Sie sind auf Seite 1von 11

J09_PT2_prn_13_15_55

Event Log - - ZLATNA /


SIMATIC 20kV / J09_PT2/7SJ662 13.07.20 13:15:55

ZLATNA / 20kV / J09_PT2

MLFB: 7SJ66256JB901FG1----0S----------
Parameter-set version: V04.30.03
Device path: E:\Electrica\Digsi Zlatna\Zlatna\P7DI\GV\SD\00000063
Author:
Creation date: 18.06.19 14:13:06
Last modified: 13.07.20 13:14:39
Operating mode: Online
Comment: GF1912501560
Setting values in: Secondary value description

PRINT - CONTENTS

1 Indications ............................................................................................................................................................................................................................................. 2
1.1 Event Log - - ZLATNA / 20kV / J09_PT2/7SJ662 V04.33.00 .............................................................................................................................................................. 2

Page 1 of 11
J09_PT2_prn_13_15_55
Indications
Event Log - - ZLATNA /
SIMATIC 20kV / J09_PT2/7SJ662 13.07.20 13:15:55

1 Indications

1.1 Event Log - - ZLATNA / 20kV / J09_PT2/7SJ662 V04.33.00

Event Log - - ZLATNA / 20kV / J09_PT2/7SJ662 V04.33.00


Number Indication Value Date and time Cause State

Reset LED ON 13.07.2020 11:33:49.363 Spontaneous


Command Issued=Local
PERMISIE CONECTARE INTR. ON 13.07.2020 07:23:33.599 Spontaneous
Com.Issued=AutoLocal
CLP 20kV ON 13.07.2020 07:23:33.551 Spontaneous
PERMISIE CONECTARE INTR. OFF 13.07.2020 07:23:33.482 Spontaneous
Com.Issued=AutoLocal
CLP 20kV Intermediate Position 13.07.2020 07:23:33.432 Spontaneous
DECL MAX1 LATCH PENTRU DISPLAY OFF 13.07.2020 00:54:44.047 Spontaneous
Com.Issued=AutoLocal
DEMAREAJ GENERAL LATCH PENTRU DISPLAY OFF 13.07.2020 00:54:44.047 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 13.07.2020 00:54:44.047 Spontaneous
Command Issued=Local
SEMNAL CIRCUIT DECLANSARE 2 ON 13.07.2020 00:46:18.540 Spontaneous
PREVENTIVE PSG OFF 13.07.2020 00:46:18.536 Spontaneous
Com.Issued=AutoLocal
SIG. DECL PENTRU IESIRE PSG OFF 13.07.2020 00:46:18.536 Spontaneous
Com.Issued=AutoLocal
SIGURANTA CC DECLANSATA OFF 13.07.2020 00:46:18.528 Spontaneous
Com.Issued=AutoLocal
SIGURANTA BC DECLANSATA OFF 13.07.2020 00:46:18.528 Spontaneous
PERMISIE CONECTARE INTR. ON 13.07.2020 00:46:11.607 Spontaneous
Com.Issued=AutoLocal
SEPARATOR BARA 2 20kV OFF 13.07.2020 00:46:11.557 Spontaneous
PERMISIE CONECTARE INTR. OFF 13.07.2020 00:46:11.477 Spontaneous
Com.Issued=AutoLocal
SEPARATOR BARA 2 20kV Intermediate Position 13.07.2020 00:46:11.460 Spontaneous
INTRERUPTOR 20kV OFF 13.07.2020 00:45:43.636 Spontaneous
04602 >52-b contact (OPEN, if bkr is closed) ON 13.07.2020 00:45:43.636 Spontaneous

Page 2 of 11
J09_PT2_prn_13_15_55

Event Log - - ZLATNA /


SIMATIC 20kV / J09_PT2/7SJ662 13.07.20 13:15:55

Event Log - - ZLATNA / 20kV / J09_PT2/7SJ662 V04.33.00(2)


