Beruflich Dokumente
Kultur Dokumente
for SIMIT
Siemens
SIMIT SP V10.1 Industry
Online
https://support.industry.siemens.com/cs/ww/en/view/109761007 Support
Legal information
Legal information
Use of application examples
Application examples illustrate the solution of automation tasks through an interaction of several
components in the form of text, graphics and/or software modules. The application examples are
a free service by Siemens AG and/or a subsidiary of Siemens AG (“Siemens”). They are non-
binding and make no claim to completeness or functionality regarding configuration and
equipment. The application examples merely offer help with typical tasks; they do not constitute
customer-specific solutions. You yourself are responsible for the proper and safe operation of the
products in accordance with applicable regulations and must also check the function of the
respective application example and customize it for your system.
Siemens grants you the non-exclusive, non-sublicensable and non-transferable right to have the
application examples used by technically trained personnel. Any change to the application
examples is your responsibility. Sharing the application examples with third parties or copying the
application examples or excerpts thereof is permitted only in combination with your own products.
The application examples are not required to undergo the customary tests and quality inspections
of a chargeable product; they may have functional and performance defects as well as errors. It is
your responsibility to use them in such a manner that any malfunctions that may occur do not
result in property damage or injury to persons.
Disclaimer of liability
Siemens shall not assume any liability, for any legal reason whatsoever, including, without
limitation, liability for the usability, availability, completeness and freedom from defects of the
application examples as well as for related information, configuration and performance data and
any damage caused thereby. This shall not apply in cases of mandatory liability, for example
under the German Product Liability Act, or in cases of intent, gross negligence, or culpable loss of
life, bodily injury or damage to health, non-compliance with a guarantee, fraudulent
non-disclosure of a defect, or culpable breach of material contractual obligations. Claims for
damages arising from a breach of material contractual obligations shall however be limited to the
© Siemens AG 2019 All rights reserved
foreseeable damage typical of the type of agreement, unless liability arises from intent or gross
negligence or is based on loss of life, bodily injury or damage to health. The foregoing provisions
do not imply any change in the burden of proof to your detriment. You shall indemnify Siemens
against existing or future claims of third parties in this connection except where Siemens is
mandatorily liable.
By using the application examples you acknowledge that Siemens cannot be held liable for any
damage beyond the liability provisions described.
Other information
Siemens reserves the right to make changes to the application examples at any time without
notice. In case of discrepancies between the suggestions in the application examples and other
Siemens publications such as catalogs, the content of the other documentation shall have
precedence.
The Siemens terms of use (https://support.industry.siemens.com) shall also apply.
Security information
Siemens provides products and solutions with industrial security functions that support the secure
operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary
to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept.
Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems, machines
and networks. Such systems, machines and components should only be connected to an
enterprise network or the Internet if and to the extent such a connection is necessary and only
when appropriate security measures (e.g. firewalls and/or network segmentation) are in place.
For additional information on industrial security measures that may be implemented, please visit
https://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more secure.
Siemens strongly recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are no longer
supported, and failure to apply the latest updates may increase customer’s exposure to cyber
threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed
at: https://www.siemens.com/industrialsecurity.
Table of contents
Legal information ......................................................................................................... 2
1 Description of the telegram .............................................................................. 4
1.1 Symbol.................................................................................................. 4
1.2 Function ................................................................................................ 4
1.3 Message frame format ......................................................................... 4
1.4 State machine ...................................................................................... 5
1.4.1 States ................................................................................................... 5
1.4.2 Control words ....................................................................................... 7
1.4.3 Status words ....................................................................................... 11
1.5 Sign of lifeswap via "STW2" and "ZSW2" .......................................... 15
1.6 Error codes ......................................................................................... 16
2 I/Os .................................................................................................................... 18
3 Parameters ....................................................................................................... 19
4 Operating window ............................................................................................ 20
5 Engineering ...................................................................................................... 26
5.1 Configuration ...................................................................................... 26
5.1.1 Configuration of the SINAMICS drive using GSDML ......................... 26
5.1.2 Configuration of the PLCSIM Advanced coupling .............................. 29
5.2 Parameter assignment ....................................................................... 32
© Siemens AG 2019 All rights reserved
1.2 Function
The standard telegram 111 is typically used in conjunction with EPOS blocks to
exchange data to and from the drive. This allows the drive to be controlled with a
programmable logic controller.
