Beruflich Dokumente
Kultur Dokumente
MELSOFT
(3) The USB cable can be used for connecting a single programmable
controller; cannot be applied to the following configurations.
<Incompatible configurations> QCPU (Q mode)/LCPU
One computer installed with USB cable
several USB ports is connected USB
to several QCPU (Q mode) cabl QCPU (Q mode)/LCPU
e
/LCPU.
QCPU (Q mode)/LCPU
USB cable USB USB cable
One computer is connected to hub US
Bc
several QCPU (Q mode)/LCPU abl QCPU (Q mode)/LCPU
e
though USB hub.
(4) Use the USB cable which conforms to the USB Standard Rev. 1.1.
(5) Refer to POINT in Section 16.1 for precautions for and restrictions on using
the USB cable to make communications.
(2) When the "Operate communication setting" check box is checked in the
<<PLC system (2)>> tab of PLC parameter, the corresponding port cannot
communicate with the programmable controller CPU. Write the setting that
the "Operate communication setting" check box is cleared from the built-in
programming port of the programmable controller CPU.
When the PLC type of the project is the FX3U(C), the channel specification
(CH1/CH2) combo box is displayed. Select "CH1" to confirm the setting.
2-3 2-3
2 SYSTEM CONFIGURATION
MELSOFT
(3) When Windows 98 or later is used, the USB cable and function expansion
R
board are available if the driver on the CD-ROM packed with the FX-USB-
AW or FX3U-USB-BD has been installed.
Note that the USB driver differs from the one for the built-in USB port of the
FX3G. Install the driver according to a connected device. GX Developer
Version8.72A or later stores a USB driver for the FX-USB-AW and
FX3U-USB-BD to its installation location, "Easysocket\FXOptionDrivers".
(4) The USB cable and function expansion board are unavailable for
Windows 95 or Windows NT Workstation 4.0.
R R
(5) On GX Developer, set the serial COM port number by choosing [Online] -
[Target setup].
(6) For the precautions and restrictions on use of the FX3U-USB-BD, refer to
the manual packed with the FX3U-USB-BD.
3: About the cable (QCPU (Q mode), LCPU, QCPU (A mode) compatible)
For communication in 115.2/57.6kbps
Fast communication cannot be made if the personal computer used is not
compatible with the communication speed of 115.2/57.6kbps.
If a communication error occurs, reduce the transmission speed setting and
restart communication.
The following cable has been confirmed by Mitsubishi Electric that it will work
properly.
Using the cable of Mitsubishi Electric make
RS-232 cable
2-4 2-4
2 SYSTEM CONFIGURATION
MELSOFT
FX-422CAB (0.3m)
FX-422CAB-150 (1.5m)
F2-232CAB-1
FX-232AWC
(when personal computer For FX0/FX0S/FX0N/FX1S/FX1N/FX2NFX2NC/FX3G/
connector is D-sub, 9-pin) FX3U/FX3UC CPU
FX-232AWC-H
(FX series only) FX-422CABO (1.5m)
How to identify compatibility of the F2-232CAB and F2-232CAB-1 cables with the
ACPU and QnACPU
Check the indication of the model label attached to the cable.
Incompatible products Compatible products (with indication of F/FX/A)
F2-232CAB F2-232CAB(F/FX/A)
Y990C Y990C
F2-232CAB-1 F2-232CAB-1(F/FX/A)
Y990C Y990C
When using A6TEL/Q6TEL as a converter, use any of the RS-232 cables shown in
the above table.
When connecting to FX3G/FX3U/FX3UC using FX-232AWC-H, select any of 9.6kbps,
19.2kbps, 38.4kbps, 57.6kbps or 115.2kbps for the transmission speed.
When connection using FX-232AWC or FX-232AW, select either 9.6kbps or
19.2kbps for the transmission speed.
Be sure to use equipment shown in the above table when connecting to FX series.
Example of connection between Windows personal computer or IBM PC/AT and QnACPU by FX-232AW(C)
Windows personal computer or IBM PC/AT QnACPU
FX-232AW(C)
1
AC30N2A FX-422CAB(-150)
F2-232CAB-1
: Depending on the used cable, a straight cable (connector) for conversion between D-sub 9-pin
D-sub 25-pin may be separately necessary.
Prepare conversion cables as necessary according to the instructions of the used Windows personal
computer IBM PC/AT.
(RS-232 cables for connection of Windows personal computer or IBM PC/AT and converter shown
above)
AC30N2A (D-sub 25-pin D-sub 25-pin)
F2-232CAB-1 (D-sub 9-pin D-sub 25-pin)
2-5 2-5
2 SYSTEM CONFIGURATION
MELSOFT
When the PLC type of the project is the FX3G or FX3U(C), the channel setting
(CH1/CH2) combo box is displayed.
