! Note: The Walk Test task should only be performed by advanced operators.
Alternative Weekly Test

To carry out a statutory weekly fire alarm test, follow the steps listed in the “Fire Alarm
Event” simulation (page 10) of this course. Before carrying out a fire alarm test, ensure
you carry out the following:

1. Inform the Remote alarm receiving centre if the system is connected.


2. Inform occupants of the building of the impending test.
3. Take care to isolate any plant shutdown circuits if these are likely to effect the
normal operation of any process and/or in itself create a hazard.

Note: The test can be conducted by activating a call point using the supplied test
key. Removal of the test key will reset the call point allowing the system to be reset
on completion of the test. Revisit steps 1, 2 and 3 above if any of these operations
has been implemented.

Walk Test
1. To select Walk Test, enter the Service Menu by pressing “7” on the keypad.
2. Press “1” (Walk Test) on the keypad.
3. Using the F3/F4 (-/+) keys, select the Area. Press F3 once; press F4 twice.
4. Press F2 (>>) to move the cursor to highlight the Zone Number.
5. To enter the Zone Number, press 001 on the keypad.
6. Press F2 (>>) to move the cursor to highlight the Device Type.
7. Using the F3/F4 keys select the Device Type (Detectors). Press F4 once.
8. Press F2 (>>) to move the cursor to highlight the Loop.
9. Using the F3/F4 (-/+) keys select the Loop (A).
10. Press F2 (>>) to move the cursor to highlight the Test Mode.
11. Using the F3/F4 (-/+) keys select Auto or Manual. Let’s select Manual for physical
testing. Press F4 twice.
12. Press F2 (>>) to move the cursor to highlight the Multisensor Device to test only
a part of the device or the complete device. Note: testing of fire detectors is best
left to a trained operator and unless training has been given, this function should
not be tested.
13. Using the F3/F4 (-/+) keys select Full. Press F4 once.
14. Once your selection is complete, press F5 (Start) to start your test. The L-C-D
display will show the number of elements that are to be tested.
15. If all devices haven’t responded before ending the test, use the F1 key (Back) to
return to the Main Menu. Press F1 twice.

Tyco Safety Products-Europe


MX Online Training Simulation Steps 2-2

16. Select option “6” from the Main Menu, View/Print Data, and then option “2” to
display Points Untested or Failed.
17. Press F1 (Back) to return to the Main Menu.
18. Return to the Walk Test menu by entering the Service Menu. Press “7” on the
keypad.
19. Press End (F5) to end your test.