Sie sind auf Seite 1von 168

STATE OF KUWAIT

MINISTRY OF ELECTRICITY AND WATER -


KUWAIT
SUPPLY AND INSTALLATION OF
SAAD AL ABDULLA ‘A’, ‘B’, ‘C’ & ‘D’ 132/11kV
SUBSTATION
Contract No. ME/EW/C/3377-2005/2006

OPERATION & MAINTENANCE


MANUAL

BATTERIES AND CHARGERS


VOLUME V

MITSUBISHI ELECTRIC
CORPORATION
TOKYO, JAPAN
MINISTRY OF ELECTRICITY AND WATER - KUWAIT
SUPPLY AND INSTALLATION OF
SAAD AL ABDULLA ‘A’, ‘B’, ‘C’ & ‘D’ 132/11kV SUBSTATION
Contract No. ME/EW/C/3377-2005/2006

Operational and Maintenance Manuals

Contents

Volumes I to VIII

Volume I – 145kV Gas Insulated Switchgear and Cranes

Section 1 – 145kV Gas Insulated Switchgear

Section 2 – Cranes

Volume II – 250kVA Transformers, Neutral Earthing Resistors,


Neutral Isolator Cabinets & Ancillary Electrical Equipment

Section 1 – 250kVA 11/0.433kV Transformers

Section 2 – Neutral Earthing Resistors & Neutral Isolator Cabinets

Section 3 – Low Voltage 415V AC Distribution Boards

Section 4 – Power Cables

Section 5 - Control, Relay, Pilot Marshalling, Telemetry Terminal Transfer panels

Volume III – 30MVA Transformers

30MVA 132/11.5kV Transformers

Volume IV – 11kV Metal clad Switchgear

11kV Metal clad Switchgear

☞Volume V – Batteries and Chargers


Section 1 – Control system - Battery, Charger and DC distribution board

Section 2 – Trip system - Battery, Charger and DC distribution board

Section 3 – Emergency system – Battery and Charger

-1-
MINISTRY OF ELECTRICITY AND WATER - KUWAIT
SUPPLY AND INSTALLATION OF
SAAD AL ABDULLA ‘A’, ‘B’, ‘C’ & ‘D’ 132/11kV SUBSTATION
Contract No. ME/EW/C/3377-2005/2006

Volume VI – Protection and Control Relays

Part 1

AREVA – Biased differential transformer protection - MICOM P631

Part 2

Section 1 – SIEMENS – Busbar Protection – SIPROTEC 7SS60

Section 2 – SIEMENS – Line Differential Protection – SIPROTEC 7SD610

Part 3

AREVA – Non Directional Overcurrent & Earth Fault Relay


MICOM P120 & P121

Part 4

Section 1 – AREVA – Directional Overcurrent & Earth Fault Relay


MICOM P127

Section 2 – AREVA – Breaker Failure Protection MICOM P821

Part 5

Section 1 – REYROLLE – Earth Fault Relay ARGUS-1

Section 2 – REYROLLE – Line Differential Protection SOLKOR-N

Section 3 – REYROLLE – Line Differential Protection SOLKOR-Rf

Section 4 – REYROLLE – RVM Voltage Regulation Relay SUPERTAPP

Section 5 – AREVA – Test Blocks MMLG 01

Section 6 – FUJI – Fault Indicators

Section 7 – FUJI – Semaphore Relays

Section 8 – TECSYSTEM – Temperature Monitoring Relay T-119

Section 9 – ENERDIS – Transducers TRIAD

Section 10 – CROMPTON – Meters

-2-
MINISTRY OF ELECTRICITY AND WATER - KUWAIT
SUPPLY AND INSTALLATION OF
SAAD AL ABDULLA ‘A’, ‘B’, ‘C’ & ‘D’ 132/11kV SUBSTATION
Contract No. ME/EW/C/3377-2005/2006

Volume VII - Intertrip Equipment

Intertrip Equipment – NSD570

Volume VIII - Fire Fighting

Section 1 – Water Fire Fighting System

Section 2 – Mobile Fire Extinguishers

Section 3– Fire Alarm System

Section 4– Fire Alarm and Detection Panels

-3-
INSTALLATION, OPERATING AND MAINTENANCE MANUAL

220V DC CONTROL BATTERY CHARGER


6CV220/63

INSTALLATION,
OPERATING AND
MAINTENANCE
MANUAL
DOCUMENT NO. : J2956BU01 REV 0

For

MITSUBISHI ELECTRIC
SAAD AL ABDULLA ‘A’, ‘B’, ‘C’ & ‘D’ SUBSTATIONS
AND EXTENSION OF UM AL-AISH ‘M’ SUBSTATION

25/07/07 J2956BU01 REV 0.doc 1


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 1 __________________________________________________________________ 4
EXPLANATION OF HAZARD INFORMATION ------------------------------------------------------------------------------- 4
HEALTH AND SAFETY PRECAUTIONS ------------------------------------------------------------------------------------- 5
SECTION 2 __________________________________________________________________ 6
INSTALLATION------------------------------------------------------------------------------------------------------------------- 6
UNPACKING THE EQUIPMENT ------------------------------------------------------------------------------------------ 6
USE OF FORK LIFT TRUCK FOR LIFTING THE EQUIPMENT ----------------------------------------------------- 6
LOCATION OF THE EQUIPMENT---------------------------------------------------------------------------------------- 6
CONNECTING THE EQUIPMENT---------------------------------------------------------------------------------------- 7
GENERAL ..................................................................................................................................................... 7
PRESERVATION PROCEDURE (GENERAL)--------------------------------------------------------------------------- 8
RECOMMENDATIONS FOR 24 MONTH STORAGE AND PRESERVATION -------------------------------------- 9
EMC HEAVY INDUSTRIAL ENVIRONMENT---------------------------------------------------------------------------- 9
SECTION 3 __________________________________________________________________ 10
EQUIPMENT DETAILS---------------------------------------------------------------------------------------------------------- 10
SECTION 4 __________________________________________________________________ 11
DESCRIPTION OF OPERATION ---------------------------------------------------------------------------------------------- 11
THE SYSTEM---------------------------------------------------------------------------------------------------------------- 11
6CV CHARGER DESCRIPTION OF OPERATION --------------------------------------------------------------------- 12
THE INTERFACE MODULE......................................................................................................................... 13
THE CONTROL AND DRIVE MODULES.................................................................................................... 13
6CV CONTROL MODULE - ARRANGEMENT............................................................................................ 14
6CV DRIVE MODULE - ARRANGEMENT ................................................................................................... 14
6CV INTERFACE MODULE - ARRANGEMENT.......................................................................................... 15
DESCRIPTION OF THE CONTROL MODULE’S LED’S AND POTENTIOMETERS------------------------------- 16
VOLTAGE DETECTION MODULES (VDVD)--------------------------------------------------------------------------------- 17
SPECIFICATION ------------------------------------------------------------------------------------------------------------ 17
VDVD BOARD ARRANGEMENT ................................................................................................................. 18
BLOCK DIAGRAM ........................................................................................................................................ 18
DESCRIPTION OF BLOCK DIAGRAM........................................................................................................ 18
SETTING/CHECKING INSTRUCTIONS --------------------------------------------------------------------------------- 19
CHECKING THE OPERATING LEVELS ...................................................................................................... 19
SETTING THE VOLTAGE PARAMETERS - WHERE SET (TRIP) VALUES ONLY ARE REQUIRED ....... 20
SETTING THE VOLTAGE PARAMETERS - WHERE BOTH SET AND RESET VALUES ARE
REQUIRED................................................................................................................................................... 20
SETTING THE TIMER.................................................................................................................................. 20
DAU DC ALARM MODULE ----------------------------------------------------------------------------------------------------- 21
OPERATING MODES------------------------------------------------------------------------------------------------------- 21
FUNCTIONS AND FEATURES ------------------------------------------------------------------------------------------- 21
INSTRUMENTATION ------------------------------------------------------------------------------------------------------- 21
LOCAL AND REMOTE ALARMS AND INDICATIONS ----------------------------------------------------------------- 21
DAU SET UP PAGES ------------------------------------------------------------------------------------------------------- 24
EQUALISE SELECTION ---------------------------------------------------------------------------------------------------- 26
FLOAT SELECTION -------------------------------------------------------------------------------------------------------- 26
BATTERY TEST ------------------------------------------------------------------------------------------------------------- 26
BATTERY DISCHARGE TEST PARAMETERS. ------------------------------------------------------------------------ 27
BATTERY HIGH IMPEDANCE ALARM ---------------------------------------------------------------------------------- 27
SETTING UP THE HIGH IMPEDANCE ALARM ------------------------------------------------------------------------ 27
SET UP PAGE SELECTION ----------------------------------------------------------------------------------------------- 27
ALARM SET UP ------------------------------------------------------------------------------------------------------------- 30

25/07/07 J2956BU01 REV 0.doc 2


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

INTERFACE MODULE ----------------------------------------------------------------------------------------------------- 33


8 RELAY EXPANSION MODULE------------------------------------------------------------------------------------------ 34
SECTION 5 __________________________________________________________________ 35
DESCRIPTION OF CONTROLS AND INDICATIONS ---------------------------------------------------------------------- 35
SECTION 6 __________________________________________________________________ 39
START-UP & SHUTDOWN ----------------------------------------------------------------------------------------------------- 39
PRE-START CHECKS------------------------------------------------------------------------------------------------------ 39
COMMISSIONING PROCEDURE----------------------------------------------------------------------------------------- 39
START-UP PROCEDURE ------------------------------------------------------------------------------------------------- 40
NORMAL OPERATION ----------------------------------------------------------------------------------------------------- 41
SHUTDOWN PROCEDURE ----------------------------------------------------------------------------------------------- 41
SECTION 7 __________________________________________________________________ 42
FAULT FINDING INSTRUCTIONS-------------------------------------------------------------------------------------------- 42
PROCEDURES -------------------------------------------------------------------------------------------------------------- 42
TESTING SEMI-CONDUCTORS------------------------------------------------------------------------------------------ 42
STUD MOUNTING SEMI-CONDUCTORS ------------------------------------------------------------------------------ 42
TEST EQUIPMENT REQUIRED ON-SITE------------------------------------------------------------------------------- 43
SETTING-UP INSTRUCTIONS ------------------------------------------------------------------------------------------- 43
6CV CHARGER CONTROLLER.................................................................................................................. 43
SOLUTIONS TO COMMON FAULTS------------------------------------------------------------------------------------- 44
HIGH OUTPUT............................................................................................................................................. 45
LOW OUTPUT.............................................................................................................................................. 45
CHARGER FAULT FINDING GUIDE ........................................................................................................... 46
STACK FAN FAILURES ............................................................................................................................... 46
SECTION 8 __________________________________________________________________ 47
MAINTENANCE INSTRUCTIONS--------------------------------------------------------------------------------------------- 47
TORQUE SETTINGS ------------------------------------------------------------------------------------------------------- 47
SECTION 9 __________________________________________________________________ 48
DRAWING FILE------------------------------------------------------------------------------------------------------------------- 48

25/07/07 J2956BU01 REV 0.doc 3


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 1

EXPLANATION OF HAZARD INFORMATION

To clarify certain points within this manual to ensure proper and safe operation of the equipment,
the following emphasis is used.

Highlights an essential element of a procedure to ensure correctness.


NOTE:-

Highlights an essential element of a procedure for installation or maintenance to


NOTE:- ensure correctness.

Indicates a procedure or practice which, if not strictly observed, could result in


CAUTION:- damage or destruction of equipment.

Indicates a procedure or practice, which could result in injury to personnel or


WARNING:- loss of life if not followed correctly.


Erskine Systems own the copyright to this manual, which cannot be copied,
reproduced or disclosed to a third party without prior written permission.

25/07/07 J2956BU01 REV 0.doc 4


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

HEALTH AND SAFETY PRECAUTIONS

• An authorised, qualified technician reconnecting power.


should only attempt installation, testing,
fault location and repair. • The above instructions must also be
followed before any such connection is
• This equipment carries dangerous modified or renewed.
voltages and stored electrical energy.

• Removal of shrouding can reveal NOTE:- Adjustments should only be


dangerous voltages and/or high carried out with non-conducting tools,
temperatures. Erskine Systems taking care not to touch any item carrying
accepts no responsibility for the safety electricity whilst doing so.
of personnel and property due to any
actions after their removal. • Reference should also be made to the
sections dealing with installation and
• Before touching, or bringing metal fault finding procedures in the
objects, e.g. tools, metal bracelets, equipment manual before installing and
rings or necklaces into contact with making external connections.
items carrying electricity, carry out the
following instructions: • If batteries are supplied as part of the
system, please refer to the battery
• Isolate the AC mains supply external to manufacturers handbook that is
the equipment. Isolate the battery and supplied.
external load from the equipment.
• As under certain conditions, batteries
• Hazardous energy levels may be give off hydrogen gas, care must be
present inside the equipment. Allow DC taken to prevent any naked flames,
filter capacitors to discharge for a cigarettes etc. from igniting it. It is
minimum of 20 seconds, before advisable to prohibit all smoking from
removing any covers. any area or room in which the battery is
situated.
• Discharge all RFI suppression circuits
as above. • Battery electrolyte is corrosive and if
spilt or splashed on equipment or
person, immediate action should be
CAUTION!:-Do not short circuit taken as indicated in the battery
capacitor terminals. handbook.

• The above instructions must always be • When handling batteries, wear


followed before making any protective clothing to protect eyes and
adjustments, and also before making exposed skin.
any electrical connections to any part of
the equipment for the purpose of • EMC cannot be guaranteed if the
servicing. Such connections should system is operated with the doors open
always be checked for safety before and/or panels removed

25/07/07 J2956BU01 REV 0.doc 5


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 2

INSTALLATION

UNPACKING THE EQUIPMENT

1. Unpack the equipment and carefully check for any damage which may have occurred during
transit. The equipment must remain upright at all times.

2. Check against the accompanying packing/delivery note to determine whether any part of the
consignment is missing.

3. Any returnable packing cases should be returned to the address on the cases.

4. Report any damage or losses immediately. Refer to Erskine Systems standard conditions of
sale.

USE OF FORK LIFT TRUCK FOR LIFTING THE EQUIPMENT

1. To avoid possible damage (e.g. scratches) to the equipment, first cover the forks with rubber
mats or other suitable material.

2. The forks should then be slotted under the equipment cubicles so as to ensure even weight
distribution - also it is important to ensure the forks reach across to the rear of the cubicle.

LOCATION OF THE EQUIPMENT

1. As the equipment relies on natural convection for cooling purposes, it is important that the
enclosures are sited in a position with a free flow of air. This also applies to equipment fitted
with cooling fans.

2. Do not locate the equipment or position other equipment against it, such that the natural
ventilation paths are blocked or restricted.

3. Do not locate the equipment in an area that has an ambient temperature above the maximum
allowed for. Equipment unless specifically stated shall not be installed in a hazardous area.

4. Equipment unless specifically stated shall not be installed in a mobile environment or a


position subject to vibration.

5. Floor standing cubicles are designed to be bolted to the floor using foundation bolts. Position
the cubicles and mark the floor - remove cubicles and drill the floor for the bolts. The cubicles
can then be placed in position and secured.

6. When batteries are installed ensure that the ambient temperature is suitable for type of cells
used and also adequate number of air changes per hour to prevent battery gas build up.

NOTE: Should any cabinet modifications be carried out during installation, it is necessary to ensure
that all swarf be removed from within the enclosure to prevent any electrical faults occurring.

25/07/07 J2956BU01 REV 0.doc 6


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

CONNECTING THE EQUIPMENT

1. The following cable should be used, to maintain the EMC performance of the equipment.
XLPE insulated to BS5467 or equivalent (BS6724 for low smoke and fume cable) for:-
• Mains Input
• DC Load Output
• Battery Cables
• Alarm Cables

2. Cables shall be steel wire armoured and/or screened. The wire armour or screen of the cable
must be bonded to the gland plates at the cable entry points using a cable gland and bonded
at the opposite end to a local earth path.

Alarm Contacts - BS5308 Part 2. Conductors may be collectively screened.

3. The above sets of cables should be separated from each other by a minimum of 250mm to
minimise noise coupling. The DC load output and battery cables may be routed together.

4. All the above sets of cables must be segregated from other cables at the installation site and
any other sources of electrical noise by a minimum of 250mm.

GENERAL
1. The equipment should first be checked to ensure that any connections which may have
become loose during transit are tightened.

2. Ensure that the supply is suitably rated. Ensure that any loads to be connected are not in
excess of the capability of the equipment.

3. Cable entry is indicated on the appropriate Arrangement Drawing and is via gland plates at
the bottom of the cubicles. The gland plates, which are supplied un-drillled, should be drilled
on-site for the compression glands and/or grommets to be used.

5. Connect an earth connection to the main earth stud provided. Ensure that the gland plate
earth cable is refitted after removal.

6. Connect the AC mains supply to the terminal block, making sure to connect to the input
voltage that corresponds with that of the mains supply. Phase rotation must be observed on
three phase systems.

NOTE:- The customer earth connection shall be adequately sized to the latest edition of the I.E.E.
wiring regulations or local equivalent and be terminated an a ring type crimp fixed utilising a spring
washer to reduce the chance of the connection becoming loose.

7. Connect all outgoing connections to the terminals provided. Connect any alarm connections
to the terminals provided.

NOTE:- When making connections, ensure polarity is correct and refer to the circuit diagram
supplied with the equipment.

25/07/07 J2956BU01 REV 0.doc 7


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

PRESERVATION PROCEDURE (GENERAL)

Generally, common sense prevails when handling and storing spare parts and goods for the
power supply systems.

Goods should be stored in an environment and manner so as to minimise any risk of physical
and climatic damage.

To ensure this the following points should be observed.

All meters should remain in the polystyrene package provided, avoiding moisture and
physical disturbances.

Special care should be taken when handling lamps due to their delicacy.

PCB’s (Static sensitive). - Special precautions must be taken when using and handling
electrostatic devices. If appropriate precautions are not taken, then it is likely that the
device will be seriously damaged or destroyed.

• New or spare PCB's will arrive with electrostatic protective packaging (conductive anti-static
bag). Never remove the board from the package until it is required. Do not stack the PCB's
during storage.

• When replacing a static sensitive PCB observe the following procedure:

• When removed from the anti-static bag, place and connect into the complete equipment
immediately.

• Insert PCB's in anti-static bag immediately on removal from the complete equipment, even if
deemed faulty. (A fault caused by static can disguise the original fault.)

• Do not carry any PCB's without anti-static bags.

• When dealing with PCB's, avoid using nylon clothing, particularly in dry and frosty conditions.

• Simultaneously touch the metal frame of the complete equipment (preferably a bare earth
connection) with one hand and the conductive packaging with the other hand to discharge any
static before fitting.

25/07/07 J2956BU01 REV 0.doc 8


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

RECOMMENDATIONS FOR 24 MONTH STORAGE AND PRESERVATION

Equipment must be packed in sealed wooden crates with desiccant and stored in a covered
warehouse such that equipment’s are protected from direct sunlight, rain, corrosive atmospheres,
flood water and extremes of climate.

Storage temperature range -30oC to +70oC.

(Temperature excursions to -40oC are permitted providing the average temperature is not less
than -30oC, over a 24 hour period.)

Please note that these equipment’s above are NOT suitable for stacking.

EMC HEAVY INDUSTRIAL ENVIRONMENT

The equipment is suitable for use only in the following environment:-

• Heavy industrial type environments where the product is intended to be connected to a power
network supplied from a high or medium voltage transformer dedicated for the supply of an
installation feeding a manufacturing or similar plant.

Therefore the equipment complies to the following European standards:-

• EN50081-2 : Emissions : Heavy Industrial

• EN50082-2 : Immunity : Heavy Industrial

It is advisory that equipment sharing the same electromagnetic environment as Erskine products
should comply with the standards as stated above.

25/07/07 J2956BU01 REV 0.doc 9


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 3

EQUIPMENT DETAILS

CHARGER 6CV220/63
Input Supply 415 Volts 50 Hz 3 Phase 4 Wire AC Mains
Nominal Output 220 Volts @ 63 Amps
Float 240.8 Volts / 55 Amps
Equalise 258.0 Volts / 55 Amps
Commissioning 283.8 Volts / 33 Amps
CEMF Diodes 25 at 25 Amps in 1 stage
Output Voltage Range 242 Vmax, 198.0 Vmin from 5 to 100% load
Earthing Negative Float

6CV SETTINGS
Mains Low Volts 332.0 V
Mains High Volts 498.0 V
DC High Volts DISABLE

BATTERY Nicad MC165P


Configured 172 cells in series

CUBICLE FSZ2 & FS19


Cable Entry Bottom
Ingress Protection IP41
Paint Finish RAL 7032 Semi-Gloss

ALARMS AND INDICATIONS

ALARM SETTING TIME REMOTE LOCAL COMMON


Common - - SPCO DAU -
CEMF Diode Fail 245.0 V 10 sec Common DAU -
Fire Response - - Yes Red -
Fuse Trip - - Common DAU 3
Breaker Open - - Common DAU -

25/07/07 J2956BU01 REV 0.doc 10


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 4

DESCRIPTION OF OPERATION

THE SYSTEM

The system supplied comprises of the following elements:

THE CHARGER - One off current limited, constant voltage type charger utilising the thyristor
phase control method of regulation. This is 100% rated to supply the load and its associated
battery. The charger supplies the load and provides a recharge current for the batteries. In the
event of a mains failure, the batteries will continue to support the load for the required standby
time.

THE BATTERIES - The batteries are recharged by the charger. They consist of 172 off NiCad
cells and are designed to support the load for the required standby time.

THE ALARMS - The charger is fitted with various alarms that are provided to enable monitoring
of the charger operation and the battery condition. The DAU Alarm Module is detailed later in this
manual. The main alarms fitted are:-

AC SUPPLY FAIL
CHARGER FAIL
LOW VOLTS
HIGH VOLTS
HIGH VOLTS TRIP
EARTH FAULT
CEMF DIODE FAIL
FUSE TRIP
FIRE RESPONSE INDICATOR
BREAKER OPEN

25/07/07 J2956BU01 REV 0.doc 11


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

6CV CHARGER DESCRIPTION OF OPERATION

The three phase and neutral mains supply is first transformed via an isolating transformer into a
suitable AC level for conversion into DC.

Regulation and rectification are provided by a fully controlled thyristor bridge. The bridge is
controlled via three modules: The Control Module, the Interface Module and the Drive Module.

The thyristors conduct in the forward direction in a similar manner to diodes, but only after a
positive triggering signal with respect to the anode is applied to the gate. Once triggered the
thyristor will continue to conduct for the rest of the half cycle. It is therefore possible to control
the mean output voltage of the bridge by controlling the instant in every half cycle at which the
gate pulses are applied.

Any rise in output voltage causes the firing pulses to be applied later in the cycle to decrease the
output voltage. Conversely, if there is a fall in output voltage the pulses will be applied earlier in
the cycle to increase it, thus a constant output voltage is maintained.

During normal operation the current circuit senses the output via a shunt. If this increases
beyond a pre-determined level, the current limit circuit will begin retarding the control pulses
accordingly to maintain the set current, and consequently reduce the voltage.

The thyristor stack relies on a fan circuit to protect the stack from overheating as indicated in the
diagram below.

F4
A1

TS1 (90oC)
F5
FAN2 FAN1

A4

A2
TS2 (100oC)

A5

A6

The above circuit shows the operation of the stack fan failure circuitry. Fan 1 is permanently on,
Fan 2 will only operate when the temperature exceeds 90oC as dictated by thermal switch TS1.
TS2 will initiate the shutdown signal to the control card if the temperature exceeds 100oC.
Terminals A2 and A4 are utilised for fan fail sensing to remote contacts and/or indication.

25/07/07 J2956BU01 REV 0.doc 12


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

THE INTERFACE MODULE


This contains all the high voltage components, all hardwired connections into the charger system
and ribbon cable connection to the control module.

The module provides:

• DC Power Supply for the control module


• Synchronisation input for the Control Module
• Earth Mode Selection via links
• Single Pole change-over contacts for remote indication of control module status.

Positive or negative earth modes are selectable via links LNK1-LNK4. The earth mode is factory
pre-set for the equipment supplied and must NOT be altered on site. Check the equipment
Circuit Diagram to determine the correct earth mode if it is suspected this may have been
tampered with. If the equipment is of a floating earth system, no modification of the board is
necessary.

THE CONTROL AND DRIVE MODULES


The function of the Control Module is to provide phase controlled firing signals to the Power
Thyristors, correctly positioned to maintain the power output required for voltage and current
regulation.

The Drive Module converts the Phase Control outputs from the Control Module into isolated drive
signals for the thyristors.

The Control Module provides:

• Differential voltage and current control.


• Soft-start facility. This prevents excessive surge when switched on.
• Three independent levels of voltage and current; i.e. Commission, Float and Equalise.
• Droop current share facility - selectable via link.
• Automatic shutdown and protection facilities.

The following conditions will cause the charger to shut-down. In each case, once the condition
has cleared the charger will re-start under soft-start control.

• If the charger output current exceeds the peak detection level.


• If an external shutdown input is applied.
• If the charger output voltage exceeds the high voltage trip level and remains high for
an adjustable timer period (selectable via links). An external inhibit input will override
this facility.
• If the average Mains Voltage goes out of limits.
• If there is an AC phase fail.

If the thyristor stack temperature exceeds a trip point, the charger output current is limited to a
pre-set level.

The charger will be prevented from starting up on negative phase rotation supplies.