© Siemens AG 2019 All rights reserved
Message frame 111 is very similar to message frame 110, but has only a larger
transmitting range of 12 PZDs.
Message frame 111 offers the following functionality:
• Basic positioner
• 32 bit actual position value
• 32 bit speed value
• Monitoring of signs of life
• Error codes via a cyclic interface
• Warning codes via a cyclic interface
1.4.1 States
The control bits listed in the following table are used to control the state machine
(state transitions). Depending on the current state, the corresponding state bits are
set as shown in the table.
The component uses the following numerical values for editing and display:
Table 1-1
State State (hex.) Description
S1 1
S2 2 2 (POM = normal)
12 12 (POM = jog)
3
S3
S3T 13
S52 6 (only) deceleration with "MaxAcc" or coast.
© Siemens AG 2019 All rights reserved
1.4.2.1 STW1
Table 1-2
Bit Abbreviation Description
0 Off1 ON - Command: 0 = OFF1 active; 1 = ON
1 Off2 0 = OFF2 active
1 = Signal: Operating condition no coast down active
2 Off3 0 = OFF3 active
1 = Operating condition no quick stop active
3 Enc Inverter enable
4 RejTrvTsk Traversing records and direct setpoint specification / MDI
Discard traversing task
0 = active movement command is rejected / axis decelerates with
100% deceleration override
1 = Do not discard traversing task (shaft can be moved)
5 IntMStop intermediate STOP traversing blocks and MDI/setpoint direct
specification - intermediate stop 0 = active motion command is
interrupted / shaft brakes with preset deceleration override
1 = no intermediate stop (shaft can be moved)
© Siemens AG 2019 All rights reserved
1.4.2.2 STW2
Table 1-3
Bit Abbreviation Description
0 DDSBit0 Drive data set Bit 0
1 DDSBit1 Drive data set Bit 1
2 DDSBit2 Drive data set Bit 2
3 DDSBit3 Drive data set Bit 3
4 DDSBit4 Drive data set Bit 4
5 GlbStart Global start
6 ResIComp Reset I-component of speed controller
7 ActPrkAxis Activate parking axis
8 TrvFixedStp Traversing to fixed endstop
9 GlbTrgCom Global triggercommand
10 Bit10 Reserved
11 MotSwOver Motor switchover completed (0->1)
12 MsZykBit0 Master sign of life bit 0
13 MsZykBit1 Master sign of life bit 1
© Siemens AG 2019 All rights reserved
1.4.2.3 POS_STW1
Table 1-4
Bit Abbreviation Description
0 TrvBit0 Set selection bit 0
1 TrvBit1 Set selection bit 1
2 TrvBit2 Set selection bit 2
3 TrvBit3 Set selection bit 3
4 TrvBit4 Set selection bit 4
5 TrvBit5 Set selection bit 5
6 Bit6 Reserved
7 Bit7 Reserved
8 MdiTyp Positioner type
0 = relative positioning
1 = absolute positioning
9 MdiPos Direction selection for setting up or absolute positioning of rotary
axes, in positive direction
10 MdiNeg Direction selection for setting up or absolute positioning of rotary
axes, in negative direction
© Siemens AG 2019 All rights reserved
11 Bit11 Reserved
12 MdiTrTyp Transfer type
0 = Applying values by rising edge on MdiEdge
1 = Signal: constant setpoint transfer
13 Bit13 Reserved
14 MdiSetup direct setpoint input/MDI – setup selection
Selection of MDI mode setup
0 = Position
1 = Setup
15 MdiStart Operating mode MDI / direct setpoint specification
1.4.2.4 POS_STW2
Table 1-5
Bit Abbreviation Description
0 TrkMode Start tracking mode
1 SetRefPt Set reference point
2 ActRefCam Enable reference cam
3 Bit3 Enable fixed stop
4 Bit4 Reserved
5 JogInc Jog:
0 = Continuous procedure
1 = Procedure by parameterized path
6 Bit6 Reserved
7 Bit7 Reserved
8 RefTyp Homing type selection
0 = Reference point approach
1 = On-the-fly homing
9 RefStDi Reference point approach start direction
0 = positive start direction
© Siemens AG 2019 All rights reserved
1.4.3.1 ZSW1
Table 1-6
Bit Abbreviation Description
