to1 Ien 0.05 x In 10
51N-1Delay TIe> 0.02..150.00 s NA
Delay type DT
Time dial Ie> TMS 0.02~1.5 0.35
IEC Curve IEC Standard NA
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)…
33kV Outgoing Feeders 1 &2
Relay type: Areva P111 Located in Panels 2 &3
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
• Power System Data 1
Title Setting Range Setting
CTs CT Primary 10..50000 A 200
CT Secondary 1A/5A 1
• Phase over current Protection: 50/51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.1~40.00 A 3.3 x In 660
50-2 Delay T I>> 0.00..150.00 s 0.1 s
51-1Pickup I> 0.4~10.00 A 0.3 x In 60
51-1Delay tI> 0.00..150.00 s NA s
Time dial I> TMS 0.02~1.5 0.2
IEC Curve IEC Standard IEC
Inverse(SI) ,IEC Extremel
Very Inverse(VI) y Inverse
,IEC Extremely
Inverse(EI)…
• Ground over current Protection: 50N/51 N
Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> 0.01 to 8 Ien 0.4 x In 80
50N-2 Delay Te>> 0.02..99.00 s 0.1
51N-1Pickup Ie> 0.002 to1 Ien 0.04 x In 8
51N-1Delay TIe> 0.02..150.00 s NA
Delay type DT
Time dial Ie> TMS 0.02~1.5 0.2
IEC Curve IEC Standard NA
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)…
Setting Details 33 kV Outdoor VCB Panel
33kV Incomer 1
Relay type: Areva P121 Located in Panel 1
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
• Power System Data 1
Title Setting Range Setting
CTs CT Primary 10..50000 A 125
CT Secondary 1A/5A 5
PT PT Primary 110..132000V 33000/√3
PT Secondary 57-130,220-480 110/√3
• Phase over current Protection: 50/51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.5~200.00 A 40 x In 1000
50-2 Delay T I>> 0.00..150.00 s 0.25 s
51-1Pickup I> 2~50 A 5.2 x In 130
51-1Delay tI> 0.00..150.00 s NA
Time dial I> TMS 0.02~1.5 0.25
IEC Curve IEC Standard IEC
Inverse(SI) ,IEC Standard
Very Inverse(VI) Inverse
,IEC Extremely
Inverse(EI)…
• Ground over current Protection: 50N/51 N
Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> 0.05 to 40 Ien 5 x In 125
50N-2 Delay Te>> 0.02..99.00 s 0.1
51N-1Pickup Ie> 0.01 to 5 Ien 0.5 x In 12.5
51N-1Delay TIe> 0.02..150.00 s NA
Delay type DT
Time dial Ie> TMS 0.02~1.5 0.5
IEC Curve IEC Standard NA
Inverse(SI) ,IEC
Very Inverse(VI)
,IEC Extremely
Inverse(EI)…
Setting Details for LT Switch Boards
Setting Details for LOW VOLTAGE MAIN DISTRIBUTION -T2
Location Device Sevice ID Feeder Breaker Phase Current Settings Ground Current Settings
of device description and rating Set OVERLOAD PROTECTION Short-time delayed short-circuit protection Instantaneous short-circuit Ground-fault protection
release Current In SETTIN Long time Primary Setting range time lag Setting Short time Primary Setting Short time Setting Instantane Primary Setting range of the operating Operating Primary Setting Delay
G Pick up Current for time-lag setting in range Isd = Pick up Current range for delay in range Ii = ous Current current Ig current Current range of time tg in
RANGE Current class tR at I2t sec Ir × ... Current delay time sec (Tsd) In × ... Current setting Ig the delay ms
IR=In setting (Ir) Settint tsd in ms in ms setting (I3) time tg in
X… (Isd) ms
F1 4000A ACB,NW INCOMER 4000 A 4000 0.4-1.0 1 4000 0.5,1,2,4,8,1 21.5-10 x Ir 4 16000 100-200- 200 2-15 6 24000 A-500,B-640,C-720, B 640 100-200- 100
40H2,Micrologic 6 2,16,20,24 300-400 D-800,E-880,F-960, 300-400-
G-1040,H-1120,J-1200 500
F2 4000A ACB,NW BUSCOUPLER 4000 A 4000 0.4-1.0 0.8 3200 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 12800 100-200- 200 2-15 6 24000 A-500,B-640,C-720, A 500 100-200- 100
40H2,Micrologic 6 2,16,20,24 300-400 D-800,E-880,F-960, 300-400-
G-1040,H-1120,J-1200 500
F3 1600A ACB,NT CAPACITOR FEEDER 1600 A 1600 0.4-1.0 1 1600 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 6400 100-200- 100 2-15 6 9600 A-500,B-640,C-720, A 100 100-200- 100
16H1,Micrologic 6 2,16,20,24 300-400 D-800,E-880,F-960, 300-400-
G-1040,H-1120,J-1200 500
F4 630A MCCB HVAC BMS-5 630 A 630 0.4-1.0 1 630 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 2520 100-200- 200 2-15 6 3780 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 126 100-200- 100
,NSX630 GRIDLINE 25 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
MICROLOGIC 6 G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
F5 125A MCCB HVAC BMS-6 125 A 125 0.8-1.0 1 125 NA NA NA NA 1250 NA NA NA NA NA NA NA NA NA NA
,NS160N TMD HEATING