25/07/07 J2956BU01 REV 0.doc 13


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

6CV CONTROL MODULE - ARRANGEMENT

CON 2 CON1
DC.HV BAL.1 BAL.2

HV RESET
HV NTC CAL
NC
RSD
PR

HL
V.STAB
HT
PHASE FAIL

190mm
DROOP
CON 5
VC1 VC2 VC3 CL1 CL2 CL3
CL

VC2

VC3 ACLV ACHV

CON5

350mm

6CV DRIVE MODULE - ARRANGEMENT

CON 1
CON 3

CON 4

CON 5

190mm

CON 6

CON 7
T7

CON 8
F2 F1

CON 2

177mm

25/07/07 J2956BU01 REV 0.doc 14


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

6CV INTERFACE MODULE - ARRANGEMENT

CON 10 CON 7

T1

244mm
T4
T2

T3

F1 F2 F3

152mm

25/07/07 J2956BU01 REV 0.doc 15


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

DESCRIPTION OF THE CONTROL MODULE’S LED’S AND POTENTIOMETERS

LED / POTENTIOMETER DESCRIPTION


‘HV’ LED This LED indicates that the DC high voltage level has been reached.
The charger will automatically shutdown on this fault condition.
When the fault has cleared the charger will automatically restart.
‘NC’ LED This LED indicates that a fault has occurred with the NTC probe
(where fitted). The fault should be rectified as soon as possible to
ensure correct charging of the battery under varying temperatures.
‘PR’ LED This LED indicates that the phase rotation is incorrect. The correct
phase rotation should be made to enable the correct functioning of
the charger system.
‘HL’ LED This LED indicates that the AC voltage has become high or low by
±20% of the input voltage. The charger will automatically shutdown if
this fault condition occurs.
When the fault has cleared the charger will automatically restart.
‘VC2’ LED This LED indicates that the charger is operating in the ‘Boost’ mode.
‘VC3’ LED This LED indicates that the charger is operating in the ‘Commission’
mode.
‘CL’ LED This LED indicates the charger is in ‘Current Limit’.
‘HT’ LED This LED indicates that the charger stack has reached its high
temperature rating. The charger will be automatically shutdown under
these conditions. When the fault has cleared the charger will
automatically restart.
‘RSD’ LED This LED indicates that the remote shutdown capabilities of the
charger has been initiated.
‘PHASE FAIL’ LED This LED indicates that one or more of the charger input phases has
failed. The charger will be automatically shutdown under these
conditions. When the fault has cleared the charger will automatically
restart.
‘DC HV’ Potentiometer This is used to set the DC High Voltage shutdown level.
‘BAL 1’ Potentiometer This is used in conjunction with ‘BAL 2’ to adjust the balance of the
system.
‘BAL 2’ Potentiometer This is used in conjunction with ‘BAL 1’ to adjust the balance of the
system.
‘ACLV’ Potentiometer This is used to set the AC Low Volts level.
‘ACHV’ Potentiometer This is used to set the AC High Volts level.
‘NTC CAL’ Potentiometer This potntiometer is used to adjust the calibration level setting of the
NTC probe.
‘DROOP’ Potentiometer This is used to adjust the ‘Droop’ level of systems in parallel.
‘VSTAB’ Potentiometer This is used to set the voltage stability of the system.
‘VC1’ Potentiometer This is used to set the ‘Float’ voltage level of the system.
‘VC2’ Potentiometer This is used to set the ‘Boost’ voltage level of the system.
‘VC3’ Potentiometer This is used to set the ‘Commissioning’ voltage level of the system.
‘CL1’ Potentiometer This is used to set the ‘Float’ current level of the system.
‘CL2’ Potentiometer This is used to set the ‘Boost’ current level of the system.
‘CL3’ Potentiometer This is used to set the ‘Commissioning’ current level of the system.

25/07/07 J2956BU01 REV 0.doc 16


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

VOLTAGE DETECTION MODULES (VDVD)

The VDVD (Voltage Detection) alarm module is designed to sense high and low DC voltage.
This is achieved by monitoring the DC supply and comparing it with a reference voltage. An
alarm is then generated when the sensed voltage goes outside pre-set levels.

NOTES:
a) If a blocking diode is included in the system and the module is configured to sense the voltage
on one side of the diode and gain its power supply from the other side link LK3 will be cut
between terminals A & B, thus allowing for a separate voltage sense signal, on terminal A, and
module power supply, on terminal B. e.g. In cases where the module is configured to sense a
charger failure.
b) If a blocking diode is not fitted the link between terminals A & B will not be cut and terminal A
will not be used.

Hence, if the sensed voltage level goes outside a pre-set level, then, in the case of low volts
alarm, the relay will de-energise or, in the case of high volts alarm, the relay will energise with a
subsequent change in state of the volt free contacts. I.e. For normal healthy conditions a low
volts detection relay will be energised and a high volts detection relay will be de-energised.

Also provided is an adjustable time delay to prevent the alarm tripping for short interruptions in
monitored voltage.

Typical applications for these types of modules include:

Charge Fail, Low Battery Volts, High Battery Volts, Battery Discharging, Voltage Detection, Low
Inverter Input Volts, High Inverter Input Volts, etc.

SPECIFICATION

The modules are available for use with the following nominal DC voltages:- 12, 24, 30, 48/50, 60,
110/120 and 220/240 (when used with an additional power supply module).

VDVD Dual channel module.


Voltage set point adjustment -25% to +40% of nominal voltage.
Voltage re-set point adjustment -1% to -25% of nominal voltage.
Timer operation mode Normal or High (CH2 only).
Timer range 0.5 - 30 seconds or 30 - 60 seconds.
Remote sensing Positive supply and sensing terminals can be split to enable
separate supply and voltage sensing.
Alarm contact ratings DPCO volt free contacts.
3A, 250V, 80W - DC
220VA - AC

25/07/07 J2956BU01 REV 0.doc 17


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

VDVD BOARD ARRANGEMENT

A BD
SET

SET R7
TERMINATIONS
R5
RESET
A POSITIVE VOLTAGE SENSING
RESET R18

R16 B POSITIVE DC POWER SUPPLY


TIME
NORMAL
TIME R23 D NEGATIVE DC POWER SUPPLY
R21

HIGH RL1 RL2


LED1 LED2

RL1 RL2

1 2 3 45 6 1 2 3 4 5 6
1 2 3 4 5 6 1 2 3 4 5 6
VD CH1 VD CH2
CHANNEL 1 CHANNEL 2

NOTE: For single channel modules channel 2 only is used.

BLOCK DIAGRAM

VOLTAGE VOLTAGE CH1


TIMER
DETECTION COMPARATOR RELAY

DC VOLTAGE VOLTAGE CH2


TIMER
SENSING DETECTION COMPARATOR RELAY

LINK

DC STABILISED POWER STABILISED POWER


SUPPLY FOR RELAY SUPPLY FOR SENSING
SUPPLY CIRCUITS & TIMER CIRCUITS

DESCRIPTION OF BLOCK DIAGRAM

The DC supply provides both power for the relay drive circuits and a stabilised logic power supply
for the control circuits, and with the link made between terminals A & B the voltage sense signal.
If the link was not made a separate sense signal would be applied to terminal.

The sensed signal is then compared, on both channel 1 & 2, with two independent pre-set
voltage reference levels which enable, via the timer circuits, the alarm relays to function.

25/07/07 J2956BU01 REV 0.doc 18


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SETTING/CHECKING INSTRUCTIONS

This procedure must be followed in the sequence given to set up, modify, or check the operating
levels of the alarm module.

The preferred method for modifying the parameters of the module is to initialise the
potentiometers, as described below, and then adjust the charger output voltage to simulate the
operating level required. Refer to the charger operating instructions for details on modifying the
charger output voltage. Remember this must be reset before putting the system back on line.

If a charger does not form part of the system, is not of the constant voltage type, or it is not
possible to use the charger, an appropriately rated DC power supply can be used as an
alternative to simulate the voltage supply. This must be connected in place of the normal supply,
i.e. the alarm module must be completed isolated from the system. Refer to the main circuit
diagram for connection details.

Assuming the charger is used as a variable DC power supply the battery and load must be
disconnected in order to check/set the alarm.

CHECKING THE OPERATING LEVELS


To prove the settings simply increase or decrease the DC power supply accordingly and monitor
the levels at which the relay/relays change state.

FOR SETTING UP PURPOSES ONLY, INITIALISE THE MODULE AS FOLLOWS:

Channel 1 R5 marked 'SET' (Trip) - fully clockwise.


R16 marked 'RESET' (Clear) - fully anti-clockwise.
R21 marked 'TIME' - fully anti-clockwise.
Channel 2 R7 marked 'SET' (Trip) - fully clockwise.
R18 marked 'RESET' (Clear) - fully anti-clockwise.
R23 marked 'TIME' - fully anti-clockwise.
J1 and J2 to Normal.

Voltage detection modules should be set up using the following procedures, which are written in
respect to channel 1, (channel 2).

25/07/07 J2956BU01 REV 0.doc 19


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SETTING THE VOLTAGE PARAMETERS - WHERE SET (TRIP) VALUES ONLY ARE
REQUIRED
Energise the variable DC supply and adjust this to the required set level. Then turn
potentiometer R5, (R7) slowly anti-clockwise until the relay just energises. If the module is being
used to sense low voltage turn R5, (R7) slowly clockwise until the relay just de-energises.

The module has now been set, however if a time delay is required refer to the section; "Setting
the timer" below.

SETTING THE VOLTAGE PARAMETERS - WHERE BOTH SET AND RESET VALUES ARE
REQUIRED
Energise the variable DC supply and adjust this to the upper voltage level. i.e. The reset (clear)
point for a low voltage detection module, and trip point for a high voltage detection module. Then
turn potentiometer R5, (R7) until the relay just energises.

Turn potentiometer R16, (R18) fully clockwise. Reduce the variable DC power supply to the
lower voltage level. i.e. The trip point for a low voltage detection module and reset (clear) point for
a high voltage detection module. Then slowly adjust potentiometer R16, (R18) until the relay just
de-energises.

The module has now been set, however if a time delay is required refer to the next section.

SETTING THE TIMER


Unless the module has been specifically supplied to allow a time delay to occur for high volts
conditions, as is indicated by the position of the jumpers J1 and J2, a time delay should only be
applied to low volts conditions.

The variable DC supply should be adjusted until a healthy condition exists. Then turn
potentiometer R21, (R23) to the approximate position required. Note, this potentiometer provides
a linear adjustment of the time period between 0.5 and 30 seconds, or 30 to 60 seconds if the
link LK1 or LK2 is broken. The time delay can then be proved by quickly simulating an abnormal
condition, and then timing the period it takes for the alarm to operate.

25/07/07 J2956BU01 REV 0.doc 20


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

DAU DC ALARM MODULE

This module provides system


instrumentation, control and
alarm functionality for single
or three phase thyristor
charger systems. The device
consists of a display/user
interface module which is
capable of front panel
mounting, and an interface
module for mounting within
the panel.

OPERATING MODES
The DAU user interface has
three modes, or levels, of
operation: User mode; set-up
mode; and service mode.

User mode; this is the


normal mode of operation.
The user has access to all the screens contained in the user level. These provide system
measurements, charger mode & system alarm status information and allow selective control of
the system.

Set-up Mode; provides access to all the user settable parameters screens. These allow the
various alarm settings and control features, to be configured or adjusted as required by the user.
Entry into this mode is protected by a user settable 4 digit password. (Note PLEASE KEEP A
RECORD OF YOUR PASSWORD, if you change it, as once you exit this mode you will be
denied access in the future with out entry of the correct password.

Service Mode; the unit functions as in set-up mode but also unlocks restricted access features,
such as analogue input calibration and control output testing. These functions are password
protected and are not accessible to the user. The Navigation around these screens, and
adjustment of the various parameters is achieved by using the push buttons which are present on
the front panel user interface module the function of which is described below.

FUNCTIONS AND FEATURES


INSTRUMENTATION
The module provides an LCD display for the indication of the charger output voltage and current.
Indications have an accuracy of ±1.5% or better. The display also serves for programming the
system control and alarm functions. In the instrumentation mode, the display indicates both
voltage and current.

LOCAL AND REMOTE ALARMS AND INDICATIONS


Facilities are provided for alarm reset, and LED test. All local LED indications are configurable
individually to be reset manually or automatically. All alarm settings have an adjustable time
delay of at least 30 seconds. In addition to the front panel time delayed LED for each alarm
function, an internally located red LED illuminates as soon as the alarm condition is initiated i.e.
before the adjustable time delay. All alarm and control functions are individually configurable from
the front panel display module.

25/07/07 J2956BU01 REV 0.doc 21


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

Alarm/ LED Function


Function Colour
AC Supply Green The charger is on and receiving an AC supply.
On

Note: AC Supply On does not indicate if the AC supply is present at the cubicle input
terminals if the charger has been switched off via its input circuit breaker. Isolate elsewhere.
AC Supply Yellow Indicates that the normal supply is not present, ie. Charger is off
Fail and does not have an AC supply (see note above).
Equalise Yellow Selection of a higher charger output voltage.
When enabled can be selected for Manual or Automatic Equalise
following an AC supply failure.
This feature is normally disabled on systems supplying VRLA
batteries.
DC Low Yellow Indicates that the DC voltage is below the pre-set level.
Volts
DC High Yellow Indicates that DC voltage is above a pre-set level. The alarm setting
Volts threshold is raised as required when the system is selected for the
equalise charge mode to prevent nuisance tripping.
Earth Fault Yellow Operates when the insulation resistance of either the positive or
negative poles to earth falls below a pre-set level and the other pole
stays above 2MΩ.
Charger Fail Red Both the voltage and current from the charger are below the pre-set
levels.
DC High Red As well as the high volts alarm it is also possible to set the DAU to
Volts Trip trip the charger input supply off if the voltages rises above the set
point. This trips the charger input circuit breaker when the voltage
is above the threshold setting.
High Battery Red This indicates when the internal resistance of the battery rises to a
Impedance level that would prevent it from operating satisfactorily on load.
DC Low On display This feature, when enabled, is provided to operate a contactor to
Volts only when disconnect the battery from the load when the voltage falls below a
Disconnect enabled pre-set level. Automatically resets on resumption of battery
charging.
Remote Red and on Inputs are provided to monitor up to five digital inputs. When active
Inputs display when the input’s label will be shown on the display and incorporated into
enabled the group alarms
Remote The DAU is equipped as standard with two output changeover
Outputs relays to which the above alarms can be mapped.
Remote The DAU can be connected to an optional separate eight relay
expansion module for remote indication or system functions.
relays

25/07/07 J2956BU01 REV 0.doc 22


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

FRONT PANEL CONTROL AND DISPLAY


The unit incorporates a screen for the display of system parameters and operator interaction
during system set-up or interrogation and set-up routines.

The system has display pages giving the system parameters. The left arrow and right arrow push
button will allow an operator to cycle through and select the required page.

The control push buttons are detailed below. On each page of the DAU display, the ‘active’ keys
(those which may be selected), are shown on the bottom line of the display.

Push Button Functions


During set-up mode this pushbutton will increment a parameter.

During set-up mode this pushbutton will decrement a parameter.

This button moves the displayed page to the next one on the left allowing the operator
to cycle through the display pages. During set-up mode this pushbutton will allow
navigation to the required set up page. Also used to move between the digits of the
password and other numeric parameters in set up.
This button moves the displayed page to the next one on the right allowing the operator
to cycle through the display pages in a reverse order to that of the left arrow
pushbutton. During set-up mode this functions as per the left arrow.
In normal mode this push button will cause the display to go to the home page which
displays the system voltage. While in set-up mode this button will cause the unit to
exit from the currently displayed page to the home page in the current level of the set-
up mode page structure. Referred to as Home in the setting up instructions.
In normal mode, this pushbutton will allow the operator to enter a password code to
gain access into set-up mode. Entry to set-up mode is protected by a 4-digit number
(see System Settings for details), which the operator must set with the arrow keys.
During set-up mode this pushbutton will accept the displayed settings of the parameter
or value. Referred to as Return in the setting up instructions)
During normal mode this pushbutton will cause all, except the AC Supply On, front
panel LED alarm indicators of the unit to illuminate.
During normal operation, this pushbutton will clear any latched alarms.

INFORMATION PAGES
The pages are displayed during normal operation and give an overview of the system voltage and
current, status, and any alarms.
No changes can be made to the system from these pages.

PAGE DISPLAY
Metering • DC Voltage(s). • Battery Impedance
• Current drawn by the load • Earth fault Vpos
from the system. • Earth Fault Vneg
Active Alarms • Any individual current and latched alarms and their groups.
Charger Mode The current state of the System e.g.:
• Float charging.
• Equalise charging and timer period.
• Charge Fail.
Battery Test • For selection of the battery test mode when enabled.
Earth Fault Test Available for positive and negative if the test circuit is included in the
system design
Battery High Impedance test Available if the test circuit is included in the system design.

25/07/07 J2956BU01 REV 0.doc 23


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

The chart below shows the pages in order. From any of these pages the use of the Home button returns you to the System
overview page. From this page Home displays the software version information.

DAU SET UP PAGES


When the DAU is first powered up, it will flash up information about the unit for several seconds, before displaying the System
Voltage and Current.

The display pages can be scrolled through, by using the left and right arrow keys. Pressing the RETURN key at any of these
pages, allows the user to enter the selected password, gaining access to the Set Up pages as shown below.

25/07/07 J2956BU01 REV 0.doc 24


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

EQUALISE MODE OPERATION

The unit has four different modes of operation for the Equalise function.

The first mode, enables automatic and manual initiation of the function. In this mode the equalise
function can be manually selected at any time, unless there is a charge fail alarm present.

When equalise is selected the output of the charger will start to rise, at a rate depending on the
capacity and state of charge of the batteries, until the Knee Point is reached. This is the point at
which the charging changes from constant current to constant voltage. The pre set equalise timer
period is now started and the charger will return to float when this is timed out (or a charge failure
occurs).

In this mode, a charge fail will automatically start a equalisation cycle. Which can be terminated
manually at any time as shown above.

The second mode allows Manual equalise with a remote enable.


This modes allows the manual selection of equalise as above provided that the Remote Mode
Control (RMC) input is active. If not present this will inhibit the selection of equalise., eg equalise
charging of the battery can be inhibited if a signal for ventilation fan failure is present.

In the third mode, the unit functions as a slave unit which is remotely controlled from a master
device using the RMC input; eg a system level Charge Fail Auto Equalise (CFAE) module. In this
mode the state of the RMC input determines the chargers equalisation mode. It will indicate the
present mode of operation but all manual control is disabled.

SET UP PAGE FUNCTION SETTING RANGE


Equalise Mode • DISABLE; Float only, normally selected for VRLA
batteries.
• MANUAL/AUTO: DAU controls the equalise function.
• REMOTE ENABLE: Manual selection of equalise
from DAU fascia but is enabled or disabled remotely.
• REMOTE CONTROLLED: DAU acts as a slave and
equalise is initiated from only a remote contact
Charge Fail Trip The voltage at which the auto equalise cycle is enabled. 75 – 100%
Charge Fail Reset The voltage at which the charge is switched into equalise. 100 – 140%
Charge Fail Delay Time between the charge fail set point being reached and 0 – 120s
its activation.
Knee Volts The point at which the battery goes from constant current 100 – 125%
to constant voltage charging and the equalise timer is
started.
Equalise Timer The time which the charge is in equalise mode after the 0.5 – 24h
knee volts point has been reached. Charge returns to
float mode.

25/07/07 J2956BU01 REV 0.doc 25


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

EQUALISE SELECTION
When the Manual/Auto mode is enabled Equalise is selected by pressing the UP key as shown
below.

Charger Mode Note: Equalise selection is inhibited when the Charge


Mode = FLOAT Fail alarm is active.
Press [UP] to start
Equalise

Charger Mode The charger is now in the *Note that the time is
Mode = EQUALISE equalise mode. To return to only shown once the
Time left = 12hours* float press knee point is reached
Press [DOWN] to stop

FLOAT SELECTION
At any point during the equalise period the charger can be returned to the float mode as shown
above.

BATTERY TEST
A feature of the DAU allowing the battery to be into the site loads. This gives confidence in the
battery to support the load in the event of a mains failure. To do this the charger is shut back to a
lower voltage (pre set) to allow the battery to discharge into the load and to be on standby in case of
a battery failure. A failure of the test will cause an alarm.

This feature checks the suitability of the battery to support the site load for a given time or for a pre-
set capacity and does not check the full battery autonomy.

A test is terminated voltage and time. If the battery voltage drops below the set level before the
timer period is met then it is failed. If the time is reached before the voltage drops too far then the
battery has passed. See system specification for settings and details below on setting up and
adjustments.

Battery Test Note: Battery test is inhibited when the Charge Fail
alarm is active.
Press [UP] to start
Battery Test

Battery Test The charger is now in the shut


Mode = Battery Test back mode. To return to float
press
Press [DOWN] to stop
Note: Battery Test is inhibited if the AC Supply Fail, Charge Fail, or a previous
Battery Test Failed alarm is present or the charger is in equalise mode. This will
appear on the display.

If the battery fails the discharge test then a latched alarm is generated. This will inhibit any further
battery discharge until reset with the push button.

25/07/07 J2956BU01 REV 0.doc 26


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

BATTERY DISCHARGE TEST PARAMETERS.


These are accessed as described below.

SET UP PAGE FUNCTION SETTING RANGE


Manual Battery Enable or Disable the function.
Test.
Battery Test Fail • Battery test minimum volts. 75 – 125%
Voltage The voltage at which the battery is deemed to have
failed the test if this point is reached before the
time/capacity has been exceeded.
Battery Test Time • Maximum time: 1 – 60m
The test is terminated after a set time has elapsed
provide that the voltage stays above the set level.

BATTERY HIGH IMPEDANCE ALARM


This alarm continuously monitors the battery and its connections for any increase in their
impedance which may affect the ability to support the load in the event of a mains failure.

SETTING UP THE HIGH IMPEDANCE ALARM


Firs the system and its batteries should be connected and fully installed.
Enter the set up pages, using the password, as described below and use the right arrow to navigate
to the High Impedance Alarm page.

Press RETURN twice to reach High Impedance Trip = xx Ohms. This shows the current setting.
Reduce the setting, using the DOWN arrow until the alarm is tripped this is done by checking the
LED on the interface board as this does not have a time delay. Now increase the setting until the
alarm is cleared. If any nuisance alarms occur the setting can be increased accordingly. Press
RETRUN to move to the High Impedance Delay page. This is set to 30seconds as default and can
be adjusted if required although reducing it may cause nuisance alarms. To save the changes
press the HOME button twice to return to the information pages

SET UP PAGE SELECTION


By use of a password (the default is blank) the set up pages of the DAU can be accessed.
Pressing the RETURN key on all information pages will take you to the password screen as shown
below.

25/07/07 J2956BU01 REV 0.doc 27


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

The first page displayed depends on the screen from which Set Up is selected:

Information Page User Set UP Mode Page


Metering Battery Impedance Alarm Set Up Pages
Active alarms Battery Impedance Alarm Set Up Pages
Charger Mode Equalise Set Up Pages
Battery Test Battery Test Set Up Pages
Positive or Negative Earth Fault Test Earth Fault Set Up Pages
Battery High Impedance Test Battery Impedance Alarm Set Up Pages

Navigation to the other pages is via the ï and ðbuttons. RETURN takes you into the relevant
pages and Home will take you back to the Information Pages.
Note; ‘Saving Settings to Non Volatile Memory’ will always be displayed briefly when coming out of
the set-up menus, even if changes have not been made.

If, when you access a set of pages, it is decided that another page of screens is required the Home
button will take you back to the selection level.

NOTE: the DAU has been set up in accordance with your specification, and for the correct
operation of the system. Before making any changes to its settings first check that they do not
affect the operation or safety of the system. Any changes should be limited to alarm and battery
test settings only. Other alarm functions are available within the DAU but are protected by a further
password, which is available on request. If in doubt, please contact Erskine Systems.

25/07/07 J2956BU01 REV 0.doc 28


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

The User Set Up mode password only allows access to the following pages.

Changes can be made to High Volts Shutdown, Low Volts Disconnect and other system function parameters, however, due to the fact that these
affect system safety and operation they are protected by an Engineering Mode password available from Erskine System on request.

25/07/07 J2956BU01 REV 0.doc 29


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

ALARM SET UP
All of the alarm pages have the following
parameters:
Trip; the point at which the alarm is activated (on
a falling voltage for low volt alarms or a rising
voltage for high volts alarms)
Reset; The point at which the alarm is cleared (on
a rising voltage for low volt alarms or a falling
voltage for high volts alarms).
Delay; the period between the alarm being
activated and it being displayed on the front panel
and activation of the remote relay. Note that the
LEDs on the interface module (see below) are
activated instantaneously.
Latch; when enabled the alarm will latch on the
display and remote relay once the time period has
elapsed. To clear the alarm the level must first be
past the reset level and the Alarm Reset button is
pressed. Note that the LEDs on the interface
board are non latching.
Common Alarm Mapping; selects the remote
relay activated by the alarm.
Expansion Relay Mapping; selects the relay
on the expansion module (if fitted) activated by the
alarm.

To enter any of the alarm set up pages press


RETURN at the desired page. The values are
altered with the UP and DOWN buttons. Press
RETURN to carry on to the next page or HOME to
return to the selection page.

Any changes made are automatically saved when


the RETURN or HOME buttons are pressed and
you return to the information pages. There is no
option to cancel the changes.

The diagram to the right shows an example page.


All others are of a similar format.

The table below shows all alarms, the pages in


the order they appear as RETURN is pressed.
A brief explanation of the alarm is given and the
limits of the settings. Voltage alarms are shown
as a percentage of the nominal system volts, 24V,
50V, 110V etc.