Select "CH1" to confirm the setting.
2-6 2-6
2 SYSTEM CONFIGURATION
MELSOFT
2-7 2-7
2 SYSTEM CONFIGURATION
MELSOFT
When the "Operate communication setting" check box is checked in the <<PLC
system (2)>> tab of PLC parameter, the corresponding port cannot communicate
with the programmable controller CPU. Write the setting that the "Operate
communication setting" check box is cleared from the built-in programming port of
the programmable controller CPU.
When the PLC type of the project is the FX3G or FX3U(C), the channel setting
(CH1/CH2) combo box is displayed.
FX3U/FX3UC series
When using the first FX3U-232-BD connected to FX3U-232ADP or FX3U-CNV-BD,
select "CH1" to confirm the setting.
When using FX3U-232ADP connected to a board other than FX3U-CNV-BD, or the
second FX3U-232ADP connected to the FX3U-CNV-BD, select "CH2" to confirm the
setting.
FX3G series (14-point/24-point types)
When using FX3G-232-BD or the first FX3U-232ADP connected to FX3G-CNV-ADP,
select "CH1" to confirm the setting.
FX3G series (40-point/60-point types)
When using FX3G-232-BD, or the first FX3U-232ADP connected to FX3G-CNV-ADP,
select "CH1" to confirm the setting. In this case, when using the second FX3U-
232ADP connected to FX3G-CNV-ADP, select "CH2" to confirm the setting.
When using FX3G-232-BD, and FX3U-232ADP connected to FX3G-CNV-ADP, select
"CH1" to confirm the setting for the FX3U-232ADP and select "CH2" to confirm the
setting for the FX3G-232-BD.
2-8 2-8
2 SYSTEM CONFIGURATION
MELSOFT
Workstation 4.0.
(4) On GX Developer, select [Online] - [Transfer setup] and set the serial COM
port number.
(5) For the precautions and restrictions on use of the FX-USB-AW, refer to the
manual packed with the FX-USB-AW.
8: Computer link
The program that uses V, Z (Indexing) cannot be monitored if routing through a
computer link module when A Series is used.
2-9 2-9
2 SYSTEM CONFIGURATION
MELSOFT
12:Via GOT
Using the transparent function of the GOT allows access to the programmable
controller via the GOT.
For details, refer to Section 16.2.5 and the following manuals.
GOT1000 Series Connection Manual
GOT-A900 Series User's Manual (Connection System Manual)
GOT-F900 Series Hardware Manual [connection]
13:USB cable (compatible with the FX3G)
(1) The USB cable is usable with Windows 98 or later on which a USB driver
R
(4) Windows 95 and Windows NT Workstation 4.0 are not compatible with
R R
the cables.
(5) Select [Online] [Transfer setup] "USB (Built-in port)" in GX Developer.
2 - 10 2 - 10
2 SYSTEM CONFIGURATION
MELSOFT
POINT
Before handling the RS-422 interface conversion cable/converter, please
read its specifications, precautions, etc. carefully in the manual of the
corresponding product and handle it correctly.
When disconnecting or reconnecting the conversion cable/converter that
receives 5VDC power from the RS-422 interface, switch power off on the
programmable controller side before starting work.
When disconnecting or reconnecting the peripheral device or conversion
cable that does not receive 5VDC power from the RS-422 interface (whose
power is supplied from an external power supply), be sure to use an earth
band or touch a grounded metal object, etc. before starting work to
discharge static electricity from the cable, human body, etc. After that,
handle it in the following procedure.
1) Switch power off on the personal computer side.
2) Power off the conversion cable/converter. When it has an FG terminal,
ground it.
3) Connect/disconnect the conversion cable/converter between the
personal computer and programmable controller.
4) Power on the conversion cable/converter.
5) Power on the personal computer.
6) Start up the software package.
When connecting a personal computer to a programmable controller CPU
with a USB/RS-232 conversion cable, refer to manuals of each cable for
checking the COM port number.
