Beruflich Dokumente
Kultur Dokumente
DISTRIBUTION SOLUTIONS
HD4
Installation and service instructions
12-40.5 kV – 630-3600 A – 16-50 kA
Table of contents
I. Introduction 2
II. Programme for the environmental protection 2
1. Packing and transport 3
2. Checking on receipt 4
3. Storage 5
4. Handling 6
5. Description 8
6. Instructions for circuit breaker operation 10
7. Installation 11
8. Putting into service 30
9. Periodical checking 32
10. Maintenance operations 32
11. Indications for handling apparatus with SF6 33
12. Spare parts and accessories 34
—
For your safety!
• Make sure that the installation room (spaces, • Check that the rated performance of the
divisions and ambient) is suitable for the apparatus is not exceeded during service.
electrical apparatus. • Check that the personnel operating the
• Check that all the installation, putting into apparatus have this instruction manual to hand
service and maintenance operations are carried as well as the necessary information for correct
out by qualified personnel with suitable intervention.
knowledge of the apparatus. • Pay special attention to the danger notes
• Make sure that the standard and legal indicated in the manual by the following symbol:
prescriptions are complied with during
installation, putting into service and Responsible behaviour safeguards
maintenance, so that installations according to your own and others’ safety!
the rules of good working practice and safety in For any requests, please contact the
the work place are constructed. ABB Assistance Service.
• Strictly follow the information given in this
instruction manual.
2 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA
—
I. Introduction
This publication contains the information necessary Apart from this booklet, it is therefore always
for installation and putting into service of HD4 necessary to refer to the latest technical
medium voltage circuit breakers. documentation available (circuit diagram, wiring
For correct usage of the product, please read this diagrams, assembly and installation drawings, any
manual carefully. studies of protection co-ordination, etc.), especially
For correct mounting of accessories and/or spare with regard to any variations from standardized
parts please refer to the relevant instructions. configurations requested.
Like all the apparatus manufactured by us, the HD4
circuit breakers are designed for different All the operations regarding installation,
installation configurations. putting into service, operation and
They do, however, allow further technical- maintenance must be carried out by
constructional variations (at the customer’s suitably qualified personnel with in-
request) to suit special installation requirements. depth knowledge of the apparatus.
For this reason, the information given below does
not always cover special configurations.
Only use original spare parts for maintenance
operations.
For further information, also see the technical
catalogue of the circuit breaker and the spare parts
catalogue.
—
II. Programme for the environmental protection
The HD4 circuit breakers comply with ISO 14000 The Product environmental declaration is available
Standards (Guidelines for the Environmental for the HD4 circuit breakers
Management). Production techniques are carried out in order to
The production system of the Medium Voltage achieve an easy dismantling and separation of the
factories complies for the environmental protection components at the end of the circuit breaker life
in terms of energy consumption, raw materials and cycle, while optimizing the recycling process.
waste.
The environmental impact of the product life cycle is
assessed by the LCA - Life Cycle Assessment
procedure, which is also the result of a well-focused
project phase in the selection of materials,
processes and packaging.
D I S T R I B U T I O N S O LU T I O N S 3
—
1. Packing and transport
The circuit breaker is shipped in special packing in
the open position with the springs discharged and
with absolute pole pressure corresponding with the
service value.
Each piece of apparatus is protected by a plastic
film to prevent any infiltration of water during the
loading and unloading stages and to keep the dust
off during storage.
—
2. Checking on receipt
Before carrying out any operation, always
make sure that the operating mechanism A
dprings are discharged and that the Circuit breaker IEC 62271-100
apparatus is in the open position. 1 HD4 ... ... ... CEI 17-1 2
CLASSIFICATION ... ... ...
3 SN ... ... ... PR. YEAR ......
On receipt, check the state of the apparatus, that the M MASS ... kV
Ur
packing is undamaged and that the nameplate data
corresponds (see fig. 1) with that specified in the order
acknowledgement and in the delivery note.
Also make sure that all the materials described in the
shipping note are included in the supply.
If any damage or irregularity is discovered on
unpacking, notify ABB (directly or through the agent or 4
supplier) as soon as possible and in any case within five
days of receipt.
The apparatus is only supplied with the accessories
specified at the time of order and confirmed in the
ELECTRIC DIAGRAM .. ... ... ...
order acknowledgement sent by ABB. FIG. ... ...