*Note :- the +Vs & +Vp terminals allow the


voltage to be sensed at either side of a charger
output blocking diode for systems built with this
feature. Vs is connected to the charger side of
this diode and Vp is connected at the system
side. The can be configured to use the +Vp input
only for systems without a blocking diode.

25/07/07 J2956BU01 REV 0.doc 30


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

Battery High Impedance Resistance of battery circuit at +Ps terminal. Alarms if the
impedance rises above the set point. Resets on low
impedance.
Enable/Disable
Trip Ohms 0.2 – 5.0 Ohm Reset set point less 0.2 Ohm
Delay S 0 – 120s
Latch Enable/Disable
Common alarm relay mapping 1 or 2
Expansion relay mapping 1 to 8

Earth Fault Fault Current +Vp terminal. Alarms when the resistance to
earth either the positive OR negative pole of the DC is low
enough to cause a current, above the set point to flow, in
the earth if a low impedance return path were present.
The other pole must be above 2MΩ .
Trip mA 1,2,4,10mA
Delay S 0 – 120s
Latch Enable/Disable
Common alarm relay mapping 1 or 2
Expansion relay mapping 1 to 8

Low Volts Alarm Voltage sensed at +Vp terminal. Alarms on a falling


voltage, resets on rising voltage.
Trip V 75 – 125%
Reset V 100 – 140%
Delay S 0 – 120s
Latch Enable/Disable
Common alarm relay mapping 1 or 2
Expansion relay mapping 1 to 8

Charger Fail Alarm Voltage sensed at +Vs terminal and current sensed at
charger output shunt. Alarms on a falling voltage AND
falling current , resets on rising voltage OR current.
When AC Fail Active • Enable – CF will alarm when AC failed.
• Disable – CF will not alarm when AC failed.
Trip V 75 – 125%
Reset V 100 – 140%
No Access to these Trip A Fixed at <10% of shunt rating Non adjustable
settings Reset A Fixed at >20% of shunt rating Non adjustable
Delay S 0 – 120s
Latch Enable/Disable
Common alarm relay mapping 1 or 2
Expansion relay mapping 1 to 8

High Volts Alarm Voltage sensed at +Vp terminal. Alarms on a rising


voltage, resets on falling voltage.
Trip (float) V 100 – 140%
Reset (float) V 75 – 100%
Trip (Equalise) V 100 – 140%
Reset (Equalise) V 75 – 100%
Delay S 0 – 120s
Latch Enable/Disable
Common alarm relay mapping 1 or 2
Expansion relay mapping 1 to 8

25/07/07 J2956BU01 REV 0.doc 31


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

AC Fail AC derived voltage received from charger controller.


Latch Enable/Disable
Common alarm relay mapping 1 or 2
Expansion relay mapping 1 to 8

The following alarms are accessed only through the Engineering Mode password.

High Volts Shutdown Voltage sensed at +Vs terminal. Alarms on a rising


voltage, resets on falling voltage.
Mode • Internal – DAU controls shutdown
• External – Charger controls shutdown, DAU marshals alarm
only.
Trip (float) V 100 – 140%
Reset (float) V 75 – 100%
Trip (Equalise) V 100 – 140%
Reset (Equalise) V 75 – 100%
Delay S 0 – 120 secs
Latch Enable/Disable
Common alarm relay mapping 1 or 2
Expansion relay mapping 1 to 8

Low Volts Disconnect Voltage sensed at +Vp terminal. Alarms on a falling


voltage, resets on rising voltage. Used to drive a battery
or load contactor to disconnect and protect a VRLA battery
or for load shedding.
Trip V 75 – 125%
Reset V 100 – 140%
Delay S 0 – 120s
Common alarm relay mapping 1 or 2
Expansion relay mapping 1 to 8

25/07/07 J2956BU01 REV 0.doc 32


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

INTERFACE MODULE
The eight LEDs in the bottom left hand corner, work
independently of the LEDs on the Display Module. They
indicate that the respective alarm is active immediately.
The front display LEDs do not light until after the time
delay has elapsed. This is used for testing and
commissioning the alarm functions.

The Interface is connected to the Display via a null


modem 9 way D Type connector on CON5, and to DCV
the charger controller by a 20 way ribbon cable on X16.
All other connections are via the two part connectors
listed below.

Ref Function RC
1.1 Group 1 volt free alarm (NO)
1.2 Group 1 volt free alarm (COM)
1.3 Group 1 volt free alarm (NC)
2.1 Group 2 volt free alarm (NO)
2.2 Group 2 volt free alarm (COM)
2.3 Group 2 volt free alarm (NC)
E Earth fault alarm ground connection
+12 High Volts Shut Down
HVSD High Volts Shut Down
-PS Power supply –Ve
+VS System voltage sense +Ve
-COM Voltage sense common –Ve
+VP Charger voltage sense +Ve
+PS Power supply +Ve
-A Current sense 75mV –Ve ü
+A Current sense 75mV +Ve ü
COM Charger common ü
P AC Supply On from charger ü
FC Remote fault input common
FC Remote fault input common
RMC Remote control mode input
F1 Remote fault input 1
F2 Remote fault input 1
F3 Remote fault input 1
F4 Remote fault input 1
F5 Remote fault input 1

All connection marked ü in the RC column are connected to the DCV controller via the 20 way
ribbon cable on X16.

25/07/07 J2956BU01 REV 0.doc 33


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

8 RELAY EXPANSION MODULE

When incorporated into a system this is connected to the DAU via a 10 way ribbon cable. One
or more alarms can be mapped to one or more relays using the ‘Expansion Relay Mapping’ page
and changing the position to [X]. The LED indicates when the relay is energised. Each relay (K)
provides a set of volt free change over contacts via the corresponding terminal block (X). the
relay can be configured, within the DAU Engineering mode, to energise or de-energise on alarm.

25/07/07 J2956BU01 REV 0.doc 34


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 5

DESCRIPTION OF CONTROLS AND INDICATIONS

CONTROLS AND INDICATIONS DESCRIPTION


AC INPUT CIRCUIT BREAKER This connects the charger input to the
incoming AC mains supply. It may be opened
to isolate the charger from the mains supply
for maintenance purposes etc. The breaker
0
also functions as the charger On/Off switch.
In the event of a fault the breaker will be
tripped to shutdown the charger.

CHARGER OUTPUT ISOLATOR This connects the charger output to the


battery and distribution circuit. The isolator
may be opened to isolate the charger from
these circuits for maintenance purposes etc.
0

COMMISSION CHARGE SELECT SWITCH This switch is used to select the chargers
initial commissioning mode. Refer to the
COMMISSIONING ‘Commissioning Procedure’ shown on the
OFF circuit diagram.

ON

25/07/07 J2956BU01 REV 0.doc 35


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

CONTROLS AND INDICATIONS DESCRIPTION


INPUT VOLTMETER SELECTOR SWITCH This switch is used in conjunction with the
VOLTMETER CHARGER INPUT VOLTMETER. The reading
obtained on the meter corresponds to the
OFF voltage measured on the phase indicated by
L1-L2 L1-N the switch position. If the switch is placed into
the ‘Off’ position meter operation is inhibited.
L2-L3 L2-N

L3-L1 L3-N

INPUT AMMETER SELECTOR SWITCH This switch is used in conjunction with the
AMMETER CHARGER INPUT AMMETER. The reading
obtained on the meter corresponds to the line
OFF current measured on the phase indicated by
the switch position. If the switch is placed into
the ‘Off’ position meter operation is inhibited.
L3 L1

L2

BATTERY CIRCUIT BREAKER This connects the battery to the charger


output and distribution circuits. The breaker
may be opened to isolate the battery from
these circuits for maintenance purposes etc.
0

DISTRIBUTION FEED CIRCUIT BREAKER This breaker connects the distribution circuits
to the charger output. The breaker may be
opened or closed as required by the load
connected.
0

25/07/07 J2956BU01 REV 0.doc 36


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

CONTROLS AND INDICATIONS DESCRIPTION


FIRE RESPONSE INDICATOR Located on the fire response indicator module,
this lamp will indicate a temperature rise,
which could be the result of a fire occurring
within the system.

AC INPUT AMMETER This meter indicates the amount of current


being drawn from the incoming AC mains
supply. The meter is read in conjunction with
the meter phase select switch to display the
individual phase currents. The values obtained
will depend on the state of charge of the
battery and the size of any load connected.

AC INPUT VOLTMETER This meter indicates the voltage level being


supplied to the charger from the incoming AC
mains supply. The meter is read in
conjunction with the meter phase select
switch. The readings obtained should be
approximately equal to the values stated in the
‘Equipment Details’ section of this manual.

BATTERY AMMETER This meter indicates the current flow through


the battery circuit. During normal mains
healthy conditions the meter will indicate the
battery recharge current. This reading will vary
depending on the state of charge of the
battery, generally a discharged battery will
consume a large current from the charger.
The level will decrease as the battery
becomes charged. In the event of a mains
failure the meter will display the current being
supplied by the battery to the load. The
reading obtained will vary depending on the
size of the load connected.
BATTERY VOLTMETER This meter indicates the voltage level present
at the battery terminals. During mains healthy
conditions the reading displayed should be
approximately equal to the ‘Float’ value shown
on the circuit diagram. In the event of a mains
or charger failure occurring, on a single
charger system the meter will indicate the
battery voltage - this will fall as the battery
becomes discharged. In the event of a single
charger failure on a dual charger, single
battery system the remaining charger will
continue to supply the battery and the reading
should not alter. Refer to the circuit diagram to
determine the configuration supplied.

25/07/07 J2956BU01 REV 0.doc 37


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

CONTROLS AND INDICATIONS DESCRIPTION


DISTRIBUTION INPUT CIRCUIT BREAKER This breaker connects the distribution circuits
to the charger output. The breaker may be
opened or closed as required by the load
connected.
0

220V DC TRIPPING DISTRIBUTION BOARD This breaker connects the 220V DC tripping
FEEDER distribution circuits to the charger output,
providing an alternative feed. The breaker may
be opened to isolate the circuits for
maintenance purposes etc.
0

LOAD CIRCUIT BREAKERS These breakers connect the individual load


circuits to the distribution circuit. Each
breaker may be opened or closed as required
by the load connected.

0-OFF 0-OFF 0-OFF 0-OFF

1-ON 1-ON 1-ON 1-ON

25/07/07 J2956BU01 REV 0.doc 38


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 6

START-UP & SHUTDOWN

PRE-START CHECKS

Once the equipment has been installed, the following (mainly visual) checks should be performed
prior to starting the equipment.

1. Check the equipment is secure and as level as possible (this is particularly important with
respect to battery cubicles).

2. Ensure the external surfaces of the equipment are free from dust, packing materials, etc.

3. Check all switches, meters and LED’s are in good condition and free from transit damage.

4. Check inside cabinets to ensure there are no obvious defects; such as loose PCB, loose or
broken connectors, loose component mounts, etc.

5. Check all fuses are secure and in place.

6. Check all external wiring to the equipment is correctly wired up and safely installed.

7. Check:-
Mains AC feeds to the charger.
Remote alarm connections.
Remote control connections.
DC load circuit connections.
Battery connections and inter-cell connections.

COMMISSIONING PROCEDURE

Before entering into operational service, it is essential that the batteries receive a once only
commission charge. This charge prepares the cells for a long and trouble free service life at
maximum capacity. To commission charge the batteries, follow the start up procedure shown on
the Circuit Diagram. The battery manufacturers Operation Manual should also be referred to, to
determine exact commissioning procedure and charge duration.

25/07/07 J2956BU01 REV 0.doc 39


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

START-UP PROCEDURE

In order to start the equipment whether it be following a controlled shut-down or post installation,
the following procedure should be observed.

The instructions should be followed in the order listed and the result given must be achieved
before proceeding on to the next instruction.

It should be noted that in some cases the results listed may take some time to occur (e.g. the
charger is fitted with a 'soft-start' facility where by the output voltage takes several seconds to
rise up to the operating level). Always operate the alarm reset push-button before observing the
results listed to clear any spurious alarm conditions caused during the start-up operations.

Procedure:-

ACTION
Initialise the System controls as stated:-
nOn the system…
• AC INPUT CIRCUIT BREAKER – OPEN
• CHARGER OUTPUT ISOLATOR – OPEN
• BATTERY CIRCUIT BREAKER – OPEN
• DISTRIBUTION FEED CIRCUIT BREAKER – OPEN
• DISTRIBUTION INPUT CIRCUIT BREAKER – OPEN
• 220V DC TRIPPING DISTRIBUTION BOARD FEEDER – OPEN
• LOAD CIRCUIT BREAKERS - OPEN
Energise the incoming mains supply.
1. Close the AC INPUT CIRCUIT BREAKER
2. Close the CHARGER OUTPUT ISOLATOR
3. Close BATTERY CIRCUIT BREAKER
4. Close the DISTRIBUTION FEED CIRCUIT BREAKER
5. Close the DISTRIBUTION INPUT CIRCUIT BREAKER
6. Close the 220V DC TRIPPING DISTRIBUTION BOARD FEEDER
7. Close the LOAD CIRCUIT BREAKERS AS REQUIRED
The charger is now up and running. The charger is supplying a recharge current to the
battery and also supplying the requirements of the load. In the event of a mains failure, the
charger will cease to operate and the load will be supported by the batteries for the
designed standby time.

25/07/07 J2956BU01 REV 0.doc 40


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

NORMAL OPERATION

During normal operating conditions only the following lamps should be illuminated:-

MAINS ON
FLOAT (or Equalise)

If any other lamps illuminate then an alarm condition is indicated. The cause should be
investigated and if possible rectified. Please refer to the 'Description of Controls' and 'Fault
Finding' sections of this manual.

SHUTDOWN PROCEDURE

To shutdown the system for maintenance purposes, etc., the following procedure should be
observed.

.NOTE:- If the system is shutdown the supply to the load may be lost. Refer to Circuit Diagram
supplied

CAUTION!:- Before proceeding with maintenance of the equipment consult the Health and Safety
section of this manual.

WARNING!:- Even though the equipment is shutdown, high voltages may still be present within
the cubicle. Refer to the Circuit Diagram supplied and isolate elsewhere before working on the
equipment.

Procedure:-n TOTAL SHUTDOWN

ACTION
1. Open the LOAD CIRCUIT BREAKERS
2. Open the 220V DC TRIPPING DISTRIBUTION BOARD FEEDER
3. Open the DISTRIBUTION INPUT CIRCUIT BREAKER
4. Open BATTERY CIRCUIT BREAKER
5. Open the DISTRIBUTION FEED CIRCUIT BREAKER
6. Open the CHARGER OUTPUT ISOLATOR
7. Open the AC INPUT CIRCUIT BREAKER
The charger is now shutdown allowing maintenance work to be performed. Refer
to start-up procedure in-order to turn the system back on when ready.
END

25/07/07 J2956BU01 REV 0.doc 41


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 7

FAULT FINDING INSTRUCTIONS

TESTING SEMI-CONDUCTORS
CAUTION!:- Fault finding should only be
undertaken by competent electrically qualified In almost every instance, a faulty power
personnel who are familiar with the equipment semi-conductor will have a short circuited
operation and it's potential hazards. The safety junction and, because of parallel paths in
instructions at the front of this manual should the circuit, a short circuit device may cause
be read and fully understood before working on several other components in proximity with
the equipment. it in the circuit electrically to also appear
faulty. If this is suspected, disconnect one
This section is designed to provide sufficient end of each device until the faulty
information to enable fault finding diagnosis component is found.
and repair/replacement down to circuit board
level. For more extensive repairs the Also due to parallel paths in the circuit,
assistance of Erskine Systems should be SCR's may not appear high resistance
sought. across anode and cathode, and diodes may
not appear low resistance in one direction
PROCEDURES and high resistance in the other. If there is
any doubt about readings, compare each
Look for the obvious fault. Often a visual component with its equivalents in the circuit;
inspection is all that is necessary to locate large differences found in this way indicate a
a fault - particularly with capacitors. fault condition.

Always check for loose or broken inner Take care when replacing components not
conductors, loose PCB's, etc. to replace forward diodes with reverse
diodes and vice versa, or to fit SCR's the
There are NO tests that require removal of wrong way round.
the earth connection from oscilloscopes or
other test equipment. Dual beam STUD MOUNTING SEMI-CONDUCTORS
oscilloscopes must have differential
facilities. Before fitting stud mounting components,
apply a smear of Dow Corning 340 Thermal
There is no practical or satisfactory way of Compound to the mating surfaces.
anticipating a malfunction before it occurs
with this type of equipment; generally the
equipment will work perfectly or shutdown.

25/07/07 J2956BU01 REV 0.doc 42


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

TEST EQUIPMENT REQUIRED ON-SITE

The following is a list of test equipment recommended for the purposes of routine testing, fault
diagnosis and repair.

1. DC stabilised Power Supply


2. AC/DC Clip-on Ammeter
3. Digital Multimeter - True RMS Reading
4. Digital Storage Oscilloscope
5. X - YT Plotter
6. Phase Rotation Meter
7. Variac
8. AC/DC Load Bank of suitable rating

Please contact the Customer Services Manager at Erskine Systems, for the suitability of test
equipment.

SETTING-UP INSTRUCTIONS
6CV CHARGER CONTROLLER

NOTE:- The charger is already set up and the instructions below should only be followed if
the settings require altering.

Before switching the charger on, ensure:


• Correct Phase connection - see note.
• Battery is disconnected.

NOTE:- Failure to observe phase rotation will result in the charger output being inhibited.

TO ADJUST VOLTAGE SETTINGS

1. Connect a load of approximately 5% of the charger nominal current rating to the charger
output.
2. Select the Initial Commission (IC) Charge Mode if applicable.
3. Switch the charger ‘On’
4. To adjust the COMMISSION VOLTAGE, turn the potentiometer marked VC3 clockwise to
increase output voltage.
5. Select the Equalise Charge Mode.
6. To adjust EQUALISE VOLTAGE, turn the potentiometer marked VC2 clockwise to increase
output voltage.
7. Select the Float Charge Mode.
8. To adjust FLOAT VOLTAGE, turn the potentiometer marked VC1 clockwise to increase
output voltage.
9. The Voltages are now set.

NOTE:- Voltage settings are independent of each other and can be set in any order.

25/07/07 J2956BU01 REV 0.doc 43


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

TO ADJUST THYRISTOR TRIGGER BALANCE

1. Switch the charger ‘Off’. Connect an oscilloscope to the DC output of the thyristor/diode
stack.

CAUTION:- Care must be taken when using earthed scopes on a charger with a DC line earthed. It
is recommended that the scope probe is fitted with an isolating device or differential models used.

2. Connect a load of approximately 80% of the charger nominal current rating to the charger
output. Switch ‘On’ the charger.
3. If the charger is in current limit, adjust the relevant current limit potentiometer until the charger
has an output of 80% nominal current.
4. Adjust potentiometers BAL.1 and BAL.2 until the vertical pulses on the scope screen are all
of equal height.
5. The charger is now balanced. Switch the charger ‘Off’ and remove the load.

TO ADJUST THE CURRENT LIMIT SETTING

1. A suitable load must be connected to achieve an output current from the charger slightly
higher than the current limit setting required.
2. Select IC, Equalise and Float Charge modes as before, set the current limit levels as follows:
3. To adjust initial commissioning current limit turn potentiometer CL1 clockwise to increase the
output current.
4. To adjust the equalise current limit turn the potentiometer marked CL2 clockwise to increase
the output current.
5. To adjust the float current limit turn potentiometer marked CL3 clockwise to increase output
current.
6. Current limits are now set.
7. Reconnect the Battery

NOTE:- Current limit settings are independent of each other and can be set in any order.

SOLUTIONS TO COMMON FAULTS

1. Before making any fault finding checks, it is advisable to disconnect any external load so as
not to disguise any fault in the charger unit itself.

2. There are two main fault conditions: Low output and High output. Care must be taken when
determining the type of fault present, as it may be possible that a High output condition has
caused the main fuse in the charger DC output line to fail, hence causing a low output
situation. Zero output is taken to be a low output condition.

25/07/07 J2956BU01 REV 0.doc 44


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

HIGH OUTPUT
1. Check that Mains input is present and that the voltage is correct.

2. Check that the correct number and type of battery cells are connected.

3. Check that the sensing voltage at the controller is the same as at the battery (if fitted).
Trace for bad or missing connections as necessary. Refer to Circuit Diagram for connection
Details (+VE and -VE output terminals).

4. Check that charger is not operating permanently in EQUALISE mode.

5. Disconnect all thyristor gate connections (Yellow leads on controller). If the voltage or output
current is still faulty it is probable that the stack assembly is faulty; replace if necessary.

6. Check controller setting and if control of voltage or current is not possible, replace controller.

LOW OUTPUT
1. Check AC mains input is present and of correct voltage.

2. Check for voltage on transformer primary when Mains Input Circuit Breaker is closed.

3. Check for voltage on transformer secondary.

4. Check for AC input to thyristor stack. If not present, check fuse (terminal A1, A2, CT when
fitted, on PCB).

5. If fuse F1 blown, the stack assembly is probably faulty, replace as necessary.

6. Check correct number and type of battery cells are connected (If fitted).

7. Check supply to the controller, terminals L and N on PCB (refer to Circuit Diagram).

8. Check that the sensing voltage at the controller is the same as battery (if fitted). Refer to
Circuit Diagram for connection Details (+VE and -VE output terminals).

9. Check controller settings and adjust to correct values if possible.

10. Check charger DC output fuses and replace as necessary.

11. Check external connections on the controller (e.g. links).

12. Disconnect each gate connection to the thyristors (Yellow leads on PCB) in turn. If the
removal of the firing signal has no effect on the system output then generally the stack could
be faulty. If no adjustment is possible, replace the controller.

NOTE:-If in doubt any problems should be referred to the Customer Services Manager - Erskine
Systems.

25/07/07 J2956BU01 REV 0.doc 45


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

CHARGER FAULT FINDING GUIDE


Once a problem has been identified with the aid of the panel indications, the following table can
be used to help identify the cause and cure the fault. Whilst fault finding, the normal start-up and
shutdown procedures should be used. Also the applicable setting up procedures should be
followed.

PROBLEM CAUSES
A B C D E F G H I J K L
Loss of Output Voltage 3 3 3 3 3 3 3 3 3 3 3
High Output Voltage 3 3 3 3 3 3

CAUSES SOLUTIONS
A Charger switched off Switch charger on
B Mains supply faulty or off Restore mains supply
C Blown control or power fuses Check for shorts and replace
D Power semi-conductor open circuits Check for shorts and replace
E Control semi-conductors open circuit Check for shorts and replace
F Thyristors not firing Replace
G Faulty control cards Replace and reset
H Incorrect voltage settings Check and adjust
I Incorrect current settings Check and adjust
J Faulty filter capacitor Replace
K System overloaded Remove some excess load
L Loose wiring connections Check and secure

STACK FAN FAILURES


Before replacement of fans is implemented it should be checked that a fan fail has actually
occurred. If the room temperature rises above the specified limit or the vents are blocked, then
the alarm may come up without a fan failure. Therefore these should be checked when the alarm
comes up but the fans are operating correctly.

25/07/07 J2956BU01 REV 0.doc 46


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 8

MAINTENANCE INSTRUCTIONS

1. As a general principle, it is better not to interfere with the control of this type of equipment,
provided that the equipment is functioning satisfactory. It is recommended that routine
maintenance is limited to simple cleaning and checking that the ventilation paths, etc. are
free from obstruction.

2. The equipment should be checked and cleaned of dust, etc. at periods depending upon the
operating climate. During the regular maintenance period, nuts, bolts and screws should be
checked for correct tightness.

3. The operation of switches, alarms and relays should be checked wherever possible. A visual
check of all components should be made to ensure that components have not deteriorated
from the effect of humidity, temperature, etc. Instruments should be zeroed as required.

4. In the event of faulty operation it is recommended that the fault finding procedures outlined be
carried out and/or consult the Customer Services Manager at Erskine Systems.

TORQUE SETTINGS

The settings shown below are the maximum torque settings to be applied and are for reference
only. Due to the varying strengths of the materials that are to be clamped, the actual torque
settings are left to the discretion of the engineer. The setting used should be sufficient to
securely clamp the materials for a given purpose, without causing damage.

