Sie sind auf Seite 1von 7

How Important is

Surface Area .? "

Fire-tube and water-tube boilers are specified gas velocities can vary, depending
widely used in the chemical process on the allowable gas pressure drop.
It's important, but industries (CPI), for example, to recover Both of these factors - tube size and gas
energy from flue gas streams and to velocity - influence the heat -transfer coef-
it should not be generate steam in gas- or oil-fired packaged ficients and, hence, the surface area.
the only criterion steam generators. One of the main criteria Sizing procedure
that engineers use to specify or eval uate The procedure for sizing a fire-tube
you use to size boilers is surface area. Packaged firetube boiler is as follows.
and specify boilers, for instance, are often specified as The required surface area, S, is
requiring 5 ft= per boiler horsepower (one calculated from:
boilers and safety boiler horsepower is equivalent to 34,500
valves. Consider Btu/h of output). S = Q/(UAT) ( 1a)
the factors However, surface area is a misleading
variable because heat transfer depends on If U is based on the tube outer diameter,
outlined here as other factors as well, including gas velocity, then the surface area is also based on the
the size of the tubes, the tube pitch and tube outer diameter; likewise, if U is based
well. on the tube inner diameter, then the
arrangement, the configuration of tube
fins, fouling factors, and others. For the surface area should be based on the tube
same duty or energy transferred, one can inner diameter. This can also be expressed
develop different designs with significant as Uo So = Ui Si , where So = πdo NL/12 and
differences in surface areas, and the Si = = πdi NL/12. Thus, Eq. 1 a can be
various designs can have widely different rewritten as either
costs.
This article outlines how to size and Si = Q/(Ui∆T) (lb)
V. Ganapathy,
specify boilers other than by simply stating
ABCO Industries or
surface area. In addition, it discusses the
selection of safety valves, which is still So = Q/(Uo∆T) (1c)
done based on surface area, and describes
The energy transferred, Q, is:
a more practical approach.
Q = Wg Cp,(T1-T2)h l=Ws Hs (2)
FIRE-TUBE BOILERS
In fire-tube boilers (Figure 1), flue gas The term h, represents the heat loss factor
flows inside the tubes while the steam is and is equal to one minus the losses due to
generated outside the tubes. Depending on radiation and convection from the boiler
the cleanliness of the gas, tube sizes can surfaces. A 2% loss, or h l = 0.98, is typical.
vary from 1.5 to 3.5 in. O.D. If slagging is The log mean temperature difference,
a concern, as in municipal solid waste ∆T, is determined by:
incineration applications, the boiler should
be of a multipass design, where the first ∆T= (T 1-t s)-(T2 -ts)/ln[(T 1-t s)(T 2 –t s) (3)
pass is a pipe with a diameter ranging from
30 to 48 in. and subsequent passes consist
of smaller diameter tubes. Packaged oil- or
gas-fired boilers have a similar
configuration. The

OCTOBER 1992 CHEMICAL ENGINEERING PROGRESS


The overall heat-transfer coefficient, Uo, is
given by:

The tube-side heat-transfer coefficient,


hi, is the sum of the convective heat-transfer
coefficient, h,., and the nonluminous heat-
transfer coefficient, h n . The value of hn
depends on the partial pressures of the tri -
atomic gases in the flue gas (e.g., CO2 , H2 O)
and is usually small - on the order of 5% of
h c in fire -tube boilers. Thus, many designers
are conservative and neglect hn. (In water-
tube boilers, however, h n is very significant
and cannot be neglected.) Further details on
calculating hn can be found in (1).
The value of h i is obtained from the Dittus-
Boelter equation:
Nu = 0.023Re0.8 Pr0.4 (5)
where Nu = h c di /12k, Re = 15.2w/( µd i), and Pr
= µCp/k. Substituting these expressions into
Eq. 5 and simplifying yields:
h,. = 2.44w 0. 8F/di 1.8 (6)
0.4 0.6
where F = (Cp /µ) k
The inside and outside fouling factors are
denoted by ffi and ffo , respectively. For

