Sie sind auf Seite 1von 8

Concrete Repair, Rehabilitation and Retrofitting II – Alexander et al (eds)

© 2009 Taylor & Francis Group, London, ISBN 978-0-415-46850-3

Assessment of post-fire reinforced concrete structures: Determination


of depth of temperature penetration and associated damage

C. Alonso
Institute of Construction Science Eduardo Torroja, Madrid, Spain

ABSTRACT: The assessment of concrete structures affected by the fire should allow understanding what
happened during fire and developing rational criteria for the evaluation of the security of the structure. The
result of the assessment should be used to take the decision on further repair, partial or total demolition of the
structure. Two main goals to be answered during the assessment analysis are: 1) The determination of the depth
of concrete exposed to temperatures that produce irreversible alteration of concrete components, and 2) the
mechanical strength decay of concrete that can affect the load bearing capacity of the element or the structure
itself. The assessment of the integrity of a concrete structure in the post fire situation involves addressing the
damaged of each component. To differentiate between concrete chemically affected by the fire or physically
damaged is an important issue. In this paper the depth of concrete of a structure exposed 48 h in fire and a tall
building, >100 m (Windsor Tower) 18 h exposed to fire are used as examples of real fires. In-situ inspection
and laboratory tests of concrete components have been performed. The heterogeneity in the distribution of the
damage is identified and the depth of concrete affected by the fire is determined.

1 INTRODUCTION at each specific temperature. Due to these reasons


strong thermal gradients appear, that induce internal
Reinforced concrete is considered a material that mechanical pressures in the concrete mass, which
shows an acceptable resistance to high temperatures, allows the development of cracks both during heat-
which allows using concrete elements without the ing and cooling, Chan et al (2000). Besides, when the
need of any additional protection. However, long temperature gradients are high, the pressures accumu-
periods of exposition of reinforced concrete to high lated inside the pores increase due to the water vapour
temperatures introduce physical-chemical changes in evolution, so the risk of spalling of external concrete
its properties that lead to mechanical strength decay layers is possible, leaving new surfaces of concrete
which produces losses in the safety of the structure, exposed directly to the external high temperatures of
(Piasta et al (1984a), Alonso & Fernandez-Municio, the fire, Bazant & Kaplan (1996).
(2004, 2008) . The physical-chemical transformations that take
The assessment of deteriorated concrete structures place in concrete components during fire are well
after fire is needed in order to identify the level of known and also very well addressed when the charac-
damage induced by the chemical and physical proc- terisation is made in the laboratory in concrete sam-
esses taking place, in all the components at high tem- ples that have been allowed to reach the steady state at
peratures and also during cooling, which contribute each temperature; an acceptable correlation with loss
to the loss of mechanical strength, Tay & Tam (1996), of mechanical properties is found, Rostasy et al (1987).
Khoury (1992), Chan et al (2000). The residual struc- It is more difficult to assure a good correlation of
tural capacity has to be accurately addressed when the real fire scenarios using equivalent time curves from
safety of the structure is in risk, in order to define codes and the level of damage in concrete, Schneider
the best strategy for repairing or to decide on its (1990). However, it is more complicated when the
demolition. fire takes place in a real structure, as many factors are
The low thermal diffusivity of concrete guarantees contributing to the damage and no clear relationship
a slow propagation of the chemical transformations can be found between the maximum temperature and
of the components of concrete, paste and aggregates, the residual concrete strength or load bearing capacity
which also need time for fully developing conversions of the structure.

