Beruflich Dokumente
Kultur Dokumente
www.elsevier.com/locate/ijepes
Abstract
This paper reports on the application of interval arithmetic technique for balanced radial distribution system power ¯ow analysis. Interval
arithmetic takes care of the uncertainty in the input parameters and provides strict bounds for the solution of the problem. In this paper,
uncertainties only in the input load parameters are considered. The results are compared with the results obtained from repeated load-¯ow
simulations. q 2002 Elsevier Science Ltd. All rights reserved.
Keywords: Interval arithmetic; Radial distribution system; Power ¯ow
In this section, the basic concepts of interval arithmetic Any complex number Z X 1 iY; where i is the
used in this paper are described. complex operator, is said to be a complex interval number
An interval number X x1 ; x2 is the set of real numbers if both its real part (X) and the imaginary part (Y) are interval
x such that x1 # x # x2 : x1 and x2 are known as the lower numbers. Hence, X can be represented as X x1 ; x2 and Y
limit and upper limit of the interval number, respectively. A can be represented as Y y1 ; y2 , where, x1 ; y1 are the
rational number k is represented as an interval number K lower limits and x2 ; y2 are the upper limits, respectively.
k; k: The conjugate of a complex interval number is given by
Let X x1 ; x2 and Y y1 ; y2 be the two interval Z p X 2 iY: Let Z1 A1 1 iB1 and Z2 A2 1 iB2 be
numbers. Then addition, subtraction, multiplication and two complex interval numbers. Then the addition, subtrac-
division of these two interval numbers are de®ned as tion, multiplication and division of these two complex inter-
below [9]: val numbers are de®ned as [9];
Z1 1 Z2
A1 1 A2 1 i
B1 1 B2
7
X 1 Y x1 1 y1 ; x2 1 y2
1
Z1 2 Z2
A1 2 A2 1 i
B1 2 B2
8
X 2 Y x1 2 y2 ; x2 2 y1
2 Z1 p Z2
A1 p A2 2 B1 p B2 1 i
A1 p B2 1 A2 p B1
9
Z1 4 Z2 C 1 iD
10
X p Y min
x1 p y1 ; x1 p y2 ; x2 p y1 ; x2 p y2 ; where C
A1 p A2 1 B1 p B2 4
A22
1 B22
and D
A2 p
3 B1 2 A1 p B2 4
A22 1 B22
max
x1 p y1 ; x1 p y2 ; x2 p y1 ; x2 p y2
It is to be noted that, Eqs. (7)±(10) can be evaluated by
applying the fundamental operations as de®ned in Eqs. (1)±
X 4 Y X p Y 21
4 (4). The detail expressions corresponding to the operations
de®ned in Eqs. (7)±(10) are given in Appendix A.
where,
Table 1
System bus voltages for 30-bus system
which shows a typical radial distribution system network with where, Vi
k21 is the calculated voltage at node i during
n buses and b
n 2 1 branches. The root node or the sub- iteration
k 2 1 and Si is the speci®ed power at node i
station node is supplied with a sinusoidal voltage source. For expressed as an interval number Si Pil ; Pih 1
the purpose of power ¯ow analysis, the branch and node iQil ; Qih where Pil ; Pih are the lower and higher limits
numbering scheme of Ref. [2] has been adopted in this of the real power and Qil ; Qih are the lower and higher
work. In this scheme, the branches in the network have been limits of the reactive power, respectively. As Si and
divided into several layers. Starting from the layer closest to Vi
k21 are both interval quantities, Eq. (11) is evaluated
the root node, the branches in the layers are numbered away using Eq. (10) and consequently, the quantity Iik is also a
sequentially [2]. The node of a branch L closest to the root complex interval quantity.
node is denoted by L1 and the other node is denoted by L2 Step 2: This step is known as the backward sweep. At
(refer Fig. 1). iteration k, starting with the branches in the last layer
For the power ¯ow solution of the network, the voltage at and moving towards the branches connected directly
the root node is assumed to be known and a ¯at voltage to the root node the current in branch L, JL is given
pro®le, equal to the voltage of the root node, has been as,
assumed for the initial voltages at the other nodes. Hence,
in per unit system, the voltage at the root node and the initial
JL
k
voltages at the other nodes is assumed to be 1:0; 1:0 1
X
i0:0; 0:0 p.u. With these initial voltages, the following
k
2IL2 1
currents in the branches emanating from node L2
steps are followed for the iterative solution of the system:
12
Step 1: At iteration k, the nodal current injection at Iik
node i is calculated as, As the currents at the right hand side of Eq. (12) are
p all interval quantities, Eq. (12) is evaluated with the
Iik Si =Vi
k21
11 help of Eq. (7).