2 - 11 2 - 11
2 SYSTEM CONFIGURATION
MELSOFT
A70BDE-J71QLP23
(Optical loop) ACPU
A70BDE-J71QLP23GE QnACPU
Driver
(Optical loop) QCPU (Q mode)
SW3DNF-MNET10 QCPU (A mode)
A70BDE-J71QBR13
(Coaxial bus) Other station programmable controller
A70BDE-J71QLR23
(Coaxial loop)
2
MELSECNET/H board
Q80BD-J71BR11
(Coaxial bus) ACPU
Q80BD-J71LP21-25
Driver QnACPU
(Optical loop)
Q80BD-J71LP21S-25 QCPU (Q mode)
SW0DNC-MNETH-B
(Optical loop) QCPU (A mode)
Q80BD-J71LP21G
(Optical loop) Other station programmable controller
Q80BD-J71LP21GE
(Optical loop)
3
GX Developer CC-Link IE Controller Network board ACPU
(SW8D5C-GPPW-E) QnACPU
Q80BD-J71GP21-SX Driver
(Optical loop) QCPU (Q mode)
SW0DNC-MNETG-B
Q80BD-J71GP21S-SX QCPU (A mode)
(Optical loop)
Other station programmable controller
4 ACPU
CC-Link Ver.1 board QnACPU
Driver LCPU
A80BDE-J61BT13 SW4DNF-CCLINK-B QCPU (Q mode)
A80BDE-J61BT11 QCPU (A mode)
5 Other station programmable controller
ACPU
CC-Link Ver.2 board QnACPU
Driver
Q80BD-J61BT11N SW1DNC-CCBD2-B LCPU
QCPU (Q mode)
6 QCPU (A mode)
Other station programmable controller
Ethernet board Driver
ACPU
Commercially available Driver supplied QnACPU
Ethernet board with commercially
available LCPU
Ethernet board QCPU (Q mode)
QCPU (A mode)
Other station programmable controller
1: MELSECNET/10 board
The following table indicates the drivers that cannot be used with the specific
Operating Systems.
Driver Name Operating Systems
SW3DNF-MNET10 Cannot be used with Windows Me/2000/XP/Vista/7/8.
R
later.
2 - 12 2 - 12
2 SYSTEM CONFIGURATION
MELSOFT
2: MELSECNET/H board
The following table indicates the drivers that cannot be used with the specific
Operating Systems.
Driver Name Operating Systems
SW0DNC-MNETH-B Cannot be used with Windows Me.R
6: Ethernet board
(1) The following Ethernet boards/cards have been confirmed by Mitsubishi
Electric to operate properly.
Maker Name Model
3COM make Ethernet Link III LAN PC Card
Center COM LA-PCM Ethernet
Allied Telesis make
Ethernet board/card PC Card LAN Adapter
10BASE-T LAN card
TDK make
(Model: LAN-CD021BX)
Ethernet board Allied Telesis make RE2000 (ISA)
2 - 13 2 - 13
2 SYSTEM CONFIGURATION
MELSOFT
ACPU
Computer link Refer to Appendix-5 QnACPU
RS-232 QCPU (Q mode)
GX Developer C24 QCPU (A mode)
(SW8D5C-GPPW-E)
CC-Link
Driver CC-Link QCPU (Q mode)
PPC-DRV-01
MELSECNET/H Driver
MELSECNET/H QCPU (Q mode)
PPC-DRV-01
Ethernet
QCPU (Q mode)
Q Sries Bus
Multiple CPU
2 - 14 2 - 14
2 SYSTEM CONFIGURATION
MELSOFT
2 - 15 2 - 15
2 SYSTEM CONFIGURATION
MELSOFT
1: When configuring the system with the Redundant CPU, use the software
package of GX Developer Version 8.18U (SW8D5C-GPPW-E) or later.
2: The following table indicates whether the interfaces may be connected to
the personal computer when the programmable controller is accessed from
the personal computer via the serial communication module.
If the module cannot be connected directly with the personal computer, it
may be usable as the "n"th module of multidropping.
2 - 16 2 - 16
2 SYSTEM CONFIGURATION
MELSOFT
4: Note that when the programmable controller is accessed from the personal
computer via the computer link module, the modules that may be
connected directly with the personal computer are limited.
If the module cannot be connected directly with the personal computer, it
may be usable as the "n"th module of 1:n connection.
1:1 1:n Connection
Type Interface
Connection First module "n"th module
RS-232
AJ71UC24
RS-422/485
AJ71C24-S6 RS-232
AJ71C24-S8 RS-422
A1SJ71C24-R2
A1SJ71C24-PRF
A1SJ71UC24-R2 RS-232
A1SJ71UC24-PRF
A1SCPUC24-R2
A1SJ71C24-R4
RS-422/485
A1SJ71UC24-R4
RS-232
A2CCPUC24
RS-422
A2CCPUUC24-PRF
RS-422/485
2 - 17 2 - 17
2 SYSTEM CONFIGURATION
MELSOFT
(2) The following list indicates modules connectable from the USB port.