The following accompanying documents are inserted in
the shipping packing: .. ... ... ... OPERATING MECHANISM
B
• Instruction manual (this document)
Fig. 1
D I S T R I B U T I O N S O LU T I O N S 5
—
3. Storage
In case a storage period is foreseen, on request our Therefore, store in a sheltered, well-ventilated area
workshops will provide a suitable packing to the with a dry, non-dusty, non-corrosive atmosphere
specified storage conditions. away from highly flammable materials, with a
On receipt, the apparatus must be carefully temperature between -5 °C and +45 °C.
unpacked and checked as described in chapter 2: In any case, avoid accidental shocks or
Checkink on receipt. accommodations that stress the structure of the
If immediate installation is not possible and the circuit breaker
circuit breaker has to be re-stored again, it is
necessary to restore the packaging at least suitable
for protection against dust.
Insert hygroscopic substances in the packaging in
the quantity of at least one standard pack per
apparatus.
6 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA
—
4. Handling
Before carrying out any operation, always check that 36 kV circuit breakers
the operating mechanism springs are discharged • Attach the tools (1) to lift and handle the circuit
and that the apparatus is in the open position. breaker (fig. 2c);
• Attach the hooks (2) as illustrated in fig. 2d and lift;
Circuit breakers up to 24 kV • On completion of the operation, remove the tools
• To lift and handle the circuit breaker, use the tool (1).
(1) (fig. 2a: shortest hooks for circuit breakers up
to 17.5 kV; all hooks for 24 kV circuit breakers). Always take great care during handling not to stress
• Put the hooks (2) in the holes prepared in the the insulating parts and the circuit breaker
circuit breaker frame and lift. terminals.
• On completion of the operation (and in any case
before putting into service) unhook the lifting tool The apparatus must not be handled by
(1) (fig. 2b) and dismantle the crosspiece (2) by inserting lifting devices directly under
unscrewing the screws (3). the apparatus itself. Should it be
necessary to use this method, place the
circuit breaker on a sturdy supporting
surface (see fig. 3).
2 2
Fig. 2a
2
3
Fig. 2b
D I S T R I B U T I O N S O LU T I O N S 7
Fig. 2c
Fig. 2d Fig. 3
8 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA
—
5. Description
5.1. General features 5.3. Fixed circuit breaker
The HD4 series are sulphur hexafluoride circuit The fixed circuit breaker (see fig. 4) corresponds to
breakers for indoor installation. For the electrical the basic version complete with a front protection
performance, please refer to the corresponding shield and frame.
technical catalogue code 1VCP000004. The anchoring holes are drilled in the lower part of
For special installation conditions please ask ABB. the frame.
The following versions are available: The terminal box, fixed on the upper protection, is
• fixed available for connection of the circuit breaker
• withdrawable for CBE, PowerCube enclosures and auxiliary circuits.
CBF fixed parts The earthing screw is located on the circuit breaker
• withdrawable for switchgear: UniGear type ZS1, side.
UniGear type ZS2, UniGear type ZS3.2 For further details, refer to the caption of fig. 4.
• withdrawable for switchgear: UniSwitch, UniMix
and UniSec.
8
1
9
2
3
7
4
10 11
5 12 6 10 - 11 (36 kV)
Fig. 4
Caption
1 Signalling device for state of SF6 pressure (on request) 7 Signalling device for closing springs charged/discharged
2 Opening push button 8 Characteristics nameplate
3 Closing push button 9 Terminals (only available for certain versions)
4 Operator counter 10 Pressure switch (on request)
5 Signalling device for circuit breaker open/closed 11 Valve for checking the SF6 gas pressure
6 Shaft for manual closing spring charging 12 Resetting button for protection circuit breaker of geared motor (on
request)
D I S T R I B U T I O N S O LU T I O N S 9
The strikers for activating the contacts (connected/ The activating lever (connection/isolation) must be
isolated), located in the enclosure or in the fully inserted. A lock prevents the truck from
switchgear, are fixed in the top part of the circuit advancing into the enclosure or fixed part (for
breaker. The slides for activating the segregation example when the earthing switch is closed). With
shutters of the medium voltage contacts of the the truck in the middle position between isolated
enclosure or switchgear are fixed on the sides of the and connected, the lock prevents closure of the
circuit breaker. The crosspiece for hooking the circuit breaker (both mechanical and electrical).
circuit breaker for the connection/isolation On request, a locking magnet can be mounted on
operation by means of the special operating lever is the truck which, when de-energised, prevents truck
mounted on the front part of the circuit breaker operation.
truck.