471
The most common requirement for in-situ scenarios of fire are considered, one underground
investigation is the estimation of concrete strength, structure 48h in fire and a tall building, Windsor
through the assessment of defined properties, adopt- Tower, 18h in fire. In-situ inspection and labora-
ing the criteria that variations in strength are taking tory tests have been performed. The heterogeneity in
place between non affected and damaged concrete. the distribution of the damage is identified, and the
The assessment of the residual capacity of concrete depth of concrete affected by the fire is determined,
structures exposed to fire is a quite complex task, that has allowed identifying the gradient of tempera-
mainly due to the heterogeneity of the concrete, but tures reached in the concrete. The depth of concrete
also associated with the irregular distribution of the for the critical temperature of 500°C has been deter-
damage induced by the fire. The possible approach mined. Finally, a protocol for assessment of con-
is to find an average response of the concrete cover crete structures affected by fire is given including
both using destructive and non destructive analysis, in non destructive and destructive methods and micro-
order to interpret the overall response of the concrete macrostructure analyses of the damage.
after fire, Feliceti (2008).
In-situ non-destructive techniques are widely
employed for distinguishing between damaged and
apparently non affected areas of concrete elements, 2 DESCRIPTIONS OF THE STRUCTURES
such as resilience, hammer-tapping, ultrasonic pulse
etc. Benedeti (1998), Benedetti & Mangoni (2004a), The Windsor Tower in Madrid, >100 m tall, was
Fellicety (2004), Calavera et al (2005), Colombo & involved in a major fire on the 13th of February 2005,
Felicetti (2006). of 18 hours duration. The fire caused an extensive
However, the determination of the penetration structural damage of the upper floors of the building.
of the damage and the differentiating between the The fire of this building caused intense interest
type of damage (chemical, physical or mechanical) among researchers seeking a better understanding
are important to ascertain the consequences of the of the performance of concrete structures under fire,
thermal gradients, which require the use of concrete due to the nature of the construction of the building,
cores for laboratory testing, usually for mechanical a large concrete frame with steel perimeter columns.
strength, petrography analysis and thermal alteration The standard structure of the tower was built around
of cement paste. a central reinforced concrete core, with columns of
More feasible methods are being adopted, includ- 50 × 220 and 50 × 180 cm size, that housed lifts and
ing infra-red thermal imaging, digital camera colori- stairways, Calavera et al (2005), Fletcher et al (2006).
metric etc., Fellicety (2004b), Colombo & Felicetti The other type of building construction considered
(2006), Short & Purkiss (2004), Zhang et al (2002). was an underground power station for distribution of
Chemical analysis of cement paste, e.g. thermo- electricity, containing three basements. The roof of
gravimetric, TG and X Ray Diffraction tests, are the first basement was built with prestressed beams.
also employed in order to determine the alteration of A reinforced concrete slab 3 m thick was constructed
hydrated cement paste components that are related to between the second and third basement. Each floor
mechanical strength decay, Alonso (2006a,b), Alonso has columns with different dimensions, 250 × 30 × 35
& Fernandez-Municio (2007). Also, attempts have and 250 × 30 × 50 cm, spaced 4 to 5 m. Some inter-
been made to assess cracking using petrographic secting concrete beams, 35 × 30 × 600 cm, complete
thin sections and Scanning Microscopy, SEM, Tay & the structure. The fire was initiated in the first base-
Tam (1996), Rilley (1991), Piasta (1984b), Cioni et al ment and reached the second and third basements.
(2001). Alonso et al (2005). In Alonso (2006a) the The duration of the active fire in the third basement
identification of indicators of damage to assess rein- was 48 hours.
forced concrete structures affected by fire is consid-
ered, and a protocol to identify the level of damage in
the concrete is given. 3 IN-SITU INSPECTION OF POST-FIRE
However, the isolated use of any method does not CONCRETE STRUCTURES
give reliable results because of the gradient and non-
homogeneity of the damage that cause differences
3.1 Visual inspection
between the external and internal strength. In addition
the assessment of post-fire reinforced concrete struc- Visual inspection was used to assess apparent dam-
tures is complex due to the overlapping of chemical age, for instance the distribution of zones of explod-
and physical phenomena inducing different type of ing concrete, as those shown in figure 1, in beams and
damages, Alonso (2006a,b). slab of the underground structure. Also the corners of
In this paper the assessment of damage of concrete the columns are weak points for explosion, as shown
in post-fire structures that have suffered different in figure 2.