Number Indication Value Date and time Cause State

INTRERUPTOR 20kV Intermediate Position 13.07.2020 00:45:43.598 Spontaneous


04602 >52-b contact (OPEN, if bkr is closed) OFF 13.07.2020 00:45:43.598 Spontaneous
SEMNAL CIRCUIT DECLANSARE 2 OFF 13.07.2020 00:45:43.566 Spontaneous
PREVENTIVE PSG ON 13.07.2020 00:45:43.566 Spontaneous
Com.Issued=AutoLocal
SIG. DECL PENTRU IESIRE PSG ON 13.07.2020 00:45:43.566 Spontaneous
Com.Issued=AutoLocal
SIGURANTA CC DECLANSATA ON 13.07.2020 00:45:43.565 Spontaneous
Com.Issued=AutoLocal
SIGURANTA BC DECLANSATA ON 13.07.2020 00:45:43.565 Spontaneous
SEMNAL RESORT ARMAT ON 13.07.2020 00:39:57.074 Spontaneous
02730 >Circuit breaker READY for reclosing ON 13.07.2020 00:39:57.074 Spontaneous
AVARIE PSG OFF 13.07.2020 00:39:54.636 Spontaneous
Com.Issued=AutoLocal
INTR. INCHIS PENTRU OSCILO OFF 13.07.2020 00:39:52.703 Spontaneous
Com.Issued=AutoLocal
INTR. DESCHIS PENTRU OSCILO ON 13.07.2020 00:39:52.703 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 72 - OFF 13.07.2020 00:39:52.598 Spontaneous
Com.Issued=AutoLocal
INTRERUPTOR 20kV OFF 13.07.2020 00:39:52.580 Spontaneous
04602 >52-b contact (OPEN, if bkr is closed) ON 13.07.2020 00:39:52.580 Spontaneous
INTRERUPTOR 20kV Intermediate Position 13.07.2020 00:39:52.561 Spontaneous
04601 >52-a contact (OPEN, if bkr is open) OFF 13.07.2020 00:39:52.561 Spontaneous
SEMNAL CIRCUIT DECLANSARE 1 OFF 13.07.2020 00:39:52.513 Spontaneous
AVARIE PSG ON 13.07.2020 00:39:52.497 Spontaneous
Com.Issued=AutoLocal
02863 79 - Lockout ON 13.07.2020 00:39:52.487 Spontaneous
Com.Issued=AutoLocal
DECL MAX1 LATCH PENTRU DISPLAY ON 13.07.2020 00:39:52.487 Spontaneous
Com.Issued=AutoLocal
INTR. INCHIS PENTRU OSCILO ON 13.07.2020 00:39:51.560 Spontaneous
Com.Issued=AutoLocal
INTRERUPTOR 20kV ON 13.07.2020 00:39:51.494 Spontaneous

Page 3 of 11
J09_PT2_prn_13_15_55

Event Log - - ZLATNA /


SIMATIC 20kV / J09_PT2/7SJ662 13.07.20 13:15:55

Event Log - - ZLATNA / 20kV / J09_PT2/7SJ662 V04.33.00(3)


Number Indication Value Date and time Cause State

04601 >52-a contact (OPEN, if bkr is open) ON 13.07.2020 00:39:51.494 Spontaneous