830 B. Das / Electrical Power and Energy Systems 24 (2002) 827±836
Table 2
Real and reactive power ¯ow in the feeders in 30-bus system
Step 3: This step is the forward sweep. In this step, 4. Numerical results
starting from the root node and moving towards the
nodes of the branches connected in the last layer, the To illustrate the application of interval arithmetic in
node voltages are updated from the latest updated distribution system power ¯ow analysis, two different
voltages of the respective previous nodes. For exam- systems have been chosen:
ple, voltage at node L2 of branch L is updated from
the knowledge of updated voltage of node L1 as (i) 30-bus balanced radial distribution system,
follows: (ii) 68-bus balanced radial distribution system.
k
k
VL2 VL1 2 ZL JL
k
13 4.1. 30-Bus radial distribution system [1]
where, ZL is the impedance of branch L. The multiplica- The data for this test system are given in Table B1 in
tion and subtraction of the complex interval numbers are Appendix B. The loading pattern given in Table B1 is termed
carried out with the help of Eqs. (9) and (8), respectively. as `base operating condition'. As already discussed in Section
Step 4: At any node m, the distance between Vm
k and 1, the uncertainties in load demand have been taken into
Vm
k21 , henceforth denoted by dm ; is calculated at iteration account by assuming that the load demands vary over a
k. As Vm
k and Vm
k21 are both complex interval numbers, certain range. In this work, the load demand at any bus k is
they can be expressed as Vm
k A1 1 jA2 and Vm
k21 assumed to vary over a range Lbk 2 5; Lbk 1 5; where Lbk is
B1 1 jB2 ; where A1 ; A2 ; B1 ; B2 are all interval numbers the base load demand at that node as given in Table B1. For
and dm is calculated as dm maxq
A1 ; B1 ; q
A2 ; B2 ; example, the base real and reactive power load demand at bus
where, q
A1 ; B1 and q
A2 ; B2 are evaluated using Eq. 2 is 522 kW and 174 kVAR, respectively (refer Table B1).
(6). If max
dm ; for m 1; 2; ¼; n; is less than speci®ed Consequently, the real power load demand at that bus is
tolerance limit, the load-¯ow is converged, otherwise the assumed to vary over an interval [517,527] kW and the reac-
algorithm goes back to Step 1. tive power load demand is assumed to vary over an interval
B. Das / Electrical Power and Energy Systems 24 (2002) 827±836 831
Table 3
System bus voltages for 68-bus system
Table 3 (continued)
[169,179] kVAR. The intervals of variation of load demands be exact, have been generated and the corresponding bus
at other buses have been decided similarly. voltages have been calculated. The minimum and maximum
When the load demands in a system vary within some values of the real and imaginary parts of the complex bus
intervals, the bus voltages and other quantities (e.g. feeder voltages have been determined from the results of these 5
power ¯ow etc.) in that system also vary within certain million load ¯ow simulations and these constitute the inter-
intervals. The intervals of variation of bus voltages in the vals of the variations of the bus voltages obtained from
sample 30-bus system have been calculated using the load repeated load ¯ow simulations. These results are also
¯ow algorithm described in Section 3. In this work, the shown in Table 1. Similarly, the minimum and maximum
voltage error tolerance limit has been kept at 0.0001 p.u. values of the real and reactive power ¯ow in the feeders
and the algorithm took eight iterations to converge. The have been determined from the results of these 5 million
results are shown in Table 1 and Table 2. In Table 1, the load ¯ow simulations. These constitute the intervals of the
intervals of variation of both real and imaginary parts of variations of the real and reactive power ¯ow in the feeders
the complex bus voltages (in kV) are given. In this table, obtained from repeated load ¯ow simulations. These results
the symbols Vrll, Vrul, Vill and Viul denote the lower limit of the are shown in Table 2. It has also been found that, even by
real part, upper limit of the real part, lower limit of the further increasing the number of operating points, the inter-
imaginary part and upper limit of the imaginary part, respec- vals of variations of the bus voltages and the power ¯ow (real
tively. In Table 2, the intervals of variation of both real and reactive) in the feeders do not change.
power ¯ow (in MW) and reactive power ¯ow (in MVAR) From the entries in Tables 1 and 2, an interesting obser-
in the feeders are given. In this table, the symbols Pll, Pul, Qll vation can be made. The intervals depicted by the repeated
and Qul denote the lower limit of the real power, upper limit load-¯ow method are always contained within the intervals
of the real power, lower limit of the reactive power and depicted by the interval arithmetic method. In other words,
upper limit of the reactive power ¯ow, respectively. the solutions given by the interval arithmetic method
The intervals of variation of the bus voltages and the real contain all the solutions obtained by the repeated load-
and reactive power ¯ow in the feeders of the sample system ¯ow method. In fact, the interval arithmetic method
have also been calculated by repeated load ¯ow simulations. suggests a slightly wider range of intervals than the repeated
In this method, the load demands at any bus have been ®xed load-¯ow method. It can also be observed from the above
at any arbitrary value within the pre-decided, corresponding two tables that the intervals obtained from these two
interval. For example, the real power load demand at bus 2 methods are also quite close to each other. In all of the
may be ®xed at 520 kW. Similarly, all the real and reactive cases, the difference in the values suggested by these two
load demand at all the other buses have been arbitrarily ®xed methods starts after the decimal point.
