! CAUTION
System must be de-energized and fully grounded before installation can begin.
INSTALLATION
IMPORTANT:Read these instructions thoroughly before operating the system. Be sure that the
connectors are rated for the intended energized use. (See Hubbell Catalog or Technical Data Sheets for
selecting the correct mating connector module.) Visually inspect parts for damage before using them.
• Clean and lubricate 200 amp interface (LRTP) and mating connector, i.e. insulating cap,
grounding elbow, loadbreak elbow, elbow arrester. Use lubrication supplied. Do not substitute.
Install mating connector and ground all shields using #10 copper wire. Connect the #10 copper
wire from ground tabs of LRTP, mating connector, and 600 amp elbow to common ground point.
Leave adequate slack for hotstick operation.
®