INTR. DESCHIS PENTRU OSCILO OFF 13.07.2020 00:39:51.496 Spontaneous
Com.Issued=AutoLocal
ANCLANSARE VOITA OFF 13.07.2020 00:39:51.494 Spontaneous
Com.Issued=AutoLocal
INTRERUPTOR 20kV ON 13.07.2020 00:39:51.491 Control Abortion Successful
Com.Issued=AutoLocal
DEMAREAJ GENERAL LATCH PENTRU DISPLAY ON 13.07.2020 00:39:51.490 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 72 - ON 13.07.2020 00:39:51.490 Spontaneous
Com.Issued=AutoLocal
SEMNAL CIRCUIT DECLANSARE 1 ON 13.07.2020 00:39:51.482 Spontaneous
SEMNAL RESORT ARMAT OFF 13.07.2020 00:39:51.478 Spontaneous
02730 >Circuit breaker READY for reclosing OFF 13.07.2020 00:39:51.478 Spontaneous
04602 >52-b contact (OPEN, if bkr is closed) OFF 13.07.2020 00:39:51.477 Spontaneous
INTRERUPTOR 20kV ON 13.07.2020 00:39:51.401 Control Issued
CommandIssued=Remote
ANCLANSARE VOITA ON 13.07.2020 00:39:51.399 Spontaneous
Com.Issued=AutoLocal
INTRERUPTOR 20kV ON 13.07.2020 00:39:51.285 Select before Operate Positiv
CommandIssued=Remote
SEMNAL CIRCUIT DECLANSARE 2 ON 13.07.2020 00:38:48.805 Spontaneous
PREVENTIVE PSG OFF 13.07.2020 00:38:48.796 Spontaneous
Com.Issued=AutoLocal
SIG. DECL PENTRU IESIRE PSG OFF 13.07.2020 00:38:48.796 Spontaneous
Com.Issued=AutoLocal
SIGURANTA CC DECLANSATA OFF 13.07.2020 00:38:48.795 Spontaneous
Com.Issued=AutoLocal
SIGURANTA BC DECLANSATA OFF 13.07.2020 00:38:48.795 Spontaneous
SEPARATOR BARA 2 20kV ON 13.07.2020 00:37:41.469 Spontaneous
SEPARATOR BARA 2 20kV Intermediate Position 13.07.2020 00:37:41.203 Spontaneous
PERMISIE CONECTARE INTR. ON 13.07.2020 00:37:18.241 Spontaneous
Com.Issued=AutoLocal
CLP 20kV OFF 13.07.2020 00:37:18.138 Spontaneous

Page 4 of 11
J09_PT2_prn_13_15_55

Event Log - - ZLATNA /


SIMATIC 20kV / J09_PT2/7SJ662 13.07.20 13:15:55

Event Log - - ZLATNA / 20kV / J09_PT2/7SJ662 V04.33.00(4)


Number Indication Value Date and time Cause State

PERMISIE CONECTARE INTR. OFF 13.07.2020 00:37:18.128 Spontaneous


Com.Issued=AutoLocal
CLP 20kV Intermediate Position 13.07.2020 00:37:17.943 Spontaneous
INTR. DESCHIS PENTRU OSCILO ON 12.07.2020 23:31:53.197 Spontaneous
Com.Issued=AutoLocal
INTRERUPTOR 20kV OFF 12.07.2020 23:31:53.160 Spontaneous
04602 >52-b contact (OPEN, if bkr is closed) ON 12.07.2020 23:31:53.160 Spontaneous
INTR. DESCHIS PENTRU OSCILO OFF 12.07.2020 23:31:53.135 Spontaneous
Com.Issued=AutoLocal
INTRERUPTOR 20kV Intermediate Position 12.07.2020 23:31:53.125 Spontaneous
04602 >52-b contact (OPEN, if bkr is closed) OFF 12.07.2020 23:31:53.125 Spontaneous
SEMNAL CIRCUIT DECLANSARE 2 OFF 12.07.2020 23:31:53.092 Spontaneous
PREVENTIVE PSG ON 12.07.2020 23:31:53.092 Spontaneous
Com.Issued=AutoLocal
SIG. DECL PENTRU IESIRE PSG ON 12.07.2020 23:31:53.092 Spontaneous
Com.Issued=AutoLocal
SIGURANTA CC DECLANSATA ON 12.07.2020 23:31:53.091 Spontaneous
Com.Issued=AutoLocal
SIGURANTA BC DECLANSATA ON 12.07.2020 23:31:53.091 Spontaneous
INTR. INCHIS PENTRU OSCILO OFF 12.07.2020 23:13:18.584 Spontaneous
Com.Issued=AutoLocal
INTR. DESCHIS PENTRU OSCILO ON 12.07.2020 23:13:18.584 Spontaneous
Com.Issued=AutoLocal
DECONECTARE VOITA PRIN BD2 OFF 12.07.2020 23:13:18.584 Spontaneous
Com.Issued=AutoLocal
DECONECTARE VOITA PRIN BD1 OFF 12.07.2020 23:13:18.584 Spontaneous
Com.Issued=AutoLocal
INTRERUPTOR 20kV OFF 12.07.2020 23:13:18.582 Feedback Positive
CommandIssued=Remote
04602 >52-b contact (OPEN, if bkr is closed) ON 12.07.2020 23:13:18.582 Spontaneous
04601 >52-a contact (OPEN, if bkr is open) OFF 12.07.2020 23:13:18.563 Spontaneous
SEMNAL CIRCUIT DECLANSARE 1 OFF 12.07.2020 23:13:18.519 Spontaneous
INTRERUPTOR 20kV OFF 12.07.2020 23:13:18.492 Control Issued
CommandIssued=Remote