PLC Series Module Model
Q00UJ, Q00U, Q01U, Q02H, Q02PH, Q02U, Q03UD, Q03UDE, Q04UDH, Q04UDEH, Q06H, Q06PH,
Q series Q06UDH, Q06UDEH, Q10UDH, Q10UDEH, Q12H, Q12PH, Q12PRH, Q13UDH, Q13UDEH, Q20UDH,
Q20UDEH, Q25H, Q25PH, Q25PRH, Q26UDH, Q26UDEH
L series L02, L26-BT
FX FX0, FX0S, FX0N, FX1S, FX1N, FX1NC, FX2N, FX2NC, FX3G, FX3U, FX3UC
series 1 2
(3) The following table indicates the modules connectable from the
MELSECNET/10 or MELSECNET/H (MELSECNET/10 mode) board.
PLC Series Module Model
Q series QJ71LP21, QJ71LP21G, QJ71BR11, QJ71LP21-25, QJ71LP21S-25
QnA series AJ71QLP21, AJ71QBR11, A1SJ71QLP21, A1SJ71QBR11
A series AJ71LP21, AJ71BR11, A1SJ71LP21, A1SJ71BR11
(4) The following table indicates the modules connectable from the MELSECNET/H
board.
PLC Series Module Model
Q series QJ71LP21, QJ71BR11, QJ71LP21-25
(5) The following table indicates the modules connectable from the CC-Link IE
Controller Network board.
PLC Series Module Model
Q series QJ71GP21-SX, QJ71GP21S-SX
(6) The following list indicates modules connectable from the CC-Link board.
PLC Series Module Model
Q series QJ61BT11, QJ61BT11N
QnA series AJ61QBT11, A1SJ61QBT11
A series AJ61BT11, A1SJ61BT11
2 - 18 2 - 18
2 SYSTEM CONFIGURATION
MELSOFT
(7) The following list indicates modules connectable from the Ethernet board.
PLC Series Module Model
QJ71E71, QJ71E71-B2, QJ71E71-100, QJ71E71-B5, Q03UDE 1, Q04UDEH 1, Q06UDEH 1,
Q series
Q10UDEH 1, Q13UDEH 1, Q20UDEH 1, Q26UDEH 1
L series L02, L26-BT
AJ71QE71, AJ71QE71-B5, A1SJ71QE71-B2, A1SJ71QE71-B5, AJ71QE71N-T, A1SJ71QE71N-T,
QnA series AJ71QE71N-B5, A1SJ71QE71N-B5, AJ71QE71N-B2, A1SJ71QE71N-B2, AJ71QE71N-B5T,
A1SJ71QE71N-B5T, AJ71QE71N3-T, A1SJ71QE71N3-T
AJ71E71-S3, A1SJ71E71-B2-S3, A1SJ71E71-B5-S3, AJ71E71N-B2, AJ71E71N-B5T,
A series A1SJ71E71N-B2, A1SJ71E71N-B5T, AJ71E71N-T, A1SJ71E71N-T, AJ71E71N-B5,
A1SJ71E71N-B5, AJ71E71N3-T, A1SJ71E71N3-T
CNC (M6/M7) 2 C6/C64 Series, M700 Series
FX series FX-ENET Series
<Example>
Control
GX Developer
QnUDE CPU QJ71LP
GX Developer (H)CPU 21-25
Ethernet
GX Developer
2: When creating the project of the numerical controller (CNC (M6/M7)), set
the PLC type to "Q4A". Refer to the following manual for details.
MITSUBISHI CNC 700 Series PLC Programming Manual
2 - 19 2 - 19
2 SYSTEM CONFIGURATION
MELSOFT
Ladder/list 2 2
MELSAP3
MELSAP-L 3
: Compatible
: Not compatible
: PLC type unsupported
1: The project saved with the registration monitor open cannot be opened.
2: Read by the execution program.
3: Read by the MELSAP3 program.
2 - 20 2 - 20
2 SYSTEM CONFIGURATION
MELSOFT
(1) About the parameters (for the High Performance Model QCPU)
GX Developer Version5 (SW5D5C-GPPW-E) or earlier cannot handle the data
where the parameters of the following items have been set.
The following dialog box appears if the project saved in the personal computer
is read or read from PLC is performed from the programmable controller.
(2) About the remote password (for the High Performance Model QCPU)
The following explains the case where the remote password-set project is
read/saved, for example.
(a) The remote password cannot be edited/changed.
(b) When the project is saved, its set remote password is not deleted. (Saved
unchanged)
(c) When the PLC type is changed (including the case where the type is
changed to other than the QCPU (Q mode)), the remote password file is
not deleted.
