Version: 1.2
Revision History
Dec. 7, 2016 1.2 Added the measured data area Jong-Eun Park
Table of Contents
1. Protocol 4
3. DI Status 34
4. DO Status 47
5. DO Control. 48
6. Time Synch 55
1. Protocol
When a master sends request packets to a slave, the slave sends response frames.
Each frame is distinguished by using the dead time. The timing diagram of the request packet
and the response packet is as follows.
.
DESCRIPTION SIZE
DATA N Byte
CRC 2 Byte
DEAD TIME
Definition of Slave
Function Code Function Code Echo or MSB=1
Acton
Additional
information which
Requested data or
the Slave needs to Data Data
Exception code
perform the
requested action
slave address.
When the slave sends a response to the slave, the address field is filled with its address.
1.5 DATA
Register address
Quantity of items to be handled
Number of bytes of actual data
1.6 CRC
Data
F.C Address Parameter Byte R/W Unit Description
Format
Analog Data
[Lead]: -1<=P.F<0
0031 Power Factor - Total 4 R Float32
[Lag] : 0<=P.F<=1
Energy - Active -
= [ High + (Low /
10000) ]
Hour)
10000) ]
Reactive Energy - Forward - Total - High
0047 4 R VarH Float32 (Unit: VarH = Var
- Lag
Hour)
Energy - Apparent
Apparent Energy - Forward - Total -
0051 4 R VAH Float32 - Fwd. - Total
High
= [ High + (Low /
10000) ]
0053 Apparent Energy - Forward - Total - Low 4 R VAH Float32 (Unit: VAH = VA
Hour)
Energy - Active -
= [ High + (Low /
10000) ]
Hour)
10000) ]
Reactive Energy - Reverse - Total - High
0063 4 R VarH Float32 (Unit: VarH = Var
- Lag
Hour)
High - Lead
[Lead]: -1<=P.F<0
0531 [TRMS] Power Factor - Total 4 R Float32
[Lag] : 0<=P.F<=1
Energy - Active -
[TRMS] Active Energy - Forward - Total -
0539 4 R WH Float32 Fwd. - Total
High
= [ High + (Low /
10000) ]
[TRMS] Active Energy - Forward - Total -
0541 4 R WH Float32 (Unit: WH = Watt
Low
Hour)
= [ High + (Low /
Hour)
Energy - Active -
[TRMS] Active Energy - Reverse - Total -
0555 4 R WH Float32 Rvs. - Total
High
= [ High + (Low /
10000) ]
[TRMS] Active Energy - Reverse - Total -
0557 4 R WH Float32 (Unit: WH = Watt
Low
Hour)
10000) ]
[TRMS] Reactive Energy - Reverse - Total
0563 4 R VarH Float32 (Unit: VarH = Var
- High - Lag
Hour)
A - Low 10000) ]
response.
At this time, the number of data points should be less than 255 bytes for the response.
2. Energy Calculation
3. The AI4to20m data address (3001) is available only when the option board mode is set
4. The latest fault data address (3101) refers to the measurement value of the fault log data which has occurred
recently.
3. DI Status
DI Status
0002 DI_02 R
0 : Off Status
0003 DI_03 R
1 : ON Status
0004 DI_04 R Unsigned
1
0005 DI_05 R Char
DI_01: CB_ON Stu
0006 DI_06 R
DI_02: CB_OFF Stu
0007 Reserved R
0010 Reserved R
0 : Off Status
0011 Reserved R
1 : ON Status
0012 Reserved R Unsigned
1
0013 Reserved R Char
0: Local Stu
0014 Reserved R
1: Remote Stu
0015 Reserved R
0366 TR - Reserved R
0367 TR - Reserved R
0378 TR - Breaker_Failure R
0379 TR - PT_Fuse_Failure R
0382 TR - Reserved R
0383 TR - PT_Circuit_Fail R
0386 TR - PF_Alarm_Lag R
0387 TR - Reserved R
0390 TR - Reserved R
0391 TR - Reserved R
0878 PU - Reserved R
0879 PU - Reserved R
0891 PU - PT_Fuse_Failure R
0894 PU - Reserved R
0895 PU - PT_Circuit_Fail R
0898 PU - PF_Alarm_Lag R
0899 PU - Reserved R
0902 PU - Reserved R
0903 PU - Reserved R
Therefore, the data of 1/8 of the query data amount X is sent [cf] X / 8 = Response size]
2. AITD (= AI4to20mA) data addresses (369 ~ 376) / Addresses (625 ~ 632) / Addresses (881 ~ 888) are only
4. DO Status
DO Status
1026 DO_02 R
0 : Off Status
1027 DO_03 R
1 : ON Status
1028 DO_04 R Unsigned
1
1029 DO_05 R Char
DO_01: CB_ON Stu
1030 DO_06 R
DO_02: CB_OFF Stu
1031 Reserved R
Therefore, the data of 1/8 of the query data amount X is sent [cf] X / 8 = Response size]
Function
Device ID NO. Byte Data 1 CRC CRC
Code
: The upper system identifies the data High/Low by bit according to the data type.
5. DO Control.
DO Control
(1) CB ON Control
: The upper system sends the following packet to the VIPAM3500C (CB ON control select
signal).
: The upper system sends the following packet to the VIPAM3500C (CB ON operation signal)
: After controlling the CB ON signal, the device sends the following response.
: The upper system sends the following packet to the VIPAM3500C (CB OFF control select signal)
: The upper system sends the following packet to the VIPAM3500C (CB OFF control operation
signal)
: After controlling the CB OFF signal, the device sends the following response.
: The upper system sends the following packet to the VIPAM3500C (DO control operation signal)
: The upper system sends the following packet to the VIPAM3500C (DO control select signal)
: The upper system sends the following packet to the VIPAM3500C (DO control operation signal)
(However, the address range for general DO control is from 0x0004 to 0x000B.)
: After controlling Lock Out Reset Cmd. (= ACK button), the device sends the following response
-> The relay operation which has occurred in the VIPAM3500C is released.
(However, the control command of the VIPAM3500C can be given by address in the same way.)
6. Time Synch
Comment
04 10 13 95 00 06 0C 07 E0 00 0B 00 09 00 0F 00 1F 00 15 XX XX
04 10 13 95 00 06 XX XX
3. Notes
1) Data format condition for Time Sync setting (for Multi Register setting)
Ex) Query: 01, 10, 13, 95, 00, 06, 0C, 07, E0, 00, 0B, 00, 09, 00, 0F, 00, 15 CRC CRC
Send the data format with Year / Month / Date Hour: Minute: Second -> available to set
Ex) Query: 01, 10, 13, 95, 00, 06, 0C, 07, E0, 00, 0B, 00, 09, 00, 0F, 00, 15, 03, 52 CRC CRC
Send the data format with Year / Month / Date Hour: Minute: Second, Millisecond -> available to set
-. If an invalid setting is sent, the Time Sync is abnormal and the time is forcibly reset to the initialization time defined in
the RTC.
2) The data range (hour, minute, second, etc.) should not be out of the range defined in the map.
-. If an invalid setting is sent, the Time Sync is abnormal and the time is forcibly reset to the initialization time defined in
the RTC.