TABLE OF CONTENTS
1.0 SCOPE
4.1 General
4.2 Design Criteria
4.3 Materials
4.4 Fabrication
4.5 Marking
5.0 TESTS
1.0 SCOPE
2.2 This TMSS shall also be read in conjunction with SEC Purchase Order or
Contract Schedules for project, as applicable.
The latest revision/amendments of the following Codes & Standards shall be applicable
for the equipment/material covered in this TMSS. In case of conflict, the
vendor/manufacturer may propose equipment/material conforming to one group of
Industry Codes and Standards quoted hereunder without jeopardizing the requirements of
this TMSS.
3.1 IEC-60502-2 Power cables with extruded insulation and their accessories
from 1 kV up to 30 kV (Um = 36 kV).
3.3 ICEA P-45-482 Short Circuit Performance of Metallic Shields and Sheaths
of Insulated Cable.
4.1 General
4.1.1 The XLPE insulated power cable rated 11 kV, 13.8 kV, 33 kV or 34.5 kV
shall meet or exceed the requirements of this Specification in all respects.
4.2.3 MV cable design shall facilitate heat shrink, cold shrink or pre-molded
joints and terminations. These requirements include the use of an extruded
inner covering under armour (where applicable).
4.3 Materials
4.3.1 Conductor
Table-1
ingress of water along the conductor axis in case of cable failure due to
any reason.
4.3.3 Insulation
The average insulation thickness shall not be less than the specified
nominal value. The minimum thickness at any point shall not fall below
the nominal value by more than 0.1mm+10% of nominal value.
Helically applied soft drawn copper wires or tapes may be used as metallic
shield in intimate contact with insulation screen/shield.
The minimum short circuit rating of the above metallic shield shall be as
specified in Data Schedule.
For three core MV cables, metallic screens of the cores shall be in contact
with each other. However, radial water ingress protection to the 3 core MV
cable shall be provided by applying copolymer coated laminated
aluminum or copper tape immediately under the outer jacket firmly
bonded to it, which will perfectly seal the underneath layers of the cable by
preventing penetration of moisture into the cable.
The inner coverings and fillers shall be of materials suitable for the
operating temperature of the cable and compatible with the insulation. The
fillers shall be extruded material or non-hygroscopic fibers to ensure that
the cable is compact and round in cross-section. The inner covering shall
be PVC type ST2 compound or PE compound.
The jacket material shall be Red PVC, type ST2 for 13.8kV cables and
Black for 34.5kV cables per IEC-60502-2. Nominal thickness of the outer
sheath shall also be as per IEC 60502-2. Minimum thickness at any point
shall not be less than 80% of nominal value. Outer jacket shall be UV
resistant & Oil resistant.
4.4 Fabrication
4.4.1 The conductor shield, XLPE insulation and insulation shield shall be
extruded by the triple extrusion method to assure homogeneity between the
insulating and semi-conducting shields.
4.4.3 The power cable shall be free of material and manufacturing defects which
would prevent it from meeting the requirements of this specification.
4.4.4 A graphite coating shall be applied over the jacket to serve as an electrode
for testing the integrity of the jacket.
4.5 Marking
4.5.1 The jacket for all the cables shall be marked by embossing in English at
intervals not exceeding one meter with the following minimum
information: -
a. Electric Cable
11TMSS04R0/HKG Date of Approval: December 12, 2011 PAGE NO. 7 OF 17
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-04, Rev. 0
4.5.2 All cables shall be marked with “Property of Saudi Electricity Company”
in both Arabic & English.
5.0 TESTS
All test results shall be provided for review and acceptance by SEC.
Routine, Type and special test shall be in accordance with latest version of the
International Standards i.e AEIC CS8, IEC 60502-2, IEC 60229 and IEC 61442.
In addition to the applicable items per 01-TMSS-01, packing and shipping of the cable
shall conform to the following:
6.1 The cable ends shall be sealed with a waterproof, heat shrinkable plastic or
elastomeric end cap with adhesive type sealing compound. Cable ends shall be
properly secured to the reel.
6.2 The cable shall be delivered without splices, on standard sized non-returnable steel
drums of sturdy construction properly packed and lagged externally to prevent the
cable from possible damage during transportation. Wood lagging shall be used and
have a minimum thickness of 50mm. The wood lagging shall also be secured with
steel straps to provide physical protection for the cables during transit and during
customary storage and handling operations.
6.3 The arbor hole for wooden reel shall be reinforced with galvanized steel plates.
The minimum diameter of the drum of the shipping reel shall not be less than the
minimum bending diameter of the power cable.
6.4.1 Cable reels/drums shall be marked in legible and indelible letters giving
the following particulars:
d. Gross weight
e. Dimensions of reel
f. Direction of Pulling
g. Manufacturer's name and country of origin
h. Purchase Order number
i. J.O. number/Contract number (if applicable)
j. Serial number of reel
k. Stock number in 10 cm high bold numerals.
l. Direction of rolling of reel
m. 11-TMSS-04, Rev.0
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.3 Materials
4.3.1 Conductor
a. Material (Al or Cu)
b. Size, mm²
c. Number of cores (1C or 3C)
d. Number of strands *
e. Diameter of strand prior to compaction *
f. Cross sectional area (mm²) *
g. Diameter, mm *
h. Temperature co-efficient at 20°C, /°C *
i. Skin effect loss factor (ks) *
j. Proximity effect loss factor (kp) Short circuit
capability of conductor in kA for 1 sec starting
with 90°C conductor temperature upto
*
maximum short circuit current temperature.
k. Water blocking material between strands *
4.3.3 Insulation
a. Material XLPE
b. Average thickness, mm 8.76
c. Minimum thickness, mm 7.884
d. Diameter over insulation, mm *
e. Thermal resistivity, k-m/W *
f. Dielectric constant (ε) *
g. Loss factor (δ) *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Official Seal/Stamp
of the Company & Date