0 RTS Ready to power up
1 RDY Ready for operation
2 IOp Drive is switched on (condition for selecting the operating mode of
the EPos)
3 Fault Active fault
4 NoOff2Act OFF2 not activated (partial condition for switching on)
5 NoOff3Act OFF3 not activated (partial condition for switching on)
6 PowInhbt Activation disable active
7 Alarm Alarm / warning active
8 NoFlwErr Following error within tolerance
9 LbCr Control required
10 TargPos Target position reached
11 RefPSet Reference point set
© Siemens AG 2019 All rights reserved
1.4.3.2 ZSW2
Table 1-7
Bit Abbreviation Description
0 ActDDSBit0 Drive data set Bit 0
1 ActDDSBit1 Drive data set Bit 1
2 ActDDSBit2 Drive data set Bit 2
3 ActDDSBit3 Drive data set Bit 3
4 ActDDSBit4 Drive data set Bit 4
5 CmdActRelBrk Release holding brake active
6 TrqContMode Torque-controlled operation
7 ParkAxisAct Parking axis selected
8 Bit8 Reserved
9 GlbTrgReq Global trigger request
10 PulsEn Pulses enabled
11 MotSwOverAct Motor data set switchover active
12 SlvZykBit0 Slave – sign of life bit 0
13 SlvZykBit1 Slave – sign of life bit 1
© Siemens AG 2019 All rights reserved
1.4.3.3 POS_ZSW1
Table 1-8
Bit Abbreviation Description
0 ActTrvBit0 Active traversing block bit 0
1 ActTrvBit1 Active traversing block bit 1
2 ActTrvBit2 Active traversing block bit 2
3 ActTrvBit3 Active traversing block bit 3
4 ActTrvBit4 Active traversing block bit 4
5 ActTrvBit5 Active traversing block bit 5
6 Bit6 Reserved
7 Bit7 Reserved
8 StpCamMinAct STOP cam minus active
9 StpCamPlsAct STOP cam plus active
10 JogAct Jog mode is active
11 RefAct Reference point mode active
12 FlyRefAct On-the-fly homing active
13 TrvBlAct Traversing blocks mode active
© Siemens AG 2019 All rights reserved
1.4.3.4 POS_ZSW2
Table 1-9
Bit Abbreviation Description
0 TrkModeAct Tracking mode active
1 VeloLimAct Speed limitation active
2 SetPStat Setpoint set
3 PrntMrkOut Print mark outside outer window
4 FWD Axis moves forward
5 BWD Axis moves backwards
6 SftSwMinAct Software limit switch minus actuated
7 SftSwPlsAct Software limit switch plus actuated
8 PosSmCam1 Position actual value <= Cam switch position 1
9 PosSmCam2 Position actual value <= Cam switch position 2
10 TrvOut1 Direct output 1 via traversing block
11 TrvOut2 Direct output 2 via traversing block
12 FxStpRd Fixed stop reached
13 FxStpTrRd Fixed stop clamping torque reached
© Siemens AG 2019 All rights reserved
Table 1-10
Error code Description
0x1C34 (7220) Guidance requested by PLC (STW1 bit 10) or control (ZSW1 bit 9) was
reset during a running movement.
0x1D1B (7451) Position monitoring responded:
The activation of the limit switches or STOP cams is requested despite
rotary axis or "SftSwMin" >= "SftSwPls" (in POS_STW2-Bit 14, 15).
The request is canceled at the same time, e.g. to avoid division by 0 or
sign errors.
The feedback of the actual values to the internal speed results in a
speed amount > 1.5 * "MaxSpeed", and the movement must be
terminated with quick stop.
0x1D1C (7452) The distance between the actual position scaled from
"Process.Gx_XIst" and the internal position is >=
"ContouringErrorDistance".
0x1D22 (7458) At the end of a homing run at the end of the normal range, the
reference point was not crossed (e.g. wrong direction specified in
POS_STW2-Bit 9).
© Siemens AG 2019 All rights reserved
0x1D28 (7464) Traversing block is inconsistent (the data of a requested motion are
invalid).
0x1D33 (7475) A negative relative positioning was tried, although the starting position
is already at the beginning or below the normal range.
0x1D34 (7476) A positive relative positioning was tried, although the starting position is
already at the end or above the normal range.