472
to the fire, 2) followed by a sudden increase of the
temperature of the wire, and 3) breaking some wires
due to loss in ductility of the steel. Also some brit-
tle fracture in reinforcements, as shown in figure 2,
indicates that the temperature has reached values
>500°C.

3.2 Non-destructive in-situ testing


The most employed ND method for assessing the
extension of the damage of concrete structures after
fire is the ultrasonic pulse velocity. The ultrasound
Figure 1. Damage in concrete elements after fire, spalling
in prestressed and reinforced beams and in concrete slab.
pulse test performed on the columns of the under-
ground structure pointed out the heterogeneities in
the damage within the column itself and between col-
umns, as shown in figure 3. The ultrasound rate varies
with: a) the height of the column, indicative of the
heterogeneous distribution of the damage, b) the pres-
ence of cracks and c) the distance to the crack. These
measurements put in evidence that sharp variations
in cracking intensity correspond well with low ultra-
sound rate measurements, however, the penetration of
the damage and the depth of chemical alteration com-
ponents due to fire cannot be deduced directly from
these measurements.

3.3 Concrete and reinforced samples


Cores of concrete in the selected zones defined from
in-situ test should contribute to the final determina-
tion of the damage penetration. The extraction of a
full core is, in most of the cases, quite complicated
Figure 2. Damage in a corner of the columns of the Wind- due to the gradient of damage, chemical alteration
sor Tower. Changes in colour and break of aggregates, oxide and generation of cracks. The observation inside the
layer covering the external bars and brittle fracture in a stir- hole of the column, after the core extraction, can help
rup (Calavera et al (2005)). to identify the propagation of cracks, as those shown
in figure 4-left.
The carbonation depth should be also determined
One concern in the inspection is to identify the in-situ at different points of the structure and in the
moment of the different explosions, if they occurred cores, using phenophtalein indicator, in order not
during fire, at high temperature, or during cooling. to misunderstand with portlandite transformation
Although this is not an easy task from a simple obser- induced by the fire, Alonso (2006a,b).
vation, some aspects in the concrete can help: The
pink colour change in the paste and siliceous aggre-
gates of the concrete of Windsor Tower suggested a 4000
temperature in the area around 800–900ºC, Alonso 3500
(2006b). Besides, the explosion zones can leave the 3000
Rate (m/s)

reinforcement exposed, if it is fully covered with a 2500


layer of oxide of brown-red or black colour, is typical 2000 1-Heavy cracked
of corrosion induced at high temperature, >500ºC. 1500 3-cracks<0.1

The pretressed beams, which are very sensitive to 4-No cracks


1000
2-cracks<0.1
fire and temperature gradients, can be subjected to 500
5-heavy cracked
explosions that partially or totally destroy the beams, 0
0 50 100 150 200 250
including breaking the presetressed wires. The explo- Column Height (cm)
sion could develop in several steps: 1) first a concrete
explosion due to thermal and pore pressure stresses Figure 3. Ultrasound pulse velocity variation in columns
in concrete that leaves the wires exposed directly of the underground building. Effect of cracking and height.

473
5
Floor P12
Floor P13
4 Floor P19
Floor P14
3

% CSH
2

Figure 4. Concrete core from a column and hole showing 1


cracks (left). Steel wire covered with oxide and brittle frac-
ture due to high temperature exposition (left).
0
0 5 10 15
Depth (cm)
Reinforcement samples should be obtained to
determine the loss of mechanical properties and the Figure 5. Depth of cement paste alteration at several con-
embrittlement, as shown in figure 4 (right). crete depths, from TG tests.

4 MECHANICAL AND CHEMICAL


CHANGES IN CONCRETE SAMPLES

Concrete samples should help to determine the


mechanical strength and to identify the temperature
depth penetration that has induced chemical changes
in concrete components.