NUTS AND BOLTS/SCREWS TORQUE (Nm) (Ft.lb)


4mm (M4) 8.1Nm 6ft.lb
6mm (M6) 16.3Nm 12ft.lb
8mm (M8) 24.4Nm 18ft.lb
10mm (M10) 32.5Nm 24ft.lb
12mm (M12) 48.8Nm 36ft.lb
THREADED INSERTS AND BOLTS/SCREWS
4mm (M4) 5.4Nm 4ft.lb
6mm (M6) 8.1Nm 6ft.lb
8mm (M8) 13.5Nm 10ft.lb
10mm (M10) 18.9Nm 14ft.lb

25/07/07 J2956BU01 REV 0.doc 47


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 9

DRAWING FILE

CHARGER CIRCUIT DIAGRAM– J2956BC01


DISTRIBUTION CIRCUIT DIAGRAM– J2956BC02
SINGLE LINE DIAGRAM– J2956BC03
BATTERY LAYOUT – J2956BF01
ARRANGEMENT – J2956BH01
INTERNAL ARRANGEMENT – J2956BH03
DAU SETTINGS – J2956BA02

25/07/07 J2956BU01 REV 0.doc 48


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

220V DC TRIPPING BATTERY CHARGER


6CV220/25

INSTALLATION,
OPERATING AND
MAINTENANCE
MANUAL
DOCUMENT NO. : J2959BU01 REV 0

For

MITSUBISHI ELECTRIC
SAAD AL ABDULLA ‘A’, ‘B’, ‘C’ & ‘D’ SUBSTATIONS
AND EXTENSION OF UM AL-AISH ‘M’ SUBSTATION

25/07/07 J2959BU01 REV 0.doc 1


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 1 __________________________________________________________________ 4
EXPLANATION OF HAZARD INFORMATION ------------------------------------------------------------------------------- 4
HEALTH AND SAFETY PRECAUTIONS ------------------------------------------------------------------------------------- 5
SECTION 2 __________________________________________________________________ 6
INSTALLATION------------------------------------------------------------------------------------------------------------------- 6
UNPACKING THE EQUIPMENT ------------------------------------------------------------------------------------------ 6
USE OF FORK LIFT TRUCK FOR LIFTING THE EQUIPMENT ----------------------------------------------------- 6
LOCATION OF THE EQUIPMENT---------------------------------------------------------------------------------------- 6
CONNECTING THE EQUIPMENT---------------------------------------------------------------------------------------- 7
GENERAL ..................................................................................................................................................... 7
PRESERVATION PROCEDURE (GENERAL)--------------------------------------------------------------------------- 9
RECOMMENDATIONS FOR 24 MONTH STORAGE AND PRESERVATION -------------------------------------- 10
EMC HEAVY INDUSTRIAL ENVIRONMENT---------------------------------------------------------------------------- 10
SECTION 3 __________________________________________________________________ 11
EQUIPMENT DETAILS---------------------------------------------------------------------------------------------------------- 11
SECTION 4 __________________________________________________________________ 12
DESCRIPTION OF OPERATION ---------------------------------------------------------------------------------------------- 12
THE SYSTEM---------------------------------------------------------------------------------------------------------------- 12
6CV CHARGER DESCRIPTION OF OPERATION --------------------------------------------------------------------- 13
THE INTERFACE MODULE......................................................................................................................... 14
THE CONTROL AND DRIVE MODULES.................................................................................................... 14
6CV CONTROL MODULE - ARRANGEMENT............................................................................................ 15
6CV DRIVE MODULE - ARRANGEMENT ................................................................................................... 15
6CV INTERFACE MODULE - ARRANGEMENT.......................................................................................... 16
DESCRIPTION OF THE CONTROL MODULE’S LED’S AND POTENTIOMETERS------------------------------- 17
VOLTAGE DETECTION MODULES (VDVD)--------------------------------------------------------------------------------- 18
SPECIFICATION ------------------------------------------------------------------------------------------------------------ 18
VDVD BOARD ARRANGEMENT ................................................................................................................. 19
BLOCK DIAGRAM ........................................................................................................................................ 19
DESCRIPTION OF BLOCK DIAGRAM........................................................................................................ 19
SETTING/CHECKING INSTRUCTIONS --------------------------------------------------------------------------------- 20
CHECKING THE OPERATING LEVELS ...................................................................................................... 20
SETTING THE VOLTAGE PARAMETERS - WHERE SET (TRIP) VALUES ONLY ARE REQUIRED ....... 21
SETTING THE VOLTAGE PARAMETERS - WHERE BOTH SET AND RESET VALUES ARE
REQUIRED................................................................................................................................................... 21
SETTING THE TIMER.................................................................................................................................. 21
DAU DC ALARM MODULE ----------------------------------------------------------------------------------------------------- 22
OPERATING MODES------------------------------------------------------------------------------------------------------- 22
FUNCTIONS AND FEATURES ------------------------------------------------------------------------------------------- 22
INSTRUMENTATION ------------------------------------------------------------------------------------------------------- 22
LOCAL AND REMOTE ALARMS AND INDICATIONS ----------------------------------------------------------------- 22
DAU SET UP PAGES ------------------------------------------------------------------------------------------------------- 25
EQUALISE SELECTION ---------------------------------------------------------------------------------------------------- 27
FLOAT SELECTION -------------------------------------------------------------------------------------------------------- 27
BATTERY TEST ------------------------------------------------------------------------------------------------------------- 27
BATTERY DISCHARGE TEST PARAMETERS. ------------------------------------------------------------------------ 28
BATTERY HIGH IMPEDANCE ALARM ---------------------------------------------------------------------------------- 28
SETTING UP THE HIGH IMPEDANCE ALARM ------------------------------------------------------------------------ 28
SET UP PAGE SELECTION ----------------------------------------------------------------------------------------------- 28
ALARM SET UP ------------------------------------------------------------------------------------------------------------- 31

25/07/07 J2959BU01 REV 0.doc 2


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

INTERFACE MODULE ----------------------------------------------------------------------------------------------------- 35


8 RELAY EXPANSION MODULE------------------------------------------------------------------------------------------ 36
SECTION 5 __________________________________________________________________ 37
DESCRIPTION OF CONTROLS AND INDICATIONS ---------------------------------------------------------------------- 37
SECTION 6 __________________________________________________________________ 41
START-UP & SHUTDOWN ----------------------------------------------------------------------------------------------------- 41
PRE-START CHECKS------------------------------------------------------------------------------------------------------ 41
COMMISSIONING PROCEDURE----------------------------------------------------------------------------------------- 41
START-UP PROCEDURE ------------------------------------------------------------------------------------------------- 42
NORMAL OPERATION ----------------------------------------------------------------------------------------------------- 43
SHUTDOWN PROCEDURE ----------------------------------------------------------------------------------------------- 43
SECTION 7 __________________________________________________________________ 44
FAULT FINDING INSTRUCTIONS-------------------------------------------------------------------------------------------- 44
PROCEDURES -------------------------------------------------------------------------------------------------------------- 44
TESTING SEMI-CONDUCTORS------------------------------------------------------------------------------------------ 44
STUD MOUNTING SEMI-CONDUCTORS ------------------------------------------------------------------------------ 44
TEST EQUIPMENT REQUIRED ON-SITE------------------------------------------------------------------------------- 45
SETTING-UP INSTRUCTIONS ------------------------------------------------------------------------------------------- 45
6CV CHARGER CONTROLLER.................................................................................................................. 45
SOLUTIONS TO COMMON FAULTS------------------------------------------------------------------------------------- 46
HIGH OUTPUT............................................................................................................................................. 47
LOW OUTPUT.............................................................................................................................................. 47
CHARGER FAULT FINDING GUIDE ........................................................................................................... 49
STACK FAN FAILURES ............................................................................................................................... 49
SECTION 8 __________________________________________________________________ 50
MAINTENANCE INSTRUCTIONS--------------------------------------------------------------------------------------------- 50
TORQUE SETTINGS ------------------------------------------------------------------------------------------------------- 50
SECTION 9 __________________________________________________________________ 51
DRAWING FILE------------------------------------------------------------------------------------------------------------------- 51

25/07/07 J2959BU01 REV 0.doc 3


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 1

EXPLANATION OF HAZARD INFORMATION

To clarify certain points within this manual to ensure proper and safe operation of the equipment,
the following emphasis is used.

Highlights an essential element of a procedure to ensure correctness.


NOTE:-

Highlights an essential element of a procedure for installation or maintenance to


NOTE:- ensure correctness.

Indicates a procedure or practice which, if not strictly observed, could result in


CAUTION:- damage or destruction of equipment.

Indicates a procedure or practice, which could result in injury to personnel or


WARNING:- loss of life if not followed correctly.


Erskine Systems own the copyright to this manual, which cannot be copied,
reproduced or disclosed to a third party without prior written permission.

25/07/07 J2959BU01 REV 0.doc 4


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

HEALTH AND SAFETY PRECAUTIONS

• An authorised, qualified technician reconnecting power.


should only attempt installation, testing,
fault location and repair. • The above instructions must also be
followed before any such connection is
• This equipment carries dangerous modified or renewed.
voltages and stored electrical energy.

• Removal of shrouding can reveal NOTE:- Adjustments should only be


dangerous voltages and/or high carried out with non-conducting tools,
temperatures. Erskine Systems taking care not to touch any item carrying
accepts no responsibility for the safety electricity whilst doing so.
of personnel and property due to any
actions after their removal. • Reference should also be made to the
sections dealing with installation and
• Before touching, or bringing metal fault finding procedures in the
objects, e.g. tools, metal bracelets, equipment manual before installing and
rings or necklaces into contact with making external connections.
items carrying electricity, carry out the
following instructions: • If batteries are supplied as part of the
system, please refer to the battery
• Isolate the AC mains supply external to manufacturers handbook that is
the equipment. Isolate the battery and supplied.
external load from the equipment.
• As under certain conditions, batteries
• Hazardous energy levels may be give off hydrogen gas, care must be
present inside the equipment. Allow DC taken to prevent any naked flames,
filter capacitors to discharge for a cigarettes etc. from igniting it. It is
minimum of 20 seconds, before advisable to prohibit all smoking from
removing any covers. any area or room in which the battery is
situated.
• Discharge all RFI suppression circuits
as above. • Battery electrolyte is corrosive and if
• spilt or splashed on equipment or
person, immediate action should be
CAUTION!:-Do not short circuit taken as indicated in the battery
capacitor terminals. handbook.

• The above instructions must always be • When handling batteries, wear


followed before making any protective clothing to protect eyes and
adjustments, and also before making exposed skin.
any electrical connections to any part of
the equipment for the purpose of • EMC cannot be guaranteed if the
servicing. Such connections should system is operated with the doors open
always be checked for safety before and/or panels removed

25/07/07 J2959BU01 REV 0.doc 5


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 2

INSTALLATION

UNPACKING THE EQUIPMENT

1. Unpack the equipment and carefully check for any damage, which may have occurred during
transit. The equipment must remain upright at all times.

2. Check against the accompanying packing/delivery note to determine whether any part of the
consignment is missing.

3. Any returnable packing cases should be returned to the address on the cases.

4. Report any damage or losses immediately. Refer to Erskine Systems standard conditions of
sale.

USE OF FORK LIFT TRUCK FOR LIFTING THE EQUIPMENT

1. To avoid possible damage (e.g. scratches) to the equipment, first cover the forks with rubber
mats or other suitable material.

2. The forks should then be slotted under the equipment cubicles so as to ensure even weight
distribution - also it is important to ensure the forks reach across to the rear of the cubicle.

LOCATION OF THE EQUIPMENT

1. As the equipment relies on natural convection for cooling purposes, it is important that the
enclosures are sited in a position with a free flow of air. This also applies to equipment fitted
with cooling fans.

2. Do not locate the equipment or position other equipment against it, such that the natural
ventilation paths are blocked or restricted.

3. Do not locate the equipment in an area that has an ambient temperature above the maximum
allowed for.

4. Equipment unless specifically stated shall not be installed in a hazardous area.

5. Equipment unless specifically stated shall not be installed in a mobile environment or a


position subject to vibration.

6. Floor standing cubicles are designed to be bolted to the floor using foundation bolts. Position
the cubicles and mark the floor - remove cubicles and drill the floor for the bolts. The cubicles
can then be placed in position and secured.

7. When batteries are installed ensure that the ambient temperature is suitable for type of cells
used and also adequate number of air changes per hour to prevent battery gas build up.

25/07/07 J2959BU01 REV 0.doc 6


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

NOTE: Should any cabinet modifications be carried out during installation, it is necessary to ensure
that all swarf be removed from within the enclosure to prevent any electrical faults occurring.

CONNECTING THE EQUIPMENT

1. The following cable should be used, to maintain the EMC performance of the equipment.
XLPE insulated to BS5467 or equivalent (BS6724 for low smoke and fume cable) for:-
• Mains Input
• DC Load Output
• Battery Cables
• Alarm Cables

2. Cables shall be steel wire armoured and/or screened. The wire armour or screen of the cable
must be bonded to the gland plates at the cable entry points using a cable gland and bonded
at the opposite end to a local earth path.

Alarm Contacts - BS5308 Part 2. Conductors may be collectively screened.

3. The above sets of cables should be separated from each other by a minimum of 250mm to
minimise noise coupling. The DC load output and battery cables may be routed together.

4. All the above sets of cables must be segregated from other cables at the installation site and
any other sources of electrical noise by a minimum of 250mm.

GENERAL
1. The equipment should first be checked to ensure that any connections which may have
become loose during transit are tightened.

2. Ensure that the supply is suitably rated. Ensure that any loads to be connected are not in
excess of the capability of the equipment.

3. Cable entry is indicated on the appropriate Arrangement Drawing and is via gland plates at
the bottom of the cubicles. The gland plates, which are supplied un-drillled, should be drilled
on-site for the compression glands and/or grommets to be used.

5. Connect an earth connection to the main earth stud provided.

6. Connect the AC mains supply to the terminal block, making sure to connect to the input
voltage that corresponds with that of the mains supply. Phase rotation must be observed on
three phase systems.

NOTE:- The customer earth connection shall be adequately sized to the latest edition of the I.E.E.
wiring regulations or local equivalent and be terminated an a ring type crimp fixed utilising a spring
washer to reduce the chance of the connection becoming loose.

7. Connect all outgoing connections to the terminals provided. Connect any alarm connections
to the terminals provided.

8. Ensure that the gland plate earth cable is refitted after removal.

25/07/07 J2959BU01 REV 0.doc 7


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

NOTE:- When making connections, ensure polarity is correct and refer to the circuit diagram
supplied with the equipment.

25/07/07 J2959BU01 REV 0.doc 8


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

PRESERVATION PROCEDURE (GENERAL)

Generally, common sense prevails when handling and storing spare parts and goods for the
power supply systems.

Goods should be stored in an environment and manner so as to minimise any risk of physical
and climatic damage.

To ensure this the following points should be observed.

All meters should remain in the polystyrene package provided, avoiding moisture and
physical disturbances.

Special care should be taken when handling lamps due to their delicacy.

PCB’s (Static sensitive). - Special precautions must be taken when using and handling
electrostatic devices. If appropriate precautions are not taken, then it is likely that the
device will be seriously damaged or destroyed.

• New or spare PCB's will arrive with electrostatic protective packaging (conductive anti-static
bag). Never remove the board from the package until it is required. Do not stack the PCB's
during storage.

• When replacing a static sensitive PCB observe the following procedure:

• When removed from the anti-static bag, place and connect into the complete equipment
immediately.

• Insert PCB's in anti-static bag immediately on removal from the complete equipment, even if
deemed faulty. (A fault caused by static can disguise the original fault.)

• Do not carry any PCB's without anti-static bags.

• When dealing with PCB's, avoid using nylon clothing, particularly in dry and frosty conditions.

• Simultaneously touch the metal frame of the complete equipment (preferably a bare earth
connection) with one hand and the conductive packaging with the other hand to discharge any
static before fitting.

25/07/07 J2959BU01 REV 0.doc 9


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

RECOMMENDATIONS FOR 24 MONTH STORAGE AND PRESERVATION

Equipment must be packed in sealed wooden crates with desiccant and stored in a covered
warehouse such that equipment’s are protected from direct sunlight, rain, corrosive atmospheres,
flood water and extremes of climate.

Storage temperature range -30oC to +70oC.

(Temperature excursions to -40oC are permitted providing the average temperature is not less
than -30oC, over a 24 hour period.)

Please note that these equipment’s above are NOT suitable for stacking.

EMC HEAVY INDUSTRIAL ENVIRONMENT

The equipment is suitable for use only in the following environment:-

• Heavy industrial type environments where the product is intended to be connected to a power
network supplied from a high or medium voltage transformer dedicated for the supply of an
installation feeding a manufacturing or similar plant.

Therefore the equipment complies to the following European standards:-

• EN50081-2 : Emissions : Heavy Industrial

• EN50082-2 : Immunity : Heavy Industrial

It is advisory that equipment sharing the same electromagnetic environment as Erskine products
should comply with the standards as stated above.

25/07/07 J2959BU01 REV 0.doc 10


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 3

EQUIPMENT DETAILS

CHARGER 6CV220/25
Input Supply 415 Volts 50 Hz 3 Phase 4 Wire AC Mains
Nominal Output 220 Volts @ 25 Amps
Float 240.8 Volts / 22 Amps
Equalise 258.0 Volts / 22 Amps
Commissioning 283.8 Volts / 5 Amps
CEMF Diodes 25 at 25 Amps in 1 stage
Output Voltage Range 242 Vmax, 198.0 Vmin from 5 to 100% load
Earthing Negative Float

6CV SETTINGS
Mains Low Volts 332.0 V
Mains High Volts 498.0 V
DC High Volts DISABLE

BATTERY Nicad HC25P


Configured 172 cells in series

CUBICLE FSZ1 & FS19


Cable Entry Bottom
Ingress Protection IP41
Paint Finish RAL 7032 Semi-Gloss

ALARMS AND INDICATIONS

ALARM SETTING TIME REMOTE LOCAL


Common - - SPCO DAU
CEMF Diode Fail 245.0 V 10 sec Common DAU
Fire Response - - Yes Red
Fuse Trip - - Common DAU
Breaker Open - - Common DAU
Input LV 192.6 / 200.0 V min - -
Standby Supply - - - Red
K4 DE 2 sec - -
K5 DE 2 sec - -

25/07/07 J2959BU01 REV 0.doc 11


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 4

DESCRIPTION OF OPERATION

THE SYSTEM

The system supplied comprises of the following elements:

THE CHARGER - One off current limited, constant voltage type charger utilising the thyristor
phase control method of regulation. This is 100% rated to supply the load and its associated
battery. The charger supplies the load and provides a recharge current for the batteries. In the
event of a mains failure, the batteries will continue to support the load for the required standby
time.

THE BATTERIES - The batteries are recharged by the charger. They consist of 172 off NiCad
cells and are designed to support the load for the required standby time.

THE ALARMS - The charger is fitted with various alarms that are provided to enable monitoring
of the charger operation and the battery condition. The DAU Alarm Module is detailed later in this
manual. The main alarms fitted are:-

AC SUPPLY FAIL
CHARGER FAIL
LOW VOLTS
HIGH VOLTS
HIGH VOLTS TRIP
EARTH FAULT
CEMF DIODE FAIL
FUSE TRIP
FIRE RESPONSE INDICATOR
BREAKER OPEN
INPUT LOW VOLTS

25/07/07 J2959BU01 REV 0.doc 12


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

6CV CHARGER DESCRIPTION OF OPERATION

The three phase and neutral mains supply is first transformed via an isolating transformer into a
suitable AC level for conversion into DC.

Regulation and rectification are provided by a fully controlled thyristor bridge. The bridge is
controlled via three modules: The Control Module, the Interface Module and the Drive Module.

The thyristors conduct in the forward direction in a similar manner to diodes, but only after a
positive triggering signal with respect to the anode is applied to the gate. Once triggered the
thyristor will continue to conduct for the rest of the half cycle. It is therefore possible to control
the mean output voltage of the bridge by controlling the instant in every half cycle at which the
gate pulses are applied.

Any rise in output voltage causes the firing pulses to be applied later in the cycle to decrease the
output voltage. Conversely, if there is a fall in output voltage the pulses will be applied earlier in
the cycle to increase it, thus a constant output voltage is maintained.

During normal operation the current circuit senses the output via a shunt. If this increases
beyond a pre-determined level, the current limit circuit will begin retarding the control pulses
accordingly to maintain the set current, and consequently reduce the voltage.

The thyristor stack relies on a fan circuit to protect the stack from overheating as indicated in the
diagram below.

F4
A1

TS1 (90oC)
F5
FAN2 FAN1

A4

A2
TS2 (100oC)

A5

A6

The above circuit shows the operation of the stack fan failure circuitry. Fan 1 is permanently on,
Fan 2 will only operate when the temperature exceeds 90oC as dictated by thermal switch TS1.
TS2 will initiate the shutdown signal to the control card if the temperature exceeds 100oC.
Terminals A2 and A4 are utilised for fan fail sensing to remote contacts and/or indication.

25/07/07 J2959BU01 REV 0.doc 13


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

THE INTERFACE MODULE


This contains all the high voltage components, all hardwired connections into the charger system
and ribbon cable connection to the control module.

The module provides:

• DC Power Supply for the control module


• Synchronisation input for the Control Module
• Earth Mode Selection via links
• Single Pole change-over contacts for remote indication of control module status.

Positive or negative earth modes are selectable via links LNK1-LNK4. The earth mode is factory
pre-set for the equipment supplied and must NOT be altered on site. Check the equipment
Circuit Diagram to determine the correct earth mode if it is suspected this may have been
tampered with. If the equipment is of a floating earth system, no modification of the board is
necessary.

THE CONTROL AND DRIVE MODULES


The function of the Control Module is to provide phase controlled firing signals to the Power
Thyristors, correctly positioned to maintain the power output required for voltage and current
regulation.

The Drive Module converts the Phase Control outputs from the Control Module into isolated drive
signals for the thyristors.

The Control Module provides:

• Differential voltage and current control.


• Soft-start facility. This prevents excessive surge when switched on.
• Three independent levels of voltage and current; i.e. Commission, Float and Equalise.
• Droop current share facility - selectable via link.
• Automatic shutdown and protection facilities.

The following conditions will cause the charger to shut-down. In each case, once the condition
has cleared the charger will re-start under soft-start control.

• If the charger output current exceeds the peak detection level.


• If an external shutdown input is applied.
• If the charger output voltage exceeds the high voltage trip level and remains high for
an adjustable timer period (selectable via links). An external inhibit input will override
this facility.
• If the average Mains Voltage goes out of limits.
• If there is an AC phase fail.

If the thyristor stack temperature exceeds a trip point, the charger output current is limited to a
pre-set level.

The charger will be prevented from starting up on negative phase rotation supplies.

25/07/07 J2959BU01 REV 0.doc 14


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

6CV CONTROL MODULE - ARRANGEMENT

CON 2 CON1
DC.HV BAL.1 BAL.2

HV RESET
HV NTC CAL
NC
RSD
PR

HL
V.STAB
HT
PHASE FAIL

190mm
DROOP
CON 5
VC1 VC2 VC3 CL1 CL2 CL3
CL

VC2

VC3 ACLV ACHV

CON5

350mm

6CV DRIVE MODULE - ARRANGEMENT

CON 1
CON 3

CON 4

CON 5

190mm

CON 6

CON 7
T7

CON 8
F2 F1

CON 2

177mm

25/07/07 J2959BU01 REV 0.doc 15


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

6CV INTERFACE MODULE - ARRANGEMENT

CON 10 CON 7

T1

244mm
T4
T2

T3

F1 F2 F3

152mm

25/07/07 J2959BU01 REV 0.doc 16


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

DESCRIPTION OF THE CONTROL MODULE’S LED’S AND POTENTIOMETERS

LED / POTENTIOMETER DESCRIPTION


‘HV’ LED This LED indicates that the DC high voltage level has been reached.
The charger will automatically shutdown on this fault condition.
When the fault has cleared the charger will automatically restart.
‘NC’ LED This LED indicates that a fault has occurred with the NTC probe
(where fitted). The fault should be rectified as soon as possible to
ensure correct charging of the battery under varying temperatures.
‘PR’ LED This LED indicates that the phase rotation is incorrect. The correct
phase rotation should be made to enable the correct functioning of
the charger system.
‘HL’ LED This LED indicates that the AC voltage has become high or low by
±20% of the input voltage. The charger will automatically shutdown if
this fault condition occurs.
When the fault has cleared the charger will automatically restart.
‘VC2’ LED This LED indicates that the charger is operating in the ‘Boost’ mode.
‘VC3’ LED This LED indicates that the charger is operating in the ‘Commission’
mode.
‘CL’ LED This LED indicates the charger is in ‘Current Limit’.
‘HT’ LED This LED indicates that the charger stack has reached its high
temperature rating. The charger will be automatically shutdown under
these conditions. When the fault has cleared the charger will
automatically restart.
‘RSD’ LED This LED indicates that the remote shutdown capabilities of the
charger has been initiated.
‘PHASE FAIL’ LED This LED indicates that one or more of the charger input phases has
failed. The charger will be automatically shutdown under these
conditions. When the fault has cleared the charger will automatically
restart.
‘DC HV’ Potentiometer This is used to set the DC High Voltage shutdown level.
‘BAL 1’ Potentiometer This is used in conjunction with ‘BAL 2’ to adjust the balance of the
system.
‘BAL 2’ Potentiometer This is used in conjunction with ‘BAL 1’ to adjust the balance of the
system.
‘ACLV’ Potentiometer This is used to set the AC Low Volts level.
‘ACHV’ Potentiometer This is used to set the AC High Volts level.
‘NTC CAL’ Potentiometer This is used to adjust the calibration level setting of the NTC probe.
‘DROOP’ Potentiometer This is used to adjust the ‘Droop’ level of systems in parallel.
‘VSTAB’ Potentiometer This is used to set the voltage stability of the system.
‘VC1’ Potentiometer This is used to set the ‘Float’ voltage level of the system.
‘VC2’ Potentiometer This is used to set the ‘Boost’ voltage level of the system.
‘VC3’ Potentiometer This is used to set the ‘Commissioning’ voltage level of the system.
‘CL1’ Potentiometer This is used to set the ‘Float’ current level of the system.
‘CL2’ Potentiometer This is used to set the ‘Boost’ current level of the system.
‘CL3’ Potentiometer This is used to set the ‘Commissioning’ current level of the system.

25/07/07 J2959BU01 REV 0.doc 17


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

VOLTAGE DETECTION MODULES (VDVD)

The VDVD (Voltage Detection) alarm module is designed to sense high and low DC voltage.
This is achieved by monitoring the DC supply and comparing it with a reference voltage. An
alarm is then generated when the sensed voltage goes outside pre-set levels.

NOTES:
a) If a blocking diode is included in the system and the module is configured to sense the voltage
on one side of the diode and gain its power supply from the other side link LK3 will be cut
between terminals A & B, thus allowing for a separate voltage sense signal, on terminal A, and
module power supply, on terminal B. e.g. In cases where the module is configured to sense a
charger failure.
b) If a blocking diode is not fitted the link between terminals A & B will not be cut and terminal A
will not be used.

