Sie sind auf Seite 1von 36

DISTRIBUTION SOLUTIONS

HD4
Installation and service instructions
12-40.5 kV – 630-3600 A – 16-50 kA

Table of contents
I. Introduction 2
II. Programme for the environmental protection 2
1. Packing and transport 3
2. Checking on receipt 4
3. Storage 5
4. Handling 6
5. Description 8
6. Instructions for circuit breaker operation 10
7. Installation 11
8. Putting into service 30
9. Periodical checking 32
10. Maintenance operations 32
11. Indications for handling apparatus with SF6 33
12. Spare parts and accessories 34


For your safety!
• Make sure that the installation room (spaces, • Check that the rated performance of the
divisions and ambient) is suitable for the apparatus is not exceeded during service.
electrical apparatus. • Check that the personnel operating the
• Check that all the installation, putting into apparatus have this instruction manual to hand
service and maintenance operations are carried as well as the necessary information for correct
out by qualified personnel with suitable intervention.
knowledge of the apparatus. • Pay special attention to the danger notes
• Make sure that the standard and legal indicated in the manual by the following symbol:
prescriptions are complied with during
installation, putting into service and Responsible behaviour safeguards
maintenance, so that installations according to your own and others’ safety!
the rules of good working practice and safety in For any requests, please contact the
the work place are constructed. ABB Assistance Service.
• Strictly follow the information given in this
instruction manual.
2 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA


I. Introduction
This publication contains the information necessary Apart from this booklet, it is therefore always
for installation and putting into service of HD4 necessary to refer to the latest technical
medium voltage circuit breakers. documentation available (circuit diagram, wiring
For correct usage of the product, please read this diagrams, assembly and installation drawings, any
manual carefully. studies of protection co-ordination, etc.), especially
For correct mounting of accessories and/or spare with regard to any variations from standardized
parts please refer to the relevant instructions. configurations requested.
Like all the apparatus manufactured by us, the HD4
circuit breakers are designed for different All the operations regarding installation,
installation configurations. putting into service, operation and
They do, however, allow further technical- maintenance must be carried out by
constructional variations (at the customer’s suitably qualified personnel with in-
request) to suit special installation requirements. depth knowledge of the apparatus.
For this reason, the information given below does
not always cover special configurations.
Only use original spare parts for maintenance
operations.
For further information, also see the technical
catalogue of the circuit breaker and the spare parts
catalogue.


II. Programme for the environmental protection
The HD4 circuit breakers comply with ISO 14000 The Product environmental declaration is available
Standards (Guidelines for the Environmental for the HD4 circuit breakers
Management). Production techniques are carried out in order to
The production system of the Medium Voltage achieve an easy dismantling and separation of the
factories complies for the environmental protection components at the end of the circuit breaker life
in terms of energy consumption, raw materials and cycle, while optimizing the recycling process.
waste.
The environmental impact of the product life cycle is
assessed by the LCA - Life Cycle Assessment
procedure, which is also the result of a well-focused
project phase in the selection of materials,
processes and packaging.
D I S T R I B U T I O N S O LU T I O N S 3


1. Packing and transport
The circuit breaker is shipped in special packing in
the open position with the springs discharged and
with absolute pole pressure corresponding with the
service value.
Each piece of apparatus is protected by a plastic
film to prevent any infiltration of water during the
loading and unloading stages and to keep the dust
off during storage.

Handling and transport must only be carried out by


expert and properly trained personnel.
Do not remove or alter the switch identification
contents and labels.
Switches subject to UN3164 standards for
transportation by air and / or sea.
Safety data sheet: 1VCD850182
4 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA


2. Checking on receipt
Before carrying out any operation, always
make sure that the operating mechanism A
dprings are discharged and that the Circuit breaker IEC 62271-100
apparatus is in the open position. 1 HD4 ... ... ... CEI 17-1 2
CLASSIFICATION ... ... ...
3 SN ... ... ... PR. YEAR ......
On receipt, check the state of the apparatus, that the M MASS ... kV
Ur
packing is undamaged and that the nameplate data
corresponds (see fig. 1) with that specified in the order
acknowledgement and in the delivery note.
Also make sure that all the materials described in the
shipping note are included in the supply.
If any damage or irregularity is discovered on
unpacking, notify ABB (directly or through the agent or 4
supplier) as soon as possible and in any case within five
days of receipt.
The apparatus is only supplied with the accessories
specified at the time of order and confirmed in the
ELECTRIC DIAGRAM .. ... ... ...
order acknowledgement sent by ABB. FIG. ... ...
The following accompanying documents are inserted in
the shipping packing: .. ... ... ... OPERATING MECHANISM
B
• Instruction manual (this document)

• Test certificate 5 -MO1 ... ... ... V


• Identification tag
Made by ABB
• Fiscal copy of shipping note
• Electrical diagram Nameplate

These other documents are sent prior to shipment: Caption


A Circuit breaker nameplate
• Order acknowledgement B Operating mechanism nameplate
• Original copy of shipping note 1 Type of apparatus
2 Symbols and compliance with Standards
• Any drawings or documents regarding special 3 Serial number
configurations/conditions. 4 Circuit breaker characteristics
5 Characteristics of the operating auxiliaries

Fig. 1
D I S T R I B U T I O N S O LU T I O N S 5


3. Storage
In case a storage period is foreseen, on request our Therefore, store in a sheltered, well-ventilated area
workshops will provide a suitable packing to the with a dry, non-dusty, non-corrosive atmosphere
specified storage conditions. away from highly flammable materials, with a
On receipt, the apparatus must be carefully temperature between -5 °C and +45 °C.
unpacked and checked as described in chapter 2: In any case, avoid accidental shocks or
Checkink on receipt. accommodations that stress the structure of the
If immediate installation is not possible and the circuit breaker
circuit breaker has to be re-stored again, it is
necessary to restore the packaging at least suitable
for protection against dust.
Insert hygroscopic substances in the packaging in
the quantity of at least one standard pack per
apparatus.
6 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA


4. Handling
Before carrying out any operation, always check that 36 kV circuit breakers
the operating mechanism springs are discharged • Attach the tools (1) to lift and handle the circuit
and that the apparatus is in the open position. breaker (fig. 2c);
• Attach the hooks (2) as illustrated in fig. 2d and lift;
Circuit breakers up to 24 kV • On completion of the operation, remove the tools
• To lift and handle the circuit breaker, use the tool (1).
(1) (fig. 2a: shortest hooks for circuit breakers up
to 17.5 kV; all hooks for 24 kV circuit breakers). Always take great care during handling not to stress
• Put the hooks (2) in the holes prepared in the the insulating parts and the circuit breaker
circuit breaker frame and lift. terminals.
• On completion of the operation (and in any case
before putting into service) unhook the lifting tool The apparatus must not be handled by
(1) (fig. 2b) and dismantle the crosspiece (2) by inserting lifting devices directly under
unscrewing the screws (3). the apparatus itself. Should it be
necessary to use this method, place the
circuit breaker on a sturdy supporting
surface (see fig. 3).

2 2

Fig. 2a

2
3

Fig. 2b
D I S T R I B U T I O N S O LU T I O N S 7

Fig. 2c

Fig. 2d Fig. 3
8 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA


5. Description
5.1. General features 5.3. Fixed circuit breaker
The HD4 series are sulphur hexafluoride circuit The fixed circuit breaker (see fig. 4) corresponds to
breakers for indoor installation. For the electrical the basic version complete with a front protection
performance, please refer to the corresponding shield and frame.
technical catalogue code 1VCP000004. The anchoring holes are drilled in the lower part of
For special installation conditions please ask ABB. the frame.
The following versions are available: The terminal box, fixed on the upper protection, is
• fixed available for connection of the circuit breaker
• withdrawable for CBE, PowerCube enclosures and auxiliary circuits.
CBF fixed parts The earthing screw is located on the circuit breaker
• withdrawable for switchgear: UniGear type ZS1, side.
UniGear type ZS2, UniGear type ZS3.2 For further details, refer to the caption of fig. 4.
• withdrawable for switchgear: UniSwitch, UniMix
and UniSec.

5.4. Withdrawable circuit breaker


The withdrawable circuit breakers (see fig. 5) are
5.2. Reference Standards consist of a truck on which the supporting structure
The HD4 series circuit breakers comply with the of the circuit breaker itself is fixed. The cord with
following Standards: the connector (plug) for connection of the operating
• IEC 62271-100 mechanism electrical accessories comes out of the
front protection of the circuit breaker.

Fixed circuit breaker

8
1
9
2

3
7
4

10 11

5 12 6 10 - 11 (36 kV)
Fig. 4

Caption
1 Signalling device for state of SF6 pressure (on request) 7 Signalling device for closing springs charged/discharged
2 Opening push button 8 Characteristics nameplate
3 Closing push button 9 Terminals (only available for certain versions)
4 Operator counter 10 Pressure switch (on request)
5 Signalling device for circuit breaker open/closed 11 Valve for checking the SF6 gas pressure
6 Shaft for manual closing spring charging 12 Resetting button for protection circuit breaker of geared motor (on
request)
D I S T R I B U T I O N S O LU T I O N S 9

The strikers for activating the contacts (connected/ The activating lever (connection/isolation) must be
isolated), located in the enclosure or in the fully inserted. A lock prevents the truck from
switchgear, are fixed in the top part of the circuit advancing into the enclosure or fixed part (for
breaker. The slides for activating the segregation example when the earthing switch is closed). With
shutters of the medium voltage contacts of the the truck in the middle position between isolated
enclosure or switchgear are fixed on the sides of the and connected, the lock prevents closure of the
circuit breaker. The crosspiece for hooking the circuit breaker (both mechanical and electrical).
circuit breaker for the connection/isolation On request, a locking magnet can be mounted on
operation by means of the special operating lever is the truck which, when de-energised, prevents truck
mounted on the front part of the circuit breaker operation.
truck.
The circuit breaker is completed with the tulip
isolating contacts. The withdrawable circuit breaker
is fitted with special locks, on the front crosspiece,
5.5. Enclosures and fixed parts
which allow hooking into the corresponding joints in For information about the enclosures and fixed
the enclosure or fixed part. The locks can only be parts, please consult the relative documentation.
activated by the handles with the truck resting
completely on the crosspiece.

Withdrawable circuit breaker

17 16 16 9 16

8
1

3 9
7
4

12

10 11
5 18 6 13 14 15
Fig. 5
10 - 11 (36 kV)

Caption
1 Signalling device for state of SF6 pressure (on request) 10 Pressure switch (on request)
2 Opening push button 11 Valve for checking the SF6 gas pressure
3 Closing push button 12 Slide for activating the enclosure shutters
4 Operator counter 13 Truck
5 Signalling device for circuit breaker open/closed 14 Locks for hooking into the fixed part
6 Shaft for manual closing spring charging 15 Lock activating handles (17)
7 Signalling device for closing springs charged/discharged 16 Strikers for activating the contacts located in the enclosure
8 Characteristics nameplate 17 Connector (plug)
9 Isolating contacts 18 Resetting button for protection circuit breaker of geared motor (on
request)
10 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA


