Beruflich Dokumente
Kultur Dokumente
1. G I s in contrast to AIS.
0 High density grid: frequent and short connections from the switchgear
elements t o the earth grid. This reduces the TGPR in the GIS and
contributes t o reduce the total earth electrode resistance, but not in
direct proportion t o the additional length.
0 Connection t o the reinforced concrete mat: connecting the reinforcing
steel mesh and structural steel t o the earth grid will reduce the total
earth electrode resistance. However this is complicated and it has t o be
Authorized licensed use limited to: UNIVERSITY TEKNOLOGI MALAYSIA. Downloaded on February 26,2010 at 03:00:18 EST from IEEE Xplore. Restrictions apply.
done in a way that avoids problems of overheating and damage of the
reinforced structure due t o excessive circulating currents.
Use of deep driven ground rods: If, after the above methods have been
applied, the earth electrode resistance is s t i l l high, then the use of dee!p
driven ground rods will be required.
3. Induced currents.
Gas Insulated Substations have a grounded outer sheath enclosing the high
voltage inner conductor, unlike conventional equipment whose closest
ground is the earth's surface. At the same time the phase separation is muc:h
smaller.
The Rogowski coil was wrapped around various earthing connections in the
GIS, e.g. grounded chambers, earth straps, inter-phase shunts, steel supports,
ladders etc. The results confirmed a high percentage of current circulating
through the enclosure (in the range from 50 t o 85% of the 2000 A of the
primary current). It was also found that a high level of circulating current
(up t o a 50%) was present in the inter-phase copper earth straps which
shunt the individual phase enclosures.
At the beginning of the GIS technology, the grounding design was based in
the classical approach of limiting the power frequency enclosure potentials
t o safe levels based on the maximum expected fault-current conditions. In
contrast t o these relatively low potentials, arcing between the grounded
enclosures and other grounded components which are indicative of much
higher potentials, were routinely observed during breakdown in HV tests or
Authorized licensed use limited to: UNIVERSITY TEKNOLOGI MALAYSIA. Downloaded on February 26,2010 at 03:00:18 EST from IEEE Xplore. Restrictions apply.
during normal disconnector operation. An exhaustive research was done t o
understand the mechanism of this particular TGPR in CIS.
The reasons for this TGPR were the specific characteristics of the breakdown
in SF6 producing overvoltages with a very fast rise time of 5-20 ns and a t the
same time the specific coaxial arrangement of the bus-duct which happened
to be very good for the transmission of these MHz range voltage surges.
Because of the low operating speed of the disconnector, each closing and
opening operation will produce tens of pre-strikes and re-strikes (figure 3).
Each pre-strike generates a fast transient wave of half the value of the
voltage across the contacts which is transmitted in both directions away
from the pre-strike point (3). When the travelling wave arrives a t the aidSF6
termination, the vertical bushing and the overhead line define external
surge impedances which allow the incident travelling wave t o "refract" out.
One part of the incident wave is reflected back into the bus duct, another
part continues through the overhead line-to-ground transmission line and
the rest forms the TGPR a t the bushing-enclosure junction (6). This TGPR is
soon attenuated by the enclosure ground straps which act as other
transmission lines.
Just t o give an idea of the order of magnitude of the TGPR these are the
results of the measurements performed in a 525 kV GIS by Ontario-Hydro (6):
Voltage across contacts during disconnector closing: 526 kV(Vs)
0 Voltage propagate through GIS bus : 0.5 Vs = 263 kV
0 Arrives a t bushing A (17.7 m from Vs) : 172 kV (33% attenuation by T of
bushin9).
0 TGPR a t bushing A: 45 kV (26% V input t o bushing)
0 Maximum TGPR measured in substation building: 3 kV
Authorized licensed use limited to: UNIVERSITY TEKNOLOGI MALAYSIA. Downloaded on February 26,2010 at 03:00:18 EST from IEEE Xplore. Restrictions apply.
Short, straight and low inductance connections to the earth grid contribute
t o reduce the TGPR. If the GIS is inside a building, then connecting the
enclosure [via short earth straps] t o the building structure when crossing the
walls will help t o attenuate the TGPR inside the substation.
Finally, special care must be taken when dealing with discontinuities in the
gas enclosure as encountered with an external CT, cable sealing end:s,
transformer connections etc. At these points the enclosures are separated bly
an insulating spacer and the associated earth strap connections are often too
long and too inductive for effective grounding of high frequency transient
potentials. Therefore significant voltages of several kV develop across the
insulated flange which may cause sparking in the surrounding air. In this
case the use of surge suppressers, such as metal oxide varistors (MOV) is
highly advisable.
5. Summary
6. References:
Authorized licensed use limited to: UNIVERSITY TEKNOLOGI MALAYSIA. Downloaded on February 26,2010 at 03:00:18 EST from IEEE Xplore. Restrictions apply.
Figurel. GIs double bus-bar
section view
Authorized licensed use limited to: UNIVERSITY TEKNOLOGI MALAYSIA. Downloaded on February 26,2010 at 03:00:18 EST from IEEE Xplore. Restrictions apply.