Hence, if the sensed voltage level goes outside a pre-set level, then, in the case of low volts
alarm, the relay will de-energise or, in the case of high volts alarm, the relay will energise with a
subsequent change in state of the volt free contacts. I.e. For normal healthy conditions a low
volts detection relay will be energised and a high volts detection relay will be de-energised.

Also provided is an adjustable time delay to prevent the alarm tripping for short interruptions in
monitored voltage.

Typical applications for these types of modules include:

Charge Fail, Low Battery Volts, High Battery Volts, Battery Discharging, Voltage Detection, Low
Inverter Input Volts, High Inverter Input Volts, etc.

SPECIFICATION

The modules are available for use with the following nominal DC voltages:- 12, 24, 30, 48/50, 60,
110/120 and 220/240 (when used with an additional power supply module).

VDVD Dual channel module.


Voltage set point adjustment -25% to +40% of nominal voltage.
Voltage re-set point adjustment -1% to -25% of nominal voltage.
Timer operation mode Normal or High (CH2 only).
Timer range 0.5 - 30 seconds or 30 - 60 seconds.
Remote sensing Positive supply and sensing terminals can be split to enable
separate supply and voltage sensing.
Alarm contact ratings DPCO volt free contacts.
3A, 250V, 80W - DC
220VA - AC

25/07/07 J2959BU01 REV 0.doc 18


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

VDVD BOARD ARRANGEMENT

A BD
SET

SET R7
TERMINATIONS
R5
RESET
A POSITIVE VOLTAGE SENSING
RESET R18

R16 B POSITIVE DC POWER SUPPLY


TIME
NORMAL
TIME R23 D NEGATIVE DC POWER SUPPLY
R21

HIGH RL1 RL2


LED1 LED2

RL1 RL2

1 2 3 45 6 1 2 3 4 5 6
1 2 3 4 5 6 1 2 3 4 5 6
VD CH1 VD CH2
CHANNEL 1 CHANNEL 2

NOTE: For single channel modules channel 2 only is used.

BLOCK DIAGRAM

VOLTAGE VOLTAGE CH1


TIMER
DETECTION COMPARATOR RELAY

DC VOLTAGE VOLTAGE CH2


TIMER
SENSING DETECTION COMPARATOR RELAY

LINK

DC STABILISED POWER STABILISED POWER


SUPPLY FOR RELAY SUPPLY FOR SENSING
SUPPLY CIRCUITS & TIMER CIRCUITS

DESCRIPTION OF BLOCK DIAGRAM

The DC supply provides both power for the relay drive circuits and a stabilised logic power supply
for the control circuits, and with the link made between terminals A & B the voltage sense signal.
If the link was not made a separate sense signal would be applied to terminal.

The sensed signal is then compared, on both channel 1 & 2, with two independent pre-set
voltage reference levels which enable, via the timer circuits, the alarm relays to function.

25/07/07 J2959BU01 REV 0.doc 19


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SETTING/CHECKING INSTRUCTIONS

This procedure must be followed in the sequence given to set up, modify, or check the operating
levels of the alarm module.

The preferred method for modifying the parameters of the module is to initialise the
potentiometers, as described below, and then adjust the charger output voltage to simulate the
operating level required. Refer to the charger operating instructions for details on modifying the
charger output voltage. Remember this must be reset before putting the system back on line.

If a charger does not form part of the system, is not of the constant voltage type, or it is not
possible to use the charger, an appropriately rated DC power supply can be used as an
alternative to simulate the voltage supply. This must be connected in place of the normal supply,
i.e. the alarm module must be completed isolated from the system. Refer to the main circuit
diagram for connection details.

Assuming the charger is used as a variable DC power supply the battery and load must be
disconnected in order to check/set the alarm.

CHECKING THE OPERATING LEVELS


To prove the settings simply increase or decrease the DC power supply accordingly and monitor
the levels at which the relay/relays change state.

FOR SETTING UP PURPOSES ONLY, INITIALISE THE MODULE AS FOLLOWS:

Channel 1 R5 marked 'SET' (Trip) - fully clockwise.


R16 marked 'RESET' (Clear) - fully anti-clockwise.
R21 marked 'TIME' - fully anti-clockwise.
Channel 2 R7 marked 'SET' (Trip) - fully clockwise.
R18 marked 'RESET' (Clear) - fully anti-clockwise.
R23 marked 'TIME' - fully anti-clockwise.
J1 and J2 to Normal.

Voltage detection modules should be set up using the following procedures, which are written in
respect to channel 1, (channel 2).

25/07/07 J2959BU01 REV 0.doc 20


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SETTING THE VOLTAGE PARAMETERS - WHERE SET (TRIP) VALUES ONLY ARE
REQUIRED
Energise the variable DC supply and adjust this to the required set level. Then turn
potentiometer R5, (R7) slowly anti-clockwise until the relay just energises. If the module is being
used to sense low voltage turn R5, (R7) slowly clockwise until the relay just de-energises.

The module has now been set, however if a time delay is required refer to the section; "Setting
the timer" below.

SETTING THE VOLTAGE PARAMETERS - WHERE BOTH SET AND RESET VALUES ARE
REQUIRED
Energise the variable DC supply and adjust this to the upper voltage level. i.e. The reset (clear)
point for a low voltage detection module, and trip point for a high voltage detection module. Then
turn potentiometer R5, (R7) until the relay just energises.

Turn potentiometer R16, (R18) fully clockwise. Reduce the variable DC power supply to the
lower voltage level. i.e. The trip point for a low voltage detection module and reset (clear) point for
a high voltage detection module. Then slowly adjust potentiometer R16, (R18) until the relay just
de-energises.

The module has now been set, however if a time delay is required refer to the next section.

SETTING THE TIMER


Unless the module has been specifically supplied to allow a time delay to occur for high volts
conditions, as is indicated by the position of the jumpers J1 and J2, a time delay should only be
applied to low volts conditions.

The variable DC supply should be adjusted until a healthy condition exists. Then turn
potentiometer R21, (R23) to the approximate position required. Note, this potentiometer provides
a linear adjustment of the time period between 0.5 and 30 seconds, or 30 to 60 seconds if the
link LK1 or LK2 is broken. The time delay can then be proved by quickly simulating an abnormal
condition, and then timing the period it takes for the alarm to operate.

25/07/07 J2959BU01 REV 0.doc 21


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

DAU DC ALARM MODULE

This module provides system


instrumentation, control and
alarm functionality for single
or three phase thyristor
charger systems. The device
consists of a display/user
interface module which is
capable of front panel
mounting, and an interface
module for mounting within
the panel.

OPERATING MODES
The DAU user interface has
three modes, or levels, of
operation: User mode; set-up
mode; and service mode.

User mode; this is the


normal mode of operation.
The user has access to all the screens contained in the user level. These provide system
measurements, charger mode & system alarm status information and allow selective control of
the system.

Set-up Mode; provides access to all the user settable parameters screens. These allow the
various alarm settings and control features, to be configured or adjusted as required by the user.
Entry into this mode is protected by a user settable 4 digit password. (Note PLEASE KEEP A
RECORD OF YOUR PASSWORD, if you change it, as once you exit this mode you will be
denied access in the future with out entry of the correct password.

Service Mode; the unit functions as in set-up mode but also unlocks restricted access features,
such as analogue input calibration and control output testing. These functions are password
protected and are not accessible to the user. The Navigation around these screens, and
adjustment of the various parameters is achieved by using the push buttons which are present on
the front panel user interface module the function of which is described below.

FUNCTIONS AND FEATURES


INSTRUMENTATION
The module provides an LCD display for the indication of the charger output voltage and current.
Indications have an accuracy of ±1.5% or better. The display also serves for programming the
system control and alarm functions. In the instrumentation mode, the display indicates both
voltage and current.

LOCAL AND REMOTE ALARMS AND INDICATIONS


Facilities are provided for alarm reset, and LED test. All local LED indications are configurable
individually to be reset manually or automatically. All alarm settings have an adjustable time
delay of at least 30 seconds. In addition to the front panel time delayed LED for each alarm
function, an internally located red LED illuminates as soon as the alarm condition is initiated i.e.
before the adjustable time delay. All alarm and control functions are individually configurable from
the front panel display module.

25/07/07 J2959BU01 REV 0.doc 22


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

Alarm/ LED Function


Function Colour
AC Supply Green The charger is on and receiving an AC supply.
On

Note: AC Supply On does not indicate if the AC supply is present at the cubicle input
terminals if the charger has been switched off via its input circuit breaker. Isolate elsewhere.
AC Supply Yellow Indicates that the normal supply is not present, ie. Charger is off
Fail and does not have an AC supply (see note above).
Equalise Yellow Selection of a higher charger output voltage.
When enabled can be selected for Manual or Automatic Equalise
following an AC supply failure.
This feature is normally disabled on systems supplying VRLA
batteries.
DC Low Yellow Indicates that the DC voltage is below the pre-set level.
Volts
DC High Yellow Indicates that DC voltage is above a pre-set level. The alarm setting
Volts threshold is raised as required when the system is selected for the
equalise charge mode to prevent nuisance tripping.
Earth Fault Yellow Operates when the insulation resistance of either the positive or
negative poles to earth falls below a pre-set level and the other pole
stays above 2MΩ.
Charger Fail Red Both the voltage and current from the charger are below the pre-set
levels.
DC High Red As well as the high volts alarm it is also possible to set the DAU to
Volts Trip trip the charger input supply off if the voltages rises above the set
point. This trips the charger input circuit breaker when the voltage
is above the threshold setting.
High Battery Red This indicates when the internal resistance of the battery rises to a
Impedance level that would prevent it from operating satisfactorily on load.
DC Low On display This feature, when enabled, is provided to operate a contactor to
Volts only when disconnect the battery from the load when the voltage falls below a
Disconnect enabled pre-set level. Automatically resets on resumption of battery
charging.
Remote Red and on Inputs are provided to monitor up to five digital inputs. When active
Inputs display when the input’s label will be shown on the display and incorporated into
enabled the group alarms
Remote The DAU is equipped as standard with two output changeover
Outputs relays to which the above alarms can be mapped.
Remote The DAU can be connected to an optional separate eight relay
expansion module for remote indication or system functions.
relays

25/07/07 J2959BU01 REV 0.doc 23


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

FRONT PANEL CONTROL AND DISPLAY


The unit incorporates a screen for the display of system parameters and operator interaction
during system set-up or interrogation and set-up routines.

The system has display pages giving the system parameters. The left arrow and right arrow push
button will allow an operator to cycle through and select the required page.

The control push buttons are detailed below. On each page of the DAU display, the ‘active’ keys
(those which may be selected), are shown on the bottom line of the display.

Push Button Functions


During set-up mode this pushbutton will increment a parameter.

During set-up mode this pushbutton will decrement a parameter.

This button moves the displayed page to the next one on the left allowing the operator
to cycle through the display pages. During set-up mode this pushbutton will allow
navigation to the required set up page. Also used to move between the digits of the
password and other numeric parameters in set up.
This button moves the displayed page to the next one on the right allowing the operator
to cycle through the display pages in a reverse order to that of the left arrow
pushbutton. During set-up mode this functions as per the left arrow.
In normal mode this push button will cause the display to go to the home page which
displays the system voltage. While in set-up mode this button will cause the unit to
exit from the currently displayed page to the home page in the current level of the set-
up mode page structure. Referred to as Home in the setting up instructions.
In normal mode, this pushbutton will allow the operator to enter a password code to
gain access into set-up mode. Entry to set-up mode is protected by a 4-digit number
(see System Settings for details), which the operator must set with the arrow keys.
During set-up mode this pushbutton will accept the displayed settings of the parameter
or value. Referred to as Return in the setting up instructions)
During normal mode this pushbutton will cause all, except the AC Supply On, front
panel LED alarm indicators of the unit to illuminate.
During normal operation, this pushbutton will clear any latched alarms.

INFORMATION PAGES
The pages are displayed during normal operation and give an overview of the system voltage and
current, status, and any alarms.
No changes can be made to the system from these pages.

PAGE DISPLAY
Metering • DC Voltage(s). • Battery Impedance
• Current drawn by the load • Earth fault Vpos
from the system. • Earth Fault Vneg
Active Alarms • Any individual current and latched alarms and their groups.
Charger Mode The current state of the System e.g.:
• Float charging.
• Equalise charging and timer period.
• Charge Fail.
Battery Test • For selection of the battery test mode when enabled.
Earth Fault Test Available for positive and negative if the test circuit is included in the
system design
Battery High Impedance test Available if the test circuit is included in the system design.

25/07/07 J2959BU01 REV 0.doc 24


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

The chart below shows the pages in order. From any of these pages the use of the Home button returns you to the System
overview page. From this page Home displays the software version information.

DAU SET UP PAGES


When the DAU is first powered up, it will flash up information about the unit for several seconds, before displaying the System
Voltage and Current.

The display pages can be scrolled through, by using the left and right arrow keys. Pressing the RETURN key at any of these
pages, allows the user to enter the selected password, gaining access to the Set Up pages as shown below.

25/07/07 J2959BU01 REV 0.doc 25


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

EQUALISE MODE OPERATION

The unit has four different modes of operation for the Equalise function.

The first mode, enables automatic and manual initiation of the function. In this mode the equalise
function can be manually selected at any time, unless there is a charge fail alarm present.

When equalise is selected the output of the charger will start to rise, at a rate depending on the
capacity and state of charge of the batteries, until the Knee Point is reached. This is the point at
which the charging changes from constant current to constant voltage. The pre set equalise timer
period is now started and the charger will return to float when this is timed out (or a charge failure
occurs).

In this mode, a charge fail will automatically start a equalisation cycle. Which can be terminated
manually at any time as shown above.

The second mode allows Manual equalise with a remote enable.


This modes allows the manual selection of equalise as above provided that the Remote Mode
Control (RMC) input is active. If not present this will inhibit the selection of equalise., eg equalise
charging of the battery can be inhibited if a signal for ventilation fan failure is present.

In the third mode, the unit functions as a slave unit which is remotely controlled from a master
device using the RMC input; eg a system level Charge Fail Auto Equalise (CFAE) module. In this
mode the state of the RMC input determines the chargers equalisation mode. It will indicate the
present mode of operation but all manual control is disabled.

SET UP PAGE FUNCTION SETTING RANGE


Equalise Mode • DISABLE; Float only, normally selected for VRLA
batteries.
• MANUAL/AUTO: DAU controls the equalise function.
• REMOTE ENABLE: Manual selection of equalise
from DAU fascia but is enabled or disabled remotely.
• REMOTE CONTROLLED: DAU acts as a slave and
equalise is initiated from only a remote contact
Charge Fail Trip The voltage at which the auto equalise cycle is enabled. 75 – 100%
Charge Fail Reset The voltage at which the charge is switched into equalise. 100 – 140%
Charge Fail Delay Time between the charge fail set point being reached and 0 – 120s
its activation.
Knee Volts The point at which the battery goes from constant current 100 – 125%
to constant voltage charging and the equalise timer is
started.
Equalise Timer The time which the charge is in equalise mode after the 0.5 – 24h
knee volts point has been reached. Charge returns to
float mode.

25/07/07 J2959BU01 REV 0.doc 26


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

EQUALISE SELECTION
When the Manual/Auto mode is enabled Equalise is selected by pressing the UP key as shown
below.

Charger Mode Note: Equalise selection is inhibited when the Charge


Mode = FLOAT Fail alarm is active.
Press [UP] to start
Equalise

Charger Mode The charger is now in the *Note that the time is
Mode = EQUALISE equalise mode. To return to only shown once the
Time left = 12hours* float press knee point is reached
Press [DOWN] to stop

FLOAT SELECTION
At any point during the equalise period the charger can be returned to the float mode as shown
above.

BATTERY TEST
A feature of the DAU allowing the battery to be into the site loads. This gives confidence in the
battery to support the load in the event of a mains failure. To do this the charger is shut back to a
lower voltage (pre set) to allow the battery to discharge into the load and to be on standby in case of
a battery failure. A failure of the test will cause an alarm.

This feature checks the suitability of the battery to support the site load for a given time or for a pre-
set capacity and does not check the full battery autonomy.

A test is terminated voltage and time. If the battery voltage drops below the set level before the
timer period is met then it is failed. If the time is reached before the voltage drops too far then the
battery has passed. See system specification for settings and details below on setting up and
adjustments.

Battery Test Note: Battery test is inhibited when the Charge Fail
alarm is active.
Press [UP] to start
Battery Test

Battery Test The charger is now in the shut


Mode = Battery Test back mode. To return to float
press
Press [DOWN] to stop
Note: Battery Test is inhibited if the AC Supply Fail, Charge Fail, or a previous
Battery Test Failed alarm is present or the charger is in equalise mode. This will
appear on the display.

If the battery fails the discharge test then a latched alarm is generated. This will inhibit any further
battery discharge until reset with the push button.

25/07/07 J2959BU01 REV 0.doc 27


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

BATTERY DISCHARGE TEST PARAMETERS.


These are accessed as described below.

SET UP PAGE FUNCTION SETTING RANGE


Manual Battery Enable or Disable the function.
Test.
Battery Test Fail • Battery test minimum volts. 75 – 125%
Voltage The voltage at which the battery is deemed to have
failed the test if this point is reached before the
time/capacity has been exceeded.
Battery Test Time • Maximum time: 1 – 60m
The test is terminated after a set time has elapsed
provide that the voltage stays above the set level.

BATTERY HIGH IMPEDANCE ALARM


This alarm continuously monitors the battery and its connections for any increase in their
impedance which may affect the ability to support the load in the event of a mains failure.

SETTING UP THE HIGH IMPEDANCE ALARM


Firs the system and its batteries should be connected and fully installed.
Enter the set up pages, using the password, as described below and use the right arrow to navigate
to the High Impedance Alarm page.

Press RETURN twice to reach High Impedance Trip = xx Ohms. This shows the current setting.
Reduce the setting, using the DOWN arrow until the alarm is tripped this is done by checking the
LED on the interface board as this does not have a time delay. Now increase the setting until the
alarm is cleared. If any nuisance alarms occur the setting can be increased accordingly. Press
RETRUN to move to the High Impedance Delay page. This is set to 30seconds as default and can
be adjusted if required although reducing it may cause nuisance alarms. To save the changes
press the HOME button twice to return to the information pages

SET UP PAGE SELECTION


By use of a password (the default is blank) the set up pages of the DAU can be accessed.
Pressing the RETURN key on all information pages will take you to the password screen as shown
below.

25/07/07 J2959BU01 REV 0.doc 28


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

The first page displayed depends on the screen from which Set Up is selected:

Information Page User Set UP Mode Page


Metering Battery Impedance Alarm Set Up Pages
Active alarms Battery Impedance Alarm Set Up Pages
Charger Mode Equalise Set Up Pages
Battery Test Battery Test Set Up Pages
Positive or Negative Earth Fault Test Earth Fault Set Up Pages
Battery High Impedance Test Battery Impedance Alarm Set Up Pages

Navigation to the other pages is via the ï and ðbuttons. RETURN takes you into the relevant
pages and Home will take you back to the Information Pages.
Note; ‘Saving Settings to Non Volatile Memory’ will always be displayed briefly when coming out of
the set-up menus, even if changes have not been made.

If, when you access a set of pages, it is decided that another page of screens is required the Home
button will take you back to the selection level.

NOTE: the DAU has been set up in accordance with your specification, and for the correct
operation of the system. Before making any changes to its settings first check that they do not
affect the operation or safety of the system. Any changes should be limited to alarm and battery
test settings only. Other alarm functions are available within the DAU but are protected by a further
password, which is available on request. If in doubt, please contact Erskine Systems.

25/07/07 J2959BU01 REV 0.doc 29


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

The User Set Up mode password only allows access to the following pages.

Changes can be made to High Volts Shutdown, Low Volts Disconnect and other system function parameters, however, due to the fact that these
affect system safety and operation they are protected by an Engineering Mode password available from Erskine System on request.

25/07/07 J2959BU01 REV 0.doc 30


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

ALARM SET UP
All of the alarm pages have the following
parameters:
Trip; the point at which the alarm is activated (on
a falling voltage for low volt alarms or a rising
voltage for high volts alarms)
Reset; The point at which the alarm is cleared (on
a rising voltage for low volt alarms or a falling
voltage for high volts alarms).
Delay; the period between the alarm being
activated and it being displayed on the front panel
and activation of the remote relay. Note that the
LEDs on the interface module (see below) are
activated instantaneously.
Latch; when enabled the alarm will latch on the
display and remote relay once the time period has
elapsed. To clear the alarm the level must first be
past the reset level and the Alarm Reset button is
pressed. Note that the LEDs on the interface
board are non latching.
Common Alarm Mapping; selects the remote
relay activated by the alarm.
Expansion Relay Mapping; selects the relay
on the expansion module (if fitted) activated by the
alarm.

To enter any of the alarm set up pages press


RETURN at the desired page. The values are
altered with the UP and DOWN buttons. Press
RETURN to carry on to the next page or HOME to
return to the selection page.

Any changes made are automatically saved when


the RETURN or HOME buttons are pressed and
you return to the information pages. There is no
option to cancel the changes.

The diagram to the right shows an example page.


All others are of a similar format.

The table below shows all alarms, the pages in


the order they appear as RETURN is pressed.
A brief explanation of the alarm is given and the
limits of the settings. Voltage alarms are shown
as a percentage of the nominal system volts, 24V,
50V, 110V etc.

*Note :- the +Vs & +Vp terminals allow the


voltage to be sensed at either side of a charger
output blocking diode for systems built with this
feature. Vs is connected to the charger side of
this diode and Vp is connected at the system
side. The can be configured to use the +Vp input
only for systems without a blocking diode.

25/07/07 J2959BU01 REV 0.doc 31


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

Battery High Impedance Resistance of battery circuit at +Ps terminal. Alarms if the
impedance rises above the set point. Resets on low
impedance.
Enable/Disable
Trip Ohms 0.2 – 5.0 Ohm Reset set point less 0.2 Ohm
Delay S 0 – 120s
Latch Enable/Disable
Common alarm relay mapping 1 or 2
Expansion relay mapping 1 to 8

Earth Fault Fault Current +Vp terminal. Alarms when the resistance to
earth either the positive OR negative pole of the DC is low
enough to cause a current, above the set point to flow, in
the earth if a low impedance return path were present.
The other pole must be above 2MΩ .
Trip mA 1,2,4,10mA
Delay S 0 – 120s
Latch Enable/Disable
Common alarm relay mapping 1 or 2
Expansion relay mapping 1 to 8

Low Volts Alarm Voltage sensed at +Vp terminal. Alarms on a falling


voltage, resets on rising voltage.
Trip V 75 – 125%
Reset V 100 – 140%
Delay S 0 – 120s
Latch Enable/Disable
Common alarm relay mapping 1 or 2
Expansion relay mapping 1 to 8

Charger Fail Alarm Voltage sensed at +Vs terminal and current sensed at
charger output shunt. Alarms on a falling voltage AND
falling current , resets on rising voltage OR current.
When AC Fail Active • Enable – CF will alarm when AC failed.
• Disable – CF will not alarm when AC failed.
Trip V 75 – 125%
Reset V 100 – 140%
No Access to these Trip A Fixed at <10% of shunt rating Non adjustable
settings Reset A Fixed at >20% of shunt rating Non adjustable
Delay S 0 – 120s
Latch Enable/Disable
Common alarm relay mapping 1 or 2
Expansion relay mapping 1 to 8

High Volts Alarm Voltage sensed at +Vp terminal. Alarms on a rising


voltage, resets on falling voltage.
Trip (float) V 100 – 140%
Reset (float) V 75 – 100%
Trip (Equalise) V 100 – 140%
Reset (Equalise) V 75 – 100%
Delay S 0 – 120s
Latch Enable/Disable
Common alarm relay mapping 1 or 2
Expansion relay mapping 1 to 8

25/07/07 J2959BU01 REV 0.doc 32


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

25/07/07 J2959BU01 REV 0.doc 33


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

AC Fail AC derived voltage received from charger controller.


Latch Enable/Disable
Common alarm relay mapping 1 or 2
Expansion relay mapping 1 to 8

The following alarms are accessed only through the Engineering Mode password.

High Volts Shutdown Voltage sensed at +Vs terminal. Alarms on a rising


voltage, resets on falling voltage.
Mode • Internal – DAU controls shutdown
• External – Charger controls shutdown, DAU marshals alarm
only.
Trip (float) V 100 – 140%
Reset (float) V 75 – 100%
Trip (Equalise) V 100 – 140%
Reset (Equalise) V 75 – 100%
Delay S 0 – 120 secs
Latch Enable/Disable
Common alarm relay mapping 1 or 2
Expansion relay mapping 1 to 8

Low Volts Disconnect Voltage sensed at +Vp terminal. Alarms on a falling


voltage, resets on rising voltage. Used to drive a battery
or load contactor to disconnect and protect a VRLA battery
or for load shedding.
Trip V 75 – 125%
Reset V 100 – 140%
Delay S 0 – 120s
Common alarm relay mapping 1 or 2
Expansion relay mapping 1 to 8

25/07/07 J2959BU01 REV 0.doc 34


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

INTERFACE MODULE
The eight LEDs in the bottom left hand corner, work
independently of the LEDs on the Display Module. They
indicate that the respective alarm is active immediately.
The front display LEDs do not light until after the time
delay has elapsed. This is used for testing and
commissioning the alarm functions.