6. Instructions for circuit breaker operation
6.1. Safety indications 6.3. Circuit breaker closing and
opening operations (fig. 6)
HD4 circuit breakers ensure a minimum
degree of protection IP2X if installed Circuit breaker operation can be manual or
under the following conditions: electrical.
• fixed version, with protection netting
• withdrawable version, installed in a a) Manual operation for spring charging
switchgear. To manually charge the closing springs, it is
Under these conditions, the operator is necessary fully insert the charging lever into the
guaranteed against accidental contact seat (6) and turn it clockwise until the yellow
with moving parts. indicator (7) appears.
Should any mechanical operations be The force which can normally be applied to the
carried out on the circuit breaker outside charging lever fitted is 130 N. In any case, the
the switchgear or with the protection maximum force which can be applied must not
netting removed, be very careful of any exceed 170 N.
moving parts.
If the operations are prevented, do not b) Electrical operation for spring charging
force the mechanical interlocks and On request the circuit breaker can be fitted with the
check that the operation sequence is following accessories for electrical operation:
correct. • geared motor for automatic charging of the
The racking-in and racking-out closing springs
operations of the circuit breaker must be • shunt closing release
carried out gradually to prevent any • shunt opening release.
impacts which might deform the The geared motor automatically recharges the
mechanical interlocks. springs after each closing operation until the yellow
indicator (7) appears. Should there be no voltage
during charging, the geared motor stops and then
6.2. Operating and signalling parts starts recharging the springs automatically when
the voltage is on again. It is, however, always
possible to complete the charging operation
manually.

c) Circuit breaker closing


This operation can only be carried out with the
closing springs completely charged.
1 For manual closing, push the push button (3).
When there is a shunt closing release, the operation
2
can also be carried out with remote control by
4 means of a control circuit. The indicator (4) shows
7 that closing has been accomplished.
5 In case of earthing truck with making capacity,
activate the key lock (in the closed position) and
3 remove the key. This is to prevent accidental
opening operations during any maintenance work
6
on the installation.

d) Circuit breaker opening


For manual opening, push the push button (2).
8
When there is a shunt opening release, the operation
can also be carried out with remote control by
Caption means of a control circuit. The indicator (4) shows
1 Signalling device for state of SF6 pressure (on request)
2 Opening push button that opening has been accomplished.
3 Closing push button
4 Operator counter
5 Signalling device for circuit breaker open/closed
6 Shaft for manual closing spring charging
7 Signalling device for closing springs charged/discharged
8 Resetting button for protection circuit breaker of geared motor (on
request)

Fig. 6
D I S T R I B U T I O N S O LU T I O N S 11


7. Installation
7.1. General 7.4. Installation of fixed circuit
Correct installation is of prime breaker
importance. The instructions given by
The circuit breaker can be mounted directly on the
the manufacturer must be carefully
supporting frames provided by the customer.
studied and followed. It is good practice
The circuit breaker, complete with supporting truck,
to use gloves to handle the pieces during
must be fixed to the floor of its compartment with
installation
special brackets.
The parts of the floor surface on which the truck
wheels rest must be perfectly level.
The areas on which the supporting frames or truck
7.2. Normal installation conditions wheels rest (if a truck is provided) must be on the
Maximum ambient air temperature + 40 °C same horizontal plane to avoid any risk of distortion
Minimum ambient air temperature – 5 °C in the breaker frame.
Relative humidity % < 95 Fit the isolating partitions if provided.
Altitude < 1000 m A minimum degree of protection (IP2X) must be
guaranteed from the front towards live parts.

It must be possible to ventilate the installation


room.
For other installation conditions, please follow what
is indicated in the product Standards.
7.5. Installation of withdrawable
For special installation requirements please contact circuit breaker
us.
The withdrawable circuit breakers are preset for
The areas affected by the passage of power
insertion in enclosures, in fixed parts or in the
conductors or auxiliary circuit conductors must be
corresponding switchgears.
protected against the possible access of animals
Insertion and racking-out of the circuit breakers
which could cause damage or anomalous service.
must be gradual to avoid any shocks which could
deform the mechanical interlocks.
If the operations are prevented, do not force the
7.3. Preliminary operations interlocks and check that the operating sequence is
correct. The force normally applicable to the
• Clean the insulating parts with clean dry rags.
insertion/racking-out lever is 250 N.
• Check that the upper and lower terminals are clean
Please also refer to the technical documentation of
and free of any deformation caused by shocks
the enclosures and switchgears for the circuit
received during transport or storage.
breaker installation operations.

The insertion and racking-out operations


must always be carried out with the
circuit breaker open.
12 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA


7. Installation
7.6. Fixed circuit breaker power Mounting procedures
• Place the connections in contact with the circuit
circuit connections breaker terminals.
7.6.1. General directions • Interpose a spring washer and a flat washer
• The connections must be made using only the between the head of the bolt and the connection.
squares-terminals supplied with the circuit • Tighten the bolt, taking care not to subject the
breaker. insulating parts to stress (see table tightening
• Select the conductor cross-section according to torque).
the operating and short-circuit current of the • Make sure that the connections do not exert force
installation. on the terminals.
• Near the terminals of fixed version circuit breakers • In case of cable connections, carefully follow the
or enclosure, provide suitable support insulators manufacturer’s instructions for terminating the
dimensioned according to the electrodynamic cables.
stresses that may arise from the short-circuit
current of the installation. Table of tightening torque
• Fit the isolating partitions if provided. Screw Tightening torque
M6 10 Nm
7.6.2. Mounting the connections
M8 30 Nm
• Check that the connection contact surfaces are
M10 40 Nm
perfectly flat and have no burrs, oxidation traces,
M12 70 Nm
or deformations due to drillings or impacts.
• Depending on the conductive material and surface
treatment used, carry out the operations indicated
in the table on the contact surface of the
conductor.

