MT6071iP/MT8071iP SERIES

1. INSTALLATION AND STARTUP GUIDE 2. UNPACKING THE UNIT 4. POWER CONNECTIONS 6. EASYBUILDER PRO SOFTWARE
SETTINGS
This document covers the installation of MT6/8071iP Unpack and check the delivery. If damage is found,
Series HMI, for the detailed specifications and notify the supplier. Launch EasyBuilder Pro software, select your project
operation, please refer to Brochure and EasyBuilder Pro file, press F7 shortcut key to open the download dialog
User Manual. box:

Install Environment: For MT6071iP, select USB cable /


(1) For MT8071iP, select Ethernet > IP tab > Enter
MT6/8071iP Series HMI is NEMA 4
NEMA Rating your HMI IP > Click Download to download this project
rated (Indoor Only).
(2) file to HMI.

It is recommended to use screensaver and backlight


(3) Note: saver to avoid image persistence caused by displaying
MT6/8071iP Series has been 1. Connect positive DC line to the ‘+’ terminal and the same image on HMI for a long time.
tested to conform to European CE the DC ground to the ‘-’ terminal.
requirements. This means that the 2. Please do not connect HMI with PLC and PC
(4) ( Please refer to EasyBuilder Pro User Manual
circuitry is designed to resist the
simultaneously to prevent potential difference for software operation details )
Electrical effects of electrical noise. This does
Environment not guarantee noise immunity in from destroying USB ports of HMI and PC.
severe cases.
1. Installation Instruction, 2-sided A4 *1
5. SYSTEM SETTINGS
Proper wire routing and grounding will 2. Human Machine Interface *1
insure proper operation. 3. Power Connector *1
When HMI is powered up and displays image,
4. Brackets & Screws *1 pack
click the system setting button.
(Default System Password: 111111)
Note:
Place the operator panel on a stable surface
It is necessary to connect the HMI to your network
during installation. Dropping it or letting it fall may
through a RJ-45 cable.
cause damage.
(N/A for MT6071iP)
(1) Make sure that the displays are
installed correctly and that the 3. INSTALLATION INSTRUCTIONS
operating limits are followed. Avoid
installing units in environments Secure the operator panel in position, using all the
where severe mechanical vibration
fastening holes and the provided brackets 7. COMMUNICATION CONNECTIONS
or shocks are present.
and screws.
(2) Do not operate the unit in areas 9 Pin, Male, D-sub
subject to explosion hazards due Screw Torque: 2.6 ~ 3.9 lbf.in. (For reaching waterproof COM1 [RS232]
to flammable gases, vapors or effect and preventing the panel from being deformed.) COM2 [RS485]
Environmental dusts.
Considerations
(3) Do not install the unit where acid Go to the Network tab, you may choose to auto get
gas, such as SO2 exists. (A) DHCP IP, or designate your own IP.
(4) This device should be mounted in Note:
(B)

the vertical position and for use on Cutout


COM2 RS-485 2W support MPI 187.5K.
the flat surface enclosure.

(5) Conform to UL508 (ISBN 0-7629-


0404-6) machine safety for use in
Pollution Degree 2 Environment.
Type A(mm) B(mm)

MT6071iP 192 138

MT8071iP 192 138


COM1 COM2 COM2 Fusing Requirements
PIN#
[RS232] [RS485] 4W [RS485] 2W If the display does not come on within DANGER!
1 Rx- Data- 5 seconds of power up, remove power.
A resettable fuse will protect against Hardware Considerations
2 Rx+ Data+
overcurrent faults in DC circuit and the The system designer should be aware that
3 Tx- resetting will take place after a period of devices in Controller systems could fail
4 Tx+ time. Check wiring for proper connections and thereby create an unsafe condition.
5 GND and try to power up again. Furthermore, electrical interference in an
6 TxD High Voltage operator interface can lead to equipment
A resettable fuse will prevent damage start-up, which could result in property
7 RTS
for overcurrent condition however it isn’t damage and/or physical injury to the
8 CTS guaranteed. DC voltage sources should operator.
9 RxD provide proper isolation from main AC If you use any programmable control
power and similar hazards. systems that require an operator, be
aware that this potential safety hazard
8. JUMPER SETTINGS Emergency Stop exists and take appropriate precautions.
A Hard-wired EMERGENCY STOP Although the specific design steps
should be fitted in any system using depend on your particular application, the
an HMI to comply with ICS Safety following precautions generally apply to
Recommendations. installation of solid-state programmable
Supply Voltage Condition control devices, and conform to the
Do not power the unit and inductive DC guidelines for installation of Controllers
loads, or input circuitry to the controller, recommended in NEMA ICS 3-304
with the same power supply. Note: The 12 Control Standards.
or 24 VDC output from some controllers Programming Considerations
may not have enough current to power To conform with ICS Safety
the unit. Recommendations, checks should be
1-2 3-4 Mode Wire Routing placed in the controller to ensure that all
a. Power wire length should be minimized writable registers that control critical parts
Touch Screen
Short Open (Max: 500m shielded, 300m unshielded). of plant or machinery have limit checks
Calibration Mode
b. Please use twisted pair cables for built into the program, with an out-of-
Open Short Boot Loader Mode power wire and signal wire and conform to limit safe shut down procedure to ensure
the impedance matching. safety of personnel.
Open Open Normal
c. If wiring is to be exposed to lightning
or surges, use appropriate surge
Please prepare a jumper cap for setting the jumpers. suppression devices.
Another way to enter touch screen calibration mode is: d. Keep AC, high energy, and rapidly
switching DC power wiring separated from
signal wires.
Press and hold anywhere on the screen for more than 2 e. Add a resistor and capacitor in
seconds when HMI starts. the parallel connection between the
ungrounded DC power supply and the
frame ground. This provides a path for
Note!
static and high frequency dissipation.
Make sure that all local and national
Typical values to use are 1M Ohm and
electrical standards are met when
CAUTION! installing the unit. Contact your local
4700pF.
authorities to determine which codes
apply.
Power
The unit can be powered by DC power
only, voltage range: 10.5~28VDC,
compatible with most controller DC
systems. The power conditioning circuitry
inside the unit is accomplished by a
switching power supply. The peak starting
current can be as high as 2A.