TECHNICAL SPECIFICATION OF 3x120 rm 2xSEYFGY (CTS) 6/10(12) kV Cable

TYPE & SIZE OF CABLE


2xSEYFGY (CTS) 3x120 rm (mm2)

VOLTAGE GRADE, U0/U (Um)


Permissible Service Voltage, U₀/U

6/10 (12) kV
6.35/11 kV

RELEVANT STANDARDS

IEC 60502-2, IEC 60228

TECHNICAL SPECIFICATION

Cross-sectional area of conductor, nominal 120 mm2

Number of core 3 core

Material Annealed Copper


Maximum conductor temperature in normal
900C
Conductor operation
Class of conductor Class 2

Shape of conductor Stranded Circular Compacted

Minimum number of wire (manufacturing) 18 (37) no./mm

Minimum and maximum diameter of conductor 12.3 - 13.5 mm

Material Semi-conducting XLPE


Conductor Screen
Thickness 0.6 mm

Material Crosslink polyethylene (XLPE)

Thickness, nominal 3.4 mm


Insulation
Thickness, minimum 2.96 mm

Color of insulation Natural

Material Semi-conducting XLPE


Insulation Screen
Thickness 0.7 mm

Material Copper Tape


Metallic Screen
Thickness of copper tape 0.06 mm

Material PVC

Inner Covering Color Black

Thickness 1.6 mm

Material Flat Galvanized Steel strip


Armour
Nominal diameter of armour 0.8 mm

Binder (Optional) Material Galvanized Steel Tape

Material Extruded PVC (ST-2)

Color Red

Sheath Thickness, nominal 2.8 mm

Thickness, minimum 2.04 mm

Overall diameter, approximate 65.0 ± 2 mm


Electrical Characteristics Other Characteristics

D.C resistance of conductor at 200C, maximum 0.153 ohm/km Minimum bending radius 15 x Overall diameter
0
A.C resistance of conductor at 90 C, maximum 0.196 ohm/km Inductance of cables 0.313 mH/km

Insulation resistance t ambient temperature 100+ G.ohm Capacitance of cables 0.459 mF/km

A.C. Voltage test for 05 minutes (3.5U₀ kV) 21 kV Operating temperature -15℃ to 90℃

Conductor short circuit rating in 1 sec 12.7 kA Weight of cable, approximate 7750 kg/km

Metallic screen short circuit rating in 1 sec 0.39 kA Standard packing length/ Drum 500 Meter Steel Drum

Current carrying capacity- A.K. M. Iftakher Ahmed


Signature
a. in free air at 30 C (Open)
0
352 A Asst. Manager (QC & QA)

b. in ground at 200C (Direct buried) 298 A Date 29-11-18