Bare copper Silver-plated copper or aluminium Bare aluminium


Clean with a fine file or emery cloth. Clean with a rough dry rag. Clean with a metallic brush or
emery cloth.
Fully tighten and smear a film of industrial In case of tough oxidation traces only, clean Immediately smear a film of
vaseline grease over the contact surfaces. with a very fine emery cloth, taking care not to industrial vaseline grease over
remove the surface layer. the contact surfaces.
Interpose the copper-aluminium bi-metal with If necessary, recondition the surface
restored surfaces between the aluminium treatment.
connection and the copper terminal (copper
side in contact with the terminal; aluminium
side in contact with the connection).
D I S T R I B U T I O N S O LU T I O N S 13

7.7. Earthing 7.8. Auxiliary circuit connection


For fixed version circuit breakers, use the screw Notes
marked with the relative symbol to effect the • The minimum cross-section of the wires used for
earthing. the auxiliary circuits must not be less than that
Clean and degrease the surrounding area for a used for internal wirings.
diameter of about 30 mm. After completion of the • Before carrying out the connection of the
assembly, cover the entire joint with vaseline. auxiliary circuits, it is advisable to check the
Use a conductor (busbar or braid) with a cross- selected type of automatism provided for
section as indicated in the Standards in force. operation of the pressure switch (if provided)
referring to the latest technical documentation
supplied by ABB.

7.8.1. Fixed circuit breaker


The connection of the circuit breaker auxiliary
circuits must be made via the terminal box mounted
on the circuit breaker structure.
Outside the circuit breaker the wires must run inside
appropriately earthed metal tubes or ducts.

Before removing the operating
mechanism cover to access the terminal
box, make sure that the circuit breaker is
open and the closing springs discharged.

7.8.2. Withdrawable circuit breaker


The auxiliary circuits of the withdrawable circuit
breaker are fully cabled in the factory as far as the
connector. For the external connections, please
refer to the electric diagram of the enclosure or of
the switchgear.
14 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA


7. Installation
7.9. Overall dimensions

Fixed circuit breakers

HD4 496
150 150 446
2XM8 depth 16 M12 depth 25
TN 1VCD000226 87 336,5 13,5
67,5
Ur 12 kV
630 A
Ir
1250 A

27
16 kA
Isc 25 kA

205
31.5 kA
586

541,5
63

27
260,5
248,5

21,5
43

347 13 M12 depth 22


402 10,5 117 2XM8 depth 16
114,5
473
270
493 332

Fixed circuit breakers

600
HD4
581 446 2XM8 depth 16 M12 depth 25
TN 1VCD000231 210 210
87 336,5 13,5
12 kV 67,5
Ur
17.5 kV
630 A
Ir

27
1250 A
16 kA
Isc 25 kA
205

31.5 kA
623

27
63

266,5
231,5

21,5
43

472 13
117 2XM8 depth 16
598 10,5 M12 depth 25
111,5
618
270 34
332
D I S T R I B U T I O N S O LU T I O N S 15

Fixed circuit breakers

HD4 600
578
TN 7163
210 210
12 kV
Ur
17.5 kV
Ir 1600 A
40 kA
Isc 2 x Ø18

310
50 kA

310
28

80
HD4 15.5 32

655

622
TN 7163 YU

12 kV

8
YU
Ur
17,5 kV

306.5
266.5
Ir 2000 A Q6
0 8
25 kA
Ø 13
31.5 kA
Isc
43

40 kA
472 Ø 10.5 35
50 kA 2.5

20
598 322

618 385
561

Fixed circuit breakers

HD4 137.5 137.5 420 min.


730
TN 7165
708
12 kV
Ur 275 275 465
17.5 kV

349.5
2500 A
Ir 3150 A
670 min.

3600 A
15

25 kA
310

28
62

31,5 kA
Isc
40 kA 20 40
655

20

622

YU
50 kA
468.5
40

YU
20
20

HD4 8

TN 7165
266.5

4 x Ø18
Ø13
Ur 24 kV
2500 A
43

602 Ø10.5 115 2


Ir 3150 A
20

322 35
728
3600 A 385
748 603
25 kA
Isc 31.5 kA Insulating partitions (only for 24 kV)
to be provided by the customer
40 kA (a special kit is available on request).
16 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA


7. Installation
7.9. Overall dimensions

Fixed circuit breakers

600 451,5
HD4 2XM8 depth 16
581 420
M12 depth 25
TN 1VCD000235 210 210 87 356,5 13,5

Ur 24 kV 103,5 103,5
67,5
630 A
Ir
1250 A

27
16 kA
Isc 25 kA

670

310
31.5 kA
695

623

27
63

468
231

43

302,5

472 10,5 13 M12 depth 25


2XM8 depth 16
598
117
618 270 34
332

Insulating partitions to be provided by the customer


(a special kit is available on request).

Fixed circuit breakers

730
HD4
705 2XM8 depth 16 M12 depth 25
451,5
TN 1VCD000237 275 275
87 356,5 13,5
67,5
Ur 24 kV
630 A 27
Ir
1250 A
16 kA
310

Isc 20 kA
27
695

25 kA
623
63

468
302,5
231

602 M12 depth 25


10,5
43

728 117 2XM8 depth 16


270 34
748 332
D I S T R I B U T I O N S O LU T I O N S 17

Fixed circuit breakers

HD4 730
708
TN 7174
275 275
Ur 24 kV
Ir 1600 A
31.5 kA
Isc
40 kA 2x Ø18

310
310

80
HD4
28
TN 7174 15.5 32

622
655
Ur 24 kV YU

8
Ir 2000 A YU

25 kA 8

306.5
266.5
Isc 31.5 kA Q6
0
Ø 13
40 kA
43

602 Ø 10.5 115 3

20
728 322
35
385
748 561

Fixed circuit breakers

HD4 400
880
358
with truck 350 350 10
Ø 22
(on request) 50

TN 7241
Ur 36 kV
630 A
362

Ir 1250 A Ø 22
729.5

28
712

639. 5

1600 A
539

16 kA
10

Isc
* 106 0

342.5

20 kA 21
302.5

* Distance with truck 3


* Ø 13
* 887

(if provided).