(d) When the [Online] PLC user data list is being displayed, the remote
password file is not displayed.
2 - 21 2 - 21
2 SYSTEM CONFIGURATION
MELSOFT
2 - 22 2 - 22
2 SYSTEM CONFIGURATION
MELSOFT
Ladder/list 2
MELSAP3
MELSAP-L
Labels used FB No labels
Structure
ST 2
FB (ST)
Ladder/list
Labels not used MELSAP3 No labels
MELSAP-L
: Compatible
: Not compatible
1: The project saved with the registration monitor open cannot be opened.
2: Read by the execution program.
2 - 23 2 - 23
2 SYSTEM CONFIGURATION
MELSOFT
2 - 24 2 - 24
2 SYSTEM CONFIGURATION
MELSOFT
POINT
PLC parameter "High speed interrupt setting"
Note that write to PLC can be performed to the programmable controller
that is incompatible with high speed interrupt setting, but the high speed
interrupt setting is ignored.
GX Developer Version7.19V (SW7D5C-GPPW-E) or later has been
improved; the project created with this version and including "Multiple PLC
setting" within which "Online module change" is disabled can be read
using GX Developer Version7.09K (SW7D5C-GPPW-E) or earlier without
changing the parameters.
For the latest GX Developer version, contact your local sales
representative.
How to read the project created with GX Developer Version7.10L to 7.18U
using GX Developer Version7.09K (SW7D5C-GPPW-E) or earlier.
2 - 25 2 - 25
2 SYSTEM CONFIGURATION
MELSOFT
FB (ST) 1
Ladder/list
Labels not used MELSAP3 No labels
MELSAP-L
: Compatible
: Not compatible
1: Read by the label program.
2 - 26 2 - 26
2 SYSTEM CONFIGURATION
MELSOFT
Projects in which parameter (a) to (g) mentioned below are set cannot be handled
using GX Developer Version 7.20W (SW7D5C-GPPW) or earlier.
When these projects are read out to a personal computer or read out from the
programmable controller to a personal computer, the following dialog box will appear.
Click the OK button, and then read out the project with all parameters default.
It is required to reset the required parameters after reading.
PLC parameter
(a) <<SFC>> tab
(b) <<PLC file>> tab
(c) <<PLC system>> tab [Intelligent function module setting]
(d) “Multiple CPU setting”
Network parameter
(e) Ethernet "E-mail settings"
(f) Ethernet "Interrupt"
(2) Parameters cannot be read by High Performance model QCPU or Process CPU
PLC parameter
(g) <<Boot file>> tab "Boot option" "Clear program memory"
2 - 27 2 - 27
2 SYSTEM CONFIGURATION
MELSOFT
The project, in which any of the following parameters has been set, cannot be
handled using GX Developer Version 8.02C (SW8DC-GPPW-E) or earlier.
The following dialog box appears when the project, where any of the above
parameters has been set, is read or read from the PLC.
Click the OK button, and then read out the project with all parameters default.
It is required to reset the required parameters after reading.
2 - 28 2 - 28
2 SYSTEM CONFIGURATION
MELSOFT
REMARK
If the projects created with GX Developer Version 8.04E (SW8D5C-GPPW-E) or
earlier using GX Developer Version8.05F (SW8D5C-GPPW-E) or later, they will be
displayed with "TCP existence confirmation setting" set to "Use the Ping".
2 - 29 2 - 29
2 SYSTEM CONFIGURATION
MELSOFT
(1) The project where the parameters indicated in (a) and (b) have been set cannot
be read from the personal computer or programmable controller using GX
Developer Version 8.17T (SW8D5C-GPPW-E) or earlier.
(a) Parameters related to the Redundant CPU have been set.
(b) "OPS connection" has been set as the open method on the open setting
screen in the Ethernet setting.
(2) The project where the following parameters (a), (b) have been set cannot be
handled by GX Developer Version 8.17T (SW8D5C-GPPW-E) or earlier.
Read it using GX Developer Version 8.18U (SW8D5C-GPPW-E) or later.
(a) Pairing setting of MELSECNET/H network range assignment
(b) IP address on Ethernet operation setting screen in Ethernet setting
(3) When the remote password of the remote I/O station has been set
The following explains the case where the remote password-set project is
read/saved.
(a) The remote password cannot be edited/changed.
(b) When the project is saved, its set remote password is not deleted. (Saved
unchanged)
2 - 30 2 - 30
2 SYSTEM CONFIGURATION
MELSOFT
In the Station type field, select the Ver. 1 remote I/O station.