CHEMICAL ENGINEERING PROGRESS OCTOBER 1992 * 71


clean gases and boiler water, they can V = 0.05wv/d i2 (7) water temperature is 220°F and steam
be assumed to be 0.001 ft2•h•°F/Btu. While it may seem easier to assume a
pressure is 150 psig.
For gas streams that can cause foul- number of tubes than to assume a
Fouling factors of ffi = 0.002
ing, ff can be much higher - on the mass flow rate and gas velocity, in
order of 0.05 ft 2•h•°F/Btu. Tables of practice, because these calculations ft2h°F/Btu for the gas and ff0 = 0.001
fouling factors are available in several are done by computer the terms are ft2h°F/Btu for the steam, heat losses
published sources, such as (2) and (3). essen tially conceived in parallel. of 2%, and an outside heat-transfer
The boiling heat-transfer coeffi cient, Based on the temperature and coefficient of h = 2,000 Btu/ft2hF are
ho is very high - on the order of 2,000 properties of the gas, h c and then U assumed. Tube sizes of 1.75 x 1.521, 2
Btu/ft2h°F. Thus, even a 20% are determined. Then Eq. 1 is used to x 1.773, and 2.5 x 2.238 (outer x inner
variation in its value will not impact calculate S, which is in turn used to diameter) will be considered. What are
U, because the tube-side coefficient, determine the tube length, L. The gas the effects on surface area
hi, which is typically on the order of pressure drop is then calculated based requirements of tube size and gas
10-20 Btu/ft 2h°F, governs U. on geometry (1): velocity (which can range from 90 to
The last term in Eq. 4 is the resis tance ∆Pg = (93x10-6)fL e vw2/d i 5 (8) 170 ft/s)?
of the tube wall to heat transfer. The For simplicity, most of the calculation
If the computed pressure drop is
thermal conductivity of the tube details are omitted. The results of the
higher than that allowed by the speci-
material, K, is about 20 -25 Btu/ calculations for the various tube sizes
fication, another mass flow rate per
ft•h•°F for carbon steel, the typical and velocities are summarized in
tube is assumed and the procedure is
material used for boilers. Table 1.
repeated.
To size the boiler, the mass flow per Example 1 For the same amount of' energy
tube, ranging from 120 to 200 lb/h Consider a fire-tube waste heat transferred, one can see significant
for a 2-in. tube, and the gas velocity, boiler required to cool 100,000 Ib/h variations in the surface area - by as
typically ranging ranging from 60 to of flue gas from 1,300°F to 474°F. much as 50%. As the gas velocity
170 ft/s, are assumed and the tube The gas is at atmospheric pressure increases, U increases, which brings
count is calculated. The relationship and consists of (by volume) 12% CO2 down the surface area,
between mass flow and velocity is: 12% H 2O, 70% N2 and 6% O2. Feed

72 OCTOBER 1992 CHEMICAL ENGINEERING PROGRESS


and the gas pressure drop increases.
Also, as the tube size increas es, U
decreases for the same velocity.
This, along with the fewer larger
tubes, results in longer tube lengths.
The main point to be noted is that
for the same duty, the surface area
can vary depending on the tube size
and gas velocity.
These conclusions also apply to
packaged fire-tube boilers firing oil or
gas. A rule of thumb that, unfortu-
nately, is still being used by specifying
engineers is 5 ft2 of surface per boiler
horsepower. One can, by using a
higher gas velocity or smaller tube
size, develop a boiler design that will
work fine with up to 10% to 20% less extended surfaces, often called finned where A, and Ai, which refer to the
surface area. However, through lack tubes, may be used. The use of finned total external and internal surface area
of knowledge of heat-transfer design, tubes makes the design very compact. per foot of tube, are used instead of
several good designs are being over- Other advantages include lower do and di. (In the case of bare tubes,
looked by potential buyers, consul- weight and lower gas pressure drop. At/Ai = d o / d i ) . Fin effectiveness is
tants, and end users. If the gas stream is dirty, as in represented by n, which equals 1 in
Boiler cost generally increases with an municipal solid waste incineration the case of bare tubes. In wat er-tube
increase in surface area. However, it systems, only bare tubes should be boilers, h o is the gas -side heat-
does not rise proportion ately because used. transfer coefficient, which is the sum
other items, such as boiler trim, of hc and h n ; h, is the tube-side
Design procedure
controls, casing, insulation, and so on, boiling heat transfer coefficient,
As with fire-tube boilers, the heat - which is in the range of 2,000 -3,000
account for a consid erable part of the
total cost and these may not increase transfer duty, Q, is calculated by: BtU/ft2hF.
proportionately. Labor costs are Bare tubes. The procedure for
Q = Wg Cp(T1-T2)hl, computing h o for bare tubes is as fol-
significant and may not be
= W s∆H s. = U S ∆T (9) lows. Grimson's correlation for con-
proportional to surface area. Each
case, therefore, must be reviewed U refers to the overall heat-transfer vective heat transfer is used for tubes in
independently. coefficient, and it is usually based on either an in -line or staggered
the outside surface area of the tube. arrangement (depicted in Figure 3):
WATER-TUBE BOILERS Uo is given by:

In water-tube boilers (Figure 2), if the


gas stream is clean (such as with gas
turbine exhaust gases), tubes with

The gas properties are evaluated at

CHEMICAL ENGINEERING PROGRESS 0 OCTOBER 1992 73


the gas film temperature, and the coef- triatomic gases present, and the beam The gas pressure drop, ∆Pg , is
ficients B and N are obtained from length, L b . b is given by: then obtained from:
Table 2. (The ratio of transverse pitch
to outside diameter (S t/d o) and of lon -
gitudinal pitch to outside diameter
(Sl/d o ) are computed. (S t /d o) is read where "surface" refers to the total
across the top of the table, and Sll d o external surface area touched by the where f is the friction factor. For an
down the side, under "Staggered" or gas. Hottels' charts (2) are used to inline arrangement, f is:
"In-line," as appropriate. The values of determine the gas emissivity, s, from
B and N are then read from the chart.) the above data. One can then calculate
Gas mass velocity, G, is h from:
calculated by:

(18a)

Once ho is computed (here, too, and for a staggered arrangement, f is:


The nonluminous heat-transfer
ho = hc + hn), Eq. 10 can be used to
coefficient, h„, could be significant
calculate Ua. S is then obtained from:
depending on the tube pitch, the par-
tial pressures of water vapor and
other

OCTOBER 1992 CHEMICAL ENGINEERING PROGRESS


Finned tubes. The correlations
The con vective and nonlumi-
for heat transfer in finned
nous heat-transfer coefficients,
tubes are more complex, so
hc and hn are computed for bare
only the chart technique for
tubes using the procedure
computing hc will be discussed
described above, and Uo is eval-
here, since the objective of this
uated from Eq. 10. The outside
article is only to show the effect
tube area, So is then computed
of a few variables on surface
and is used, along with the
area and not the complete
assumed tube length (L) and
design procedure for finned
number of tubes wide (Nw), to
tubes. [The interested reader
determine Nd, the required num-
can find further details in (1).[
ber of rows of tubes deep. Then
Figure 4 can be used to esti-
Eq. 17 is used to calculate ∆P g.
mate h,., the convective heat-
For finned tubes, the gas
transfer coefficient, for in -line
arranged tubes having a 2-in. mass velocity is calculated and
is used to obtain h . from Figure
O.D. and a 4-in. square pitch. 4. The fin effectiveness, η and the gas
The heat-transfer coefficient, fin
exhaust. Gas data: Flow = 150,000 pressure drop for 10 rows are also
effectiveness (11), and gas pressure
lb/h. Iinlet gas temperature = read from the chart. At and Aw can be
drop are shown for 10 tube rows
1,000°F. Exit gas temperature = obtained from standard reference
based on a gas turbine exhaust at an
382°F. Feed water temperature = charts or can be calculated based on
average temperature of 600°F.
240°F. Inside and outside fouling the fin geometry (1). Beam length is
The real value of the chart, however,
factors = 0.001 ft2h°F/Btu. ho = calculated and used to determine h„.
is not in estimating hc. Rather, it
2,000 Btu/ft2•h•°F. The geometry Then Eq. 10 is employed to compute
illustrates the effect of fin configura-
is as follows: 18 tubes/row, tube U(), which is used to determine Nd
tion (that is, fin density, n, and fin
O.D. = 2 in., I.D. = 1.77 in., length and ∆P g.
height, h) on hc . From this figure, one
= 10 ft, in-line arrangement with Table 3 summarizes the results
can see that:
transverse and longitudinal and compares the bare-tube and
• as fin density increases, h
decreases; (square) pitch = 4 in., and material finned tube cases. The advantages
• the higher the fin density, the of construction is carbon steel. of using finned tubes are clear: The
higher the gas pressure drop will be, How do designs using bare tubes finned tube boiler is more compact
even after adjusting for the effect of and serrated finned tubes (fin (it has only 20 rows deep, vs. 122
the different number of rows density = 5 fins/in., height = 0.75 rows of bare tubes), has a lower gas
required; and in., thickness = 0.05 in.) compare? pressure drop (3.2 vs. 4.5 in the
• fin effectiveness decreases with Again, the calculation details bare tube boiler), and weighs less
are omitted. [The complete (26,000 lb vs. 48,000 lb). On the
fin height.
Hence, the simple conclusion procedure can be found in (1).] other hand, the sur
that can be drawn from Figure Here we will discuss the most
4 is that a higher fin density
(or surface area per unit
length) results in a lower hc
and a lower Uo, which in turn
means that more surface area
is required.
Let us now look at two specific
examples to see how different
fin configurations, and how the
difference between bare and
finned tubes, can significantly
affect surface area.
This example also illustrates
the advantages of using
extended surfaces, particularly
in clean gas applications.
A boiler evaporator needs
to be designed for a gas
turbine