755
2x Ø 10.5 120
881 363.5 270
43

901 695.4 37
*4.9
* 348

*Ø 13

* 855 * Ø 13 * 200
* 355 *85
*4

* 915 *40
* 955 * 516.4
18 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA


7. Installation
7.9. Overall dimensions

Fixed circuit breakers

HD4 730
708
with truck
(on request)
TN 7268
Ur 36 kV
1250 A
Ir
1600 A
25 kA
Isc
31.5 kA

HD4
with truck
(on request)
TN 7268
Ir 2000 A
20 kA
Isc 25 kA
31.5 kA

Insulating partitions to be provided by the customer


(a special kit is available on request).
* Distance with truck (if provided).

Fixed circuit breakers

HD4
with truck
(on request)
TN 7315
Ur 36 kV
Ir 2000 A
20 kA
Isc 25 kA
31.5 kA

Insulating partitions to be provided by the customer


(a special kit is available on request).
* Distance with truck (if provided).
D I S T R I B U T I O N S O LU T I O N S 19

HD4/P withdrawable circuit breakers for UniGear type ZS1 switchgears

HD4/P
496 125

10
TN 1VCD000227 30 203 119 9
12 kV
Ur
17.5 kV
630 A

98,5
Ir
1250 A
16 kA

205 ±1
35
586
Isc 25 kA

619 ±2
619
622,5

31.5 kA

541
Also suitable for
PowerCube PB1

260 ±1

154 ±1

19,5
340
4

21,5

4
503 25 320
531 370
501 416 53
492
456 ±2 437 0 + 2
150 150 558
661
608

55
20 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA


7. Installation
7.9. Overall dimensions

HD4/P withdrawable circuit breakers for UniGear type ZS1 switchgears

HD4/P 636
640
579
TN 7350 210 ±1 210 ±1 119
12 kV 272
111.5 17
Ur 44

10
17.5 kV
Ir 1250 A
Isc 40 kA

Ø 79
68

Ø 122
HD4/P 67.5

310 ±1
TN 7350
12 kV
691

Ur

688
686

668.5
17.5 kV
63

Ir 1600 A

543
25 kA 53.5

280 ±1
31.5 kA 40
Isc
245

164.5 ±1

89
40 kA (*) 21

Ø 19.5
50 kA (*) 20

550 4

21.5
(*) A lso suitable for 29 359

4
4

PowerCube PB2. 626 ±2


416
653
36 551 ±1.5 53
682

HD4/P withdrawable circuit breakers for UniGear type ZS1 switchgears

HD4/P 636
640
579
TN 7351 210 ±1 210 ±1 119
12 kV 272 111.5 17
Ur 44 10
17.5 kV
Ir 2000 A
25 kA
31.5 kA
Isc
Ø 79

68
Ø 122

40 kA (*) 67.5
310 ±1

50 kA (*)

(*) A lso suitable for


691

688
686

669

PowerCube PB2.
63

543

53.5
280 ±1

40
245

164.5 ±1

89

21
Ø 19.5

20
4
550
21.5

359
4

29
4

626 ±2
416
653 36 551 ±1.5 53
682
D I S T R I B U T I O N S O LU T I O N S 21

HD4/P withdrawable circuit breakers for UniGear type ZS1 switchgears

HD4/P 842
643
TN 7352 (*) 708
119
375
12 kV 111.5 17
Ur 275 ±1 275 ±1
17.5 kV 144

10
Ir 2500 A
25 kA
31.5 kA
Isc

Ø 109
40 kA

Ø 152
67.5

310 ±1
50 kA

(*) A lso suitable for

688
691
686

668.5
PowerCube PB3.
58
63

43.5

280 ±1
30
245

89
21

164.5 ±1

Ø 19.5
750 4

21.5

4
4

29 359
806 ±2
416
853
36 554 ±1.5 53
882

HD4/P withdrawable circuit breakers for UniGear type ZS1 switchgears

HD4/P 842
708 643
TN 7371
375
12 kV 96.5 17
Ur 275 ±1 275 ±1

10
17.5 kV
Ir 3150 A (*)
25 kA
31.5 kA
Isc
40 kA
Ø 109

Ø 152

50 kA 67.5
310 ±1

(*) 3150 A with forced


730

732

switchgear ventilation
730

(consult the UniGear


type ZS1 switchgear 58
63

technical catalogue).

43.5
30
280 ±1
245

89
164.5 ±1

21
Ø 19.5

4
21.5

750 29 359
4

806 ±2 416
853 36 554 ±1.5 53

882
22 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA


7. Installation
7.9. Overall dimensions

HD4/P withdrawable circuit breakers for UniGear type ZS1 switchgears

HD4/P 636
210 ±1 210 ±1
TN 1VCD000236 119 24
276

20
Ur 24 kV 44

630 A
Ir
1250 A
16 kA (*)
Isc 20 kA
25 kA

310 ±1
(*) 6 30 A only.

35
772,5
766,5

768
717

645
63

325 ±1
254,5

125
198 ±2
461 ±1
4

610 ±2
697 53
653
746 ±1,5
681

HD4/P withdrawable circuit breakers for UniGear type ZS1 switchgears

HD4/P 641
799
578
TN 1VCD000099 210 ±1 210 ±1 23
Ur 24 kV 272
67.5 44
Ir 1250 A
20