Page 5 of 11
J09_PT2_prn_13_15_55

Event Log - - ZLATNA /


SIMATIC 20kV / J09_PT2/7SJ662 13.07.20 13:15:55

Event Log - - ZLATNA / 20kV / J09_PT2/7SJ662 V04.33.00(5)


Number Indication Value Date and time Cause State

DECONECTARE VOITA PRIN BD2 ON 12.07.2020 23:13:18.491 Spontaneous


Com.Issued=AutoLocal
DECONECTARE VOITA PRIN BD1 ON 12.07.2020 23:13:18.491 Spontaneous
Com.Issued=AutoLocal
INTRERUPTOR 20kV OFF 12.07.2020 23:13:18.366 Select before Operate Positiv
CommandIssued=Remote
SEMNAL RESORT ARMAT ON 12.07.2020 23:09:33.461 Spontaneous
02730 >Circuit breaker READY for reclosing ON 12.07.2020 23:09:33.461 Spontaneous
INTR. INCHIS PENTRU OSCILO ON 12.07.2020 23:09:28.827 Spontaneous
Com.Issued=AutoLocal
INTR. DESCHIS PENTRU OSCILO OFF 12.07.2020 23:09:28.827 Spontaneous
Com.Issued=AutoLocal
ANCLANSARE VOITA OFF 12.07.2020 23:09:28.826 Spontaneous
Com.Issued=AutoLocal
INTRERUPTOR 20kV ON 12.07.2020 23:09:28.824 Feedback Positive
CommandIssued=Remote
04601 >52-a contact (OPEN, if bkr is open) ON 12.07.2020 23:09:28.824 Spontaneous
SEMNAL CIRCUIT DECLANSARE 1 ON 12.07.2020 23:09:28.812 Spontaneous
SEMNAL RESORT ARMAT OFF 12.07.2020 23:09:28.807 Spontaneous
04602 >52-b contact (OPEN, if bkr is closed) OFF 12.07.2020 23:09:28.807 Spontaneous
02730 >Circuit breaker READY for reclosing OFF 12.07.2020 23:09:28.807 Spontaneous
INTRERUPTOR 20kV ON 12.07.2020 23:09:28.731 Control Issued
CommandIssued=Remote
ANCLANSARE VOITA ON 12.07.2020 23:09:28.730 Spontaneous
Com.Issued=AutoLocal
INTRERUPTOR 20kV ON 12.07.2020 23:09:28.621 Select before Operate Positiv
CommandIssued=Remote
DECL MAX1 LATCH PENTRU DISPLAY OFF 12.07.2020 22:43:29.900 Spontaneous
Com.Issued=AutoLocal
DEMAREAJ GENERAL LATCH PENTRU DISPLAY OFF 12.07.2020 22:43:29.900 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 12.07.2020 22:43:29.900 Spontaneous
Command Issued=Local

Page 6 of 11
J09_PT2_prn_13_15_55

Event Log - - ZLATNA /


SIMATIC 20kV / J09_PT2/7SJ662 13.07.20 13:15:55

Event Log - - ZLATNA / 20kV / J09_PT2/7SJ662 V04.33.00(6)


