Sie sind auf Seite 1von 5

SIPROTEC 5

Configuration
Nov 11, 2020 8:35 PM

Device: 7SS85 Busbar Protection


2 zones, 4 bays incl., discIm

Product code
Short: P1E281359
Long: 7SS85-DAAA-AA0-0AAAA0-AMB111-12111B-BAA000-000AC0-CC1BA1-CC1CB1-CG0CG0

Firmware: Current version


Housing width: 1 x 19''
Housing type: Flush mounting
Binary inputs: 51
Binary outputs: 33 Relays (19 Standard, 14 Fast, 0 High-Speed, 0 Power)
Current transformers: 20 for protection
Voltage transformers: 4 standard
Measuring-transducer inputs: 0 (20 mA or 10 V, fast)
0 (20 mA, standard)
CPU: CP300
Modules in 19" row 1: IO203 , PS201 , IO203 , IO202 , IO207 , IO207
Modules in 19" row 2:
LEDs/Push-buttons: 16 LEDs
Operation Panel: Integrated
Key switch: Without
Display type: Small display
Front Design: Standard
Power Supply: DC 60 V-250 V, AC 100 V-230 V
Redundant Power Supply: No

Communication/Plug-in modules:
Communications encryption: Normal
Integrated Ethernet port J: for DIGSI 5
Plug-in module position E: ETH-BB-2FO: 2x optical Ethernet 100 Mbit/s, 1300 nm, duplex LC connector,
2 km over 50/125 um or 62.5/125 um multimode optical fiber Communication
Protocols: applicable for DIGSI 5, IEC 61850-8-1 MMS and GOOSE, IEC
60870-5-104, DNP3 TCP, Modbus TCP, Synchrophasor (IEEE C37.118 - IP),
Profinet IO, SUP, DHCP, SNTP, SNMP, etc. Redundancy protocols: Line Mode,
RSTP, HSR, PRP
SIPROTEC 5
Configuration
Nov 11, 2020 8:35 PM

Plug-in module position F: Port is available but not assembled

Functions:
Function points class: Base + 200 function points

Note on function-points class


The function-points class results from the sum of the function points of the selected functions. You can apply these
functions as selected. The device allows also each other selection of functions as long as the sum of the required
function points is within the selected function-points class. With the maximum function-points class of 1400 it is
possible to activate all the functions in the device. The function-points exceeding 1400 are free of charge. In the
engineering phase DIGSI 5 checks that the selected configuration is suitable (capable of running in the device) before
loading it to the device.

Miscellaneous:
Warranty: 5 years
Firmware: Current version
SIPROTEC 5
Configuration
Nov 11, 2020 8:35 PM

Functional scope 7SS85 Busbar Protection:


Always Add selected Result
ANSI Function Abbr. included Qty. x Value = Points Qty.
Protection functions for 3-pole tripping 3-pole

Protection functions for 1-pole tripping 1-pole

Hardware quantity structure expandable I/O

Process Bus Client Protocol (Note: This PB client


function requires at least one dedicated
ETH-BD-2FO plug-in module, with
V8.0)
IEC61850-9-2 Merging Unit stream MU x 200 =
(Note: This function requires a
dedicated ETH-BD-2FO per stream,
with V8.0)
21T Impedance protection for transformers Z< x 130 =
27 Undervoltage protection: "3-phase" V< x 5 =
or "positive-sequence system V1" or
"universal Vx"
38 Temperature supervision >

47 Overvoltage protection, negative- V2> x 5 =


sequence system
50/51 Overcurrent protection, phases I> x 30 =
TD
50N/ Overcurrent protection, ground IN>
51N TD
50BF Circuit-breaker failure protection, 3-pole CBFP x 15 =
50BF Circuit-breaker failure protection, 1-/3- CBFP x 25 =
pole
50BF Inherent circuit-breaker failure CBFP
protection
50EF End-fault protection x 5 =
59, 59N Overvoltage protection: "3-phase" V> x 5 =
or "zero-sequence system V0" or
"universal Vx"
67 Directional overcurrent protection, I>, (V,I) x 30 =
phases
67N Directional overcurrent protection, IN>, (V,I) x 30 =
ground
SIPROTEC 5
Configuration
Nov 11, 2020 8:35 PM

Functional scope 7SS85 Busbar Protection:


Always Add selected Result
ANSI Function Abbr. included Qty. x Value = Points Qty.
74TC Trip-circuit supervision TCS

81 Frequency protection: "f>" or "f<" or "df/ f<>; df/ x 5 =


dt" dt<>
87B Busbar differential protection I

87B Bus coupler differential protection I x 50 =


Bay 4x x 50 = 4x
Cross stabilization x 250 =
86 Lockout

Broken-wire detection for differential


protection
87 Stub-fault differential protection (for
STUB breaker-and-a-half scheme)
PMU Synchrophasor measurement PMU x 40 =
AFD Arc-protection (only with plug-in module
ARC-CD-3FO)
Measured values, standard

Measured values, extended: Min, Max, x 3 =


Avg
Basic PQ measurements: THD and
harmonics (from V8.01)
Switching statistic counters

Circuit-breaker wear monitoring Ix, I²t, 2P x 10 =


CFC (Standard, control)

CFC arithmetic x 40 =
Switching sequences function x 5 =
Inrush current detection

External trip initiation

Control

Circuit-breaker

Disconnector/Grounding switch
SIPROTEC 5
Configuration
Nov 11, 2020 8:35 PM

Functional scope 7SS85 Busbar Protection:


Always Add selected Result
ANSI Function Abbr. included Qty. x Value = Points Qty.
Fault recording of analog and binary
signals
Monitoring and supervision

Protection interface, serial

Cyber Security: Role-Based Access x 25 =


Control (from V7.8)
Temperature acquisition via
communication protocol
Cyber Security: IEEE 802.1X based x 10 =
network authentication (from V8.3)
Sum: 0