4.1 Mechanical strength losses Figure 6. Microscopy of cement paste and aggregate alter-
ation due to fire.
The determination of the mechanical losses due to the
action of fire is a complicated task, as the damage
does not distribute homogenously. Besides, a gradient SEM was used to confirm the type of damage. In
of concrete with different levels of alteration of chem- the case of the concrete from the prestressed beams
ical components exists. In addition, most of the time of the underground building, intense micro crack-
it is not possible to get a full core, as the case shown ing in the mass of the concrete was observed, both in
in figure 4, with the external zone broken; however aggregates and cement paste, figure 6 (left); but the
the inner part can be used for the determination of cement paste did not show chemical alteration. These
mechanical strength of the mass of the concrete not damages are attributed to the explosions due thermal
affected by the fire. and pore pressures accumulated inside the concrete
(Alonso, 2006a).
4.2 Methods for the determination of chemical The Backscattering Microscopy allowed identify-
and physical transformations in cement paste ing the degradation of cement paste and aggregates;
loss of density of the material and bond between
The CSH gel of hydrated cement paste is the main paste and aggregates are indicative that the depth of
component and responsible for mechanical strength, the concrete has been exposed to temperatures above
Alonso & Fernandez-Municio (2008). The dehydra- 350°C, figure 6 (right). The presence of ettringite
tion of CSH identified with the TG test at a weight crystals indicate that the temperature reached values
loss between 100 to 350°C does not take place at below 100°C at a specific depth, Alonso (2006b).
ambient temperature, as happens with portlandite The micro-hardness measurements in cement
transformation due to carbonation, Alonso (2006a,b). paste have allowed differentiation between different
The CSH transformation allows identifying the depth damaged zones and quality of concretes. The poros-
of concrete exposed to temperatures up to 350ºC, as ity has contributed; although to a lesser extent, to dif-
shown in figure 5 for columns of the Windsor Tower ferentiating between levels of damage. Increases in
of different floors, given a maximum depth for CSH porosity are generally associated with dehydration
transformation up to 3 cm, while in the underground processes, but also due to the formation of microc-
building up to 7 cm, Alonso (2006a,b). racking, Alonso (2006a,b).

474
5 ANALYSES OF THE METHODOLOGIES 1000
FOR ASSESSMENT OF FIRE CONCRETE 900
DAMAGE
800

Although there are several techniques to determine 700


the depth of concrete altered by the temperature, their 600

Tª ºC
use alone do not allow accurately determining the 500
depth of concrete affected by the fire, and some of
400
them are not able to discriminate between the type of
damage, physical or chemical. None of the methods, 300
neither NDT nor DT is able to determine the loss of 200
mechanical strength even with the direct measure-
100
ment of the strength, because of the presence of a
gradient of damage in the concrete elements. 0
0 2 4 6 8 10 12
Measurement of the ultrasound velocity has the Depth (cm)
advantage of a NDT technique able to differentiate
among damaged and non-damaged zones. However, Figure 7. Mean temperature depth in concrete columns
the determination of the depth of concrete cover exposed to fire of Windsor Tower.
affected is difficult from this method, as the ultra-
sound velocity variation in a fired concrete structure
400
changes not only due to the dehydration of cement
paste, but also because of the crack formation; how- 350
ever, the presence of cracks does not necessarily mean
900
a fire alteration of the concrete components; in fact, 300 700
most of cracks are due to the thermal stresses during
fire, Alonso (2006a). 500
250
Ultrasound velocity measurements taken in Calavera
Cover (mm)