The circuit breaker is completed with the tulip
isolating contacts. The withdrawable circuit breaker
is fitted with special locks, on the front crosspiece,
5.5. Enclosures and fixed parts
which allow hooking into the corresponding joints in For information about the enclosures and fixed
the enclosure or fixed part. The locks can only be parts, please consult the relative documentation.
activated by the handles with the truck resting
completely on the crosspiece.
17 16 16 9 16
8
1
3 9
7
4
12
10 11
5 18 6 13 14 15
Fig. 5
10 - 11 (36 kV)
Caption
1 Signalling device for state of SF6 pressure (on request) 10 Pressure switch (on request)
2 Opening push button 11 Valve for checking the SF6 gas pressure
3 Closing push button 12 Slide for activating the enclosure shutters
4 Operator counter 13 Truck
5 Signalling device for circuit breaker open/closed 14 Locks for hooking into the fixed part
6 Shaft for manual closing spring charging 15 Lock activating handles (17)
7 Signalling device for closing springs charged/discharged 16 Strikers for activating the contacts located in the enclosure
8 Characteristics nameplate 17 Connector (plug)
9 Isolating contacts 18 Resetting button for protection circuit breaker of geared motor (on
request)
10 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA
—
6. Instructions for circuit breaker operation
6.1. Safety indications 6.3. Circuit breaker closing and
opening operations (fig. 6)
HD4 circuit breakers ensure a minimum
degree of protection IP2X if installed Circuit breaker operation can be manual or
under the following conditions: electrical.
• fixed version, with protection netting
• withdrawable version, installed in a a) Manual operation for spring charging
switchgear. To manually charge the closing springs, it is
Under these conditions, the operator is necessary fully insert the charging lever into the
guaranteed against accidental contact seat (6) and turn it clockwise until the yellow
with moving parts. indicator (7) appears.
Should any mechanical operations be The force which can normally be applied to the
carried out on the circuit breaker outside charging lever fitted is 130 N. In any case, the
the switchgear or with the protection maximum force which can be applied must not
netting removed, be very careful of any exceed 170 N.
moving parts.
If the operations are prevented, do not b) Electrical operation for spring charging
force the mechanical interlocks and On request the circuit breaker can be fitted with the
check that the operation sequence is following accessories for electrical operation:
correct. • geared motor for automatic charging of the
The racking-in and racking-out closing springs
operations of the circuit breaker must be • shunt closing release
carried out gradually to prevent any • shunt opening release.
impacts which might deform the The geared motor automatically recharges the
mechanical interlocks. springs after each closing operation until the yellow
indicator (7) appears. Should there be no voltage
during charging, the geared motor stops and then
6.2. Operating and signalling parts starts recharging the springs automatically when
the voltage is on again. It is, however, always
possible to complete the charging operation
manually.
Fig. 6
D I S T R I B U T I O N S O LU T I O N S 11
—
7. Installation
7.1. General 7.4. Installation of fixed circuit
Correct installation is of prime breaker
importance. The instructions given by
The circuit breaker can be mounted directly on the
the manufacturer must be carefully
supporting frames provided by the customer.
studied and followed. It is good practice
The circuit breaker, complete with supporting truck,
to use gloves to handle the pieces during
must be fixed to the floor of its compartment with
installation
special brackets.
The parts of the floor surface on which the truck
wheels rest must be perfectly level.
The areas on which the supporting frames or truck
7.2. Normal installation conditions wheels rest (if a truck is provided) must be on the
Maximum ambient air temperature + 40 °C same horizontal plane to avoid any risk of distortion
Minimum ambient air temperature – 5 °C in the breaker frame.
Relative humidity % < 95 Fit the isolating partitions if provided.
Altitude < 1000 m A minimum degree of protection (IP2X) must be
guaranteed from the front towards live parts.
—
7. Installation
7.6. Fixed circuit breaker power Mounting procedures
• Place the connections in contact with the circuit
circuit connections breaker terminals.