2 - 31 2 - 31
2 SYSTEM CONFIGURATION
MELSOFT
REMARK
When the project set by GX Developer Version 8.17T (SW8D5C-GPPW-E) or
earlier is handled by GX Developer Version 8.18U (SW8D5C-GPPW-E) or later, the
remote station points are changed as shown in the following table.
Points set by GX Developer Version 8.17T Points set by GX Developer Version 8.18U
(SW8D5C-GPPW-E) or earlier (SW8D5C-GPPW-E) or later
Number of occupied Number of remote Number of occupied Number of remote
stations station points stations station points
0 points
(reserved station)
8 points
1 station occupied 8 points + 8 points 1 station occupied Setting unchanged
(reserved)
16 points
32 points
0 points 0 points
(reserved station) (reserved station)
8 points
2 station occupied 8 points + 8 points 2 station occupied
(reserved) 64 points
16 points
32 points
0 points 0 points
(reserved station) (reserved station)
8 points
3 station occupied 8 points + 8 points 3 station occupied
(reserved) 96 points
16 points
32 points
0 points 0 points
(reserved station) (reserved station)
8 points
4 station occupied 8 points + 8 points 4 station occupied
(reserved) 128 points
16 points
32 points
: This setting is not supported by GX Developer Version 8.18U (SW8D5C-GPPW-E) or later.
The following dialog box will appear if the project, where this setting has been made by GX
Developer Version 8.17T (SW8D5C-GPPW-E) or earlier, is read.
Click OK to change the settings to those indicated in the above table and read the new settings.
(The parameters need not be set again.)
2 - 32 2 - 32
2 SYSTEM CONFIGURATION
MELSOFT
The project, in which the following parameter has been set, cannot be handled using
GX Developer Version 8.19V (SW8D5C-GPPW-E) or earlier.
The following dialog box will appear, when the project, in which the above parameter
has been set, is read to personal computer or read from the PLC.
Click the OK button, set all parameters to defaults and read the project.
After reading, the necessary parameters must be set again.
It is required to reset the required parameters after reading.
2 - 33 2 - 33
2 SYSTEM CONFIGURATION
MELSOFT
2 - 34 2 - 34
2 SYSTEM CONFIGURATION
MELSOFT
The project, in which the following parameter has been set, cannot be handled using
GX Developer Version 8.22Y (SW8D5C-GPPW-E) or earlier.
(1) PLC Parameter ”Multiple CPU setting” ”Refresh settings” ”Set the start
device to each PLC”
(2) PLC Parameter <<PLC RAS(2) >> tab (Process CPU only)
The following dialog box will appear, when the project, in which the above parameter
has been set, is read to personal computer or read from the PLC.
Click the OK button, set all parameters to defaults and read the project.
After reading, the necessary parameters must be set again.
It is required to reset the required parameters after reading.
2 - 35 2 - 35
2 SYSTEM CONFIGURATION
MELSOFT
When changing and setting the condition for inspection as "No conditional settings
(Character String send)" in the following settings are made:
"Ethernet parameter setting"-"E-mail settings"-"News setting"
(1) When "Ethernet news setting" screen is closed with End button.
(2) When PLC type is changed to other than QCPU (Q mode), and then return to
QCPU (Q mode).
"No conditional settings (Character String send)" setting will remain when the above
operation is not done.
REMARK
If the projects created with GX Developer Version 8.25B (SW8D5C-GPPW-E) or
earlier using GX Developer Version 8.27D (SW8D5C-GPPW-E) or later, they will be
displayed with "Condition for inspection" set to "No conditional settings".
2 - 36 2 - 36
2 SYSTEM CONFIGURATION
MELSOFT
Click the OK button, set all parameters to defaults and read the project.
After reading, the necessary parameters must be set again.
It is required to reset the required parameters after reading.
REMARK
If the projects created with GX Developer Version 8.28E (SW8D5C-GPPW-E) or
earlier using GX Developer Version8.29F (SW8D5C-GPPW-E) or later, they will be
displayed with "Transit setting" set to "2".
2 - 37 2 - 37
2 SYSTEM CONFIGURATION
MELSOFT
The FB definition program having more than 500 steps cannot be edited, replaced
and converted.
Click the OK button, and then read out the project with all parameters default.
It is required to reset the required parameters after reading.
2 - 38 2 - 38
2 SYSTEM CONFIGURATION
MELSOFT
2 - 39 2 - 39
2 SYSTEM CONFIGURATION
MELSOFT
When the project with any of the above parameters is read from personal computer
or the PLC, the following dialog box appears.