300
et al (2004) in Windsor Tower showed that the direct 200 100
ultrasound velocity measurement data did not always
allow discriminating with respect to the depth of 150
damage, and laboratory tests on cores were needed
to calibrate the measurements on-site to give an over- 100
estimation (up to a depth of 10 cm) of the depth at
which the compressive strength of the concrete was 50
considered irreversibly affected.
Microscopic techniques allow differentiating bet- 0
0 50 100 150 200 250
ween the microstructure changes in the paste, aggre- Cover (mm)
gates, the interface bonding loss and the cracking,
but experience is needed to identify the origin of the Figure 8. Isotherm in concrete columns of Windsor Tower
damage. exposed to fire. Determination of the depth of isotherm
Thermo-gravimetric tests are able to identify 500°C.
the local chemical changes in cement paste and the
level of dehydration of CSH, which is the compo- The damage induced by the fire in the concrete
nent responsible for concrete strength development. elements is very heterogeneous; the reason is attrib-
Variations in CSH transformation and microstructure uted to the fact that in a real scenario the fire is not
changes in concrete elements from different floors of homogenous within the structure, and even within the
the Windsor Tower indicated that the alteration of con- same floor or column. The surface temperature varies
crete due to fire penetrated up to a maximum of 3 cm, between one place and another and also the duration
Alonso (2006b), which did not agree with the values of the intensity of the fire, so that the effect of the
predicted in Calavera et al (2005). Figure 7 shows the concrete damage also will be different. In the case of
concrete depth of temperature penetration determined Windsor Tower the extension of the damage varied
from microstructure testing. from one floor to another, i.e. in floors 12 to 19 the
Relationships have been found between several differences were very relevant and the results showed
indicators of concrete damage, including micro- that in the higher floors the depth of concrete affected
hardness, porosity and CSH transformation. A transfor- by the fire did not penetrate more than 1.5 cm, while
mation of at least 55% CSH is needed to induce in the lower floors the penetration of damaged reached
relevant changes in the other properties, Alonso (2006). a depth of 3 cm.