7.6.1. General directions • Interpose a spring washer and a flat washer
• The connections must be made using only the between the head of the bolt and the connection.
squares-terminals supplied with the circuit • Tighten the bolt, taking care not to subject the
breaker. insulating parts to stress (see table tightening
• Select the conductor cross-section according to torque).
the operating and short-circuit current of the • Make sure that the connections do not exert force
installation. on the terminals.
• Near the terminals of fixed version circuit breakers • In case of cable connections, carefully follow the
or enclosure, provide suitable support insulators manufacturer’s instructions for terminating the
dimensioned according to the electrodynamic cables.
stresses that may arise from the short-circuit
current of the installation. Table of tightening torque
• Fit the isolating partitions if provided. Screw Tightening torque
M6 10 Nm
7.6.2. Mounting the connections
M8 30 Nm
• Check that the connection contact surfaces are
M10 40 Nm
perfectly flat and have no burrs, oxidation traces,
M12 70 Nm
or deformations due to drillings or impacts.
• Depending on the conductive material and surface
treatment used, carry out the operations indicated
in the table on the contact surface of the
conductor.
—
7. Installation
7.9. Overall dimensions
HD4 496
150 150 446
2XM8 depth 16 M12 depth 25
TN 1VCD000226 87 336,5 13,5
67,5
Ur 12 kV
630 A
Ir
1250 A
27
16 kA
Isc 25 kA
205
31.5 kA
586
541,5
63
27
260,5
248,5
21,5
43
600
HD4
581 446 2XM8 depth 16 M12 depth 25
TN 1VCD000231 210 210
87 336,5 13,5
12 kV 67,5
Ur
17.5 kV
630 A
Ir
27
1250 A
16 kA
Isc 25 kA
205
31.5 kA
623
27
63
266,5
231,5
21,5
43
472 13
117 2XM8 depth 16
598 10,5 M12 depth 25
111,5
618
270 34
332
D I S T R I B U T I O N S O LU T I O N S 15
HD4 600
578
TN 7163
210 210
12 kV
Ur
17.5 kV
Ir 1600 A
40 kA
Isc 2 x Ø18
310
50 kA
310
28
80
HD4 15.5 32
655
622
TN 7163 YU
12 kV
8
YU
Ur
17,5 kV
306.5
266.5
Ir 2000 A Q6
0 8
25 kA
Ø 13
31.5 kA
Isc
43
40 kA
472 Ø 10.5 35
50 kA 2.5
20
598 322
618 385
561
349.5
2500 A
Ir 3150 A
670 min.
3600 A
15
25 kA
310
28
62
31,5 kA
Isc
40 kA 20 40
655
20
622
YU
50 kA
468.5
40
YU
20
20
HD4 8
TN 7165
266.5
4 x Ø18
Ø13
Ur 24 kV
2500 A
43
322 35
728
3600 A 385
748 603
25 kA
Isc 31.5 kA Insulating partitions (only for 24 kV)
to be provided by the customer
40 kA (a special kit is available on request).
16 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA
—
7. Installation
7.9. Overall dimensions
600 451,5
HD4 2XM8 depth 16
581 420
M12 depth 25
TN 1VCD000235 210 210 87 356,5 13,5
Ur 24 kV 103,5 103,5
67,5
630 A
Ir
1250 A
27
16 kA
Isc 25 kA
670
310
31.5 kA
695
623
27
63
468
231
43
302,5
730
HD4
705 2XM8 depth 16 M12 depth 25
451,5
TN 1VCD000237 275 275
87 356,5 13,5
67,5
Ur 24 kV
630 A 27
Ir
1250 A
16 kA
310
Isc 20 kA
27
695
25 kA
623
63
468
302,5
231
HD4 730
708
TN 7174
275 275
Ur 24 kV
Ir 1600 A
31.5 kA
Isc
40 kA 2x Ø18
310
310
80
HD4
28
TN 7174 15.5 32
622
655
Ur 24 kV YU
8
Ir 2000 A YU
25 kA 8
306.5
266.5
Isc 31.5 kA Q6
0
Ø 13
40 kA
43
20
728 322
35
385
748 561
HD4 400
880
358
with truck 350 350 10
Ø 22
(on request) 50
TN 7241
Ur 36 kV
630 A
362
Ir 1250 A Ø 22
729.5
28
712
639. 5
1600 A
539
16 kA
10
Isc
* 106 0
342.5
20 kA 21
302.5
(if provided).