Number Indication Value Date and time Cause State

AVARIE PSG OFF 12.07.2020 22:42:44.096 Spontaneous


Com.Issued=AutoLocal
00301 Power System fault 71 - OFF 12.07.2020 22:42:42.105 Spontaneous
Com.Issued=AutoLocal
INTR. INCHIS PENTRU OSCILO OFF 12.07.2020 22:42:40.747 Spontaneous
Com.Issued=AutoLocal
INTR. DESCHIS PENTRU OSCILO ON 12.07.2020 22:42:40.747 Spontaneous
Com.Issued=AutoLocal
INTRERUPTOR 20kV OFF 12.07.2020 22:42:40.664 Spontaneous
04602 >52-b contact (OPEN, if bkr is closed) ON 12.07.2020 22:42:40.664 Spontaneous
INTRERUPTOR 20kV Intermediate Position 12.07.2020 22:42:40.646 Spontaneous
04601 >52-a contact (OPEN, if bkr is open) OFF 12.07.2020 22:42:40.646 Spontaneous
SEMNAL CIRCUIT DECLANSARE 1 OFF 12.07.2020 22:42:40.602 Spontaneous
AVARIE PSG ON 12.07.2020 22:42:40.586 Spontaneous
Com.Issued=AutoLocal
02863 79 - Lockout ON 12.07.2020 22:42:40.577 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 71 - ON 12.07.2020 22:42:39.584 Spontaneous
Com.Issued=AutoLocal
SEMNAL RESORT ARMAT ON 12.07.2020 22:42:36.269 Spontaneous
02730 >Circuit breaker READY for reclosing ON 12.07.2020 22:42:36.269 Spontaneous
INTR. INCHIS PENTRU OSCILO ON 12.07.2020 22:42:31.630 Spontaneous
Com.Issued=AutoLocal
INTR. DESCHIS PENTRU OSCILO OFF 12.07.2020 22:42:31.630 Spontaneous
Com.Issued=AutoLocal
ANCLANSARE VOITA OFF 12.07.2020 22:42:31.629 Spontaneous
Com.Issued=AutoLocal
INTRERUPTOR 20kV ON 12.07.2020 22:42:31.627 Feedback Positive
CommandIssued=Remote
04601 >52-a contact (OPEN, if bkr is open) ON 12.07.2020 22:42:31.627 Spontaneous
SEMNAL CIRCUIT DECLANSARE 1 ON 12.07.2020 22:42:31.615 Spontaneous
SEMNAL RESORT ARMAT OFF 12.07.2020 22:42:31.611 Spontaneous
02730 >Circuit breaker READY for reclosing OFF 12.07.2020 22:42:31.611 Spontaneous
04602 >52-b contact (OPEN, if bkr is closed) OFF 12.07.2020 22:42:31.610 Spontaneous

Page 7 of 11
J09_PT2_prn_13_15_55

Event Log - - ZLATNA /


SIMATIC 20kV / J09_PT2/7SJ662 13.07.20 13:15:55

Event Log - - ZLATNA / 20kV / J09_PT2/7SJ662 V04.33.00(7)


Number Indication Value Date and time Cause State

INTRERUPTOR 20kV ON 12.07.2020 22:42:31.534 Control Issued


CommandIssued=Remote
ANCLANSARE VOITA ON 12.07.2020 22:42:31.533 Spontaneous
Com.Issued=AutoLocal
INTRERUPTOR 20kV ON 12.07.2020 22:42:31.406 Select before Operate Positiv
CommandIssued=Remote
AVARIE PSG OFF 12.07.2020 22:42:30.296 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 70 - OFF 12.07.2020 22:42:28.304 Spontaneous
Com.Issued=AutoLocal
INTR. INCHIS PENTRU OSCILO OFF 12.07.2020 22:42:22.323 Spontaneous
Com.Issued=AutoLocal
INTR. DESCHIS PENTRU OSCILO ON 12.07.2020 22:42:22.323 Spontaneous
Com.Issued=AutoLocal
INTRERUPTOR 20kV OFF 12.07.2020 22:42:22.085 Spontaneous
04602 >52-b contact (OPEN, if bkr is closed) ON 12.07.2020 22:42:22.085 Spontaneous
INTRERUPTOR 20kV Intermediate Position 12.07.2020 22:42:22.067 Spontaneous
04601 >52-a contact (OPEN, if bkr is open) OFF 12.07.2020 22:42:22.067 Spontaneous
SEMNAL CIRCUIT DECLANSARE 1 OFF 12.07.2020 22:42:22.022 Spontaneous
AVARIE PSG ON 12.07.2020 22:42:22.006 Spontaneous
Com.Issued=AutoLocal
02863 79 - Lockout ON 12.07.2020 22:42:21.997 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 70 - ON 12.07.2020 22:42:20.999 Spontaneous
Com.Issued=AutoLocal
SEMNAL RESORT ARMAT ON 12.07.2020 22:42:18.539 Spontaneous
02730 >Circuit breaker READY for reclosing ON 12.07.2020 22:42:18.539 Spontaneous
INTR. INCHIS PENTRU OSCILO ON 12.07.2020 22:42:13.923 Spontaneous
Com.Issued=AutoLocal
INTR. DESCHIS PENTRU OSCILO OFF 12.07.2020 22:42:13.923 Spontaneous
Com.Issued=AutoLocal
ANCLANSARE VOITA OFF 12.07.2020 22:42:13.923 Spontaneous
Com.Issued=AutoLocal