475
Finally the isotherms of the temperature depths Alonso, C. 2006b. Influence of fire in the damages of
inside the concrete columns were drown (figure 8), concrete in the Windsord Building. Int Cong on Fire
and in particular the isotherm for the depth of 500°C safety in tall buildings. Santander, Spain: 111–127.
was determined, which can be used for further calcu- Alonso, C. & Fernandez-Municio, L., 2008. Dehydration
and rehydration processes in cementitious materials after
lation of residual load bearing capacity. fire. Correlation between micro and macrostructural
transformations. fib workshop on Fire design of concrete
structures. Coimbra: in press.
6 CONCLUSIONS Bazant, Z.P. &. Kaplan, M.F. 1996. Concrete at high tem-
peratures: Material properties and mathematical mod-
The use of a set of tests allows differentiating between ells. Logman Grp. Ltd., England .
several levels of damage and to identify indicators of Benedeti, A. 1998. On the ultrasonic pulse propagation into
damage in post-fire structures. fire damaged concrete, ACI structural J., 95 (3).
Benedetti, A. & Mangoni, E., 2004. Damage assessment in
• The use of ultrasound pulse as a non destructive actual fire situations by means of non-destructive tech-
technique allows identifying damaged areas of the niques and concrete tests, WSp Fire design of concrete
structure, but does not give the penetration of the structures: what now?, what next? edt P. Gambarova,
damage. R. Felicetti, A. Meda and P. Riva, Milan: 231–239.
Chan, S.Y.N., Luo, X. & Sun, W. 2000. Effect of high tem-
• The TG test is an accurate method to determine
perature and cooling regimes on the compressive strength
the chemical degradation of the cement paste, and pore properties of high performance concrete, Con-
The determination of % of CSH transformation in struction and Building Mat. 14: 261–266.
cement paste allows discriminating between damage Calavera, J., Izquierdo J.M. et al, 2005. Fire in the Windsor
and undamaged depths of concrete, Tª < 350°C. building. Survey of the fire resistance and residual bear-
• The microscopy analysis allow differentiating ing capacity of the structure after the fire. NIT INTEMAC,
between sound and altered zones due to fire and is dec: 1–35.
a good method to identify the presence of cracking Cioni, P., Croce, P. & Salvatore, W. 2001. Assessing fire
and its distribution in the mass of the concrete. damage to R/C elements, Fire Safety J., 36: 181–199.
Colombo, M., & Felicetti, R. 2006. New NDT techniques for
The depth of the damage is identified with this
the assessment of FIRE damaged concrete structures. 4th
technique. Int. WSp. Structures in Fire, SIF´06. Aveiro: 721–734.
• The isotherm for 500°C can be determined from Fellicety, R. 2004a. The drilling resistance test for the
microstructure tests. assessment of the thermal damage concrete. WSp Fire
• The penetration of the damage inside the concrete design of concrete structures: what now?, what next?, edt
in a real fire is heterogeneously distributed. P. Gambarova, R. Felicetti, A. Meda & P. Riva, Milan:
241–248.
Fellicety, R. 2004b. Digital camera colorimetry for the
assessment of fire-damaged concrete. WSp Fire design
ACKNOWLEDGEMENTS of concrete structures: what now?, what next?, edt P.
Gambarova, R. Felicetti, A. Meda and P. Riva, Milan:
The author wants to thank MEC of Spain for the 211–220.
financial support of this work, PSE 11, HABITAT Feliceti, R. 2008. Recent advances and research needs in
the assessment of fire damaged concrete structures, fib
2030, PSS-380000-2008-14.
workshop on Fire design of concrete structures. Coim-
bra: in press.
Fletcher, I., Borg, H., Hitchen, N. & Welch, S. 2006. Per-
REFERENCES formance of concrete in fire. A review of the state of the
art with a case study of the Windsor Tower fire. 4th Int.
Alonso, C. 2006a. Assessment of damage in concrete WSp. Structures in Fire, SIF´06. Aveiro: 779–790.
structures exposed to fire. Micro and macrostructural Khoury, G.A. 1992. Compressive strength of concrete at
analysis. 4th Int. WSp. Structures in Fire, SIF´06, Aveiro: high temperatures: a reassessment., Magz of Conc Rs.
599–611. 161: 291–309.
Alonso, C., Andrade, C., Menendez, E. & Gayo, E. 2005. Piasta, Z. Sawicz, and L. Rudzinski, 1984a. Changes in
Microstructure changes in high and ultra high concrete structure of hardened cement pastes due to high tempera-
exposed to high temperature environments. Quality of ture, Mater. & Struct. 17: 291–295.
concrete structures and recent advances in concrete Piasta, P. 1984b. Heat deformation of cement phases and
materials and testing. ACI, SP-229-19, Edt. P. Helene, microstructure of cement paste, Mater. & Struct. 17:
E. Pazini, T. Holland & R. Bittencourt, edt Lindsay K. 415–420.
Kennedy: 289–302. Rilley, M.A. 1991. Possible new method for assessment of
Alonso, C. & Fernandez-Municio, L. 2004. Dehydration and fire-damaged concrete, Magz. of Conc. Rs., 43: 87–92
rehydration processes of cement paste exposed to high Rostasy, F., Ehm, C. & Hinrichsmeyer, K. 1987. Structural
temperature environments, J. Mater. Sci. 39: 3015–3024. alterations in concrete due to thermal and mechanical

476
stresses. Int Cong. Pore Structure and Contruction Mate- Tay, D.C. & Tam, C.T. 1996. In situ investigation of the
rials Properties, Versailles. strength of deteriorated concrete. Construction & build-
Schneider, U. 1990. Reparability of fire-damaged structures, ing materials, 10 (1):17–26.
Fire Safety J. 16: 251–336. Zhang, X. Du, H.X. Zhang, B. & Philips, D.V. 2002.
Short, N. & Purkiss, J. 2004. Petrographic analisis of fire Assessment of fire damage of concrete by using infrared
damaged concrete. WSp Fire design of concrete struc- thermal imaging method. Int Cong. Concrete for extreme
tures: what now?, what next?, edt P. Gambarova, R. conditions, Edt R.K. Dhir, M.J. McCarthy & M.D.
Felicetti, A. Meda and P. Riva, Milan: 221–230. Newlands: 590–604.

477

Das könnte Ihnen auch gefallen