The Interface is connected to the Display via a null


modem 9 way D Type connector on CON5, and to DCV
the charger controller by a 20 way ribbon cable on X16.
All other connections are via the two part connectors
listed below.

Ref Function RC
1.1 Group 1 volt free alarm (NO)
1.2 Group 1 volt free alarm (COM)
1.3 Group 1 volt free alarm (NC)
2.1 Group 2 volt free alarm (NO)
2.2 Group 2 volt free alarm (COM)
2.3 Group 2 volt free alarm (NC)
E Earth fault alarm ground connection
+12 High Volts Shut Down
HVSD High Volts Shut Down
-PS Power supply –Ve
+VS System voltage sense +Ve
-COM Voltage sense common –Ve
+VP Charger voltage sense +Ve
+PS Power supply +Ve
-A Current sense 75mV –Ve ü
+A Current sense 75mV +Ve ü
COM Charger common ü
P AC Supply On from charger ü
FC Remote fault input common
FC Remote fault input common
RMC Remote control mode input
F1 Remote fault input 1
F2 Remote fault input 1
F3 Remote fault input 1
F4 Remote fault input 1
F5 Remote fault input 1

All connection marked ü in the RC column are connected to the DCV controller via the 20 way
ribbon cable on X16.

25/07/07 J2959BU01 REV 0.doc 35


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

8 RELAY EXPANSION MODULE

When incorporated into a system this is connected to the DAU via a 10 way ribbon cable. One
or more alarms can be mapped to one or more relays using the ‘Expansion Relay Mapping’ page
and changing the position to [X]. The LED indicates when the relay is energised. Each relay (K)
provides a set of volt free change over contacts via the corresponding terminal block (X). the
relay can be configured, within the DAU Engineering mode, to energise or de-energise on alarm.

25/07/07 J2959BU01 REV 0.doc 36


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 5

DESCRIPTION OF CONTROLS AND INDICATIONS

CONTROLS AND INDICATIONS DESCRIPTION


AC INPUT CIRCUIT BREAKER This connects the charger input to the
incoming AC mains supply. It may be opened
to isolate the charger from the mains supply
for maintenance purposes etc. The breaker
0
also functions as the charger On/Off switch.
In the event of a fault the breaker will be
tripped to shutdown the charger.

CHARGER OUTPUT ISOLATOR This connects the charger output to the


battery and distribution circuit. The isolator
may be opened to isolate the charger from
these circuits for maintenance purposes etc.
0

COMMISSION CHARGE SELECT SWITCH This switch is used to select the chargers
initial commissioning mode. Refer to the
COMMISSIONING ‘Commissioning Procedure’ shown on the
OFF circuit diagram.

ON

25/07/07 J2959BU01 REV 0.doc 37


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

CONTROLS AND INDICATIONS DESCRIPTION


INPUT VOLTMETER SELECTOR SWITCH This switch is used in conjunction with the
VOLTMETER CHARGER INPUT VOLTMETER. The reading
obtained on the meter corresponds to the
OFF voltage measured on the phase indicated by
L1-L2 L1-N the switch position. If the switch is placed into
the ‘Off’ position meter operation is inhibited.
L2-L3 L2-N

L3-L1 L3-N

INPUT AMMETER SELECTOR SWITCH This switch is used in conjunction with the
AMMETER CHARGER INPUT AMMETER. The reading
obtained on the meter corresponds to the line
OFF current measured on the phase indicated by
the switch position. If the switch is placed into
the ‘Off’ position meter operation is inhibited.
L3 L1

L2

BATTERY CIRCUIT BREAKER This connects the battery to the charger


output and distribution circuits. The breaker
may be opened to isolate the battery from
these circuits for maintenance purposes etc.
0

DISTRIBUTION FEED CIRCUIT BREAKER This breaker connects the distribution circuits
to the charger output. The breaker may be
opened or closed as required by the load
connected.
0

25/07/07 J2959BU01 REV 0.doc 38


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

CONTROLS AND INDICATIONS DESCRIPTION


FIRE RESPONSE INDICATOR Located on the fire response indicator module,
this lamp will indicate a temperature rise,
which could be the result of a fire occurring
within the system.

AC INPUT AMMETER This meter indicates the amount of current


being drawn from the incoming AC mains
supply. The meter is read in conjunction with
the meter phase select switch to display the
individual phase currents. The values obtained
will depend on the state of charge of the
battery and the size of any load connected.

AC INPUT VOLTMETER This meter indicates the voltage level being


supplied to the charger from the incoming AC
mains supply. The meter is read in
conjunction with the meter phase select
switch. The readings obtained should be
approximately equal to the values stated in the
‘Equipment Details’ section of this manual.

BATTERY AMMETER This meter indicates the current flow through


the battery circuit. During normal mains
healthy conditions the meter will indicate the
battery recharge current. This reading will vary
depending on the state of charge of the
battery, generally a discharged battery will
consume a large current from the charger.
The level will decrease as the battery
becomes charged. In the event of a mains
failure the meter will display the current being
supplied by the battery to the load. The
reading obtained will vary depending on the
size of the load connected.
BATTERY VOLTMETER This meter indicates the voltage level present
at the battery terminals. During mains healthy
conditions the reading displayed should be
approximately equal to the ‘Float’ value shown
on the circuit diagram. In the event of a mains
or charger failure occurring, on a single
charger system the meter will indicate the
battery voltage - this will fall as the battery
becomes discharged. In the event of a single
charger failure on a dual charger, single
battery system the remaining charger will
continue to supply the battery and the reading
should not alter. Refer to the circuit diagram to
determine the configuration supplied.

25/07/07 J2959BU01 REV 0.doc 39


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

CONTROLS AND INDICATIONS DESCRIPTION


DISTRIBUTION INPUT CIRCUIT BREAKER This breaker connects the distribution circuits
to the charger output. The breaker may be
opened or closed as required by the load
connected.
0

LOAD CIRCUIT BREAKERS These breakers connect the individual load


circuits to the distribution circuit. Each
breaker may be opened or closed as required
by the load connected.

0-OFF 0-OFF 0-OFF 0-OFF

1-ON 1-ON 1-ON 1-ON

25/07/07 J2959BU01 REV 0.doc 40


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 6

START-UP & SHUTDOWN

PRE-START CHECKS

Once the equipment has been installed, the following (mainly visual) checks should be performed
prior to starting the equipment.

1. Check the equipment is secure and as level as possible (this is particularly important with
respect to battery cubicles).

2. Ensure the external surfaces of the equipment are free from dust, packing materials, etc.

3. Check all switches, meters and LED’s are in good condition and free from transit damage.

4. Check inside cabinets to ensure there are no obvious defects; such as loose PCB, loose or
broken connectors, loose component mounts, etc.

5. Check all fuses are secure and in place.

6. Check all external wiring to the equipment is correctly wired up and safely installed.

7. Check:-
Mains AC feeds to the charger.
Remote alarm connections.
Remote control connections.
DC load circuit connections.
Battery connections and inter-cell connections.

COMMISSIONING PROCEDURE

Before entering into operational service, it is essential that the batteries receive a once only
commission charge. This charge prepares the cells for a long and trouble free service life at
maximum capacity. To commission charge the batteries, follow the start up procedure shown on
the Circuit Diagram. The battery manufacturers Operation Manual should also be referred to, to
determine exact commissioning procedure and charge duration.

25/07/07 J2959BU01 REV 0.doc 41


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

START-UP PROCEDURE

In order to start the equipment whether it be following a controlled shut-down or post installation,
the following procedure should be observed.

The instructions should be followed in the order listed and the result given must be achieved
before proceeding on to the next instruction.

It should be noted that in some cases the results listed may take some time to occur (e.g. the
charger is fitted with a 'soft-start' facility where by the output voltage takes several seconds to
rise up to the operating level). Always operate the alarm reset push-button before observing the
results listed to clear any spurious alarm conditions caused during the start-up operations.

Procedure:-

ACTION
Initialise the System controls as stated:-
nOn the system…
• AC INPUT CIRCUIT BREAKER – OPEN
• CHARGER OUTPUT ISOLATOR – OPEN
• BATTERY CIRCUIT BREAKER – OPEN
• DISTRIBUTION FEED CIRCUIT BREAKER – OPEN
• DISTRIBUTION INPUT CIRCUIT BREAKER – OPEN
• CONTROL CIRCUIT BREAKERS - OPEN
• LOAD CIRCUIT BREAKERS - OPEN
Energise the incoming mains supply.
1. Close the AC INPUT CIRCUIT BREAKER
2. Close the CHARGER OUTPUT ISOLATOR
3. Close the DISTRIBUTION FEED CIRCUIT BREAKER
4. Close BATTERY CIRCUIT BREAKER
5. Close the DISTRIBUTION INPUT CIRCUIT BREAKER
6. Close the CONTROL CIRCUIT BREAKERS AS REQUIRED
7. Close the LOAD CIRCUIT BREAKERS AS REQUIRED
The charger is now up and running. The charger is supplying a recharge current to the
battery and also supplying the requirements of the load. In the event of a mains failure, the
charger will cease to operate and the load will be supported by the batteries for the
designed standby time.

25/07/07 J2959BU01 REV 0.doc 42


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

NORMAL OPERATION

During normal operating conditions only the following lamps should be illuminated:-

MAINS ON
FLOAT (or Equalise)

If any other lamps illuminate then an alarm condition is indicated. The cause should be
investigated and if possible rectified. Please refer to the 'Description of Controls' and 'Fault
Finding' sections of this manual.

SHUTDOWN PROCEDURE

To shutdown the system for maintenance purposes, etc., the following procedure should be
observed.

.NOTE:- If the system is shutdown the supply to the load may be lost. Refer to Circuit Diagram
supplied

CAUTION!:- Before proceeding with maintenance of the equipment consult the Health and Safety
section of this manual.

WARNING!:- Even though the equipment is shutdown, high voltages may still be present within
the cubicle. Refer to the Circuit Diagram supplied and isolate elsewhere before working on the
equipment.

Procedure:-n TOTAL SHUTDOWN

ACTION
1. Open the LOAD CIRCUIT BREAKERS
2. Open the DISTRIBUTION INPUT CIRCUIT BREAKER
3. Open BATTERY CIRCUIT BREAKER
4. Open the DISTRIBUTION FEED CIRCUIT BREAKER
5. Open the CHARGER OUTPUT ISOLATOR
6. Open the CONTROL CIRCUIT BREAKERS
7. Open the AC INPUT CIRCUIT BREAKER
The charger is now shutdown allowing maintenance work to be performed. Refer
to start-up procedure in-order to turn the system back on when ready.
END

25/07/07 J2959BU01 REV 0.doc 43


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 7

FAULT FINDING INSTRUCTIONS

TESTING SEMI-CONDUCTORS
CAUTION!:- Fault finding should only be
undertaken by competent electrically qualified In almost every instance, a faulty power
personnel who are familiar with the equipment semi-conductor will have a short circuited
operation and it's potential hazards. The safety junction and, because of parallel paths in
instructions at the front of this manual should the circuit, a short circuit device may cause
be read and fully understood before working on several other components in proximity with
the equipment. it in the circuit electrically to also appear
faulty. If this is suspected, disconnect one
This section is designed to provide sufficient end of each device until the faulty
information to enable fault finding diagnosis component is found.
and repair/replacement down to circuit board
level. For more extensive repairs the Also due to parallel paths in the circuit,
assistance of Erskine Systems should be SCR's may not appear high resistance
sought. across anode and cathode, and diodes may
not appear low resistance in one direction
PROCEDURES and high resistance in the other. If there is
any doubt about readings, compare each
Look for the obvious fault. Often a visual component with its equivalents in the circuit;
inspection is all that is necessary to locate large differences found in this way indicate a
a fault - particularly with capacitors. fault condition.

Always check for loose or broken inner Take care when replacing components not
conductors, loose PCB's, etc. to replace forward diodes with reverse
diodes and vice versa, or to fit SCR's the
There are NO tests that require removal of wrong way round.
the earth connection from oscilloscopes or
other test equipment. Dual beam STUD MOUNTING SEMI-CONDUCTORS
oscilloscopes must have differential
facilities. Before fitting stud mounting components,
apply a smear of Dow Corning 340 Thermal
There is no practical or satisfactory way of Compound to the mating surfaces.
anticipating a malfunction before it occurs
with this type of equipment; generally the
equipment will work perfectly or shutdown.

25/07/07 J2959BU01 REV 0.doc 44


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

TEST EQUIPMENT REQUIRED ON-SITE

The following is a list of test equipment recommended for the purposes of routine testing, fault
diagnosis and repair.

1. DC stabilised Power Supply


2. AC/DC Clip-on Ammeter
3. Digital Multimeter - True RMS Reading
4. Digital Storage Oscilloscope
5. X - YT Plotter
6. Phase Rotation Meter
7. Variac
8. AC/DC Load Bank of suitable rating

Please contact the Customer Services Manager at Erskine Systems, for the suitability of test
equipment.

SETTING-UP INSTRUCTIONS
6CV CHARGER CONTROLLER

NOTE:- The charger is already set up and the instructions below should only be followed if
the settings require altering.

Before switching the charger on, ensure:


• Correct Phase connection - see note.
• Battery is disconnected.

NOTE:- Failure to observe phase rotation will result in the charger output being inhibited.

TO ADJUST VOLTAGE SETTINGS

1. Connect a load of approximately 5% of the charger nominal current rating to the charger
output.
2. Select the Initial Commission (IC) Charge Mode if applicable.
3. Switch the charger ‘On’
4. To adjust the COMMISSION VOLTAGE, turn the potentiometer marked VC3 clockwise to
increase output voltage.
5. Select the Equalise Charge Mode.
6. To adjust EQUALISE VOLTAGE, turn the potentiometer marked VC2 clockwise to increase
output voltage.
7. Select the Float Charge Mode.
8. To adjust FLOAT VOLTAGE, turn the potentiometer marked VC1 clockwise to increase
output voltage.
9. The Voltages are now set.

NOTE:- Voltage settings are independent of each other and can be set in any order.

25/07/07 J2959BU01 REV 0.doc 45


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

TO ADJUST THYRISTOR TRIGGER BALANCE

1. Switch the charger ‘Off’. Connect an oscilloscope to the DC output of the thyristor/diode
stack.

CAUTION:- Care must be taken when using earthed scopes on a charger with a DC line earthed. It
is recommended that the scope probe is fitted with an isolating device or differential models used.

2. Connect a load of approximately 80% of the charger nominal current rating to the charger
output. Switch ‘On’ the charger.
3. If the charger is in current limit, adjust the relevant current limit potentiometer until the charger
has an output of 80% nominal current.
4. Adjust potentiometers BAL.1 and BAL.2 until the vertical pulses on the scope screen are all
of equal height.
5. The charger is now balanced. Switch the charger ‘Off’ and remove the load.

TO ADJUST THE CURRENT LIMIT SETTING

1. A suitable load must be connected to achieve an output current from the charger slightly
higher than the current limit setting required.
2. Select IC, Equalise and Float Charge modes as before, set the current limit levels as follows:
3. To adjust initial commissioning current limit turn potentiometer CL1 clockwise to increase the
output current.
4. To adjust the equalise current limit turn the potentiometer marked CL2 clockwise to increase
the output current.
5. To adjust the float current limit turn potentiometer marked CL3 clockwise to increase output
current.
6. Current limits are now set.
7. Reconnect the Battery

NOTE:- Current limit settings are independent of each other and can be set in any order.

SOLUTIONS TO COMMON FAULTS

1. Before making any fault finding checks, it is advisable to disconnect any external load so as
not to disguise any fault in the charger unit itself.

2. There are two main fault conditions: Low output and High output. Care must be taken when
determining the type of fault present, as it may be possible that a High output condition has
caused the main fuse in the charger DC output line to fail, hence causing a low output
situation. Zero output is taken to be a low output condition.

25/07/07 J2959BU01 REV 0.doc 46


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

HIGH OUTPUT
1. Check that Mains input is present and that the voltage is correct.

2. Check that the correct number and type of battery cells are connected.

3. Check that the sensing voltage at the controller is the same as at the battery (if fitted).
Trace for bad or missing connections as necessary. Refer to Circuit Diagram for connection
Details (+VE and -VE output terminals).

4. Check that charger is not operating permanently in EQUALISE mode.

5. Disconnect all thyristor gate connections (Yellow leads on controller). If the voltage or output
current is still faulty it is probable that the stack assembly is faulty; replace if necessary.

6. Check controller setting and if control of voltage or current is not possible, replace controller.

LOW OUTPUT
1. Check AC mains input is present and of correct voltage.

2. Check for voltage on transformer primary when Mains Input Circuit Breaker is closed.

3. Check for voltage on transformer secondary.

4. Check for AC input to thyristor stack. If not present, check fuse (terminal A1, A2, CT when
fitted, on PCB).

5. If fuse F1 blown, the stack assembly is probably faulty, replace as necessary.

6. Check correct number and type of battery cells are connected (If fitted).

7. Check supply to the controller, terminals L and N on PCB (refer to Circuit Diagram).

8. Check that the sensing voltage at the controller is the same as battery (if fitted). Refer to
Circuit Diagram for connection Details (+VE and -VE output terminals).

9. Check controller settings and adjust to correct values if possible.

10. Check charger DC output fuses and replace as necessary.

11. Check external connections on the controller (e.g. links).

12. Disconnect each gate connection to the thyristors (Yellow leads on PCB) in turn. If the
removal of the firing signal has no effect on the system output then generally the stack could
be faulty.

13. If no adjustment is possible, replace the controller.

NOTE:-If in doubt any problems should be referred to the Customer Services Manager - Erskine
Systems.

25/07/07 J2959BU01 REV 0.doc 47


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

25/07/07 J2959BU01 REV 0.doc 48


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

CHARGER FAULT FINDING GUIDE


Once a problem has been identified with the aid of the panel indications, the following table can
be used to help identify the cause and cure the fault. Whilst fault finding, the normal start-up and
shutdown procedures should be used. Also the applicable setting up procedures should be
followed.

PROBLEM CAUSES
A B C D E F G H I J K L
Loss of Output Voltage 3 3 3 3 3 3 3 3 3 3 3
High Output Voltage 3 3 3 3 3 3

CAUSES SOLUTIONS
A Charger switched off Switch charger on
B Mains supply faulty or off Restore mains supply
C Blown control or power fuses Check for shorts and replace
D Power semi-conductor open circuits Check for shorts and replace
E Control semi-conductors open circuit Check for shorts and replace
F Thyristors not firing Replace
G Faulty control cards Replace and reset
H Incorrect voltage settings Check and adjust
I Incorrect current settings Check and adjust
J Faulty filter capacitor Replace
K System overloaded Remove some excess load
L Loose wiring connections Check and secure

STACK FAN FAILURES


Before replacement of fans is implemented it should be checked that a fan fail has actually
occurred. If the room temperature rises above the specified limit or the vents are blocked, then
the alarm may come up without a fan failure. Therefore these should be checked when the alarm
comes up but the fans are operating correctly.

25/07/07 J2959BU01 REV 0.doc 49


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 8

MAINTENANCE INSTRUCTIONS

1. As a general principle, it is better not to interfere with the control of this type of equipment,
provided that the equipment is functioning satisfactory. It is recommended that routine
maintenance is limited to simple cleaning and checking that the ventilation paths, etc. are
free from obstruction.

2. The equipment should be checked and cleaned of dust, etc. at periods depending upon the
operating climate. During the regular maintenance period, nuts, bolts and screws should be
checked for correct tightness.

3. The operation of switches, alarms and relays should be checked wherever possible. A visual
check of all components should be made to ensure that components have not deteriorated
from the effect of humidity, temperature, etc. Instruments should be zeroed as required.

4. In the event of faulty operation it is recommended that the fault finding procedures outlined be
carried out and/or consult the Customer Services Manager at Erskine Systems.

TORQUE SETTINGS

The settings shown below are the maximum torque settings to be applied and are for reference
only. Due to the varying strengths of the materials that are to be clamped, the actual torque
settings are left to the discretion of the engineer. The setting used should be sufficient to
securely clamp the materials for a given purpose, without causing damage.

NUTS AND BOLTS/SCREWS TORQUE (Nm) (Ft.lb)


4mm (M4) 8.1Nm 6ft.lb
6mm (M6) 16.3Nm 12ft.lb
8mm (M8) 24.4Nm 18ft.lb
10mm (M10) 32.5Nm 24ft.lb
12mm (M12) 48.8Nm 36ft.lb
THREADED INSERTS AND BOLTS/SCREWS
4mm (M4) 5.4Nm 4ft.lb
6mm (M6) 8.1Nm 6ft.lb
8mm (M8) 13.5Nm 10ft.lb
10mm (M10) 18.9Nm 14ft.lb

25/07/07 J2959BU01 REV 0.doc 50


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 9

DRAWING FILE

CHARGER CIRCUIT DIAGRAM– J2959BC01


DISTRIBUTION CIRCUIT DIAGRAM– J2959BC02
SINGLE LINE DIAGRAM– J2959BC03
BATTERY LAYOUT – J2959BF01
ARRANGEMENT – J2959BH01
INTERNAL ARRANGEMENT – J2959BH03
DAU SETTINGS – J2959BA02

25/07/07 J2959BU01 REV 0.doc 51


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

110V DC EMERGENCY LIGHTING SYSTEM

DCV110/25

INSTALLATION,
OPERATING AND
MAINTENANCE
MANUAL
Document No. : J2961BU01 REV 0

For

MITSUBISHI
SAAD AL ABDULLA ‘A’, ‘B’, ‘C’ & ‘D’ SUBSTATIONS
AND EXTENSION OF UM AL-AISH ‘M’ SUBSTATION

25/07/07 J2961BU01 REV 0.doc 1


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 1 __________________________________________________________________ 4
REVISION HISTORY OF MANUAL-------------------------------------------------------------------------------------------- 4
DISTRIBUTION OF MANUAL -------------------------------------------------------------------------------------------------- 4
EXPLANATION OF HAZARD INFORMATION ------------------------------------------------------------------------------- 4
HEALTH AND SAFETY PRECAUTIONS ------------------------------------------------------------------------------------- 5
SECTION 2 __________________________________________________________________ 6
INSTALLATION------------------------------------------------------------------------------------------------------------------- 6
UNPACKING THE EQUIPMENT ------------------------------------------------------------------------------------------ 6
USE OF FORK LIFT TRUCK FOR LIFTING THE EQUIPMENT ----------------------------------------------------- 6
LOCATION OF THE EQUIPMENT---------------------------------------------------------------------------------------- 6
CONNECTING THE EQUIPMENT---------------------------------------------------------------------------------------- 7
EMC HEAVY INDUSTRIAL ENVIRONMENT---------------------------------------------------------------------------- 8
PRESERVATION PROCEDURE (GENERAL)--------------------------------------------------------------------------- 9
RECOMMENDATIONS FOR 24 MONTH STORAGE AND PRESERVATION -------------------------------------- 9
SECTION 3 __________________________________________________________________ 10
BASIC SPECIFICATION -------------------------------------------------------------------------------------------------------- 10
CIRCUIT DESCRIPTION--------------------------------------------------------------------------------------------------- 10
REGULATION---------------------------------------------------------------------------------------------------------------- 10
OUTPUT CHARACTERISTICS ------------------------------------------------------------------------------------------- 10
SECTION 4 __________________________________________________________________ 11
EQUIPMENT DETAILS---------------------------------------------------------------------------------------------------------- 11
DAU PARAMETER SETTINGS-------------------------------------------------------------------------------------------- 13
SECTION 5 __________________________________________________________________ 15
DAU DC ALARM MODULE ----------------------------------------------------------------------------------------------------- 15
OPERATING MODES------------------------------------------------------------------------------------------------------- 15
FUNCTIONS AND FEATURES ------------------------------------------------------------------------------------------- 15
INSTRUMENTATION ------------------------------------------------------------------------------------------------------- 15
LOCAL AND REMOTE ALARMS AND INDICATIONS ----------------------------------------------------------------- 15
FUNCTION SETTINGS AND RANGES ---------------------------------------------------------------------------------- 17
DAU SET UP PAGES ------------------------------------------------------------------------------------------------------- 19
EQUALISE SELECTION ---------------------------------------------------------------------------------------------------- 20
EQUALISE REMOTE CONTROL------------------------------------------------------------------------------------------ 20
FLOAT SELECTION -------------------------------------------------------------------------------------------------------- 20
BATTERY TEST ------------------------------------------------------------------------------------------------------------- 20
BATTERY HIGH IMPEDANCE ALARM ---------------------------------------------------------------------------------- 21
SETTING UP THE HIGH IMPEDANCE ALARM ------------------------------------------------------------------------ 21
ALARM SET UP ------------------------------------------------------------------------------------------------------------- 24
INTERFACE MODULE ----------------------------------------------------------------------------------------------------- 25
SECTION 6 __________________________________________________________________ 26
DESCRIPTION OF OPERATION ---------------------------------------------------------------------------------------------- 26
THE SYSTEM---------------------------------------------------------------------------------------------------------------- 26
SECTION 7 __________________________________________________________________ 29
DESCRIPTION OF CONTROLS AND INDICATIONS ---------------------------------------------------------------------- 29
START-UP & SHUTDOWN ----------------------------------------------------------------------------------------------------- 32
COMMISSIONING PROCEDURE----------------------------------------------------------------------------------------- 32
START-UP PROCEDURE ------------------------------------------------------------------------------------------------- 33
SHUTDOWN PROCEDURE ----------------------------------------------------------------------------------------------- 34
SECTION 9 __________________________________________________________________ 35
FAULT FINDING INSTRUCTIONS-------------------------------------------------------------------------------------------- 35

25/07/07 J2961BU01 REV 0.doc 2


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

PROCEDURES -------------------------------------------------------------------------------------------------------------- 35
TESTING SEMI-CONDUCTORS------------------------------------------------------------------------------------------ 35
STUD MOUNTING SEMI-CONDUCTORS ------------------------------------------------------------------------------ 35
TEST EQUIPMENT REQUIRED ON-SITE------------------------------------------------------------------------------- 35
SOLUTIONS TO COMMON FAULTS------------------------------------------------------------------------------------- 36
HIGH OUTPUT AND HIGH OUTPUT SHUTDOWN ................................................................................... 36
LOW OUTPUT.............................................................................................................................................. 36
CHARGER FAULT FINDING GUIDE ........................................................................................................... 37
SECTION 10 _________________________________________________________________ 38
MAINTENANCE INSTRUCTIONS--------------------------------------------------------------------------------------------- 38
TORQUE SETTINGS ------------------------------------------------------------------------------------------------------- 38
SECTION 11 _________________________________________________________________ 39
DRAWING LIST------------------------------------------------------------------------------------------------------------------- 39

25/07/07 J2961BU01 REV 0.doc 3


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

SECTION 1

REVISION HISTORY OF MANUAL

REVISION DATE DRAWN COMMENTS


0 25/07/07 Simon Drayton First issue for customer
1
2
3

DISTRIBUTION OF MANUAL

REVISION DATE QUANTITY FOR THE ATTENTION OF


0 25/07/07 1 WITH EQUIPMENT
1
2
3

EXPLANATION OF HAZARD INFORMATION

To clarify certain points within this manual to ensure proper and safe operation of the equipment,
the following emphasis is used.

