Inductive voltage transformer type EMF

Product information EMF 52 - 84

This brochure contains information about our ABB’s inductive voltage transformers are
updated inductive voltage transformer EMF intended for connection between phase and
52-84, that will replace earlier model EMFC ground in networks with insulated or direct-
52-84. Some information regarding design and grounded neutral points.
technical data, by that, replaces those in our
Buyer’s Guide Ed 4.

Brief Performance Data


Installation Outdoor
Design Inductive type
Insulation Oil-paper-quartz
Highest voltage for
52 - 84 kV
equipment
Voltage factor (Vf) Up to 1.9/8 hrs
Porcelain
Insulators
(On request silicon rubber)
Creepage distance ≥ 25 mm/kV
(Porcelain) (Longer on request)
Service conditions
Ambient temperature -40˚C to +40˚C
(Others on request)

Design altitude Maximum 1000 m


(Others on request)

Tank, expansion system and insulator Secondary terminal box and terminals
Tank and expansion vessel consists of selected Secondary terminals accept wires with cross-sections
aluminum alloys that give a high degree of resistance up to 10 mm2.
to corrosion, without the need of extra protection. Protection class for the terminal box is IP 55.
Anodized details can be offered on request.
The insulator, in its standard design, consists of Primary Terminals
high quality, brown glazed porcelain. The voltage EMF 52-84 is as standard equipped with an aluminum
transformers can also be supplied with silicone rubber bar terminal, suitable for IEC specifications.
insulators.
The sealing system consists of O-ring gaskets. The
seals are under the oil level, which prevents drying and
leakage.
Design data and dimensions
Test Voltages IEC 60044-2, (IEC 186)
Type Highest voltage for equipment 1min LIWL RIV test Max RIV
(Um) wet/dry 1.2/50 µs voltage level
kV kV kV kV µV
EMF 52 52 95 250 30 125
EMF 72 72,5 140 325 46 125
EMF 84 84 150 380 54 125

Test voltages above are valid for altitudes < 1000 meters above sea level.

Test Voltages IEEE C 57.13 (CAN 3 – C 131 – M83)


Type Highest voltage for equipment AC-test AC-test BIL

Appendix to catalogue publication 1HSM9543 42-00en, Outdoor Instrument Transformers Buyer’s Guide, Edition 4, 2006-01
(Um) dry, 1 min wet, 10 sec 1.2/50 µs
kV kV kV kV Max.
EMF 52 52 95 95 250
EMF 72 72,5 140 175 350
EMF 84 84 150 175 380

Test voltages above are valid for altitudes < 1000 meters above sea level.

Dimensions EMF 52 - 84
A B C D E F
Type Total height Flash-over Height to Fixing hole Ground plane Expansion vessel
distance terminal box dimensions height diameter

mm mm mm mm mm mm
Information with
EMF 52, 72 and 84 1464 630 335 x 335 580 324
offer/order

Nominal Flash-Over and Creepage Distance �

Normal porcelain (min. nom. values)

Typ Flash-over Creepage Protected creepage


distance distance distance
mm mm mm
EMF 52 630 2248 950
EMF 72 630 2248 950

EMF 84 630 2248 950




�����
� �

EMF 52 - 84
ABB Power Technologies Note: Primary terminal will be mounted at site
High Voltage Products
SE-771 80 LUDVIKA, Sweden
Tel +46 240 78 20 00
Fax +46 240 78 36 50
NOTE: ABB Power Technologies AB is working continuously to
E-mail: instr.transf@se.abb.com improve the products. We therefore reserve the right to change
Internet: http://www.abb.com designs, dimensions and data without prior notice.