Click the OK button, set all parameters to defaults and read the project.
After the reading, reset the required parameters.
2 - 40 2 - 40
2 SYSTEM CONFIGURATION
MELSOFT
(1) Projects created with the Q02U cannot be used for GX Developer Version
8.45X (SW8D5C-GPPW-E) or earlier.
(2) The following table shows the results of data (project and data in the
programmable controller) read from the Universal model QCPU (excluding the
Q02UCPU) using GX Developer Version 8.45X (SW8D5C-GPPW-E).
2 - 41 2 - 41
2 SYSTEM CONFIGURATION
MELSOFT
(1) Projects created with the Q13UDH or Q26UDH cannot be used for GX
Developer Version 8.58L (SW8D5C-GPPW-E) or earlier.
(2) The project, in which any of the following parameters has been set, cannot be
handled using GX Developer Version 8.58L (SW8D5C-GPPW-E) or earlier.
Remote I/O
A project where “Continue” is set at H/W error time PLC operation mode in
Detailed setting of the <<I/O assignment>> tab
Universal model QCPU (Q02U, Q03UD, Q04UDH, Q06UDH)
A project where “Local device” is set at File usability setting of the
<<Program>> tab
When the project with any of the above parameters is read from personal computer
or the PLC, the following dialog box appears.
Click the Yes button, set all parameters to defaults and read the project.
After the reading, reset the required parameters.
(3) A setting to connect personal computer with programmable controller via C24
using the GOT transparent mode cannot be made with GX Developer Version
8.58L (SW8D5C-GPPW-E) or earlier.
When handling the product with the settings (a) below, make sure to cancel and
then reset the connection destination settings.
2 - 42 2 - 42
2 SYSTEM CONFIGURATION
MELSOFT
2 - 43 2 - 43
2 SYSTEM CONFIGURATION
MELSOFT
(1) The project, in which any of the following parameters has been set, cannot be
handled using GX Developer Version 8.58L (SW8D5C-GPPW-E) or earlier.
A QSCPU project where "Safety data monitoring time" has been set in the
Setting the CC-Link list. screen
A QSCPU project where "CC IE Control (Normal station)" or "Ethernet" has
been set at Network type in network parameter
When the project with any of the above parameters is read from personal computer
or the PLC, the following dialog box appears.
Click the Yes button, set all parameters to defaults and read the project.
After the reading, reset the required parameters.
2 - 44 2 - 44
2 SYSTEM CONFIGURATION
MELSOFT
(1) Projects created with the Q02PH, Q03UDE, Q04UDEH, Q06PH, Q06UDEH,
Q13UDEH or Q26UDEH cannot be used for GX Developer Version 8.65T
(SW8D5C-GPPW-E) or earlier.
(2) The project, in which any of the following parameters has been set, cannot be
handled using GX Developer Version 8.65T (SW8D5C-GPPW-E) or earlier.
The setting of the redundant power supply system in the <<PLC RAS>> tab
is set not to diagnose in the project of the Universal model QCPU
In Q00JCPU, Q00CPU, or Q01CPU project, CC IE Control (Normal station)
is set at Network type.
CC IE Control (Control station) or CC IE Control (Normal station) is selected
as Network Type in the project of the Q12PHCPU, Q12PRHCPU,
Q25PHCPU or Q25PRHCPU
The shared group is set for the network range assignment of CC IE Control
(Control station) in the project of the Universal model QCPU
The pairing is set for the network range assignment of CC IE Control
(Control station)
When the project with any of the above parameters is read from personal computer
or the PLC, the following dialog box appears.
Click the Yes button, set all parameters to defaults and read the project.
After the reading, reset the required parameters.
(3) The project, in which any of the following parameters has been set, cannot be
opened using GX Developer Version 8.65T (SW8D5C-GPPW-E) or earlier.
The points of either M or B in the <<Device>> tab exceed 32K points in the
project of the Universal model QCPU
"Use ZZ" is set in the project of the Universal model QCPU
0 point is set for S in the <<Device>> tab in the project of the Universal
model QCPU
2 - 45 2 - 45
2 SYSTEM CONFIGURATION
MELSOFT
(4) Comments, device memory, and device initial values created within the
extended device range are deleted in the project of the Universal model
QCPU if the project is opened using GX Developer Version 8.65T (SW8D5C-
GPPW-E) or earlier.
(5) The auto start setting of the sampling trace cannot be changed in the project
of the Universal model QCPU.
Recreate a trace setting and overwrite it to the CPU to prevent the auto start
of the sampling trace.