Highlights an essential element of a procedure to ensure correctness.


NOTE:-

Highlights an essential element of a procedure for installation or maintenance to


NOTE:- ensure correctness.

Indicates a procedure or practice which, if not strictly observed, could result in


CAUTION:- damage or destruction of equipment.

Indicates a procedure or practice which could result in injury to personnel or


WARNING:- loss of life if not followed correctly.


Erskine Systems own the copyright to this manual, which may not be copied,
reproduced or disclosed to a third party without prior written permission.

25/07/07 J2961BU01 REV 0.doc 4


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

HEALTH AND SAFETY PRECAUTIONS

• Installation, testing, fault location and • The above instructions must also be
repair should only be attempted by an followed before any such connection is
authorised, qualified technician. modified or renewed.

• This equipment carries dangerous


voltages and stored electrical energy. NOTE:- Adjustments should only be
carried out with non-conducting tools,
• Removal of shrouding can reveal taking care not to touch any item carrying
dangerous voltages and/or high electricity whilst doing so.
temperatures. Erskine Systems
accepts no responsibility for the safety • Reference should also be made to the
of personnel and property due to any sections dealing with installation and
actions after their removal. fault finding procedures in the
equipment manual before installing and
• Before touching, or bringing metal making external connections.
objects, e.g. tools, metal bracelets,
rings or necklaces into contact with • EMC cannot be guaranteed if the
items carrying electricity, carry out the system is operated with the doors open
following instructions: and/or panels removed.

• Isolate the AC mains supply external to


the equipment.

• Isolate the battery and external load


from the equipment.

• Hazardous energy levels may be


present inside the equipment. Allow DC
filter capacitors to discharge for a
minimum of 20 seconds, before
removing any covers.

• Discharge all RFI suppression circuits


as above.

CAUTION!:-Do not short circuit


capacitor terminals.

• The above instructions must always be


followed before making any
adjustments, and also before making
any electrical connections to any part of
the equipment for the purpose of
servicing. Such connections should
always be checked for safety before
reconnecting power.

25/07/07 J2961BU01 REV 0.doc 5


INSTALLATION, OPERATION & MAINTENANCE MANUAL

SECTION 2

INSTALLATION

UNPACKING THE EQUIPMENT

1. Unpack the equipment and carefully check for any damage, which may have occurred during
transit. The equipment should remain upright at all times.

2. Check against the accompanying packing/delivery note to determine whether any part of the
consignment is missing.

3. Any returnable packing cases should be returned to the address on the cases.

4. Report any damage or losses immediately. Refer to Erskine Systems standard conditions of
sale.

USE OF FORK LIFT TRUCK FOR LIFTING THE EQUIPMENT

1. To avoid possible damage (e.g. scratches) to the equipment, first cover the forks with rubber
mats or other suitable material.

2. The forks should then be slotted under the equipment cubicles so as to ensure even weight
distribution - also it is important to ensure the forks reach across to the rear of the cubicle.

LOCATION OF THE EQUIPMENT

1. As the equipment relies on natural convection for cooling purposes, it is important that the
enclosures are sited in a position with a free flow of air. This also applies to equipment fitted
with cooling fans.

2. Do not locate the equipment or position other equipment against it, such that the natural
ventilation paths are blocked or restricted. Do not locate the equipment in an area that has an
ambient temperature above the maximum allowed for - normally 40oC.

3. Equipment unless specifically stated shall not be installed in a hazardous area. Equipment
unless specifically stated shall not be installed in a mobile environment or a position subject
to vibration.

4. Floor standing cubicles are designed to be bolted to the floor using foundation bolts. Position
the cubicles and mark the floor - remove cubicles and drill the floor for the bolts. The cubicles
can then be placed in position and secured.

5. When batteries are installed ensure that the ambient temperature is suitable for type of cells
used and also adequate number of air changes per hour to prevent battery gas build up.

NOTE: Should any cabinet modifications be carried out during installation, it is necessary to ensure
that all swarf be removed from within the enclosure to prevent any electrical faults occurring.

25/07/07 J2961BU01 REV 0.doc 6


INSTALLATION, OPERATION & MAINTENANCE MANUAL

CONNECTING THE EQUIPMENT

1. The following cable should be used, to maintain the EMC performance of the equipment.

XLPE insulated to BS5467 or equivalent (BS6724 for low smoke and fume cable) for:-

• Mains Input
• DC Load Output
• Battery Cables
• Alarm Cables

2. Cables shall be steel wire armoured and/or screened. The wire armour or screen of the cable
must be bonded to the gland plates at the cable entry points using a cable gland and bonded
at the opposite end to a local earth path.

• Alarm Contacts - BS5308 Part 2. Conductors may be collectively screened.

3. The above sets of cables should be separated from each other by a minimum of 250mm to
minimise noise coupling. The DC load output and battery cables may be routed together.

4. All the above sets of cables must be segregated from other cables at the installation site and
any other sources of electrical noise by a minimum of 250mm.

5. Where it is not possible to use screened cables, cables should be routed in conductive
trunking or conduit. In either case, the trunking or conduit must be correctly terminated at the
cabinet such that there is a low impedance bond to the cabinet.

6. Trunking and conduit should not contain filtered mains cables as well as unfiltered mains
cables.

7. Trunking or conduit should not contain AC cables as well as DC cables.

8. Trunking or conduit should not contain input cables as well as output cables.

9. Trunking or conduit should not contain power cables as well as signal cables.

10. All joints or junctions in the trunking or conduit must use earth links to maintain continuity of
the low impedance path.

25/07/07 J2961BU01 REV 0.doc 7


INSTALLATION, OPERATION & MAINTENANCE MANUAL

EMC HEAVY INDUSTRIAL ENVIRONMENT

The equipment is suitable for use only in the following environment:-

• Heavy industrial type environments where the product is intended to be connected to a power
network supplied from a high or medium voltage transformer dedicated for the supply of an
installation feeding a manufacturing or similar plant.

Therefore the equipment complies to the following European standards:-

• EN50081-2 : Emissions : Heavy Industrial

• EN50082-2 : Immunity : Heavy Industrial

It is advisory that equipment sharing the same electromagnetic environment as Erskine products
should comply with the standards as stated above.

GENERAL

1. The equipment should first be checked to ensure that any connections which may have
become loose during transit are tightened.

2. Ensure that the supply is suitably rated.

3. Ensure that any loads to be connected are not in excess of the capability of the equipment.

4. Cable entry is indicated on the appropriate Arrangement Drawing and is via gland plates at
the bottom of the cubicles. The gland plates, which are supplied un-drillled, should be drilled
on-site for the compression glands and/or grommets to be used.

5. Connect an earth connection to the main earth stud provided.

6. Connect the AC mains supply to the terminal block making sure to connect to the input
voltage that corresponds with that of the mains supply.

NOTE:- On cubicle models a terminal block is provided on the chassis.

NOTE:- The customer earth connection shall be adequately sized to the latest edition of the I.E.E.
wiring regulations or local equivalent and be terminated an a ring type crimp fixed utilising a spring
washer to reduce the chance of the connection becoming loose.

7. Connect all outgoing connections to the terminals provided.

8. Connect any alarm connections to the terminals provided.

9. Ensure that the gland plate earth cable is refitted after removal.

NOTE:- When making connections, ensure polarity is correct and refer to the circuit diagram
supplied with the equipment.

25/07/07 J2961BU01 REV 0.doc 8


INSTALLATION, OPERATION & MAINTENANCE MANUAL

PRESERVATION PROCEDURE (GENERAL)

Generally, common sense prevails when handling and storing spare parts and goods for the
power supply systems.

Goods should be stored in an environment and manner so as to minimise any risk of physical
and climatic damage.

To ensure this the following points should be observed.

All meters should remain in the polystyrene package provided, avoiding moisture and
physical disturbances.

Special care should be taken when handling lamps due to their delicacy.

PCB’s (Static sensitive) - Special precautions must be taken when using and handling
electrostatic devices. If appropriate precautions are not taken, then it is likely that the
device will be seriously damaged or destroyed.

• New or spare PCB's will arrive with electrostatic protective packaging (conductive anti-static
bag). Never remove the board from the package until it is required. Do not stack the PCB's during
storage.

When replacing a static sensitive PCB observe the following procedure:-

• When removed from the anti-static bag, place and connect into the complete equipment
immediately.

• Insert PCB's in anti-static bag immediately on removal from the complete equipment, even if
deemed faulty (a fault caused by static can disguise the original fault).

• Do not carry any PCB's without anti-static bags.

• When dealing with PCB's, avoid using nylon clothing, particularly in dry and frosty conditions.

• Simultaneously touch the metal frame of the complete equipment (preferably a bare earth
connection) with one hand and the conductive packaging with the other hand to discharge any
static before fitting.

RECOMMENDATIONS FOR 24 MONTH STORAGE AND PRESERVATION

Equipment must be packed in sealed wooden crates with desiccant and stored in a covered
warehouse such that equipment’s are protected from direct sunlight, rain, corrosive atmospheres,
flood water and extremes of climate.

Storage temperature range -30oC to +70oC.

(Temperature excursions to -40oC are permitted providing the average temperature is not less
than -30oC, over a 24 hour period.)

Please note that these equipment’s above are NOT suitable for stacking.

25/07/07 J2961BU01 REV 0.doc 9


INSTALLATION, OPERATION & MAINTENANCE MANUAL

SECTION 3

BASIC SPECIFICATION

The following information is provided as a


basic guide to the equipment specification. REGULATION
The exact specification for the charger
system can be found on the circuit diagram. The charger output characteristic is
(i.e. Voltage level settings, output ratings generally to DIN41773 providing a static
etc.) output voltage regulation of ±1% and a
current regulation of ±2% providing that the
CIRCUIT DESCRIPTION mains input variations do not exceed ±10%
voltage, ±5% frequency for load changes 0-
The Erskine constant voltage charger is 100%.
completely solid state, using thyristors as a
means of varying the output. A double OUTPUT CHARACTERISTICS
wound transformer of special design
supplies power to a full wave, half controlled, +/-1%

bridge rectifier incorporating diodes and VE


thyristors. This in turn supplies the battery +/-1%

and load via a smoothing inductor. VF

The thyristors are triggered by a controller


which automatically adjusts the conduction +/-2%
angle to suit the power output requirement.
Voltage feedback is used to maintain
regulation and current feedback to provide 0% Charger Output Current 100%
current limit. A soft start-up facility is V E = Equalise Voltage
V F = Float Voltage
included.

The charger controller PCB is of Erskine


design using conservatively rated, high
quality components. Screw type terminals
are provided. A fibreglass printed circuit
board carries pre-set potentiometers for
adjustment of voltage and current settings in
float and equalise modes.

A peak sensing current limit circuit provides


protection against sudden overload or short
circuit. Recovery to a constant voltage
characteristic occurs automatically at the
end of an overload period.

25/07/07 J2961BU01 REV 0.doc 10


INSTALLATION, OPERATION & MAINTENANCE MANUAL

SECTION 4

EQUIPMENT DETAILS

CHARGER

Type Single DCV110/25


Input Supply 240 Volts 50 Hz 1 Phase AC Mains
Nominal Output 110 Volts @ 25 Amps
Settings:
Float 126.0 Volts / 22 Amps
Equalise 148.5 Volts / 22 Amps
Commission 148.5 Volts / 22 Amps
Earthing Negative Float

BATTERY

Type NiCad
Configuration 90 off MC110P cells in series

CUBICLE

Type FS19
Cable Entry Bottom
Ingress Protection IP41
Paint Finish Cubicle – RAL7032 Semi-Gloss

ALARMS AND INDICATIONS

ALARM SETTING TIME REMOTE LOCAL COMMON


Common - - SPCO DAU -
Fire Response - - Yes Red -
Fuse Trip - - Common DAU 3
Breaker Open - - Common DAU -

25/07/07 J2961BU01 REV 0.doc 11


INSTALLATION, OPERATION & MAINTENANCE MANUAL

DAU PARAMETER SETTINGS

Alarms and indications LED Trip Reset Time Reset Mapping Other
colour Group Control relay
1 2 1 2 3 4 5 6 7 8
AC supply on Green
AC supply fail Yellow Auto þ þ
Charger fail Red 117.0 V 121.5 V 30 s Auto þ Enable on AC fail
Low volts Yellow 99.0 V 121.5 V 30 s Auto þ
Low volts disconnect 85.0 V 121.5 V 30 s
High volts (float) Yellow 151.5 V 150.0 V 5s Auto þ
High volts (equalise) Yellow 151.5 V 150.0 V 5s Auto þ
High volts trip (float) Red 153.0 V 151.5 V 5s Latch þ Source DCV
High volts trip (equalise) Red 153.0 V 151.5 V 5s Latch þ
Earth fault Yellow 2.0 mA 30 s Auto þ Enable
Battery high impedance Red 5O 30 s Auto Disable
Equalise Yellow 12 h Manual
Fault Red

Control functions Trip Reset Time Reset Mapping Other


Group Control relay
1 2 1 2 3 4 5 6 7 8
Shunt rating 25 A
Charge fail 117.0 V 121.5 V 30 s
Knee volts 135.0 V
Battery test 90.0 V 10 s Disable
Positive earth fault test Disable
Negative earth fault test Disable
Battery high impedance test Disable

25/07/07 J2961BU01 REV 0.doc 13


INSTALLATION, OPERATION & MAINTENANCE MANUAL

System settings Label (18 characters maximum) Reset Mapping Other


Group Control relay
1 2 1 2 3 4 5 6 7 8
Fault input 1 label DIST BREAKER OPEN Auto þ Open contact on alarm
Fault input 2 label CHARGER FUSE FAIL Auto þ Open contact on alarm
Fault input 3 label CH BREAKER OPEN Auto þ Open contact on alarm
Fault input 4 label CH ISOLATOR OPEN Auto þ Open contact on alarm
Fault input 5 label
Vs voltmeter label
Vp voltmeter label Charger Voltage
Ammeter label Charger Current
Group 1 label Common Alarm
Group 2 label Lighting CCT on
Control relay 1 label
Control relay 2 label Energise
Control relay 3 label when active
Control relay 4 label
Control relay 5 label
Control relay 6 label
Control relay 7 label
Control relay 8 label
Password for setup pages 8 digits maximum
Password for test pages 8 digits maximum

25/07/07 J2961BU01 REV 0.doc 14


INSTALLATION, OPERATION & MAINTENANCE MANUAL

SECTION 5

DAU DC ALARM MODULE

This module provides system instrumentation, control and alarm functionality for single or three
phase thyristor charger systems. The device consists of a display/user interface module which
is capable of front panel mounting, and an interface module for mounting within the panel.

OPERATING MODES
The DAU user interface has three modes, or levels, of operation: User mode; set-up mode; and
service mode.

User mode; this is the normal mode of operation. The user has access to all the screens
contained in the user level. These provide system measurements, charger mode & system
alarm status information and allow selective control of the system.

Set-up Mode; provides access to all the user settable parameters screens. These allow the
various alarm settings and control features, to be configured or adjusted as required by the user.
Entry into this mode is protected by a user settable 4 digit password. (Note PLEASE KEEP A
RECORD OF YOUR PASSWORD, if you change it, as once you exit this mode you will be
denied access in the future with out entry of the correct password.

Service Mode; the unit functions as in set-up mode but also unlocks restricted access
features , such as analogue input calibration and control output testing. These functions are
password protected and are not accessible to the user.

The Navigation around these screens, and adjustment of the various parameters is achieved by
using the push buttons which are present on the front panel user interface module the function
of which is described below.

FUNCTIONS AND FEATURES

INSTRUMENTATION
The module provides an LCD display for the indication of the charger output voltage and current.
Indications have an accuracy of ±1.5% or better. The display also serves for programming the
system control and alarm functions. In the instrumentation mode, the display indicates both
voltage and current.

LOCAL AND REMOTE ALARMS AND INDICATIONS


Facilities are provided for alarm reset, and LED test. All local LED indications are configurable
individually to be reset manually or automatically. All alarm settings have an adjustable time
delay of at least 30 seconds. In addition to the front panel time delayed LED for each alarm
function, an internally located red LED illuminates as soon as the alarm condition is initiated i.e.
before the adjustable time delay. All alarm and control functions are individually configurable
from the front panel display module.

25/07/07 J2961BU01 REV 0.doc 15


INSTALLATION, OPERATION & MAINTENANCE MANUAL

Alarm/ LED Function


Function Colour
AC Supply Green The charger is on and receiving an AC supply.
On

Note: AC Supply On does not indicate if the AC supply is present at the cubicle input
terminals if the charger has been switched off via its input circuit breaker. Isolate elsewhere.

AC Supply Yellow Indicates that the normal supply is not present, ie. Charger is off
Fail and does not have an AC supply (see note above).
Charge Fail Red Both the voltage and current from the charger are below the pre-set
levels.
DC High Yellow Indicates that DC voltage is above a pre-set level. The alarm setting
Volts threshold is raised as required when the system is selected for the
equalise charge mode to prevent nuisance tripping.
DC Low Yellow Indicates that the DC voltage is below the pre-set level.
Volts
DC High On display As well as the high volts alarm it is also possible to set the DAU to
Volts Trip only when trip the charger input supply off if the voltages rises above the set
enabled point. This trips the charger input circuit breaker when the voltage
is above the threshold setting.
DC Low On display This feature, when enabled, is provided to operate a contactor to
Volts only when disconnect the battery from the load when the voltage falls below a
Disconnect enabled pre-set level. Automatically resets on resumption of battery
charging.
Earth Fault Yellow Operates when the insulation resistance of either the positive or
negative poles to earth falls below a pre-set level and the other pole
stays above 2MΩ.
Equalise Yellow Selection of a higher charger output voltage.
When enabled can be selected for Manual or Automatic Equalise
following an AC supply failure.
This feature is normally disabled on systems supplying VRLA
batteries.
High Battery Red This indicates when the internal resistance of the battery rises to a
Impedance level that would prevent it from operating satisfactorily on load.
Remote On display Inputs are provided to monitor up to five digital inputs. When active
Inputs only when the input’s label will be shown on the display and incorporated into
enabled the group alarms
Remote The DAU is equipped as standard with two output changeover
Outputs relays to which the above alarms can be mapped.
Remote The DAU can be connected to an optional separate eight relay
expansion module for remote indication or system functions.
relays

25/07/07 J2961BU01 REV 0.doc 16


INSTALLATION, OPERATION & MAINTENANCE MANUAL

FUNCTION SETTINGS AND RANGES


Function Parameter/Node Trip Range Reset Range Timer Range
Charger Fail - Voltage/Vs 75 – 125% 100 – 140% 0 – 120s
Voltage
Charger Fail - Shunt <10% >20% 0 – 120s
Current
High DC Voltage Voltage/Vs 100 – 140% 75 – 100% 0 – 120s
Trip
High DC Voltage Voltage/Vp 100 – 140% 75 – 100% 0 – 120s
Alarm
Low Voltage Voltage/Vp 75 – 125% 100 – 140% 0 – 120s
Disconnect
DC Earth Fault Current/Vp 1,2,4,10mA N/A 0 – 120s
Alarm
High Impedance Resist./+Ps 0.2 – 5Ohm 0.2 Ohm 0 – 120s
Alarm
Battery Test - Voltage/Vp 75 – 125% N/A 0 – 120s
Terminate
Battery Test - Time N/A N/A 1 – 60m
Duration
Auto Equalise – Voltage/Vp 75 – 125% 100 – 140% 0 – 120s
Charge Fail
Auto Equalise – Voltage/Vp 100 – 125% N/A 0 – 120s
Knee Point
Auto Equalise - Time N/A N/A 0.5 – 24h
Timer

FRONT PANEL CONTROL AND DISPLAY

The unit incorporates a


liquid crystal screen for the
display of system
parameters and operator
interaction during system
set-up or interrogation and
set-up routines.

The system has display


pages giving the system
parameters. The left arrow
and right arrow push button
will allow an operator to
cycle through and select the
required page.

The control push buttons


are detailed below. On each
page of the DAU display,
the ‘active’ keys (those
which may be selected), are
shown on the bottom line of
the display.

25/07/07 J2961BU01 REV 0.doc 17


INSTALLATION, OPERATION & MAINTENANCE MANUAL

Push Button Functions


During set-up mode this pushbutton will increment a parameter.

During set-up mode this pushbutton will decrement a parameter.

This button moves the displayed page to the next one on the left allowing the operator
to cycle through the display pages. During set-up mode this pushbutton will allow
navigation to the required set up page. Also used to move between the digits of the
password and other numeric parameters in set up.
This button moves the displayed page to the next one on the right allowing the operator
to cycle through the display pages in a reverse order to that of the left arrow
pushbutton. During set-up mode this functions as per the left arrow.
In normal mode this push button will cause the display to go to the home page which
displays the system voltage. While in set-up mode this button will cause the unit to
exit from the currently displayed page to the home page in the current level of the set-
up mode page structure. Referred to as Home in the setting up instructions.
In normal mode, this pushbutton will allow the operator to enter a password code to
gain access into set-up mode. Entry to set-up mode is protected by a 4-digit number
(see System Settings for details), which the operator must set with the arrow keys.
During set-up mode this pushbutton will accept the displayed settings of the parameter
or value.
During normal mode this pushbutton will cause all, except the AC Supply On, front
panel LED alarm indicators of the unit to illuminate.
During normal operation, this pushbutton will clear any latched alarms.

INFORMATION PAGES
The pages are displayed during normal operation and give an overview of the system voltage and
current, status, and any alarms.
No changes can be made to the system from these pages.

PAGE DISPLAY
Metering • DC Voltage(s).
• Current drawn by the load from the system.
Active • Any individual current and latched alarms and their groups.
Alarms
Charger The current state of the System e.g.:
Mode • Float charging.
• Equalise charging and timer period.
• Charge Fail.
Battery Test • For selection of the battery test mode when enabled.

The chart below shows the pages in order. From any of these pages the use of the Home
button returns you to the System overview page. From this page Home displays the software
version information.

25/07/07 J2961BU01 REV 0.doc 18


INSTALLATION, OPERATION & MAINTENANCE MANUAL

DAU SET UP PAGES


When the DAU is first powered up, it will flash up information about the unit for several seconds, before displaying the System
Voltage and Current.

The display pages can be scrolled through, by using the left and right arrow keys. Pressing the SET key at any of these pages,
allows the user to enter the selected password, gaining access to the Set Up pages as shown below.

25/07/07 J2961BU01 REV 0.doc 19


INSTALLATION, OPERATION & MAINTENANCE MANUAL

EQUALISE SELECTION
If the Equalise function is enabled it is selected from the Charger Mode page:

Charger Mode Note: Equalise selection is inhibited when the Charge


Mode = FLOAT Fail alarm is active.
Press [UP] to start
Equalise

Charger Mode The charger is now in the


Mode = EQUALISE equalise mode. To return to
Time left = 12hours float press
Press [DOWN] to stop

When equalise is selected the output of the charger will start to rise, at a rate depending on the
capacity and state of charge of the batteries, until the Knee Point is reached. This is the point at
which the charging changes from constant current to constant voltage. The pre set equalise timer
period is now started and the charger will return to float when this is timed out (or a charge failure
occurs).

EQUALISE REMOTE CONTROL


The DAU can be set up to accept a remote equalise start signal, in this case the local control is
inhibited or;

A remote inhibit signal can be set to prevent the selection of equalise eg ventilation fan failure.

FLOAT SELECTION
At any point during the equalise period the charger can be returned to the float mode as shown
above.

BATTERY TEST
A feature of the DAU allowing the battery to be into the site loads. This gives confidence in the
battery to support the load in the event of a mains failure. To do this the charger is shut back to a
lower voltage (pre set) to allow the battery to discharge into the load and to be on standby in case of
a battery failure. A failure of the test will cause an alarm.

This feature checks the suitability of the battery to support the site load for a given time or for a pre-
set capacity and does not check the full battery autonomy.

A test is terminated voltage and time. If the battery voltage drops below the set level before the
timer period is met then it is failed. If the time is reached before the voltage drops too far then the
battery has passed. See system specification for settings and details below on setting up and
adjustments.