Isc 31.5 kA
Ø 92.6
310 ±1

28
Ø 35

792
776

718

682
63

8
329 ±1

25.5
293

125

10
202 ±1

550 4
Ø 19.5
21.5

610 ±2 460
653 36 710 ±1.5 53
682
D I S T R I B U T I O N S O LU T I O N S 23

HD4/P withdrawable circuit breakers for UniGear type ZS1 switchgears

HD4/P 842 788


708
TN 7355 (*) 119 23
275 ±1 275 ±1

20
Ur 24 kV 144 232 19

Ir 1600 A
16 kA
20 kA
Isc
25 kA

Ø 79
31.5 kA

Ø 122
67.5

310 ±1
(*) A lso suitable for
PowerCube PB5. 58
817.5

814
807

733
63

700
43.5

345 ±1
30
310

125
11

198 ±1 4
806 ±2
4

4
457
853
882 36 699 ±1.5 53

HD4/P withdrawable circuit breakers for UniGear type ZS1 switchgears

HD4/P 842 788


TN 7356 (**) 708 23
119
275 ±1 275 ±1

20
Ur 24 kV 19
144 232
Ir 2000 A
Isc 16 kA
20 kA
Ø 79

25 kA
31,5 kA
Ø 122

67.5
310 ±1

HD4/P 58
814
817.5

TN 7356 (**)
807

733

Ur 24 kV
63

700

Ir 2500 A (*)
Isc 20 kA 43.5

25 kA
345 ±1

30
310

125

31,5 kA
198 ±1

11

(*) 2500 A with forced


ventilation; 2300
A with natural 4
Ø 19.5

750
21.5

4
4

457
4

ventilation. 806 ±2
(**) A lso suitable for 853 36 699 ±1 53
PowerCube PB5.
882
24 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA


7. Installation
7.9. Overall dimensions

HD4/W withdrawable circuit breakers for PowerCube modules

HD4/W 119
636 111,5
TN 1VCD000228 44 228 63 15

10
12 kV
Ur

35
17.5 kV
630 A
Ir
1250 A
16 kA

310 ±1
Isc 25 kA 28
688

31.5 kA

691

692
640
280 ±1

89
165 ±1
550 +2

19,5
21,5
359 0
4

626
653 416

681 539

587 ±1,50 53

210 ±1 210 ±1
586,5

55
D I S T R I B U T I O N S O LU T I O N S 25

HD4/W withdrawable circuit breakers for PowerCube modules

HD4/W 636
578
56
TN 7421 210 ±1 210 ±1
44 228 63 15
12 kV

10
Ur
17.5 kV
Ir 1250 A
40 kA

Ø 35
Ø 79
Isc
50 kA 67.5

310 ±1
28

688
688

691

636
63

16

280 ±1
245

89
165 ±1
4

Ø 19.5
626 ±2

21.5
4
4

29 359 40
653
416
682 36 551 ±1.5 53
640

HD4/W withdrawable circuit breakers for PowerCube modules

HD4/W 636
578
TN 7239
210 ±1 210 ±1
56
12 kV 272
Ur 63 15
44
17.5 kV
1600 A
10

Ir
2000 A
16 kA
Isc 25 kA 67.5
310 ±1

31.5 kA 28
698
691
668.5

635.5
63

8
Ø 122
Ø 79
280 ±1
245

89
165 ±1

4
Ø 20

550
4
21.5
4

29 359 40
626 ±2
653 36 551 ±1.5 53
682 640
26 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA


7. Installation
7.9. Overall dimensions

HD4/W withdrawable circuit breakers for PowerCube modules

HD4/W 842
708
TN 1VCD000053
375 643
12 kV 275 ±1 275 ±1 112 16
Ur
17.5 kV 144

10
Ir 3150 A
31.5 kA

Ø 109
Isc 40 kA
50 kA

Ø 152
67.5

310 ±1
742

730
730

732
58
63

43.5

280 ±1
30
245

164.5 ±1
89
21

Ø 19.5
750 29 359

21.5
4

806 ±2 416
853
36 554 ±1.5 53
882
D I S T R I B U T I O N S O LU T I O N S 27

Withdrawable circuit breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module

HD4/W 842 788


708
TN 7402 275 275 119 23
Ur 36 kV 67.5 144 232 19

20
Ir 1250 A
20 kA
Isc
25 kA

Ø 35
380
78
941.5

949
952

833
63

60
44
480

198
345

10

125
198

805 4
4

457
836
36 699 53
853
882

Withdrawable circuit breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module

HD4/W 842
730
TN 7316 706 18
23
Ur 36 kV 275 275
Ø 35

Ir 1250 A
Isc 31.5 kA
380

953
956
973
484

125
202

805 4
456
836
30 701 57
853
882
28 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA


7. Installation
7.9. Overall dimensions

Withdrawable circuit breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module

HD4/W 842 788


708
TN 7317 119 23
275 275
19

20
Ur 36 kV 67.5 144 232

1600 A
Ir 2000 A
2500 A (*)

Ø 122
Ø 79
20 kA

380
Isc 25 kA
31.5 kA 78

(*) With forced ventilation.


941.5
952

949
903.5

833
63

60
44
480
345

125
10

198
21.5
750

Ø 20
4

4
805 457
836 36 699 53
853
882

HD4/Z withdrawable circuit breakers for UniGear type ZS3.2 - 40.5 kV switchgears

HD4/Z/40,5 kV
840 245
TN 7227 280 280

Ur 40,5 kV
1250 A 385

1600 A 2÷5
Ir
2000 A
2500 A (*)
25 kA
328

Isc
31,5 kA
ØA

(*) W ith natural ventilation


in loose enclosure
type Powerbloc; with
1575

forced ventilation in
switchgear type
1288.5

ZS3.2.
27
15

Ø 20
100
50

900

23 23
30 40
550

43 43
485

22
Ø 16
Ø 18
120

85

80

32.5 45 103
ØA 140 150
100
25 230 200
1250-1600 A 35 mm
718 503
2000-2500 A (*) 79 mm
760 582
D I S T R I B U T I O N S O LU T I O N S 29