0x1D39 (7481) The internal position has gone below the normal range, e.g. after
changing "XIstLowerEndSwitch".
The error is only triggered once so that movements in the direction of
the normal range remain possible after acknowledgment and restart.
0x1D3A (7482) The internal position has gone above the normal range, e.g. after
changing "XIstUpperEndSwitch".
The error is only triggered once so that movements in the direction of
the normal range remain possible after acknowledgment and restart.
0x1D3B (7485) When requested to travel to the fixed stop, the movement was
completed without the criteria for reaching the fixed stop being met at
any time.
0x1D42 (7490) The enable (STW1 bit 0-3) has been canceled during a running motion,
but not during jogging or a normal stop, not even by fast stop or
coasting.
0x1D45 (7493) "XIST_A": Range overflow
0x0E12 (3602) "NIST_B": Raw value overflow
0x0E13 (3603) "NIST_B": Raw value undercut
0x0E14 (3604) Reference speed scaling error (reference speed <= 0.0)
0x0F02 (3842) Sign-of-life error
There are also the following messages, warnings and alarms taken from
"SINAMICS S120/S150 List Manual, 07/2018" which are displayed at output
WARN_CODE. These messages are canceled after the causes have been
eliminated by a subsequent rising edge of one of the STW1 bits 0-3, 6-9, 11 or 13.
Exceptions are:
• Warning 7457 ends when the combination of input signals is valid again,
unless after successful travel to fixed stop.
• Warning 7463 ends if not all bits 0-4 are set in STW1, ie if there is no enable or
"Discard traversing task" and external block change are thus no longer
possible. The warning will be interrupted during an intermediate stop.
• Warning 7479/7480 ends when followed by a traversing block, stopping or
standstill, as long as the target or stopping position is in the normal range, and
the deceleration did not need to be increased.
• A warning resulting from the limit switch handling ends if an error results from
the limit switch handling.
Table 1-11
Alarm code Description
0x1D1F (7455) The "MaxSpeed" speed causes the movement of more than ¼ of the
value range per SIMIT cycle of a rotary axis (parameterization error).
0x1D20 (7456) A movement with target speed > "MaxSpeed" is limited to this speed
when "MaxSpeed" is reached.
© Siemens AG 2019 All rights reserved
0x1D21 (7457) The combination of input signals is inadmissible (jogging, homing, etc.).
0x1D25 (7461) An absolute positioning was attempted although the system is not
homed.
0x1D26 (7462) The selected traversing block number (> "N_Trv" - 5) does not exist. No
movement can be triggered.
0x1D27 (7463) With continuation type "Continue external alarm", the external block
change was not requested in time.
0x1D29 (7465) For a continuation type other than "End", the entered traversing block
number is invalid for the continuation (> "N_Trv" - 5).
0x1D2D (7469) The target position of the traversing block is below the normal range.
0x1D2E (7470) The target position of the traversing block is above the normal range.
0x1D2F (7471) With a rotary axis, an initiated movement has an absolute target
position outside the module area, which is automatically converted.
0x1D30 (7472) Positioning type "absolute, only forward / reverse" is not possible (no
rotary axis, relative positioning).
0x1D35 (7477) The target position of an absolute positioning is below the normal range
and the current position.
0x1D36 (7478) The target position of an absolute positioning is above the normal
range and the current position.
0x1D37 (7479) The target position of a relative positioning with negative traverse path
was restricted to the lower end of the normal range, software limit
switch or STOP cam minus is approached.
0x1D38 (7480) The target position of a relative positioning with positive traverse path
was restricted to the upper end of the normal range, software limit
switch or STOP cam minus is approached.
0x1D3E (7486) An attempt was made to start a traversing block although STW1 bit 5 is
set to 0 (intermediate stop).
0x1D3F (7487) An attempt was made to start a traversing block although STW1 bit 4 is
set to 0 (discard motion job).