F6 400A NSX400 HVAC BMS-6 400 A 400 0.4-1.0 0.4 160 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 640 100-200- 200 2-15 6 2400 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 80 100-200- 100
MICROLOGIC 6 HEATING 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
F7 1000A ACB,NT PDP 1002 1000 A 1000 0.4-1.0 1 1000 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 4000 100-200- 200 2-15 6 6000 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 200 100-200- 100
10H1,Micrologic 6 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
F8 1250A ACB,NT PDP 1003 1000 A 1000 0.4-1.0 1 1000 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 4000 100-200- 200 2-15 6 6000 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 200 100-200- 100
12H1,Micrologic 6 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
F9 1000A ACB,NT PDP 1007 1000 A 1000 0.4-1.0 1 1000 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 4000 100-200- 200 2-15 6 6000 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 200 100-200- 100
10H1,Micrologic 6 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
F10 630A MCCB PDP 1016 630 A 630 0.4-1.0 1 630 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 2520 100-200- 200 2-15 6 3780 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 126 100-200- 100
,NSX630 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
MICROLOGIC 6 G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
F11 2000A ACB,NT AIR COMPRESSOR 2000 A 2000 0.4-1.0 1 2000 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 8000 100-200- 200 2-15 6 12000 A-500,B-640,C-720, A 500 100-200- 100
20H1,Micrologic 6 PANEL 2,16,20,24 300-400 D-800,E-880,F-960, 300-400-
G-1040,H-1120,J-1200 500
F12 400A NSX400 SD MAIN 400 A 400 0.4-1.0 0.6 240 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 960 100-200- 200 2-15 6 2400 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 80 100-200- 100
MICROLOGIC 6 DISTRIBUTION 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
F13 400A NSX400 SD MAIN 400 A 400 0.4-1.0 0.6 240 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 960 100-200- 200 2-15 6 2400 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 80 100-200- 100
MICROLOGIC 6 DISTRIBUTION 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
Setting Details for LOW VOLTAGE MAIN DISTRIBUTION -T1
Location Device Sevice ID Feeder Breaker Phase Current Settings Ground Current Settings
of device description and rating Set OVERLOAD PROTECTION Short-time delayed short-circuit protection Instantaneous short-circuit Ground-fault protection
release Current In SETTIN Long time Primary Setting range time lag Setting Short time Primary Setting Short time Setting Instantane Primary Setting range of the operating Operating Primary Setting Delay
G Pick up Current for time-lag setting in range Isd = Pick up Current range for delay in range Ii = ous Current current Ig current Current range of time tg in
RANGE Current class tR at I2t sec In × ... Current delay time sec (Tsd) In × ... Current setting Ig the delay ms
IR=In setting (I1) Settint tsd in ms in ms setting (I3) time tg in
X… (Isd) ms
F1 4000A ACB,NW INCOMER 4000 A 4000 0.4-1.0 1 4000 0.5,1,2,4,8,1 21.5-10 x Ir 4 16000 100-200- 200 2-15 6 24000 A-500,B-640,C-720, B 640 100-200- 100
40H2,Micrologic 6 2,16,20,24 300-400 D-800,E-880,F-960, 300-400-
G-1040,H-1120,J-1200 500
F9 4000A ACB,NW BUSCOUPLER 4000 A 4000 0.4-1.0 1 4000 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 16000 100-200- 200 2-15 6 24000 A-500,B-640,C-720, A 500 100-200- 100
40H2,Micrologic 6 2,16,20,24 300-400 D-800,E-880,F-960, 300-400-
G-1040,H-1120,J-1200 500
F2 125A MCCB HVAC BMS-1 125 A 125 0.8-1.0 1 125 NA NA NA NA 1250 NA NA NA NA NA NA NA NA NA NA
,NS160N TMD