HD4/SEC withdrawable circuit breakers for UniSec switchgears

HD4/SEC 24 kV 625 ±1 740


604
TN 1VCD000220 149 40
255
Ur 24 kV 307 121,5 ±1
37

25
229
630 A
Ir

45°
1250 A

1
169 kA
Isc 68

79
20 kA

310 ±1

739
35
A

644,5
734,5

435,5 ±2
63

36 8

325 ±1
254

653 25 320
19

4
681 370
382 4
650 414
210 ±1 210 ±1 687 ±1,5 53

19,5
36,3
25
55

DETAIL A
SCALE 1 : 2
30 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA


8. Putting into service
8.1. General procedures

All the operations regarding putting into Before putting the circuit breaker into service carry
service must be carried out by ABB out the following operations:
personnel or customer personnel who are • check the tightness of the power connections on
suitably qualified and have an in-depth the circuit breaker terminals;
knowledge of the apparatus and • establish the setting of the direct solid-state
installation. overcurrent release (if provided);
If the operations are prevented, do not • check that the value of the supply voltage for the
force the mechanical interlocks, but auxiliary circuits is within 85% and 110% of the
check that the operation sequence is rated voltage of the electrical devices;
correct. • check that no foreign body, such as packaging, has
The operating forces which can be got into the moving parts;
applied are indicated in paragraph 6.3. • check that air circulation in the circuit breaker
installation site is adequate so that there is no
danger of overheating;
• carry out the checks indicated in the following
table:

Subject of the inspection Procedure Positive check


1 Insulation resistance. Medium voltage circuits The insulation resistance should be at least 50 MΩ
With a 2500 V Megger, measure the insulation resistance and, in any case, constant in time.
between phases and exposed conductive part of the circuit.
Auxiliary circuits The insulation resistance should be a few MΩ and, in
With a 500 V Megger (installed equipment permitting) any case, constant in time
measure the insulation resistance between the auxiliary
circuits and the exposed conductive part.
2 Auxiliary circuits. Check that the connections to the control circuit are correct; Normal switchings and signallings
proceed with relative supply.
3 Manual operating Carry out a few closing and opening operations (see chap. 6). The operations and relative signals occur correctly.
mechanism. N.B. Supply the u/v release and the locking magnet on the
operating mechanism at the relative rated voltage (if
provided).
4 Motor operator (if provided) Supply the geared motor for spring charging at the relative The springs are charged correctly.
rated voltage. The signals are correct.
The geared motor cuts off when the springs are
charged.
Carry out a few closing and opening operations. The geared motor recharges the springs after each
N.B. Supply the undervoltage release and the locking magnet closing operation.
on the operating mechanism at the relative rated voltage (if
provided).
5 Undervoltage release (if Supply the undervoltage release at the relative rated voltage The circuit breaker closes correctly.
provided). and carry out the circuit breaker closing operation. The signals are correct.
Disconnect the power supply to the release. The circuit breaker opens.
The signal changes over.
D I S T R I B U T I O N S O LU T I O N S 31

Subject of the inspection Procedure Positive check


6 Shunt opening release and Close the circuit breaker. The circuit breaker opens correctly.
additional shunt opening Supply the shunt opening release at the relative rated The signals are correct.
release (if provided). voltage.
7 Shunt closing release (if Open the circuit breaker. Supply the shunt closing release at The circuit breaker closes correctly.
provided). the relative rated voltage. The signals are correct.
8 Key lock (if provided). Open the circuit breaker. Neither manual nor electric closing takes place.
Turn the key and remove it.
Attempt the circuit breaker closing operation.
Insert the key again and turn it 90°. Both electric and manual closing take place
Carry out the closing operation. correctly; in this position the key cannot be
removed.
9 Locking electromagnet (YL1) With the circuit breaker open, springs charged and locking Closing is not possible.
(if provided). electromagnet not supplied, attempt to close the circuit
breaker both manually and electrically.
10 Auxiliary contacts in the Insert the auxiliary contacts into suitable signalling circuits. Signals occur correctly.
operating mechanism. Carry out a few closing and opening operations.
11 Locking electromagnet on With the circuit breaker open in the isolated for test position Connection is not possible.
the circuit breaker truck and the locking electromagnet not supplied, attempt to
(YL2) (if provided). connect the circuit breaker.
Supply the locking electromagnet and carry out the Connection takes place correctly.
connection operation.
12 Auxiliary transmitted Insert the auxiliary contacts into suitable signalling circuits. The signals of the relative operations occur
contacts for indicating that With the circuit breaker inside the enclosure carry out a few correctly.
the circuit breaker is translation operations from the isolated for test position to
connected, isolated (CBE or the connected position.
PowerCube enclosures). Put the circuit breaker in the withdrawn position.
13 Electromechanical locking With no supply to the locking device try to rack-in the circuit Racking-in is not possible.
device (if provided) (CBE or breaker into the enclosure.
PowerCube enclosures). Supply the locking device at the relative rated voltage. Carry Racking-in is possible.
out the racking-in operation.
32 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA


9. Periodical checking
Before carrying out any operation, make sure that the operating mechanism springs are
discharged and that the apparatus is in the open position.

9.1. General
During normal service, the circuit breakers are maintenance-free. The frequency and sort of inspections
basically depend on the service conditions. Various factors must be taken into account: frequency of
operations, interrupted current values, relative power factor and the installation ambient.
The following paragraph gives the checking programme table, showing the relevant time intervals.
As far as the time interval between these operations is concerned, it is advisable to comply with
specifications given in the table, at least during the first check. On the basis of the results obtained
during the periodic inspections, set the optimal time limits for carrying out the following operations.

9.2. Checking programme


Checking operation Time interval Critera
1 Carry out five mechanical opening closing 1 year. The circuit breaker must operate normally without stopping
operations. in intermediate positions
2 Visual inspection of the poles (parts in 1 year or 5.000 The parts in resin must be free of any accumulation of dust,
resin). operations. dirt, cracks, discharges or traces of surface discharges.
3 Visual inspection of the operating 1 year or 5,000 The elements must be free of any deformation.
mechanism and transmission. operations. Screws, nuts, bolts, etc. must be tight.
4 Visual inspection of the isolating contacts. 5 year or 5.000 The isolating contacts must be free of any deformation or
operations. erosion.
Lubricate the contact elements with industrial vaseline
greaseindustriale.
5 Measuring the insulation resistance. 5 year or 5.000 See para. 8.1. point 2.
operations.
6 Checking interlock operation. 5 year. The interlocks provided must operate correctly.