755
2x Ø 10.5 120
881 363.5 270
43
901 695.4 37
*4.9
* 348
*Ø 13
* 855 * Ø 13 * 200
* 355 *85
*4
* 915 *40
* 955 * 516.4
18 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA
—
7. Installation
7.9. Overall dimensions
HD4 730
708
with truck
(on request)
TN 7268
Ur 36 kV
1250 A
Ir
1600 A
25 kA
Isc
31.5 kA
HD4
with truck
(on request)
TN 7268
Ir 2000 A
20 kA
Isc 25 kA
31.5 kA
HD4
with truck
(on request)
TN 7315
Ur 36 kV
Ir 2000 A
20 kA
Isc 25 kA
31.5 kA
HD4/P
496 125
10
TN 1VCD000227 30 203 119 9
12 kV
Ur
17.5 kV
630 A
98,5
Ir
1250 A
16 kA
205 ±1
35
586
Isc 25 kA
619 ±2
619
622,5
31.5 kA
541
Also suitable for
PowerCube PB1
260 ±1
154 ±1
19,5
340
4
21,5
4
503 25 320
531 370
501 416 53
492
456 ±2 437 0 + 2
150 150 558
661
608
55
20 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA
—
7. Installation
7.9. Overall dimensions
HD4/P 636
640
579
TN 7350 210 ±1 210 ±1 119
12 kV 272
111.5 17
Ur 44
10
17.5 kV
Ir 1250 A
Isc 40 kA
Ø 79
68
Ø 122
HD4/P 67.5
310 ±1
TN 7350
12 kV
691
Ur
688
686
668.5
17.5 kV
63
Ir 1600 A
543
25 kA 53.5
280 ±1
31.5 kA 40
Isc
245
164.5 ±1
89
40 kA (*) 21
Ø 19.5
50 kA (*) 20
550 4
21.5
(*) A lso suitable for 29 359
4
4
HD4/P 636
640
579
TN 7351 210 ±1 210 ±1 119
12 kV 272 111.5 17
Ur 44 10
17.5 kV
Ir 2000 A
25 kA
31.5 kA
Isc
Ø 79
68
Ø 122
40 kA (*) 67.5
310 ±1
50 kA (*)
688
686
669
PowerCube PB2.
63
543
53.5
280 ±1
40
245
164.5 ±1
89
21
Ø 19.5
20
4
550
21.5
359
4
29
4
626 ±2
416
653 36 551 ±1.5 53
682
D I S T R I B U T I O N S O LU T I O N S 21
HD4/P 842
643
TN 7352 (*) 708
119
375
12 kV 111.5 17
Ur 275 ±1 275 ±1
17.5 kV 144
10
Ir 2500 A
25 kA
31.5 kA
Isc
Ø 109
40 kA
Ø 152
67.5
310 ±1
50 kA
688
691
686
668.5
PowerCube PB3.
58
63
43.5
280 ±1
30
245
89
21
164.5 ±1
Ø 19.5
750 4
21.5
4
4
29 359
806 ±2
416
853
36 554 ±1.5 53
882
HD4/P 842
708 643
TN 7371
375
12 kV 96.5 17
Ur 275 ±1 275 ±1
10
17.5 kV
Ir 3150 A (*)
25 kA
31.5 kA
Isc
40 kA
Ø 109
Ø 152
50 kA 67.5
310 ±1
732
switchgear ventilation
730
technical catalogue).
43.5
30
280 ±1
245
89
164.5 ±1
21
Ø 19.5
4
21.5
750 29 359
4
806 ±2 416
853 36 554 ±1.5 53
882
22 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA
—
7. Installation
7.9. Overall dimensions
HD4/P 636
210 ±1 210 ±1
TN 1VCD000236 119 24
276
20
Ur 24 kV 44
630 A
Ir
1250 A
16 kA (*)
Isc 20 kA
25 kA
310 ±1
(*) 6 30 A only.