F3 630A MCCB HVAC BMS-2 630 A 630 0.4-1.0 1 630 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 2520 100-200- 200 2-15 6 3780 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 126 100-200- 100
,NSX630 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
MICROLOGIC 6 G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
F4 630A MCCB HVAC BMS-3 630 A 630 0.4-1.0 1 630 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 2520 100-200- 200 2-15 6 3780 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 126 100-200- 100
,NSX630 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
MICROLOGIC 6 G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
F5 630A MCCB HVAC BMS-4 630 A 630 0.4-1.0 1 630 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 2520 100-200- 200 2-15 6 3780 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 126 100-200- 100
,NSX630 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
MICROLOGIC 6 G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
F6 1000A ACB,NT PDP 1006 1000 A 1000 0.4-1.0 1 1000 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 4000 100-200- 200 2-15 6 6000 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 200 100-200- 100
10H1,Micrologic 6 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
F7 125A MCCB SDL MAIN 125 A 125 0.8-1.0 1 125 NA NA NA NA 1250 NA NA NA NA NA NA NA NA NA NA
,NS160N TMD DISTRIBUTION

F8 400A NSX400 SPARE 400 A 400 0.4-1.0 0.4 160 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 640 100-200- 200 2-15 6 2400 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 80 100-200- 100
MICROLOGIC 6 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
Setting Details for LOW VOLTAGE MAIN DISTRIBUTION -GENERATOR
Location Device Sevice ID Feeder Breaker Phase Current Settings Ground Current Settings
of device description and rating Set OVERLOAD PROTECTION Short-time delayed short-circuit protection Instantaneous short-circuit Ground-fault protection
release Current In SETTIN Long time Primary Setting range time lag Setting Short time Primary Setting Short time Setting Instantane Primary Setting range of the operating Operating Primary Setting Delay
G Pick up Current for time-lag setting in range Isd = Pick up Current range for delay in range Ii = ous Current current Ig current Current range of time tg in
RANGE Current class tR at I2t sec In × ... Current delay time sec (Tsd) In × ... Current setting Ig the delay ms
IR=In setting (I1) Settint tsd in ms in ms setting (I3) time tg in
X… (Isd) ms
F21 4000A ACB,NW INCOMER 4000 A 4000 0.4-1.0 1 4000 0.5,1,2,4,8,1 21.5-10 x Ir 4 16000 100-200- 200 2-15 6 24000 A-500,B-640,C-720, B 640 100-200- 100
40H2,Micrologic 6 2,16,20,24 300-400 D-800,E-880,F-960, 300-400-
G-1040,H-1120,J-1200 500
F10 800A ACB,NT PDP 1001 800 A 800 0.4-1.0 1 800 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 3200 100-200- 200 2-15 6 4800 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 160 100-200- 100
08H1,Micrologic 6 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
F11 630A ACB NT PDP 1008 630 A 630 0.4-1.0 1 630 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 2520 100-200- 200 2-15 6 3780 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 126 100-200- 100
08H1,Micrologic 6 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
F12 1600A ACB,NT PDP 1010 1600 A 1600 0.4-1.0 0.85 1360 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 5440 100-200- 100 2-15 6 9600 A-500,B-640,C-720, A 500 100-200- 100
16H1,Micrologic 6 2,16,20,24 300-400 D-800,E-880,F-960, 300-400-
G-1040,H-1120,J-1200 500
F13 125A MCCB UPS 125 A 125 0.8-1.0 1 125 NA NA NA NA 1250 NA NA NA NA NA NA NA NA 100-200- 100
,NS160N TMD 300-400-
500
F14 1600A ACB,NT PDP 1011 1600 A 1600 0.4-1.0 0.85 1360 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 5440 100-200- 100 2-15 6 9600 A-500,B-640,C-720, A 500 100-200- 100
16H1,Micrologic 6 2,16,20,24 300-400 D-800,E-880,F-960, 300-400-
G-1040,H-1120,J-1200 500
F15 1000A ACB,NT PDP 1012 1000 A 1000 0.4-1.0 0.85 850 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 3400 100-200- 100 2-15 6 6000 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 200 100-200- 100
10H1,Micrologic 6 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
F16 1250A ACB,NT PDP 1014 1250 A 1250 0.4-1.0 0.85 1062.5 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 4250 100-200- 100 2-15 6 7500 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 250 100-200- 100
12H1,Micrologic 6 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
F17 125A MCCB SPARE 125 A 125 0.8-1.0 1 125 NA NA NA NA 1250 NA NA NA NA NA NA NA NA NA NA
,NS160N TMD

