Sie sind auf Seite 1von 3

KK INDUSTRIES 9/28/2020

DESIGN CHECK FOR TRUSS & PURLIN OF TAJ AMBER


S.NO DESCRIPTION UDL TOTAL YDL LOAD ON DESIGN (+25%) UDL LOAD ON
1 DESIGN PARAMETERS KG/M2 PURLIN TRUSS PURLIN TRUSS
A Sumperimposed Dead Load DL 100 175 220
B LIVE LOAD LL 75 210 265
C SERVICE LOAD ( AC DUCTING/LIGHTS/CABLES/PIPES ETC) SL 35
D WIND LOAD WL 0 (INDOOR ,SURROUNDED BY HOTEL BUILDING )

11 PURLIN -ISMC 150X75( IS: 2062 ) W(KG/M) A(cm2) Lxx(cm)4 Zxx(cm3)


SECTIONAL PROPERTIES ( IS :800& IS 808) 16.4 20.88 788 103.9
TRUSS SPAN (M) 4.2
PURLIN PITCH (m ) 1.54
UDL Load on single Purlin 338.8 kg/m (Includes DL+LL )
Max Bending Moment in Purlin=(1/8)*w*L2,simply supported on Truss 747.1 kg-m
74705 kg-cm
Allow,Bending stress in ISMC (IS 2062) 1650 KG/CM2
Calculated Mmt.of Inertia,Zxx 45.28 cm3 Provided 103.9 cm3
Calculated , Sectional Modulus ,Lxx 340 cm4 788 cm4 HENCE, SAFE .

111 TRUSS FRAME


TATA STEEL RHS/SHS PIPES(Gr Fe -350 ) a(cm2) Lxx(cm)4
Top/Bottom Member -RHS 240X120X8 53.39 3851.84
Vertical Support MemberSHS :100X6 21.63 311.47

Truss Frame :Lower Height 1200:Higher Height.2400-30800mm Lg. within 21 purlins @1540mm pitch
Avg. Truss Frame Ht ={(1200+2400)/2}=1800mm 180 cm
Distance between c/c of RHS Top & Bottom 156 cm
Vertical Distance in between RHS Top& Bottom 132 cm

Sectional Modulus of Builtup Truss Frame,Lxx=(a)+(b)


(a)from RHS:240X120X8 (Top/Bottom) 657353 cm4
(b)from SHS :100X6( 1320MM-Vertical Support ), 229997 cm4
Total Sectional Modulus ,Lxx= 887350 cm4
Max.Available ,Mmt ,Of Inertia,Zxx= 11376 cm3

Truss Span (m) 420 cm


Purlin Pitch,Lp= 154 cm
Truss Lengrh (over 21 Purlins@pitch 1540mm),L= 3080 cm

Total Load on TRUSS FRAME ( via Purlin Cleats ),P= 34280 kg (Includes DL+LL+SL)
Load on frame ( via Individual Purlin Cleats ),P= 1632 kg
Reaction Load on Civil Column (at both Truss ends ),R= 17140.2 kg

CASE A
Bending Mmts due to Direct Forces (R&P)ON Truss Frame
Bending Moment @centre of truss frame,due to
(a) Reaction Load,R ( clockwise ) 26395908 kg-cm
(b) Individual PurlinLoads,P (COUNTERCLOCKWISE ) 138264280 kg-cm
Max,Effective BM(+/-)= 111868372 KG-CM

Allow,Bending Stress in (RHS/SHS ) Member (Fe-350) 2145 kg-cm2


Calculated ,Mmt .of Interia ,Zxx 12306 cm3 Provided 11376cm3
Caculated ,Sectional Modulus ,Lxx 959851 cm4 887350 cm4 BORDERLINE CASE

CASE (b)
Bending Mmts due to UDL Load on truss Frame
Assuming,Purlin Cleats Load (P, each ) is converted to UDL on Truss
Max.UDL on Truss Frame ,w 11.13 kg/cm
Max ,MB in Truss =(1/8)*w*L2,Simply supported Truss Ends 13197954 kg-cm

Allow,Bending Stress in (RHS/SHS ) Member (Fe-350) 2145 kg-cm2

Calculated ,Mmt of Interia Zxx 6153 cm3 Provided 11376 cm3


Calculated Sectional Modulus Lxx 479926 cm4 HENCE , SAFE .

NOTE : DESIGN NOT CHECKED FOR DEFLECTION OR INDIVIDUAL SUPPORT SIZES .