35
772,5
766,5
768
717
645
63
325 ±1
254,5
125
198 ±2
461 ±1
4
610 ±2
697 53
653
746 ±1,5
681
HD4/P 641
799
578
TN 1VCD000099 210 ±1 210 ±1 23
Ur 24 kV 272
67.5 44
Ir 1250 A
20
Isc 31.5 kA
Ø 92.6
310 ±1
28
Ø 35
792
776
718
682
63
8
329 ±1
25.5
293
125
10
202 ±1
550 4
Ø 19.5
21.5
610 ±2 460
653 36 710 ±1.5 53
682
D I S T R I B U T I O N S O LU T I O N S 23
20
Ur 24 kV 144 232 19
Ir 1600 A
16 kA
20 kA
Isc
25 kA
Ø 79
31.5 kA
Ø 122
67.5
310 ±1
(*) A lso suitable for
PowerCube PB5. 58
817.5
814
807
733
63
700
43.5
345 ±1
30
310
125
11
198 ±1 4
806 ±2
4
4
457
853
882 36 699 ±1.5 53
20
Ur 24 kV 19
144 232
Ir 2000 A
Isc 16 kA
20 kA
Ø 79
25 kA
31,5 kA
Ø 122
67.5
310 ±1
HD4/P 58
814
817.5
TN 7356 (**)
807
733
Ur 24 kV
63
700
Ir 2500 A (*)
Isc 20 kA 43.5
25 kA
345 ±1
30
310
125
31,5 kA
198 ±1
11
750
21.5
4
4
457
4
ventilation. 806 ±2
(**) A lso suitable for 853 36 699 ±1 53
PowerCube PB5.
882
24 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA
—
7. Installation
7.9. Overall dimensions
HD4/W 119
636 111,5
TN 1VCD000228 44 228 63 15
10
12 kV
Ur
35
17.5 kV
630 A
Ir
1250 A
16 kA
310 ±1
Isc 25 kA 28
688
31.5 kA
691
692
640
280 ±1
89
165 ±1
550 +2
19,5
21,5
359 0
4
626
653 416
681 539
587 ±1,50 53
210 ±1 210 ±1
586,5
55
D I S T R I B U T I O N S O LU T I O N S 25
HD4/W 636
578
56
TN 7421 210 ±1 210 ±1
44 228 63 15
12 kV
10
Ur
17.5 kV
Ir 1250 A
40 kA
Ø 35
Ø 79
Isc
50 kA 67.5
310 ±1
28
688
688
691
636
63
16
280 ±1
245
89
165 ±1
4
Ø 19.5
626 ±2
21.5
4
4
29 359 40
653
416
682 36 551 ±1.5 53
640
HD4/W 636
578
TN 7239
210 ±1 210 ±1
56
12 kV 272
Ur 63 15
44
17.5 kV
1600 A
10
Ir
2000 A
16 kA
Isc 25 kA 67.5
310 ±1
31.5 kA 28
698
691
668.5
635.5
63
8
Ø 122
Ø 79
280 ±1
245
89
165 ±1
4
Ø 20
550
4
21.5
4
29 359 40
626 ±2
653 36 551 ±1.5 53
682 640
26 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA
—
7. Installation
7.9. Overall dimensions
HD4/W 842
708
TN 1VCD000053
375 643
12 kV 275 ±1 275 ±1 112 16
Ur
17.5 kV 144
10
Ir 3150 A
31.5 kA
Ø 109
Isc 40 kA
50 kA
Ø 152
67.5
310 ±1
742
730
730
732
58
63
43.5
280 ±1
30
245
164.5 ±1
89
21
Ø 19.5
750 29 359
21.5
4
806 ±2 416
853
36 554 ±1.5 53
882
D I S T R I B U T I O N S O LU T I O N S 27
Withdrawable circuit breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module
20
Ir 1250 A
20 kA
Isc
25 kA
Ø 35
380
78
941.5
949
952
833
63
60
44
480
198
345
10
125
198
805 4
4
457
836
36 699 53
853
882
Withdrawable circuit breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module
HD4/W 842
730
TN 7316 706 18
23
Ur 36 kV 275 275
Ø 35
Ir 1250 A
Isc 31.5 kA
380
953
956
973
484
125
202
805 4
456
836
30 701 57
853
882
28 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA
—
7. Installation
7.9. Overall dimensions
Withdrawable circuit breakers HD4/W for UniGear type ZS2 switchgear and for PowerCube module
20
Ur 36 kV 67.5 144 232
1600 A
Ir 2000 A
2500 A (*)
Ø 122
Ø 79
20 kA
380
Isc 25 kA
31.5 kA 78
949
903.5
833
63
60
44
480
345
125
10
198
21.5
750
Ø 20
4
4
805 457
836 36 699 53
853
882
HD4/Z withdrawable circuit breakers for UniGear type ZS3.2 - 40.5 kV switchgears
HD4/Z/40,5 kV
840 245
TN 7227 280 280
Ur 40,5 kV
1250 A 385
1600 A 2÷5
Ir
2000 A
2500 A (*)
25 kA
328
Isc
31,5 kA
ØA
forced ventilation in
switchgear type
1288.5
ZS3.2.