2 I/Os
Table 2-1
Input Description
STW1 Control word 1 from the PROFIdrive message frame
POS_STW1 Positioning control word 1 from the PROFIdrive message
frame
POS_STW2 Positioning control word 2 from the PROFIdrive message
frame
STW2 Control word 2 from the PROFIdrive message frame
OVERRIDE OVERRIDE from the PROFIdrive message frame
MDI_TARPOS Position setpoint with direct setpoint input (MDI) from the
PROFIdrive message frame
MDI_VELOCITY MDI velocity from the PROFIdrive message frame
MDI_ACC MDI acceleration value from the PROFIdrive message frame
MDI_DEC MDI deceleration value from the PROFIdrive message frame
USER_IN USER entry from the PROFIdrive message frame (user-
defined)
USER_Out USER input from external processing
NIst Velocity (raw value)
© Siemens AG 2019 All rights reserved
Table 2-2
Output Description
ZSW1 State word 1 from the PROFIdrive message frame
POS_ZSW1 Positioning state word 1 from the PROFIdrive message
frame
POS_ZSW2 Positioning state word 2 from the PROFIdrive message
frame
ZSW2 State word 2 from the PROFIdrive message frame
MELDW State word messages from the PROFIdrive message frame
XIST_A Actual position value (32 bit) from the PROFIdrive message
frame
NIST_B Velocity from the PROFIdrive message frame
WARN_CODE Number of the current warning from the PROFIdrive
message frame
FAULT_CODE Number of the current malfunction from the PROFIdrive
message frame
USER_OUT USER entry from the PROFIdrive message frame (user-
defined)
USER_In USER output for external processing
NSoll Setpoint velocity for external processing
XSoll Position setpoint for external processing
Drive Structure for interconnecting further PROFIdrive components
3 Parameters
Table 3-1
Parameters Description
N_Trv Enter the number of traversing blocks set up + 4 (for
jogging, homing, MDI).
G1_EncoderSystem Enter the type of encoder here
0: The sensor of the upstream PROFIdrive component is a
"SensorProcessRotatory".
1: The sensor of the upstream PROFIdrive component is a
"SensorProcessLinear".
MaxAcc Enter the maximum acceleration and deceleration here.
CoastDec Specify the deceleration for coasting here.
ReferenceAcceleration Enter the reference value for the acceleration here.
(0x4000 equivalent for "OVERRIDE", "MDI_ACC" and
"MDI_DEC")
ReferencePosition Enter the display or rotary axis range of "XIst" here.
HysteresisDistance Enter the tolerance range of "XIst" for "Target position
reached" here.
FollowingErrorDistance Enter the deviation of "XIst" for the tracking error here.
(≤ 0 = deactivation of tracking error detection)
© Siemens AG 2019 All rights reserved
4 Operating window
The operating window is divided into six areas due to its wide range of functions.
Figure 4-1
2 3 4 5
6
© Siemens AG 2019 All rights reserved
Table 4-1
No. Description Operating window
1. The current position and speed of the axis are 1
6
3. Position (XIst value) of cam switch 7
position 1. 8
• -1: Jog 1 5
6
• -2: Jog 2 7
8
•
9
-3: Homing approach 10
11
Bit 8-10:
Type of positioning:
• 0 (2, 4, 6): relative
• 1: absolute, fastest way, with on-the-
fly transition not necessarily the
shortest one
• 3: absolute, only forward
• 5: absolute, only backwards
• 7: absolute, shortest path
Bit 12-14:
Condition for advancing (continuation
type):
• 0 (6, 7): End (termination of the
current traversing block when the
target position has been reached. No
other traversing block)
• 1: Continue with stop
(The next traversing block is
executed when the target position is
reached and the machine is at a
standstill).
• 2: Continue on the fly
(The next traversing block is
activated at the brake application
point).
• 3: Continue externally on the fly
(Next traversing block with external
signal E: STW1-Bit 13; if the signal E
is missing it continues with
"Continue on the fly").
• 4: Continue external maintenance
4
2. Display of the current absolute target 5
position. 6
7
3. Display of the current velocity. 8
deceleration.
5. Type of positioning and continuation:
10
Bit 0-5:
Traversing block number for a possible
continuation
Bit 6, 7:
Entries for POS_ZSW2-Bit 10, 11 (direct
output 1, 2 active)
Bit 8-10:
Type of positioning:
• 0 (2, 4, 6): relative
• 1: absolute, fastest way, with on-the-
fly transition not necessarily the
shortest one
• 3: absolute, only forward
• 5: absolute, only backwards
• 7: absolute, shortest path
Bit 12-14:
Condition for advancing (continuation
type):
• 0 (6, 7): End (termination of the
current traversing block when the
target position has been reached. No
other traversing block)
• 1: Continue with stop
(The next traversing block is
Bit 2:
The target position of relative movements
is based on the stop position.
