Trip Log - 000067 /


SIMATIC 7/12/2020 6:02:47.147 13.07.20 13:17:00

ZLATNA / 20kV / J09_PT2

MLFB: 7SJ66256JB901FG1----0S----------
Parameter-set version: V04.30.03
Device path: E:\Electrica\Digsi Zlatna\Zlatna\P7DI\GV\SD\00000063
Author:
Creation date: 18.06.19 14:13:06
Last modified: 13.07.20 13:14:39
Operating mode: Online
Comment: GF1912501560
Setting values in: Secondary value description

PRINT - CONTENTS

1 Indications ............................................................................................................................................................................................................................................. 2
1.1 Trip Log - 000067 / 7/12/2020 6:02:47.147 PM - ZLATNA / 20kV / J09_PT2/7SJ662 V04.33.00 .................................................................................................... 2

Page 1 of 2
J09_PT2_prn_13_17_00
Indications
Trip Log - 000067 /
SIMATIC 7/12/2020 6:02:47.147 13.07.20 13:17:00

1 Indications

1.1 Trip Log - 000067 / 7/12/2020 6:02:47.147 PM - ZLATNA / 20kV / J09_PT2/7SJ662 V04.33.00

Trip Log - 000067 / 7/12/2020 6:02:47.147 PM - ZLATNA / 20kV / J09_PT2/7SJ662 V04.33.00


Number Indication Value Date and time Cause State

00301 Power System fault 67 - ON 12.07.2020 18:02:47.147


00302 Fault Event 69 - ON 12.07.2020 18:02:47.147
00501 Relay PICKUP ON 0 ms
01761 50(N)/51(N) O/C PICKUP ON 0 ms
01762 50/51 Phase A picked up ON 0 ms
01763 50/51 Phase B picked up ON 0 ms
01764 50/51 Phase C picked up ON 0 ms
01810 50-1 picked up ON 0 ms
INTR. INCHIS PENTRU OSCILO ON 70 ms
01764 50/51 Phase C picked up OFF 342 ms
01762 50/51 Phase A picked up OFF 353 ms
01763 50/51 Phase B picked up OFF 353 ms
01810 50-1 picked up OFF 353 ms
01761 50(N)/51(N) O/C PICKUP OFF 353 ms
00545 Time from Pickup to drop out 353 ms 353 ms
00301 Power System fault 67 - OFF 12.07.2020 18:02:47.500