several sensitivity tests and it was found to be the one with
the best precision/computational effort ratio. Type 1
For the 3D simulation, a tetrahedral/hexahedral hybrid mesh Temperature
Simplified (°C)
with 2 450 000 elements was created. The mesh size is in
average 2.5 mm, although in critical zones, the mesh
refinement is 0.7 mm.
Detailed
Paper 0361
Paper 0361
afterwards. The probes were positioned to measure the In ONAF cooling, the appropriate corrections must be made
temperatures of the hottest spot inside the disc and the to the boundary conditions for a physically consistent
adjacent oil in the radial duct. These are shown in Table 4. model, in order to obtain realistic results. It was detected
flow inversions between two consecutive washers. These
Table 4. Measured hot-spot temperatures and the total flow inversions can be the main source of overheating in
range of temperatures modelled inside the disc ONAF cooling. By acting on the placement of washers, it
and oil duct from the CFD simulations. was demonstrated that it is possible to control potential
Fibre optic probe TExperimental (°C) T2D (°C)
HV 116 ± 2 99.1 - 115.1
inversions of the oil and to reduce the hot-spot temperature
Disc by as much 10°C which has a strong direct impact on the
LV 109 ± 2 90.8 - 103.7
Oil
HV 98 ± 2 91.0 - 115.5 power transformer’s lifetime.
LV 98 ± 2 89.8 - 99.6
ACKNOWLEDGMENTS
Deviations to the experiments can be either explained by the
use of a simplified heat conduction model or overestimation Carlos M. Fonte gratefully acknowledges the PhD grant
of the effective area for heat transfer since only a 2D axis- from FCT (SFRH/BD/39040/2007).
symmetric model is used.
REFERENCES
OPTIMIZATION [1] N. El Wakil, N.-C. Chereches, J. Padet, 2006,
Flow inversion was observed to occur, in some operating "Numerical study of heat transfer and fluid flow in a
ONAF cases, between two consecutive washers. The heated power transformer ", Int. J. Therm. Sci. vol. 45, 615-
oil in a radial duct re-enters the upper radial duct, leading to 626.
a local increase of average temperature. This causes the disc [2] R. Hosseini, M. Nourolahi, G.B. Gharehpetian, 2008,
to overheat since the driving force for the heat transfer "Determination of OD cooling system parameters
decreases leading to a poor heat removal, and hence a poor based on thermal modeling of power transformer
performance of the power transformer. winding", Simul. Modell. Pract. Theory, vol. 16, 585-
A study was performed to the HV winding in order to 596.
overcome this inversion problem and several geometries [3] J.-M. Mufuta, E. van den Bulck, 2000, "Modelling of
were tested. By adding new washers and repositioning them, the mixed convection in the windings of a disc-type
it is possible to align the oil flow between consecutive power transformer," Appl. Therm. Eng., vol. 20, 417-
washers. A decrease of 6.2°C in the hot-spot temperature 437.
and 1.7°C in the winding average was achieved by this way [4] F. Torriano, M. Chaaban, P. Picher, 2010, "Numerical
as reported in Table 5. study of parameters affecting the temperature
distribution in a disc-type transformer winding" Appl.
Table 5. Comparison of average and hot-spot temperature Therm. Eng., vol. 30, 2034-2044.
for the normal and modified geometry. [5] J. Smolka, A. Nowak, 2008, "Experimental validation
Geometry THV average (°C) THV maximum (°C) of the coupled fluid flow, heat transfer and
Normal 92.3 118.1 electromagnetic numerical model of the medium-power
Modified 90.6 111.9
dry-type electrical transformer," Int. J. Therm. Sci.,
vol. 47, 1393-1410.
CONCLUSIONS [6] E.J. Kranenborg, C.O. Olsson, B.R. Samuelsson, L.- Å.
CFD simulations can provide a non-intrusive way of Lundin, R.M. Missing, 2008, "Numerical study on
analysing thermal performance of power transformers under mixed convection and thermal streaking in power
in-service conditions. Detailed temperature and flow transformer windings", Proceedings of the 5th
distribution along the windings can be obtained as well as European Thermal-Sciences Conference, The
the location and magnitude of hot-spots. Netherlands.
For the 2D axis-symmetric model, the spacers’ effect cannot [7] H. Campelo, C.M. Fonte, R.G. Sousa, M.M. Dias,
be taken directly into account in hydrodynamic and thermal J.C.B Lopes, R. Lopes, J. Ramos, D. Couto, 2009,
simulation. A proposed correction on the temperature was "Detailed CFD analysis of ODAF power transformers"
introduced by taking into account the heat transfer area Proceedings of the International Colloquium
reduction. Transformer Research and Asset Management,
The 3D model gives the best estimates for the experimental Croatia.
temperatures. Observed deviations can be caused by several
uncertainties like on the estimation of the inlet/outlet
temperatures or real differences on geometrical parameters
since the CFD simulation assumes a perfect construction.