Page 8 of 11
J09_PT2_prn_13_15_55

Event Log - - ZLATNA /


SIMATIC 20kV / J09_PT2/7SJ662 13.07.20 13:15:55

Event Log - - ZLATNA / 20kV / J09_PT2/7SJ662 V04.33.00(8)


Number Indication Value Date and time Cause State

INTRERUPTOR 20kV ON 12.07.2020 22:42:13.921 Feedback Positive


CommandIssued=Remote
04601 >52-a contact (OPEN, if bkr is open) ON 12.07.2020 22:42:13.921 Spontaneous
SEMNAL CIRCUIT DECLANSARE 1 ON 12.07.2020 22:42:13.909 Spontaneous
SEMNAL RESORT ARMAT OFF 12.07.2020 22:42:13.905 Spontaneous
02730 >Circuit breaker READY for reclosing OFF 12.07.2020 22:42:13.905 Spontaneous
04602 >52-b contact (OPEN, if bkr is closed) OFF 12.07.2020 22:42:13.904 Spontaneous
INTRERUPTOR 20kV ON 12.07.2020 22:42:13.829 Control Issued
CommandIssued=Remote
ANCLANSARE VOITA ON 12.07.2020 22:42:13.827 Spontaneous
Com.Issued=AutoLocal
INTRERUPTOR 20kV ON 12.07.2020 22:42:13.746 Select before Operate Positiv
CommandIssued=Remote
AVARIE PSG OFF 12.07.2020 22:41:46.935 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 69 - OFF 12.07.2020 22:41:44.937 Spontaneous
Com.Issued=AutoLocal
INTR. INCHIS PENTRU OSCILO OFF 12.07.2020 22:41:44.638 Spontaneous
Com.Issued=AutoLocal
INTR. DESCHIS PENTRU OSCILO ON 12.07.2020 22:41:44.638 Spontaneous
Com.Issued=AutoLocal
INTRERUPTOR 20kV OFF 12.07.2020 22:41:44.145 Spontaneous
04602 >52-b contact (OPEN, if bkr is closed) ON 12.07.2020 22:41:44.145 Spontaneous
INTRERUPTOR 20kV Intermediate Position 12.07.2020 22:41:44.127 Spontaneous
04601 >52-a contact (OPEN, if bkr is open) OFF 12.07.2020 22:41:44.127 Spontaneous
SEMNAL CIRCUIT DECLANSARE 1 OFF 12.07.2020 22:41:44.082 Spontaneous
AVARIE PSG ON 12.07.2020 22:41:44.065 Spontaneous
Com.Issued=AutoLocal
02863 79 - Lockout ON 12.07.2020 22:41:44.056 Spontaneous
Com.Issued=AutoLocal
DECL MAX1 LATCH PENTRU DISPLAY ON 12.07.2020 22:41:44.056 Spontaneous
Com.Issued=AutoLocal
DEMAREAJ GENERAL LATCH PENTRU DISPLAY ON 12.07.2020 22:41:43.057 Spontaneous
Com.Issued=AutoLocal