F18 800A ACB,NT WASHER 1 800 A 800 0.4-1.0 0.85 680 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 2720 100-200- 100 2-15 6 4800 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 160 100-200- 100
08H1,Micrologic 6 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
F19 800A ACB,NT WASHER 2 800 A 800 0.4-1.0 0.85 680 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 2720 100-200- 100 2-15 6 4800 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 160 100-200- 100
08H1,Micrologic 6 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
F20 630A MCCB ELECTRICAL FIRE 630 A 630 0.4-1.0 1 630 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 2520 100-200- 200 2-15 6 3780 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 126 100-200- 100
,ETU45B PUMP 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
Setting Details for AIR COMPRESSOR PANEL
Location Device Sevice ID Feeder Breaker Phase Current Settings Ground Current Settings
of device description and rating Set OVERLOAD PROTECTION Short-time delayed short-circuit protection Instantaneous short-circuit Ground-fault protection
release Current In SETTIN Long time Primary Setting range time lag Setting Short time Primary Setting Short time Setting Instantane Primary Setting range of the operating Operating Primary Setting Delay
G Pick up Current for time-lag setting in range Isd = Pick up Current range for delay in range Ii = ous Current current Ig current Current range of time tg in
RANGE Current class tR at I2t sec In × ... Current delay time sec (Tsd) In × ... Current setting Ig the delay ms
IR=In setting (I1) Settint tsd in ms in ms setting (I3) time tg in
X… (Isd) ms
F1 2000A ACB,NT INCOMER 2000 A 2000 0.4-1.0 1 2000 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 8000 100-200- 200 2-15 6 12000 A-500,B-640,C-720, A 500 100-200- 100
20H1,Micrologic 6 2,16,20,24 300-400 D-800,E-880,F-960, 300-400-
G-1040,H-1120,J-1200 500
F2 1000A ACB,NT AIR COMPRESSOR 1 1000 A 1000 0.4-1.0 0.4 400 0.5,1,2,4,8,1 4 1.5-10 x Ir 8 3200 100-200- 200 2-15 6 6000 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 200 100-200- 100
10H1,Micrologic 6 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
F3 1000A ACB,NT AIR COMPRESSOR2 1000 A 1000 0.4-1.0 0.4 400 0.5,1,2,4,8,1 4 1.5-10 x Ir 8 3200 100-200- 200 2-15 6 6000 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 200 100-200- 100
10H1,Micrologic 6 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
Setting Details for SD MAIN DISTRIBUTION (POWER)
Location Device Sevice ID Feeder Breaker Phase Current Settings Ground Current Settings