25/07/07 J2961BU01 REV 0.doc 20


INSTALLATION, OPERATION & MAINTENANCE MANUAL

Battery Test Note: Equalise selection is inhibited when the Charge


Fail alarm is active.
Press [UP] to start
Battery Test

Battery Test The charger is now in the


Mode = Battery Test equalise mode. To return to
float press
Press [DOWN] to stop
Note: Battery Test is inhibited if the AC Supply Fail, Charge Fail, or a previous
Battery Test Failed alarm is present. This will appear on the display.

If the battery fails the discharge test then a latched alarm is generated. This will inhibit any further
battery discharge until reset with the push button.

BATTERY DISCHARGE TEST PARAMETERS.


These are accessed as described below.

SET UP PAGE FUNCTION


Battery Test Manual Enable or Disable the function.
Start/Stop.
Battery Discharge The criteria by which a battery either passes or fails a discharge test.
Test Settings Battery test minimum volts.
The voltage at which the battery is deemed to have failed the test if this point
is reached before the time/capacity has been exceeded.
Maximum time:
The test is terminated after a set time has elapsed provide that the voltage
stays above the set level.

BATTERY HIGH IMPEDANCE ALARM


This alarm continuously monitors the battery and its connections for any increase in their
impedance which may affect the ability to support the load in the event of a mains failure.

SETTING UP THE HIGH IMPEDANCE ALARM


Firs the system and its batteries should be connected and fully installed.
Enter the set up pages, using the password, as described below and use the right arrow to navigate
to the High Impedance Alarm page.
Press ENTER twice to reach High Impedance Trip = xx Ohms. This shows the current setting.
Reduce the setting, using the DOWN arrow until the alarm is tripped this is done by checking the
LED on the interface board as this does not have a time delay. Now increase the setting until the
alarm is cleared. If any nuisance alarms occur the setting can be increased accordingly. Press
ENTER to move to the High Impedance Delay page. This is set to 30seconds as default and can
be adjusted if required although reducing it may cause nuisance alarms. To save the changes
press the HOME button twice to return to the information pages

25/07/07 J2961BU01 REV 0.doc 21


INSTALLATION, OPERATION & MAINTENANCE MANUAL

SET UP PAGE SELECTION


By use of a password (the default is blank) the set up pages of the DAU can be accessed.

Pressing the SET key on all information pages will take you to the password screen as shown
below.

The first page displayed is always System Settings. Navigation to the other pages is via the ï and
ðbuttons. SET takes you into the relevant pages and Home will take you back to the Information
Pages.
Note; ‘Saving Settings to Non Volatile Memory’ will always be displayed briefly when coming out of
the set-up menus, even if changes have not been made.

If, when you access a set of pages, it is decided that another page of screens is required the Home
button will take you back to the selection level.

NOTE: the DAU has been set up in accordance with your specification, and for the correct
operation of the system. Before making any changes to its settings first check that they do not
affect the operation or safety of the system. Any changes should be limited to alarm and battery
test settings only (not greyed out in the chart below). If in doubt contact Erskine Systems.

25/07/07 J2961BU01 REV 0.doc 22


INSTALLATION, OPERATION & MAINTENANCE MANUAL

Changes should only be made to; High Volts Alarm, Charge Fail Alarm; Low Volts Alarm; Earth Fault Alarm; High Impedance Alarm; Auto/Manual
Equalise; Battery Test; Change Password. All other options have been set in the factory for correct system operation.

25/07/07 J2961BU01 REV 0.doc 23


INSTALLATION, OPERATING AND MAINTENANCE MANUAL

ALARM SET UP
All of the alarm pages have the following
parameters:
Trip; the point at which the alarm is activated (on
a falling voltage for low volt alarms or a rising
voltage for high volts alarms)
Reset; The point at which the alarm is cleared (on
a rising voltage for low volt alarms or a falling
voltage for high volts alarms).
Delay; the period between the alarm being
activated and it being displayed on the front panel
and activation of the remote relay. Note that the
LEDs on the interface module (see below) are
activated instantaneously.
Latch; when enabled the alarm will latch on the
display and remote relay once the time period has
elapsed. To clear the alarm the level must first be
past the reset level and the Alarm Reset button is
pressed. Note that the LEDs on the interface
board are non latching.
Common Alarm Mapping; selects the remote
relay activated by the alarm.
Expansion Relay Mapping; selects the relay
on the expansion module (if fitted) activated by the
alarm.

To enter any of the alarm set up pages press SET


at the desired page. The values are altered with
the UP and DOWN buttons. Press SET to carry
on to the next page or HOME to return to the
selection page.

Any changes made are automatically saved when


the SET or HOME buttons are pressed and you
return to the information pages. There is no
option to cancel the changes.

The diagram to the right shows an example page.


All others are of a similar format.

25/07/07 J2961BU01 REV 0.doc 24


INSTALLATION, OPERATION & MAINTENANCE MANUAL

INTERFACE MODULE
The eight LEDs in the bottom left hand corner, work independently of the LEDs on the Display Module.
They indicate that the respective alarm is active
immediately. The front display LEDs do not light until
after the time delay has elapsed. This is used for testing
and commissioning the alarm functions.

The Interface is connected to the Display via a null


modem 9 way D Type connector on CON5, and to DCV
the charger controller by a 20 way ribbon cable on X16.
All other connections are via the two part connectors
listed below.

Ref Function RC
1.1 Group 1 volt free alarm (NO)
1.2 Group 1 volt free alarm (COM)
1.3 Group 1 volt free alarm (NC)
2.1 Group 2 volt free alarm (NO)
2.2 Group 2 volt free alarm (COM)
2.3 Group 2 volt free alarm (NC)
E Earth fault alarm ground connection
+12 High Volts Shut Down
HVSD High Volts Shut Down
-PS Power supply –Ve
+VS System voltage sense +Ve
-COM Voltage sense common –Ve
+VP Charger voltage sense +Ve
+PS Power supply +Ve
-A Current sense 75mV –Ve ü
+A Current sense 75mV +Ve ü
COM Charger common ü
P AC Supply On from charger ü
FC Remote fault input common
FC Remote fault input common
RMC Remote control mode input
F1 Remote fault input 1
F2 Remote fault input 1
F3 Remote fault input 1
F4 Remote fault input 1
F5 Remote fault input 1

All connection marked ü in the RC column are connected to the DCV controller via the 20 way ribbon
cable on X16.

25/07/07 J2961BU01 REV 0.doc 25


INSTALLATION, OPERATION & MAINTENANCE MANUAL

SECTION 6

DESCRIPTION OF OPERATION

THE SYSTEM

THE CHARGER - The charger type is as detailed on the circuit diagram. With a single charger system,
the charger will supply the load and maintain the battery in a fully charged state. Should the mains fail
the supply will be lost.

THE ALARM MODULES - To monitor system operation and to warn of abnormal conditions the system
is often fitted with an Erskine DAU alarm module.

SIMPLIFIED BASIC CHARGER SCHEMATIC

THE POWER CIRCUIT - The secondary of the mains input transformer is connected to the half
controlled thyristor/diode bridge located on the charger PCB. The DC output of the bridge is smoothed
by an L.C. network in conjunction with the battery, if fitted, (the inductor is external to the PCB).
Internal fusing in the charger output protect it from the reverse connection of a battery. The load is
connected to the +VE and -VE DC output terminals with fuse protection.

25/07/07 J2961BU01 REV 0.doc 26


INSTALLATION, OPERATION & MAINTENANCE MANUAL

32A CONTROLLER PCB ARRANGEMENT

CONTROL CONNECTIONS
TERMINAL FUNCTION
L AC supply
N AC supply
N1 Connection for optional external negative temperature coefficient (NTC) probe.
N2 Return for NTC probe (internally connected to 0V)
SB Shut Back; connect to CM or 0V to inhibit output.
CM Common connection, (internally connected to 0V)
P +12V auxiliary for connection to other Erskine modules only.
IC NiCad commissioning voltage set by IC VOLT pot selected for output voltage,
connect to CM or 0V to enable function. NOTE: Set IC VOLT potentiometer
before other output voltage setting potentiometers.
ES EQUALISE or BOOST setting set by EQU VOLT potentiometer. Connect to
CM or 0V to enable
0V 0V return connections for signals, do not use as a power return.
CC Current limit reference input
C1 Current limit reference output, connect to CC for current limit set by CL1
C2 Current limit reference output, connect to CC for current limit set by CL2
A+ 75mV feed to external ammeter positive
A- 75mV feed to external ammeter negative (internally connected to 0V)
V+ Positive feed to an external voltmeter, output is internally protected against
short circuit via a positive temperature coefficient thermistor.
V- Negative feed to an external voltmeter, output is internally protected against
short circuit via a positive temperature coefficient thermistor.

25/07/07 J2961BU01 REV 0.doc 27


INSTALLATION, OPERATION & MAINTENANCE MANUAL

POWER CONNECTIONS
TERMINAL FUNCTION
A1 Main transformer secondary start
A2 Main transformer secondary finish
L1+ Output to main inductor
L1- Return from main inductor
L2+ Output to optional second inductor. Link to L2- unless second inductor is
required.
L2- Return from second inductor.
DC O/P +VE Main DC positive output terminals to load
DC O/P -VE Main DC negative output terminals to load

POTENTIOMETERS
All potentiometers are factory set and should not be adjusted as the safety and rating of the charger
may be affected.

LED INDICATIONS
LED FUNCTION
EQU Indicates that the charge is in the Equalise charging mode
CL Indicates that the charge is operaiting in current limit. Note that this is not an
alarm or charger fault condition and is a function of the load.
OVP Indicates that the charger has shut down due to a high DC voltage. To restart
the charge switch off at the AC input isolator or MCB and reclose. If the problem
persists contact Erskine Systems Ltd service department.

LINKS
LINK FUNCTION
TEMP Enables or disables the NTC function. This should only be in the enable position
PROBE if a temperature probe is fitted to terminals N1 and N2.
DROOP When enabled the charger outout regulation is set to droop as load is applied to
improve sharing with a second charger.

25/07/07 J2961BU01 REV 0.doc 28


INSTALLATION, OPERATION & MAINTENANCE MANUAL

SECTION 7

DESCRIPTION OF CONTROLS AND INDICATIONS

CONTROL/INDICATION DESCRIPTION
AC INPUT CIRCUIT BREAKER This connects the charger to the incoming AC
mains supply. It may be opened to isolate the
charger for maintenance purposes etc. The
breaker is used as the charger On/Off switch.

0-OFF

1-ON

CHARGER OUTPUT ISOLATOR This connects the charger output to the


battery and distribution circuit. The isolator
may be opened to isolate the charger from
these circuits for maintenance purposes etc.
0

COMMISSION CHARGE SELECT SWITCH This switch is used to select the chargers
initial commissioning mode. Refer to the
COMMISSIONING ‘Commissioning Procedure’ shown on the
OFF circuit diagram.

ON

25/07/07 J2961BU01 REV 0.doc 29


INSTALLATION, OPERATION & MAINTENANCE MANUAL

CONTROL/INDICATION DESCRIPTION
BATTERY CIRCUIT BREAKER This connects the battery to the charger
output and distribution circuits. The breaker
may be opened to isolate the battery from
these circuits for maintenance purposes etc.
0

DISTRIBUTION FEED CIRCUIT BREAKER This breaker connects the distribution circuits
to the charger output. The breaker may be
opened or closed as required by the load
connected.
0

LOAD CIRCUIT BREAKERS These breakers connect the individual load


circuits to the distribution circuit. Each
breaker may be opened or closed as required
by the load connected.

0-OFF 0-OFF 0-OFF

1-ON 1-ON 1-ON

25/07/07 J2961BU01 REV 0.doc 30


INSTALLATION, OPERATION & MAINTENANCE MANUAL

CONTROL/INDICATION DESCRIPTION
AC INPUT VOLTMETER This meter indicates the voltage level being
supplied to the charger from the incoming AC
mains supply. The meter is read in
conjunction with the meter phase select
switch. The readings obtained should be
approximately equal to the values stated in the
‘Equipment Details’ section of this manual.

AC INPUT AMMETER This meter indicates the amount of current


being drawn from the incoming AC mains
supply. The meter is read in conjunction with
the meter phase select switch to display the
individual phase currents. The values obtained
will depend on the state of charge of the
battery and the size of any load connected.

BATTERY AMMETER This meter indicates the current flow through


the battery circuit. During normal mains
healthy conditions the meter will indicate the
battery recharge current. This reading will vary
depending on the state of charge of the
battery, generally a discharged battery will
consume a large current from the charger.
The level will decrease as the battery
becomes charged. In the event of a mains
failure the meter will display the current being
supplied by the battery to the load. The
reading obtained will vary depending on the
size of the load connected.
BATTERY VOLTMETER This meter indicates the voltage level present
at the battery terminals. During mains healthy
conditions the reading displayed should be
approximately equal to the ‘Float’ value shown
on the circuit diagram. In the event of a mains
or charger failure occurring, on a single
charger system the meter will indicate the
battery voltage - this will fall as the battery
becomes discharged.

25/07/07 J2961BU01 REV 0.doc 31


INSTALLATION, OPERATION & MAINTENANCE MANUAL

START-UP & SHUTDOWN

Once the equipment has been installed, the following (mainly visual) checks should be performed prior
to starting the equipment.

1. Check the equipment is secure and as level as possible.

2. Ensure the external surfaces of the equipment are free from dust, packing materials, etc.

3. Check all switches, meters and lamps are in good condition and free from transit damage.

4. Check inside cabinets to ensure there are no obvious defects; such as loose PCB, loose or broken
connectors, loose component mounts, etc.

5. Check all fuses are secure and in place.

6. Check all external wiring to the equipment is correctly wired up and safely installed.

7. Check :-
Mains AC feeds to the charger.
DC load circuit connections.

COMMISSIONING PROCEDURE

Before entering into operational service, it is essential that the batteries receive a once only commission
charge. This charge prepares the cells for a long and trouble free service life at maximum capacity. To
commission charge the batteries, follow the start up procedure shown on the Circuit Diagram. The
battery manufacturers Operation Manual should also be referred to, to determine exact commissioning
procedure and charge duration.

25/07/07 J2961BU01 REV 0.doc 32


INSTALLATION, OPERATION & MAINTENANCE MANUAL

START-UP PROCEDURE

In order to start the equipment whether it be following a controlled shut-down or post installation, the
following procedure should be observed.

The instructions should be followed in the order listed and, it should be noted that in some cases a
result may take some time to occur (e.g. the charger is fitted with a 'soft-start' facility where by the
output voltage takes several seconds to rise up to the operating level).

CHARGER SYSTEM START-UP

ACTION
Initialise the system controls as stated:-
nOn the system…
• AC INPUT CIRCUIT BREAKER – OPEN
• CHARGER OUTPUT ISOLATOR – OPEN
• BATTERY CIRCUIT BREAKER – OPEN
• DISTRIBUTION FEED CIRCUIT BREAKER – OPEN
• DISTRIBUTION INPUT CIRCUIT BREAKER – OPEN
• LOAD CIRCUIT BREAKERS - OPEN
Energise the incoming mains supply.
1. Close the AC INPUT CIRCUIT BREAKER
2. Close the CHARGER OUTPUT ISOLATOR
3. Close BATTERY CIRCUIT BREAKER
4. Close the DISTRIBUTION FEED CIRCUIT BREAKER
5. Close the DISTRIBUTION INPUT CIRCUIT BREAKER
6. Close the LOAD CIRCUIT BREAKERS AS REQUIRED
The charger is now up and running. The charger is supplying a recharge current to the
battery and also supplying the requirements of the load. In the event of a mains failure, the
charger will cease to operate and the load will be supported by the batteries for the
designed standby time.

NORMAL OPERATION

During normal operating conditions only the following lamps should be illuminated:-

AC SUPPLY ON LED

If any other lamps illuminate, please refer to the ‘DAU’ section of this manual for details of its meaning
and methods of rectification.

25/07/07 J2961BU01 REV 0.doc 33


INSTALLATION, OPERATION & MAINTENANCE MANUAL

SHUTDOWN PROCEDURE

To shutdown the system for maintenance purposes, etc., the following procedure should be observed.

.NOTE:- If the system is shutdown the supply to the load may be lost. Refer to Circuit Diagram supplied

CAUTION!:- Before proceeding with maintenance of the equipment consult the Health and Safety section
of this manual.

WARNING!:- Even though the equipment is shutdown, high voltages may still be present within the
cubicle. Refer to the Circuit Diagram supplied and isolate elsewhere before working on the equipment.

Procedure:-

n TOTAL SHUTDOWN

ACTION
1. Open the LOAD CIRCUIT BREAKERS
2. Open the DISTRIBUTION INPUT CIRCUIT BREAKER
3. Open BATTERY CIRCUIT BREAKER
4. Open the DISTRIBUTION FEED CIRCUIT BREAKER
5. Open the CHARGER OUTPUT ISOLATOR
6. Open the AC INPUT CIRCUIT BREAKER
The charger is now shutdown allowing maintenance work to be performed. Refer
to start-up procedure in-order to turn the system back on when ready.
END

The system or charger is now SHUTDOWN, allowing maintenance work to be performed.

25/07/07 J2961BU01 REV 0.doc 34


INSTALLATION, OPERATION & MAINTENANCE MANUAL

SECTION 9

FAULT FINDING INSTRUCTIONS

CAUTION!:- Fault finding should only be undertaken by competent electrically qualified personnel who are
familiar with the equipment operation and it's potential hazards. The safety instructions at the front of this
manual should be read and fully understood before working on the equipment.

This section is designed to provide sufficient information to enable fault finding diagnosis and
repair/replacement down to individual module level. For more extensive repairs the assistance of Erskine
Systems should be sought.

PROCEDURES
Look for the obvious fault. Often a visual inspection is all that is necessary to locate a fault - particularly
with capacitors. Always check for loose/broken inner conductors, loose PCB's, etc.
There are NO tests that require removal of the earth connection from oscilloscopes or other test
equipment. Dual beam oscilloscopes must have differential facilities.
There is no practical or satisfactory way of anticipating a malfunction before it occurs with this type of
equipment; generally the equipment will work perfectly or shutdown.

TESTING SEMI-CONDUCTORS
In almost every instance, a faulty power semi-conductor will have a short circuited junction and,
because of parallel paths in the circuit, a short circuit device may cause several other components in
proximity with it in the circuit electrically to also appear faulty. If this is suspected, disconnect one end
of each device until the faulty component is found.
Also due to parallel paths in the circuit, SCR's may not appear high resistance across anode and
cathode, and diodes may not appear low resistance in one direction and high resistance in the other. If
there is any doubt about readings, compare each component with its equivalents in the circuit; large
differences found in this way indicate a fault condition.
Take care when replacing components not to replace forward diodes with reverse diodes (check part
numbers) and vice versa, or to fit SCR modules the wrong way round.

STUD MOUNTING SEMI-CONDUCTORS


Before fitting stud mounting components, apply a smear of Dow Corning 340 Thermal Compound to the
mating surfaces. Stud mounted devices should be tightened to the correct torque. Failure to correctly fit
the device correctly can cause overheating and premature failure of the component. For correct
tightening torque’s please refer to Customer Services Department - Erskine Systems.

TEST EQUIPMENT REQUIRED ON-SITE


The following is a list of test equipment recommended for the purposes of routine testing, fault diagnosis
and repair.
1. DC stabilised Power Supply 1A with a voltage range of between 0V and up to
approximately 25% higher than the highest level setting (see circuit diagram).
2. AC/DC Clip-on Ammeter
3. Digital Multimeter - True RMS Reading
4. Digital Storage Oscilloscope
6. Variac
7. DC Load Bank of suitable rating

Please contact the Customer Services Manager at Erskine Systems, for suitability of test equipment.

25/07/07 J2961BU01 REV 0.doc 35


INSTALLATION, OPERATION & MAINTENANCE MANUAL

SOLUTIONS TO COMMON FAULTS

1. Before making any fault finding checks, it is advisable to disconnect any external load and the
battery so as not to disguise any fault in the charger unit itself.
2. There are two main fault conditions: Low output and High output. Care must be taken when
determining the type of fault present, as it may be possible that a High output condition has caused
the main fuse in the charger DC output line to fail, hence causing a low output situation. Zero
output is taken to be a low output condition.

HIGH OUTPUT AND HIGH OUTPUT SHUTDOWN

1. If the High Volts Shutdown operates then the charger’s input relay will be latched open. If this has
occurred due to nuisance tripping then the input MCB should be opened to clear the fault and re
closed. If the problem persists then continue through the instructions below.
2. Check that the AC Mains input is present and that the voltage is correct. The correct input voltage
is shown on the circuit diagram.
3. Check that the sensing voltage at the controller is the same as the charger output terminals (or at
the charger side of the charger output isolator). Trace for bad or missing connections as necessary.
Refer to Circuit Diagram for connection Details (+VE and -VE output terminals).
4. Remove the incoming AC mains and disconnect one gate connection to the thyristors. Re-instate
the incoming AC mains. Generally, if the removal of the firing signal has no effect on the high
system output then the stack assembly could be faulty. Repeat this step for the remaining
thyristors.
5. Check controller setting (refer to setting up procedure) and if control of voltage or current is not
possible, replace controller.

LOW OUTPUT

1. Check that the AC Mains input is present and that the voltage is correct. The correct input voltage
is shown on the circuit diagram..
2. Check for voltage on transformer primary when Charger Input Circuit Breaker is closed. This should
be equal to the incoming AC mains supply.
3. Check for AC input to thyristor stack (terminals A1, A2 on PCB). If not present, check fuse F1. If F1
is blown, the stack assembly is probably faulty, replace as necessary.
4. Check supply to the controller, terminals L and N on PCB (refer to Circuit Diagram).
5. Check that the sensing voltage at the controller is the same as the charger output terminals (or at
the charger side of the charger output isolator). Trace for bad or missing connections as necessary.
Refer to Circuit Diagram for connection Details (+VE and -VE output terminals).
6. Check controller settings (refer to setting up procedure) if possible.
7. Check charger DC output fuses and replace as necessary.
8. Check external connections on the controller (e.g. links).

NOTE:-If in doubt any problems should be referred to the Customer Services Manager - Erskine Systems.

25/07/07 J2961BU01 REV 0.doc 36


INSTALLATION, OPERATION & MAINTENANCE MANUAL

CHARGER FAULT FINDING GUIDE

Once a problem has been identified with the aid of the panel indications, the following table can be used
to help identify the cause and cure the fault. Whilst fault finding, the normal start-up and shutdown
procedures should be used. Also the applicable setting up procedures should be followed.

PROBLEM CAUSES
A B C D E F G H I J K L
Loss of Output Voltage 3 3 3 3 3 3 3 3 3 3 3
High Output Voltage 3 3 3 3 3 3

CAUSES SOLUTIONS
A Charger switched off Switch charger on
B Mains supply faulty (* = or off) Restore mains supply to within limits
C Blown control or power fuses Check for shorts and replace
D Power semi-conductor open circuits Check for shorts and replace
E Power semi-conductors short circuit Check for shorts and replace
F Thyristors not firing Replace
G Faulty control cards Replace and reset
H Incorrect voltage settings Check and adjust
I Incorrect current settings Check and adjust
J Faulty filter capacitor Replace
K System overloaded Remove some excess load
L Loose wiring connections Check and secure

25/07/07 J2961BU01 REV 0.doc 37


INSTALLATION, OPERATION & MAINTENANCE MANUAL

SECTION 10

MAINTENANCE INSTRUCTIONS

1. As a general principle, it is better not to interfere with the control of this type of equipment, provided
that the equipment is functioning satisfactorily. It is recommended that routine maintenance is
limited to simple cleaning and checking that the ventilation paths, etc. are free from obstruction.
Maintenance procedures concerning the batteries may be found in the battery manufacturer's
handbook - supplied with the batteries.

2. The equipment should be checked and cleaned of dust, etc. at periods depending upon the
operating climate. During the regular maintenance period, nuts, bolts and screws should be
checked for correct tightness.

3. The manual operation of switches should be checked wherever possible. A visual check of all
components should be made to ensure that components have not deteriorated from the effect of
humidity, temperature, etc. Instruments should be zeroed as required.

4. In the event of faulty operation it is recommended that the fault finding procedures outlined be
carried out and/or consult the Customer Services Manager at Erskine Systems.

TORQUE SETTINGS

The settings shown below are the maximum torque settings to be applied and are for reference only.
Due to the varying strengths of the materials that are to be clamped, the actual torque settings are left
to the discretion of the engineer. The setting used should be sufficient to securely clamp the materials
for a given purpose, without causing damage.

NUTS AND BOLTS/SCREWS TORQUE (Nm) (Ft.lb)


4mm (M4) 8.1Nm 6ft.lb
6mm (M6) 16.3Nm 12ft.lb
8mm (M8) 24.4Nm 18ft.lb
10mm (M10) 32.5Nm 24ft.lb
12mm (M12) 48.8Nm 36ft.lb
THREADED INSERTS AND BOLTS/SCREWS
4mm (M4) 5.4Nm 4ft.lb
6mm (M6) 8.1Nm 6ft.lb
8mm (M8) 13.5Nm 10ft.lb
10mm (M10) 18.9Nm 14ft.lb

25/07/07 J2961BU01 REV 0.doc 38


INSTALLATION, OPERATION & MAINTENANCE MANUAL

SECTION 11

DRAWING LIST

CHARGER CIRCUIT DIAGRAM – J2961BC01


SINGLE LINE DIAGRAM – J2961BC02
BATTERY LAYOUT – J2961BF01
EXTERNAL ARRANGEMENT – J2961BH01
INTERNAL ARRANGEMENT – J2961BH02

25/07/07 J2961BU01 REV 0.doc 39

Das könnte Ihnen auch gefallen