After 10,000 operations or after 10 years, for installation in polluted and aggressive ambients, it is advisable
to contact an ABB service center to have the circuit breaker checked.


10. Maintenance operations
Maintenance must only be carried out by ABB personnel or in any case by suitably qualified
customer personnel who have in-depth knowledge of the apparatus (IEC 62271-1 para 10.4.2).
Should the maintenance by carried out by the customer’s personnel, responsibility for any
interventions lies with the customer.
Replacement of any parts not included in the “List of spare parts/accessories” must only be
carried out by ABB personnel.
In particular:
• Complete pole with bushings/connections
• Operating mechanism
• Closing spring unit
• Opening spring.
D I S T R I B U T I O N S O LU T I O N S 33


11. Indications for handling apparatus with SF6 6

SF6 in its pure state is an odourless, colourless, non- The Electric Industry is reported as the most
toxic gas with a density about six times higher than important user of SF6, worldwide. In spite of being
air. For this reason, although it does not have any the most important user of SF6, the Electric Industry
specific physiological effects, it can produce the is a low contributor to the global emission of SF6, far
effects caused by lack of oxygen in ambients below to other industries or users with “open
saturated with SF6. application” of the gas. However, its importance as
During the interruption phase of the circuit breaker, source substantially varies from region to region and
an electric arc is produced which decomposes a very from country to country, depending on the SF6
small amount of SF6. The decomposition products handling procedures adopted, the tightness of the
remain inside the poles and are absorbed by special electric power equipment and the amount of gas
substances which act as molecular sieves. The banked in electric equipment.
probability of contact with decomposed SF6 is For info about Life Cycle Assessment of apparatus,
extremely remote, and its presence in small see document (1VCP000264).
quantities (1-3 ppm) is immediately noticeable To dispose of the SF6 gas, please contact the ABB
because of its sour and unpleasant smell. In this case, Assistance Service (see contact persons at http:
the room must be aired before anybody enters it. //www.abb.com/ServiceGuide/alphabetical.aspx) as
The strong infrared absorption of SF6 and its long this operation must be done only by trained and
lifetime in the environment are the reasons for its qualified personal; on request are available specific
high Global Warming Potential (GWP) which is 22.800 instructions for the evacuation of the SF6 gas from
higher than CO2, according to the Fourth Assessment the apparatuses.
Report. The volume of SF6 in each apparatus is indicated on
The GWP is calculated over a time period of 100-years the nameplate.
warming potential of 1 kg of a gas referred to 1 kg of
CO2. Its overall contribution to the global greenhouse
gas effect from all applications amounts to
approximately 0,2% overall.
However, the GWP of SF6 alone is not adequate to
measure the environmental impact of electric power
equipment based on SF6 technology.
The environmental impact of any specific application
should be evaluated and/or compared using the Life
Cycle Assessment – LCA approach as regulated by ISO
14040.
The Electric Industry utilises SF6 in a closed cycle,
banking it e.g. in gas insulated substations (GIS),
medium-voltage and high-voltage gas circuit
breakers (GCB), high-voltage gas insulated lines (GIL),
gas insulated voltage transformers (GVT). In Asia,
significant quantities of SF6 are banked in gas
insulated power transformers (GIT) as well.
34 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA


12. Spare parts and accessories
All assembly operations of spare parts/ 12.1. List of spare parts
accessories
• Shunt opening release
regarding installation, putting into
• Additional shunt opening release
service, service and maintenance must
• Undervoltage release
be carried out by ABB personnel or
• Contact signalling undervoltage release
suitably qualified customer personnel
energised/de-energised
with in-depth knowledge of the
• Undervoltage release delay device
apparatus (IEC 62271-1 para. 10.4.2).
• Mechanical exclusion device for undervoltage
Should the maintenance by carried out by
release
the customer’s personnel, responsibility
• Shunt closing release
for any interventions lies with the
• Spring charging geared motor with electric
customer.
signalling of springs charged
Before carrying out any operation, check
• Geared motor thermomagnetic protection circuit
that the circuit breaker is open, the
breaker
springs discharged and that there is no
• Contact signalling geared motor protection circuit
voltage (medium voltage circuit and
breaker open/closed
auxiliary circuits).
• Contact signalling closing springs charged/
discharged
To order accessories or spare parts, please refer to • Transient contact with momentary closure during
the commercial ordering codes given in the circuit breaker opening
technical catalogue and always indicate: • Auxiliary circuit breaker contacts
• circuit breaker type • Locking electromagnet on operating mechanism
• circuit breaker rated voltage • Position contact of withdrawable truck
• circuit breaker rated thermal current • Contacts signalling connected/isolated
• circuit breaker breaking capacity • Opening solenoid
• circuit breaker serial number • Key lock in open position
• rated voltage of any electrical accessories. • Isolation interlock with door
For availability and ordering of spare parts please • Protection for opening pushbutton
contact our Service department.e. • Protection for closing pushbutton
• Locking electromagnet on withdrawable truck
• Sliding earthing contact of withdrawable truck
• Opening/closing knob
• Set of six tulip contacts
• SF6 gas pressure monitoring device.
D I S T R I B U T I O N S O LU T I O N S 35

For further details please contact:

1VCD601246 - Rev. S - en Instruction Manual 2018.10 (HD4) (gs)


More product information:
abb.com/mediumvoltage
Your contact center:
abb.com/contactcenters
More service information:
abb.com/service

The data and illustrations are not binding. We reserve the right to modify the
contents of this document following technical developments.

© Copyright 2018 ABB. All rights reserved.

Das könnte Ihnen auch gefallen