Page 9 of 11
J09_PT2_prn_13_15_55

Event Log - - ZLATNA /


SIMATIC 20kV / J09_PT2/7SJ662 13.07.20 13:15:55

Event Log - - ZLATNA / 20kV / J09_PT2/7SJ662 V04.33.00(9)


Number Indication Value Date and time Cause State

00301 Power System fault 69 - ON 12.07.2020 22:41:43.056 Spontaneous


Com.Issued=AutoLocal
SEMNAL RESORT ARMAT ON 12.07.2020 22:41:21.235 Spontaneous
02730 >Circuit breaker READY for reclosing ON 12.07.2020 22:41:21.235 Spontaneous
INTR. INCHIS PENTRU OSCILO ON 12.07.2020 22:41:16.659 Spontaneous
Com.Issued=AutoLocal
INTR. DESCHIS PENTRU OSCILO OFF 12.07.2020 22:41:16.659 Spontaneous
Com.Issued=AutoLocal
ANCLANSARE VOITA OFF 12.07.2020 22:41:16.658 Spontaneous
Com.Issued=AutoLocal
INTRERUPTOR 20kV ON 12.07.2020 22:41:16.656 Feedback Positive
CommandIssued=Remote
04601 >52-a contact (OPEN, if bkr is open) ON 12.07.2020 22:41:16.656 Spontaneous
SEMNAL CIRCUIT DECLANSARE 1 ON 12.07.2020 22:41:16.644 Spontaneous
SEMNAL RESORT ARMAT OFF 12.07.2020 22:41:16.641 Spontaneous
02730 >Circuit breaker READY for reclosing OFF 12.07.2020 22:41:16.641 Spontaneous
04602 >52-b contact (OPEN, if bkr is closed) OFF 12.07.2020 22:41:16.639 Spontaneous
INTRERUPTOR 20kV ON 12.07.2020 22:41:16.563 Control Issued
CommandIssued=Remote
ANCLANSARE VOITA ON 12.07.2020 22:41:16.562 Spontaneous
Com.Issued=AutoLocal
INTRERUPTOR 20kV ON 12.07.2020 22:41:16.452 Select before Operate Positiv
CommandIssued=Remote
DECL MAX1 LATCH PENTRU DISPLAY OFF 12.07.2020 22:40:26.877 Spontaneous
Com.Issued=AutoLocal
DEMAREAJ GENERAL LATCH PENTRU DISPLAY OFF 12.07.2020 22:40:26.877 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 12.07.2020 22:40:26.877 Spontaneous
Command Issued=Local
AVARIE PSG OFF 12.07.2020 22:39:34.094 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 68 - OFF 12.07.2020 22:39:32.100 Spontaneous
Com.Issued=AutoLocal

Page 10 of 11
J09_PT2_prn_13_15_55

Event Log - - ZLATNA /


SIMATIC 20kV / J09_PT2/7SJ662 13.07.20 13:15:55

Event Log - - ZLATNA / 20kV / J09_PT2/7SJ662 V04.33.00(10)


Number Indication Value Date and time Cause State

AVARIE PSG ON 12.07.2020 22:39:28.914 Spontaneous


Com.Issued=AutoLocal
02863 79 - Lockout ON 12.07.2020 22:39:28.905 Spontaneous
Com.Issued=AutoLocal
DECL MAX1 LATCH PENTRU DISPLAY ON 12.07.2020 22:39:28.905 Spontaneous
Com.Issued=AutoLocal
DEMAREAJ GENERAL LATCH PENTRU DISPLAY ON 12.07.2020 22:39:27.906 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 68 - ON 12.07.2020 22:39:27.906 Spontaneous
Com.Issued=AutoLocal
SEMNAL CIRCUIT DECLANSARE 2 ON 12.07.2020 22:38:42.071 Spontaneous
PREVENTIVE PSG OFF 12.07.2020 22:38:41.996 Spontaneous
Com.Issued=AutoLocal
SIG. DECL PENTRU IESIRE PSG OFF 12.07.2020 22:38:41.996 Spontaneous
Com.Issued=AutoLocal
SIGURANTA CC DECLANSATA OFF 12.07.2020 22:38:41.988 Spontaneous
Com.Issued=AutoLocal

Page 11 of 11