at any value within their corresponding, pre-decided inter-
vals. Thus, an operating point other than the `base operating 4.2. 68-Bus radial distribution system [10]
point' is obtained and the system bus voltages are calculated
using the load ¯ow algorithm given in Ref. [2]. Similarly, by The data for this test system are given in Table B2 in
®xing the bus load demands at other values within their pre- Appendix B. As before, the loading pattern given in Table
decided, corresponding intervals, a large number of different B2 is termed as `base operating condition'. Similarly, the
operating points of the system can be obtained and the corre- load demand at any bus k is assumed to vary over a range
sponding system bus voltages can be calculated. Theoreti- Lbk 2 5; Lbk 1 5; where Lbk is the base load demand at that
cally, by this method, in®nite number of operating points node as given in Table B2. For this system also, the voltage
can be generated. As it is not possible to perform load ¯ow error tolerance limit has been kept at 0.0001 p.u. and the
simulations for in®nite number of operating points, in this algorithm took seven iterations to converge. The results are
work a very large number of operating points, 5 millions to shown in Tables 3 and 4. In Table 3, the intervals of
B. Das / Electrical Power and Energy Systems 24 (2002) 827±836 833
Table 4
Real and reactive power ¯ow in the feeders in 68-bus system
Table 4 (continued)
variation of both real and imaginary parts of the complex of these two numbers is given as
bus voltages (in kV) are given (for both interval method and
Z1 1 Z2 x11 1 x21 ; x12 1 x22 1 iy11 1 y21 ; y12 1 y22
repeated load ¯ow method). In this table, the symbols Vrll,
Vrul, Vill and Viul assume the same connotations as in Table 1.
A1
In Table 4, the intervals of variation of both real power ¯ow The difference Z1 2 Z2 is de®ned as,
(in MW) and reactive power ¯ow (in MVAR) in the feeders
Z1 2 Z2 x11 2 x22 ; x12 2 x21 1 iy11 2 y22 ; y12 2 y21
are given (again for both interval method and repeated load
¯ow method). In this table, the symbols Pll, Pul, Qll and Qul
A2
denote the same quantities as in Table 2. Multiplication of these two numbers is de®ned as
The entries of Tables 3 and 4 also af®rm the observations
Z1 p Z2 a 2 d; b 2 c 1 ie 1 g; f 1 h
A3
of Tables 1 and 2, that is, the intervals depicted by the
repeated load-¯ow method are always contained within where,
the intervals depicted by the interval arithmetic method a min
x11 p x21 ; x11 p x22 ; x12 p x21 ; x12 p x22
and the intervals obtained from these two methods are
quite close to each other. b max
x11 p x21 ; x11 p x22 ; x12 p x21 ; x12 p x22
The above observation has a very important implication.
In the planning and design studies, where it is necessary to c min
y11 p y21 ; y11 p y22 ; y12 p y21 ; y12 p y22
consider a large number of operating conditions, interval
arithmetic can be quite useful. As the interval arithmetic d max
y11 p y21 ; y11 p y22 ; y12 p y21 ; y12 p y22
based method encompasses all the solutions obtainable by
repeated simulations, interval arithmetic can be used instead e min
y11 p x21 ; y11 p x22 ; y12 p x21 ; y12 p x22
of the repeated simulations, thereby saving a lot of time and
effort. Although in the ®nal stage, a number of repeated f max
y11 p x21 ; y11 p x22 ; y12 p x21 ; y12 p x22
simulations may still be necessary before reaching the ulti-
mate conclusion, in the initial stages, interval arithmetic can g min
x11 p y21 ; x11 p y22 ; x12 p y21 ; x12 p y22
be used fruitfully to save on the time and efforts required.
h max
x11 p y21 ; x11 p y22 ; x12 p y21 ; x12 p y22
References real time distribution system analysis. IEEE Trans Power Syst
1995;10(2):671±9.
[1] Goswami SK, Basu SK. Direct solution of distribution system. IEE [6] Luo GX, Semlyen A. Ef®cient load ¯ow for large weakly meshed
Proc C 1991;138(1):78±88. networks. IEEE Trans Power Syst 1990;5(4):1309±16.
[2] Shirmohammadi D, Long HW, Semlyen A, Luo GX. A compen- [7] Zimmerman RD, Chiag HD. Fast decoupled power ¯ow for unba-
sation based power ¯ow method for weakly meshed distribution lanced radial distribution systems. IEEE Trans Power Syst
and transmission networks. IEEE Trans Power Syst 1995;10(4):2045±52.
1988;3(2):753±62. [8] Wang Z, Alvarado FL. Interval arithmetic in power ¯ow analysis.
[3] Renato Cespedes G. New method for the analysis of distribution IEEE Trans Power Syst 1992;7(3):1341±9.
networks. IEEE Trans Power Delivery 1990;5(1):391±6. [9] Alefeld G, Herzberger J. Introduction to interval computations. New
[4] Rajicic D, Ackovski R, Taleski R. Voltage correction power ¯ow. York: Academic Press, 1983.
IEEE Trans Power Delivery 1994;9(2):1056±61. [10] Baran ME, Wu FF. Optimal capacitor placement on radial distribution
[5] Cheng CS, Shirmohammadi D. A three phase power ¯ow method for systems. IEEE Trans Power Delivery 1989;4(1):725±34.