Bit 3:
The target position of relative movements
is based on the current position.
• The priority is Bit 3 > Bit 2 > Bit 0.
• Bit 0, 2, 3 = 0: The target position is
maintained.
Bit 4:
Introduction of a movement according to
the traversing block or MDI
Bit 5:
Jog 1
Bit 6:
Jog 2
Bit 7:
Jog, maintain velocity
Bit 8:
Homing approach
Bit 9:
Stop according to parameterized
deceleration
Bit 10:
Rapid stop / coast-out
• The priority is Bit 10 > Bit 9 > all
other bits
7. Sequence of motion types:
• 0: Standstill
• 1: same type of movement forwards
• 2: Acceleration forward
operating window.
1. Status bits of control word "STW1" (see
chapter 1.4.2.1)
2. Status bits of control word "ZSW1" (see 9 10 11 12 13
chapter 1.4.3.1)
3. Status bits of control word "STW2" (see
chapter 1.4.2.2)
4. Status bits of control word "ZSW2" (see
chapter 1.4.3.2)
5. Status bits of control word "POS_STW1"
(see chapter 1.4.2.3)
6. Status bits of control word "POS_ZSW1"
(see chapter 1.4.3.3)
7. Status bits of control word "POS_STW2"
(see chapter 1.4.2.4)
8. Status bits of control word "POS_ZSW1"
(see chapter 1.4.3.3)
9. Number of simulation cycles between the
last two changes of the received life sign
bits or 0 if no meaningful bit sequence
was detected or after a restart of the
simulation.
© Siemens AG 2019 All rights reserved
5 Engineering
The application example shows how to use the behavior model "EPOS_Tel111"
with the application example "SINAMIC S: Epos configuration with startdrive and
control with SINA_POS".
Note The application example and the corresponding application documentation are
available at the following link:
https://support.industry.siemens.com/cs/ww/en/view/98961635
To be able to use the application example with the behavior model EPOS_Tel111,
further steps have to be taken with the application example. The reason for this is
that it is currently not possible to perform a PLCSIM advanced coupling with an
integrated drive component from the hardware catalog. For this purpose, a drive
component must be used using a GSDML.
The use of integrated drive components from the hardware catalog is planned for
one of the upcoming TIA Portal versions.
The adapted application example describes the interaction of the SINA_POS with
the behavior model. This document describes the reaction of the behavior model
"EPOS_Tel111" when using the individual operating modes on the SINA_POS.
Note The description of the individual operating modes of the SINA_POS can be
found in chapter 5.2 "Operating mode type selection of the Epos with
SINA_POS" of the manual "Blocks for controlling the SINAMICS with SIMATIC
© Siemens AG 2019 All rights reserved
5.1 Configuration
5.1.1 Configuration of the SINAMICS drive using GSDML
With the GSDML variant of a SINAMICS drive, you can load the configuration of
the SINAMICS S120 station used into PLCSIM Advanced and establish a link to
SIMIT. The following step-by-step procedure describes how this must be done.
Table 5-1
No. Action Note
1. Add a SINAMICS S120/S150 CU320-2
PN V5.1 (GSDML-V2.32-SIEMENS-
SINAMICS_S_CU3X0-20171107.XML)
to the "Network view" of your TIA
Portal V15 project.
The following step table describes the necessary procedure for coupling the
behavior model "EPOS_Tel111" via a PLCSIM advanced coupling with the GSDML
variant of the SINAMICS S120 station.
Table 5-2
No. Action Note
1. In order to better assign the
individual inputs and outputs in the
PLCSIM Advanced coupling, these
should be created according to
Message frame format as a PLC
tag.
6. 1. Create a chart.
2. Select the behavior model
"EPOS_Tel111" from the
component library under "Own
components and drag it into the
chart via drag & drop.
Table 5-3
No. Action Note
1. 1. Select the component to display
its parametrization.
2. Select the "Parameters" menu.
© Siemens AG 2019 All rights reserved
Table 5-4
No. SIMIT Startdrive
p2544 HysteresisDistance LR Positioning window
p2546 FollowingErrorDistance LR dynamic following error monitoring tolerance
p2547 PosSmCam[0] LR cam switch position 1
p2548 PosSmCam[1] LR cam switch position 2
p2571 MaxSpeed EPOS maximum speed
5.3 Operation
5.3.1 Relative positioning
The operating mode " Relative positioning " enables the position-controlled
movement of travel paths via the integrated position controller of the behavior
model "EPOS_Tel111".
