RXQ-A(M)

RXQ20AY1S
RXQ6AY1S / RXQ8AY1S / RXQ10AY1S / RXQ12AY1S / RXQ14AY1S / RXQ16AY1S / RXQ18AY1S /
RXQ20AY14
RXQ6AY14 / RXQ8AY14 / RXQ10AY14 / RXQ12AY14 / RXQ14AY14 / RXQ16AY14 / RXQ18AY14 /
RXQ6AYM / RXQ8AYM / RXQ10AYM / RXQ12AYM / RXQ14AYM / RXQ16AYM / RXQ18AYM / RXQ20AYM

7. Electric Characteristics

EDAMT341716
Model name Units Power supply Compressor OFM
Combination unit Independent Unit Hz Volts Min. Max. MCA TOCA MFA MSC RLA kW FLA
RXQ6AYM 380 – 4.7
50 400 342 456 – 4.5
RXQ6AY14 16.1 18.5 20 0.55 0.8
415 – 4.3
RXQ6AY1S 60 380 342 418 – 4.7
RXQ8AYM 380 – 7.4
50 400 342 456 – 7.0
RXQ8AY14 16.1 18.5 20 0.55 1.4
415 – 6.8
RXQ8AY1S 60 380 342 418 – 7.4
RXQ10AYM 380 – 9.7
50 400 342 456 – 9.2
RXQ10AY14 21.2 25.8 25 0.55 1.4
415 – 8.9
RXQ10AY1S 60 380 342 418 – 9.7
RXQ12AYM 380 – 13.2
50 400 342 456 – 12.6
RXQ12AY14 22.5 25.8 25 0.55 1.6
415 – 12.1
RXQ12AY1S 60 380 342 418 – 13.2
RXQ14AYM 380 – 14.4
50 400 342 456 – 13.7
RXQ14AY14 26.9 28.5 30 0.75x2 1.1+1.2
415 – 13.2
RXQ14AY1S 60 380 342 418 – 14.4
RXQ16AYM 380 – 9.5 + 9.5
50 400 342 456 – 9.0 + 9.0
RXQ16AY14 30.2 37.4 35 0.75x2 1.1+1.2
415 – 8.7 + 8.7
RXQ16AY1S 60 380 342 418 – 9.5 + 9.5
RXQ18AYM 380 – 11.8 + 11.8
50 400 342 456 – 11.2 + 11.2
RXQ18AY14 30.2 37.4 35 0.75x2 1.1+1.2
415 – 10.8 + 10.8
RXQ18AY1S 60 380 342 418 – 11.8 + 11.8
RXQ20AYM 380 – 9.9 + 16.5
50 400 342 456 – 9.4 + 15.6
RXQ20AY14 38.9 48.2 45 0.75x2 1.4+1.9
415 – 9.1 + 15.1
RXQ20AY1S 60 380 342 418 – 9.9 + 16.5
Symbols : Notes :
MCA : Min. Circuit Amps. (A) 1. RLA is based on the following conditions.
TOCA : Total Over-current Amps. (A) Indoor temp. 27°CDB / 19°CWB
MFA : Max. Fuse Amps. (A) Outdoor temp. 35°CDB

Electric Characteristics
MSC : Max. Starting current
RLA : Rated Load Amps. (A) 2. TOCA means the total value of each OC set.
OFM : Outdoor Fan motor 3. MSC means the Max. current during the starting of compressor.
FLA : Full load Amps. (A) 4. Voltage range
kW : Rated Motor Output (kW) Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
5. Maximum allowable voltage variation between phases is 2%.
6. Select wire size based on the value of MCA.
7. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
8. For Thailand and Indonesia, the power supply is 50 Hz.

C: 3D111598
87

3
88

RXQ30AMY1S / RXQ32AMY1S
RXQ18AMY1S / RXQ20AMY1S / RXQ22AMY1S / RXQ24AMY1S / RXQ26AMY1S / RXQ28AMY1S /
RXQ30AMY14 / RXQ32AMY14
RXQ18AMY14 / RXQ20AMY14 / RXQ22AMY14 / RXQ24AMY14 / RXQ26AMY14 / RXQ28AMY14 /
RXQ30AMYM / RXQ32AMYM
RXQ18AMYM / RXQ20AMYM / RXQ22AMYM / RXQ24AMYM / RXQ26AMYM / RXQ28AMYM /