27
15
Ø 20
100
50
900
23 23
30 40
550
43 43
485
22
Ø 16
Ø 18
120
85
80
32.5 45 103
ØA 140 150
100
25 230 200
1250-1600 A 35 mm
718 503
2000-2500 A (*) 79 mm
760 582
D I S T R I B U T I O N S O LU T I O N S 29
25
229
630 A
Ir
45°
1250 A
1
169 kA
Isc 68
79
20 kA
310 ±1
739
35
A
644,5
734,5
435,5 ±2
63
36 8
325 ±1
254
653 25 320
19
4
681 370
382 4
650 414
210 ±1 210 ±1 687 ±1,5 53
19,5
36,3
25
55
DETAIL A
SCALE 1 : 2
30 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA
—
8. Putting into service
8.1. General procedures
All the operations regarding putting into Before putting the circuit breaker into service carry
service must be carried out by ABB out the following operations:
personnel or customer personnel who are • check the tightness of the power connections on
suitably qualified and have an in-depth the circuit breaker terminals;
knowledge of the apparatus and • establish the setting of the direct solid-state
installation. overcurrent release (if provided);
If the operations are prevented, do not • check that the value of the supply voltage for the
force the mechanical interlocks, but auxiliary circuits is within 85% and 110% of the
check that the operation sequence is rated voltage of the electrical devices;
correct. • check that no foreign body, such as packaging, has
The operating forces which can be got into the moving parts;
applied are indicated in paragraph 6.3. • check that air circulation in the circuit breaker
installation site is adequate so that there is no
danger of overheating;
• carry out the checks indicated in the following
table:
—
9. Periodical checking
Before carrying out any operation, make sure that the operating mechanism springs are
discharged and that the apparatus is in the open position.
9.1. General
During normal service, the circuit breakers are maintenance-free. The frequency and sort of inspections
basically depend on the service conditions. Various factors must be taken into account: frequency of
operations, interrupted current values, relative power factor and the installation ambient.
The following paragraph gives the checking programme table, showing the relevant time intervals.
As far as the time interval between these operations is concerned, it is advisable to comply with
specifications given in the table, at least during the first check. On the basis of the results obtained
during the periodic inspections, set the optimal time limits for carrying out the following operations.
After 10,000 operations or after 10 years, for installation in polluted and aggressive ambients, it is advisable
to contact an ABB service center to have the circuit breaker checked.
—
10. Maintenance operations
Maintenance must only be carried out by ABB personnel or in any case by suitably qualified
customer personnel who have in-depth knowledge of the apparatus (IEC 62271-1 para 10.4.2).
Should the maintenance by carried out by the customer’s personnel, responsibility for any
interventions lies with the customer.
Replacement of any parts not included in the “List of spare parts/accessories” must only be
carried out by ABB personnel.
In particular:
• Complete pole with bushings/connections
• Operating mechanism
• Closing spring unit
• Opening spring.
D I S T R I B U T I O N S O LU T I O N S 33
—
11. Indications for handling apparatus with SF6 6
SF6 in its pure state is an odourless, colourless, non- The Electric Industry is reported as the most
toxic gas with a density about six times higher than important user of SF6, worldwide. In spite of being
air. For this reason, although it does not have any the most important user of SF6, the Electric Industry
specific physiological effects, it can produce the is a low contributor to the global emission of SF6, far
effects caused by lack of oxygen in ambients below to other industries or users with “open
saturated with SF6. application” of the gas. However, its importance as
During the interruption phase of the circuit breaker, source substantially varies from region to region and
an electric arc is produced which decomposes a very from country to country, depending on the SF6
small amount of SF6. The decomposition products handling procedures adopted, the tightness of the
remain inside the poles and are absorbed by special electric power equipment and the amount of gas
substances which act as molecular sieves. The banked in electric equipment.