Table 5-5
No. Action Note
1. 1. Select the created chart in
SIMIT.
2. Start the SIMIT simulation.
When the simulation is started, an
instance with the coupling
parameters is automatically created
at PLCSIM Advanced.
project
2. Start the HMI simulation.
If you have started the SIMIT
simulation for the first time, you must
load the hardware configuration and
the user program of the TIA Portal
V15-Projektes in the instance created
under PLCSIM Advanced. The data
is then stored in the memory of the
instance under PLCSIM Advanced.
Table 5-6
No. Action Note
1. 1. Select the created chart in SIMIT.
2. Start the SIMIT simulation.
When the simulation is started, an
instance with the coupling parameters
is automatically created at PLCSIM
Advanced.
Table 5-7
No. Action Note
1. 1. Select the created chart in SIMIT.
2. Start the SIMIT simulation.
When the simulation is started, an
instance with the coupling parameters is
automatically created at PLCSIM
Advanced.
The operating mode "Homing - Homing movement" enables the axis to perform a
homing movement in positive or negative direction with a defined speed in homing
mode.
Table 5-8
No. Action Note
1. 1. Select the created chart in SIMIT.
2. Start the SIMIT simulation.
When the simulation is started, an
instance with the coupling parameters is
automatically created at PLCSIM
Advanced.
3 2
been reached, the error message
"8401" is displayed and the display
shows "Error".
The operating mode "Homing - Set reference point" allows the axis to be
referenced at any position.
Table 5-9
No. Action Note
1. 1. Select the created chart in SIMIT.
2. Start the SIMIT simulation.
When the simulation is started, an
instance with the coupling parameters
is automatically created at PLCSIM
Advanced.
The operating mode " Traversing blocks " enables the retraction of stored settings.
Table 5-10
No. Action Note
1. 1. Select the created chart in SIMIT.
2. Start the SIMIT simulation.
When the simulation is started, an
instance with the coupling parameters
is automatically created at PLCSIM
Advanced.
position.
2. The stored value of the "Position"
parameter from traversing block
"1" is added to the current position
and displayed as the target
position.
3. The velocity assumes a positive
value because the movement is
carried out in the reverse
direction.
© Siemens AG 2019 All rights reserved
5.3.7 Jogging
Table 5-11
No. Action Note
1. Assign parameters to the following
values:
1. DefaultSpeed = 24.0
2. DefaultAcc = 0.2
3. DefaultDec = 0.25
© Siemens AG 2019 All rights reserved
Table 5-12
No. Action Note
1. Assign parameters to the following
values:
1. DefaultIncrement = 1200.0
2. DefaultSpeed = 36.0
3. DefaultAcc = 0.3
4. DefaultDec = 0.36
© Siemens AG 2019 All rights reserved
The "Homing on the fly" mode of operation allows the drive to be referenced during
operation.
Table 5-13
No. Action Note
1. Assign a parameter to the following
value:
• FollowingErrorDistance = 0.1
1 2
6 Appendix
6.1 Service and support
Industry Online Support
Do you have any questions or need assistance?
Siemens Industry Online Support offers round the clock access to our entire
service and support know-how and portfolio.
The Industry Online Support is the central address for information about our
products, solutions and services.
Product information, manuals, downloads, FAQs, application examples and videos
– all information is accessible with just a few mouse clicks:
support.industry.siemens.com
Technical Support
The Technical Support of Siemens Industry provides you fast and competent
support regarding all technical queries with numerous tailor-made offers
– ranging from basic support to individual support contracts. Please send queries
to Technical Support via Web form:
www.siemens.com/industry/supportrequest
© Siemens AG 2019 All rights reserved
Service offer
Our range of services includes the following:
• Plant data services
• Spare parts services
• Repair services
• On-site and maintenance services
• Retrofitting and modernization services
• Service programs and contracts
You can find detailed information on our range of services in the service catalog
web page:
support.industry.siemens.com/cs/sc
6.3 Abbreviations
PZD Process data
PLC Programmable logic controller
© Siemens AG 2019 All rights reserved