Electric Characteristics
Model name Units Power supply Compressor OFM
Combination unit Independent Unit Hz Volts Min. Max. MCA TOCA MFA MSC RLA kW FLA
380 – 7.4 + 9.7
RXQ18AMYM RXQ8AYM RXQ10AYM
50 400 342 456 – 7.0 + 9.2
RXQ18AMY14 RXQ8AY14 RXQ10AY14 30.2 44.3 35 0.55 x 2 1.4 + 1.4
415 – 6.8 + 8.9
RXQ18AMY1S RXQ8AY1S RXQ10AY1S
60 380 342 418 – 7.4 + 9.7
380 – 7.4 + 13.2
RXQ20AMYM RXQ8AYM RXQ12AYM
50 400 342 456 – 7.0 + 12.6
RXQ20AMY14 RXQ8AY14 RXQ12AY14 38.9 44.3 45 0.55 x 2 1.4 + 1.6
415 – 6.8 + 12.1
RXQ20AMY1S RXQ8AY1S RXQ12AY1S
60 380 342 418 – 7.4 + 13.2
380 – 9.7 + 13.2
RXQ22AMYM RXQ10AYM RXQ12AYM
50 400 342 456 – 9.2 + 12.6
RXQ22AMY14 RXQ10AY14 RXQ12AY14 43.7 51.6 50 0.55 x 2 1.4 + 1.6
415 – 8.9 + 12.1
RXQ22AMY1S RXQ10AY1S RXQ12AY1S
60 380 342 418 – 9.7 + 13.2
380 – 13.2 x 2
RXQ24AMYM RXQ12AYM RXQ12AYM
50 400 342 456 – 12.6 x 2
RXQ24AMY14 RXQ12AY14 RXQ12AY14 45.0 51.6 50 0.55 x 2 1.6 x 2
415 – 12.1x 2
RXQ24AMY1S RXQ12AY1S RXQ12AY1S
60 380 342 418 – 13.2 x 2
380 – 13.2 + 14.4
RXQ26AMYM RXQ12AYM RXQ14AYM
50 400 342 456 – 12.6 + 13.7
RXQ26AMY14 RXQ12AY14 RXQ14AY14 49.4 54.3 60 0.55 + 0.75x2 1.6+(1.1+1.2)
415 – 12.1 + 13.2
RXQ26AMY1S RXQ12AY1S RXQ14AY1S
60 380 342 418 – 13.2 + 14.4
380 – 13.2 + 9.5 + 9.5
RXQ28AMYM RXQ12AYM RXQ16AYM
50 400 342 456 – 12.6 + 9.0 + 9.0
RXQ28AMY14 RXQ12AY14 RXQ16AY14 52.8 63.2 60 0.55 + 0.75x2 1.6+(1.1+1.2)
415 – 12.1 + 8.7 + 8.7
RXQ28AMY1S RXQ12AY1S RXQ16AY1S
60 380 342 418 – 13.2 + 9.5 + 9.5
380 – 13.2 + 11.8 + 11.8
RXQ30AMYM RXQ12AYM RXQ18AYM
50 400 342 456 – 12.6 + 11.2 + 11.2
RXQ30AMY14 RXQ12AY14 RXQ18AY14 52.8 63.2 60 0.55 + 0.75x2 1.6+(1.1+1.2)
415 – 12.1 + 10.8 + 10.8
RXQ30AMY1S RXQ12AY1S RXQ18AY1S
60 380 342 418 – 13.2 + 11.8 + 11.8
380 – 14.4 + 11.8 + 11.8
RXQ32AMYM RXQ14AYM RXQ18AYM
50 400 342 456 – 13.7 + 11.2 + 11.2
RXQ32AMY14 RXQ14AY14 RXQ18AY14 57.1 65.9 70 (0.75x2) x 2 (1.1+1.2) x 2
415 – 13.2 + 10.8 + 10.8
RXQ32AMY1S RXQ14AY1S RXQ18AY1S
60 380 342 418 – 14.4 + 11.8 + 11.8

Symbols : Notes :
MCA : Min. Circuit Amps. (A) 1. RLA is based on the following conditions.
TOCA : Total Over-current Amps. (A) Indoor temp. 27°CDB / 19°CWB
MFA : Max. Fuse Amps. (A) Outdoor temp. 35°CDB
MSC : Max. Starting current
RLA : Rated Load Amps. (A) 2. TOCA means the total value of each OC set.
OFM : Outdoor Fan motor 3. MSC means the Max. current during the starting of compressor.
FLA : Full load Amps. (A) 4. Voltage range
kW : Rated Motor Output (kW) Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.

EDAMT341716
5. Maximum allowable voltage variation between phases is 2%.
6. Select wire size based on the value of MCA.
7. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
RXQ-A(M)

8. For Thailand and Indonesia, the power supply is 50 Hz.