Trip circuit –

supervision relay
Model TCSR- □□□□

DAIDONG INDUSTRIAL SYSTEM CO.,LTD

daidongs@hanmail.net DAIDONG Industrial System co.,ltd 1


Features Description
- Continuous supervision of complete The supervision relay TCSR is designed for the
trip circuit, independent of the circuit supervision of trip circuits and other important
breaker position control and monitoring circuits. The supervision
- Detects faults in the supervised function is based on a low-level (~ 6 mA) current
circuits, such as loss of voltage, injection principle. The injected current is
circuit breakage, contact sensed by two opto-couplers. In normal
degeneration in connections and condition the indicator LED glows red and
increased resistance in wires, output relays are in ‘picked-up’ condition. In the
contacts and coils event of a fault, the measuring current goes
- Low-level measuring current below the operating value of the relay or
enables application in sensitive or completely stops flowing. The supervision relay
high resistance circuits operates (drops-off) after a delay of 1.0 sec and
- Operation delay to avoid spurious the indicator LED turns red. The supervision
signals. (For instance, on circuit relay, for its functioning requires an auxiliary
breaker operations) voltage (AC or DC) of a rated value to be
- Operation indication by a single connected to the terminals of section 5.
dual-color LED This voltage can be the same as that of the
- Complete range of rated voltages supervised circuit or it could be a separate
(either AC or DC) source with same magnitude (AC or DC).
- Galvanic isolation is possible Should a fault occur in the auxiliary voltage
between the auxiliary source and supply, the LED does not glow and the output
supervised circuit relay drops off. Relays with differing rated
- Very low burden on the auxiliary voltage for supervision circuit and auxiliary
source supply can be supplied as a special execution

Application
The supervision function is
particularly important when there is
only one tripping coil and CB tripping
is vital. (For instance, in the case of
generator circuit breakers or any
other important circuit breaker in
distribution networks.)

The supervision relay type


TCSR is intended for continuous
supervision of a circuit breaker trip
circuit and to sound an alarm for loss
of auxiliary supply or faults on the trip
coil or its wires.
This is independent of the breaker
position, faults on the breaker
auxiliary contacts and faults in the
supervision relay itself.

daidongs@hanmail.net DAIDONG Industrial System co.,ltd 2


Technical data

1. Energizing quantities, rated values and limits


Rated voltage of super voided
100 110 (125) V DC
and auxiliary circuit UAUX

Operative voltage range 80-110% of rated Uaux


Operate (Drop-off) time
0.9sec.
at rated voltage UAUX & 25℃

Burden at rated voltage 100 110 125

–Auxiliary circuit(W) 2 2.2 2.5

–Supervision circuit(W) 0.25 0.28 0.32

Mechanical durability 1Million switching operation

2. Contact data
Contact configuration (self reset) 1 NO+1NC(1ab)
Max voltage with inconstant system 250V DC/AC
Rated current 5A
Max. switching current (0.5sec) 10A
Max. switching power 1250VA/240W
Breaking capacity(dc) 1A / 0.25A /0.15A

Electrical endurance 100,000 operations, at 110Vdc, cos0.35

3. Test and Standard


Dielectric test voltage (IEC60255-5) 2 kV, 60 Hz, 1 min
Test voltages
Impulse test voltage (IEC 60255-5) 5 kV, 1.2/50 μs
HF disturbance test (IEC 60255-5) 2.5 kV, 1 MHz
Disturbance tests Fast transients (IEC 61000-4-4) 2 kV, 5/50 ns, 1 min.
Spark interference 4…8 kV
Service temperature range -10…+55°C
Environmental
Transport and storage
conditions -40…+70°C
temperature range

daidongs@hanmail.net DAIDONG Industrial System co.,ltd 3


4. When ordering, please specify:

TCSR - 1 2 3 4

Selection 1 : Socket type for internal mounted -– S


YSSK08 –Applied socket by Yong sung
The surface mounted of the switchboard. --- F
Selection 2 : Rated voltage of super voided and auxiliary circuit Uaux
DC 110V ----11
DC 125V ----12
DC 220V ----22
The other spec. –X
Selection 3 : Operate (Drop-off) time (sec)
0.5 sec ----5 (options)
0.9 sec ----9
The other spec. --Y
Selection 4 : Contact configuration
1ab (NO+NC) --1
2ab (NO+NC) –- 2 (options)

5. Connection diagram and Contact configuration

daidongs@hanmail.net DAIDONG Industrial System co.,ltd 4


6. Dimensions

TCSR –S1191. (Socket)]

TCSR –F1191.

daidongs@hanmail.net DAIDONG Industrial System co.,ltd 5