of device description and rating Set OVERLOAD PROTECTION Short-time delayed short-circuit protection Instantaneous short-circuit Ground-fault protection
release Current In SETTIN Long time Primary Setting range time lag Setting Short time Primary Setting Short time Setting Instantane Primary Setting range of the operating Operating Primary Setting Delay
G Pick up Current for time-lag setting in range Isd = Pick up Current range for delay in range Ii = ous Current current Ig current Current range of time tg in
RANGE Current class tR at I2t sec In × ... Current delay time sec (Tsd) In × ... Current setting Ig the delay ms
IR=In setting (I1) Settint tsd in ms in ms setting (I3) time tg in
X… (Isd) ms
F1 400A NSX400 INCOMER 400 A 4000 0.4-1.0 1 4000 0.5,1,2,4,8,1 2 1.5-10 x Ir 4 16000 100-200- 200 2-15 6 24000 A-0.2x In ,B-0.3xIn,C-0.4xIn, A 800 100-200- 100
MICROLOGIC 6 2,16,20,24 300-400 D-0.5xIn,E-0.6xIn,F-0.7 xIn 300-400-
G-0.8 xIn ,H-0.9xIn ,J-1 xIn 500
F2 100A MCCB SD-A1/1 100 A 100 0.8-1.0 1 100 NA NA NA NA 800 NA NA NA NA NA NA NA NA NA NA
,NS100N TMD

F3 100A MCCB SD-A1/2 100 A 100 0.8-1.0 1 100 NA NA NA NA 800 NA NA NA NA NA NA NA NA NA NA


,NS100N TMD

F10 100A MCCB SD-C1 100 A 100 0.8-1.0 1 100 NA NA NA NA 800 NA NA NA NA NA NA NA NA NA NA


,NS100N TMD

F12 100A MCCB SD-D1 100 A 100 0.8-1.0 1 100 NA NA NA NA 800 NA NA NA NA NA NA NA NA NA NA


,NS100N TMD

F14 100A MCCB SD-E 100 A 100 0.8-1.0 1 100 NA NA NA NA 800 NA NA NA NA NA NA NA NA NA NA


,NS100N TMD

F16 100A MCCB SPARE 100 A 100 0.8-1.0 1 100 NA NA NA NA 800 NA NA NA NA NA NA NA NA NA NA


,NS100N TMD

OTHER FEEDERS ARE WITH MCBs AND THERE IS NO VARIABLE SETTINGS AVAILABLE, THEREFORE NOT INCLUDED
Setting Details for SD MAIN DISTRIBUTION (LIGHTING)
Location Device Sevice ID Feeder Breaker Phase Current Settings Ground Current Settings
of device description and rating Set OVERLOAD PROTECTION Short-time delayed short-circuit protection Instantaneous short-circuit Ground-fault protection
release Current In SETTIN Long time Primary Setting range time lag Setting Short time Primary Setting Short time Setting Instantane Primary Setting range of the operating Operating Primary Setting Delay
G Pick up Current for time-lag setting in range Isd = Pick up Current range for delay in range Ii = ous Current current Ig current Current range of time tg in
RANGE Current class tR at I2t sec In × ... Current delay time sec (Tsd) In × ... Current setting Ig the delay ms
IR=In setting (I1) Settint tsd in ms in ms setting (I3) time tg in
X… (Isd) ms
F1 125A MCCB INCOMER 125 A 125 0.8-1.0 1 125 NA NA NA NA 1250 NA NA NA NA NA NA NA NA NA NA
,NS160N TMD