CHEMICAL ENGINEERING PROGRESS * OCTOBER 1992 * 75


LITERATURE CITED
1. (:antipathy, V., "Waste Heat Boiler
Deskbook," Fairmont Press, Atlanta
(1991) (also available from the
author). 2. Ganapathy, V, "Applied
Heat Transfer," Pennwell Books,
Tulsa, OK (1982).
3. Tabular Exchanger Manufacturers
Association, "Standards of the
Tubular Exchanger Manufacturers
Association (TEMA), 7th ed., New
York, NY (1988).
4. American Society of Mechanical
Engineers, Sec. I, Rules for
Construction of Power Boilers, 1989.

face area is much higher - nearly


twice the area of the bare-tube
boiler - because of the lower overall
heattransfer coefficient.

Example 3
The choice between bare and finned Btu/ft2h°F compared with 2,000 100% of the steam simply by varying
tubes is not the only factor that BtU/ft2h°F for boiling water) results the fuel input to the burner. To illus -
affects surface area. One can also see in a much lower U . Hence, more trate, a heat recovery boiler for a
significant variations in surface area surface area is required for the typical 3-5 MW gas turbine can
for the same duty with finned tubes
same duty. Similar results are generate about 20,000 lb/h of steam
of different configurations.
obtained for cases 3 and 4, which in the unfired mode but can be
Consider a finned-tube superheater
have the same duty. designed to generate up to 100,000
being designed for the following condi -
Comparing cases 2 and 3, we see Ib/h of steam with the same surface
tions: Gas flow = 200,000 lb/h. Gas
that case 3 transfers more energy area simply by firing auxiliary fuel.
inlet temperature = 1,200°F. Gas
with less surface area. This is due That is, the same boiler with th e
analysis (vol. %) = 7% CO2 ,12% H2O,
to a better fin configuration [as same surface area can generate a
75% N 2 and 6% O2. Steam flow=
explained fully in (l)]. maximum of only 30,000 lb/h at one
100,000 Ib/h. Steam inlet tempera-
Thus, the bottom line is that simply site because the demand is only
ture = 491°F (saturated) at 600 psig.
relying on surface area for 30,000 Ib/h or 90,000 Ib/h at
Fouling factors for the gas and steam=
specifying a boiler is simplistic and another location because that site
0.001 ft2-•h•°F/Btu. The tube configu-
can lead to wrong decisions by needs 90,000 lb/h of steam. Now,
ration is: tube O.D. = 2 in., I.D. =
eliminating designs that can according to ASME code, the safety
1.738, 22 tubes/row, length = 10 ft,
transfer the same duty but with a valve sizing remains unaffected, as
inline arrangement with square pitch
= 4 in., countercurrent flow, and 22 lower surface area. the surface area is the same!
streams (100,000 lb/h of steam flows
through 22 tubes). The duty is SAFETY VALVE SIZING AND
between 14 and 18 million Btu/h. ASME CODE
What happens when the number of Section 1 of the American
rows deep is varied, the fin density is Society of Mechanical Engineers'
varied from 2 to 5 fins/ in., and the Code (4) on boilers recommends
fin height is varied from 0.5 to 0.75 that safety valves should be sized
in. (fin thickness is constant at 0.075 based on the surface area used in
in.)? the boiler. This is not a prudent way
The procedure is very similar to of sizing safety relief valves. As we
that used in Example 2. In this case, have just seen, one can transfer the
though, the tube-side heat-transfer same duty with variations in surface
coefficient, hi must be computed using area of 50 to 100%.
Eq. 6. The results are presented in It is more practical to use the
Table 4. steaming capacity as the criterion
Though cases l and 2 transfer the for relief valve sizing. For example,
same energy, the surface areas are in gas turbine exhaust applications,
significantly different, varying by one can generate anywhere from
nearly 100%. The reason is that the 20% to
high fin density coupled with a
smaller hi (on the order of 200-250

76 OCTOBER 1992 0 CHEMICAL ENGINEERING PROGRESS

Das könnte Ihnen auch gefallen