Harmonic filtering
Harmonic filters are used to limit the harmonic
currents flowing into the upstream network and to
decrease the resonance effect causing current
amplification along the 25kV supply line. The filter
could be located on the loco itself or on the substation.
Because of the different type of locos running
simultaneously on the same traction section the most
effective place for the harmonic filter location is the
25kV side of the substation. Basically there are two Fig. 6. With 17th and 19th harmonic filter
kinds of filters: passive and active filters.
The passive harmonic filter is a set of series
resonance circuits tuned to the frequencies to be filtered.
The passive harmonic filter has low impedance on its
tuned frequency that is why it shunts the network for the
harmonic current of the tuned harmonic order. Harmonic
filtering is often linked with the problem of fundamental
frequency reactive power balance. The passive filter
could be used to compensate reactive power, because is
shows capacitive reactance on the fundamental
frequency.
Fig. 7. With full filtering
contact line system. Using the model it is possible to solution, regarding the composition of reactive power
calculate the voltage and current spectrum along the compensation and harmonic filtering. [3]
supply line. As an example on Fig. 5, the voltage and
Information about the authors
current at the substation are seen. The resonance effect is
Dr. András Dán is with the Department of Electric
the highest at the 17th and 19th harmonics.
Power Engineering at the Budapest University of
Filtering 17th and 19th harmonics. After installing an
Technology and Economics since 1970 where he
active filter in the substation the following results can be
currently holds the rank of professor habil. and acts as a
calculated. (Fig. 6.) This filter is basically a simple
consultant for local industry. His expertise is in power
current generator injecting the calculated 17th and 19th
electronics, power quality and reactive power
harmonic current as anti-phase value at the substation.
compensation especially associated with power system
It could be concluded that the current and voltage
harmonics.
component on the filtered harmonic orders are reduced
Péter Kiss is the Ph.D. student of the Department of
dramatically.
Electric Power Engineering at the Budapest University
Using the active filter on each harmonic order the
of Technology and Economics since 2005. His thesis is
network side current will be sinusoidal .The HV system
dealing with the harmonic effect and mitigation technics
is no more disturbed (Fig. 7.), but the disturbing current
associated with the railway systems.
in the contact line decreases only to the half
In case of passive filtering method the network References
resonance can decrease by means of a broadband filter [1.] A. Dán, J. Kisvölcsey, Gy. Varjú: Filtering of
decreasing the equivalent disturbing current along the harmonics generated by thyristor controlled AC traction
contact line to one -third. systems. In Proc. II. International Conference on
Harmonics in Power Systems, pp.404-413., Winnipeg, 6-
Psophometric values
7. October, 1986.
Using the harmonic components of the currents and
[2.] A. Dán, T. Tersztyánszky, Gy. Varjú, Electric
voltages the psophometric and THD values can be
Power Quality (Villamosenergia min ség). Budapest:
calculated along the supply line. The Table 1 shows the
Invest-Marketing Ltd, 2006.
value of the psophometric voltages by the substation and
[3.] A. Dán, P. Kiss: Effect on Power Quality of the
psophometric currents by the substation on the contact
High Power Electric Traction (Double Domain
line and the upstream network side unfiltered one.
Computer Simulation vs. Site Measurements). In Proc.
Besides this the THD values are given in the table.
International Conference on Renewable Energies and
Table 1: Psofometric and THD values
Power Quality, Palma de Mallorca, 5-7. April 2006.
V substation I HV>sub I sub>loco
Vp THDV Ip THDI Ip THDI
[4.] A. Dán, P. Kiss: Advanced Calculation Method
unfiltere 503V 2.11 2.98 35.5 2.98 35.5 for Modeling of Harmonic Effect of AC High Power
d % A % A % Electric Traction. In Proc. 12th International Conference
17th, 19th 212V 1.37 1.54 33.9 1.59 34.1 on Harmonics and Quality of Power, Cascais, 1-5.
% A % A % October 2006.
all harm. 18.6 0% 0.02 0% 1.72 34.2 [5.] M.M.M. L. Arini: Time domain load modelling
V A A % technique and harmonic analysis. In Proc. 8th.
International Conference on Harmonics and Quality of
Conclusion
Power pp.930-939., Athens, 14-16. October, 1998.
It can be concluded that using active harmonic
[6.] P. Brogan, R. Yacamini: Measurements and
filtering the network side harmonic distortion is reduced
simulation of an active filter based on voltage feedback.
very effectively, but the psophometric effect caused by
In Proc. 8th. International Conference on Harmonics and
the current along the traction system does not change so
Quality of Power pp.930-939., Athens, 14-16. October,
much. In critical cases a broadband passive filter might
1998.
be necessary to decrease the harmonic impedance
[7.] F. Foiadelli, P. Pinato, D. Zaninelli: Statistical
resonance causing the increase of equivalent disturbing
Model for Harmonic Propagation Studies in Electric
current.
Traction Supply Systems in Proc. 11th International
This kind of calculation is a suitable method to
Conference on Harmonics and Quality of Power, Lake
perform an analysis on both the harmonic distortion and
Placid, September 12-15, 2004.
psophometric effect. The double domain simulation
method will help to select the most advantageous