probability of contact with decomposed SF6 is For info about Life Cycle Assessment of apparatus,
extremely remote, and its presence in small see document (1VCP000264).
quantities (1-3 ppm) is immediately noticeable To dispose of the SF6 gas, please contact the ABB
because of its sour and unpleasant smell. In this case, Assistance Service (see contact persons at http:
the room must be aired before anybody enters it. //www.abb.com/ServiceGuide/alphabetical.aspx) as
The strong infrared absorption of SF6 and its long this operation must be done only by trained and
lifetime in the environment are the reasons for its qualified personal; on request are available specific
high Global Warming Potential (GWP) which is 22.800 instructions for the evacuation of the SF6 gas from
higher than CO2, according to the Fourth Assessment the apparatuses.
Report. The volume of SF6 in each apparatus is indicated on
The GWP is calculated over a time period of 100-years the nameplate.
warming potential of 1 kg of a gas referred to 1 kg of
CO2. Its overall contribution to the global greenhouse
gas effect from all applications amounts to
approximately 0,2% overall.
However, the GWP of SF6 alone is not adequate to
measure the environmental impact of electric power
equipment based on SF6 technology.
The environmental impact of any specific application
should be evaluated and/or compared using the Life
Cycle Assessment – LCA approach as regulated by ISO
14040.
The Electric Industry utilises SF6 in a closed cycle,
banking it e.g. in gas insulated substations (GIS),
medium-voltage and high-voltage gas circuit
breakers (GCB), high-voltage gas insulated lines (GIL),
gas insulated voltage transformers (GVT). In Asia,
significant quantities of SF6 are banked in gas
insulated power transformers (GIT) as well.
34 H D 4 - I N S TA L L AT I O N A N D S E R V I C E I N S T R U C T I O N S 1 2 - 4 0 . 5 k V – 630-3600 A – 16-50 kA
—
12. Spare parts and accessories
All assembly operations of spare parts/ 12.1. List of spare parts
accessories
• Shunt opening release
regarding installation, putting into
• Additional shunt opening release
service, service and maintenance must
• Undervoltage release
be carried out by ABB personnel or
• Contact signalling undervoltage release
suitably qualified customer personnel
energised/de-energised
with in-depth knowledge of the
• Undervoltage release delay device
apparatus (IEC 62271-1 para. 10.4.2).
• Mechanical exclusion device for undervoltage
Should the maintenance by carried out by
release
the customer’s personnel, responsibility
• Shunt closing release
for any interventions lies with the
• Spring charging geared motor with electric
customer.
signalling of springs charged
Before carrying out any operation, check
• Geared motor thermomagnetic protection circuit
that the circuit breaker is open, the
breaker
springs discharged and that there is no
• Contact signalling geared motor protection circuit
voltage (medium voltage circuit and
breaker open/closed
auxiliary circuits).
• Contact signalling closing springs charged/
discharged
To order accessories or spare parts, please refer to • Transient contact with momentary closure during
the commercial ordering codes given in the circuit breaker opening
technical catalogue and always indicate: • Auxiliary circuit breaker contacts
• circuit breaker type • Locking electromagnet on operating mechanism
• circuit breaker rated voltage • Position contact of withdrawable truck
• circuit breaker rated thermal current • Contacts signalling connected/isolated
• circuit breaker breaking capacity • Opening solenoid
• circuit breaker serial number • Key lock in open position
• rated voltage of any electrical accessories. • Isolation interlock with door
For availability and ordering of spare parts please • Protection for opening pushbutton
contact our Service department.e. • Protection for closing pushbutton
• Locking electromagnet on withdrawable truck
• Sliding earthing contact of withdrawable truck
• Opening/closing knob
• Set of six tulip contacts
• SF6 gas pressure monitoring device.
D I S T R I B U T I O N S O LU T I O N S 35
—
For further details please contact:
—
More product information:
abb.com/mediumvoltage
Your contact center:
abb.com/contactcenters
More service information:
abb.com/service
The data and illustrations are not binding. We reserve the right to modify the
contents of this document following technical developments.