OTHER FEEDERS ARE WITH MCBs AND THERE IS NO VARIABLE SETTINGS AVAILABLE, THEREFORE NOT INCLUDED

Setting Details for UPS 2.11


Location Device Sevice ID Feeder Breaker Phase Current Settings Ground Current Settings
of device description and rating Set OVERLOAD PROTECTION Short-time delayed short-circuit protection Instantaneous short-circuit Ground-fault protection
release Current In SETTIN Long time Primary Setting range time lag Setting Short time Primary Setting Short time Setting Instantane Primary Setting range of the operating Operating Primary Setting Delay
G Pick up Current for time-lag setting in range Isd = Pick up Current range for delay in range Ii = ous Current current Ig current Current range of time tg in
RANGE Current class tR at I2t sec In × ... Current delay time sec (Tsd) In × ... Current setting Ig the delay ms
IR=In setting (I1) Settint tsd in ms in ms setting (I3) time tg in
X… (Isd) ms
F1 80A MCCB ,NS100N INCOMER 80 A 80 0.8-1.0 1 80 NA NA NA NA 800 NA NA NA NA NA NA NA NA NA NA
TMD

OTHER FEEDERS ARE WITH MCBs AND THERE IS NO VARIABLE SETTINGS AVAILABLE, THEREFORE NOT INCLUDED

Setting Details for UPS I/C DB


Location Device Sevice ID Feeder Breaker Phase Current Settings Ground Current Settings
of device description and rating Set OVERLOAD PROTECTION Short-time delayed short-circuit protection Instantaneous short-circuit Ground-fault protection
release Current In SETTIN Long time Primary Setting range time lag Setting Short time Primary Setting Short time Setting Instantane Primary Setting range of the operating Operating Primary Setting Delay
G Pick up Current for time-lag setting in range Isd = Pick up Current range for delay in range Ii = ous Current current Ig current Current range of time tg in
RANGE Current class tR at I2t sec In × ... Current delay time sec (Tsd) In × ... Current setting Ig the delay ms
IR=In setting (I1) Settint tsd in ms in ms setting (I3) time tg in
X… (Isd) ms
F1 125A MCCB INCOMER 125 A 125 0.8-1.0 1 125 NA NA NA NA 1250 NA NA NA NA NA NA NA NA NA NA
,NS160N TMD

OTHER FEEDERS ARE WITH MCBs AND THERE IS NO VARIABLE SETTINGS AVAILABLE, THEREFORE NOT INCLUDED
Time Current Characterstic Curves
10000

AC_OG1
AC1
1000

T2_F11

AC_IC

T2_F1
MP_OG1-TR2
100

OD VCB
MP_IC
S
HG FUSE
10
Time in Seconds
1
.1
.01

.5 1 10 100 1000 10000


Current in Amperes X 100
415 Volt Phase Time-Current Characteristic Curves 05-13-2017
0 - Path: Grid -Outdoor Pnl-33kV switch board-2500kVA transformer- 14:12:21
-Main Panel-Compressor Panel-motor
rexam
10000
1000
100

T2_F1
MP_IC
MP_OG1-TR2
10
Time in Seconds
1

OD VCB

1033735 SCA @ 415V


.1

(OD VCB)
.01

.5 1 10 100 1000 10000


Current in Amperes X 100
415 Volt Ground Time-Current Characteristic Curves 05-13-2017
0 - Path: Grid -Outdoor Pnl-33kV switch board-2500kVA transformer- 14:17:41
-Main Panel-Compressor Panel-motor