2 - 46 2 - 46
2 SYSTEM CONFIGURATION
MELSOFT
(1) The project, in which any of the following parameters has been set, cannot be
opened using GX Developer Version 8.68W (SW8D5C-GPPW-E) or earlier.
When extended data register or extended link register has been set in the
Universal model QCPU project
(1) Projects created with the FX3G cannot be used for GX Developer Version
8.70Y (SW8D5C-GPPW-E) or earlier.
2 - 47 2 - 47
2 SYSTEM CONFIGURATION
MELSOFT
(2) The project, in which any of the following parameters has been set, cannot be
opened using GX Developer Version 8.74C (SW8D5C-GPPW-E) or earlier.
The project in which the same network number is set for CC IE Control
(Control station) and CC IE Control (Normal station), or CC IE Control (Normal
station) of different modules on the Ethernet/CC IE/MELSECNET setting
screen.
The project in which any of the twist is set for the Baud rate setting of MNET/H
mode (Control station) or MNET/H Ext. mode (Control station) on the
Ethernet/CC IE/MELSECNET setting screen.
The Q02UCPU project in which "Use serial communication" is set in the serial
communication setting.
The Universal model QCPU project in which PLC module change is set in the
PLC system setting.
The Universal model QCPU project in which some of index registers are
specified as local devices in the device setting.
The Universal model QCPU project in which Compatibility with A-PLC is
selected in the PLC system setting.
The Built-in Ethernet port QCPU project in which "Socket communication" is
set for the open system of the open setting in the Built-in Ethernet port setting.
(3) When instructions or rising pulse close contact/falling pulse close contact that are
newly added for Universal model QCPU (first 5 digits of serial number are
"101002" or later) are used, and if that project is opened using GX Developer
Version 8.74C (SW8D5C-GPPW-E) or earlier, an instruction code error occurs.
2 - 48 2 - 48
2 SYSTEM CONFIGURATION
MELSOFT
2 - 49 2 - 49
2 SYSTEM CONFIGURATION
MELSOFT
(1) The project, in which the following parameter has been set, cannot be handled
using GX Developer Version 8.80J (SW8D5C-GPPW-E) or earlier.
The Universal model QCPU project in which "Module error log (Intelligent
function module)" is set in the PLC RAS (2) tab
When the project with the above parameter is read from personal computer or
the PLC, the following dialog box appears.
Click the Yes button, set all parameters to defaults and read the project.
After the reading, reset the required parameters.
(1) Projects created with the LCPU cannot be handled using GX Developer Version
8.85P (SW8D5C-GPPW-E) or earlier.
2 - 50 2 - 50
2 SYSTEM CONFIGURATION
MELSOFT
(1) The project, in which the following parameter has been set, cannot be handled
using GX Developer Version 8.95Z (SW8D5C-GPPW-E) or earlier.
A QSCPU project in which the CC-Link IE Field Network parameters are set.
A QSCPU project in which the value of 65 to 120 is set to the "Relay station
No." of routing parameters.
When the project with the above parameter is read from personal computer or
the PLC, the following dialog box appears.
Click the Yes button, set all parameters to defaults and read the project.
After the reading, reset the required parameters.
POINT
CC-Link IE Field Network parameters cannot be written to QSCPU whose
first 5 digits of the serial number are "13041" or earlier.
(2) Opening a project where transfer setup is set as shown below (a) with GX
Developer Version 8.95Z (SW8D5C-GPPW-E) or earlier changes "Other
station" to "No specification".
Cancelling the transfer setup settings and then resetting the settings is required.
(a) Content of transfer setup
<QSCPU project>
PC side I/F setting
CPU module (QSCPU)
Other station
Other station (Single network)
Network route
CC IE Cont, CC IE Field, NET/10(H), Ethernet
2 - 51 2 - 51
2 SYSTEM CONFIGURATION
MELSOFT
(3) When opening a project which "CC-Link IE Field board" is set to connection
destination designation PC side I/F with GX Developer Version 8.95Z
(SW8D5C-GPPW-E) or earlier, PC side I/F is changed to "NET/10 board".
2 - 52 2 - 52
2 SYSTEM CONFIGURATION
MELSOFT
(1) The project, in which the following parameter has been set, cannot be handled
using GX Developer Version 8.103H (SW8D5C-GPPW-E) or earlier.
Click the Yes button, set all parameters to defaults and read the project.
After the reading, reset the required parameters.
POINT
When nine or more CC-Link IE Controller Network (Normal station) refresh
parameters are set, they cannot be written to QSCPU whose first 5 digits
of the serial number are "14051" or earlier.
2 - 53 2 - 53